PROFIBUS Interface - Bardac · 2017. 1. 17. · Data Exchange green LED (DE) Bus Fault red LED (BF)...

2
PROFIBUS Interface PROFIBUS-DP Interface The PROFIBUS-DP Interface allows the Elite or Xtravert Series of AC motor controllers to be connected directly to a PROFIBUS network. The interface is based around the Siemens SPC-3 ASIC (PROFIBUS- DP slave ASIC), this in combination with the latest bus interface components ensures device compatibility with the latest 12 Mb technology. Use of the standard D-SUB 9 connector on the bus interface reduces the wiring effort by allowing standard 12Mb Bus connectors to be used. The I/O data interface has also been simplified by the users of the PROFIDRIVE profile for AC Drives. This ensures that uses need only learn one common interface for products from multiple vendors. Configuration Full use of the PROFIBUS GSD file is made to simplify the setup and commissioning of the interface during the network configuration stage. Standard PROFIBUS configuration tools such as COM PROFIBUS from Siemens use the GSD file to present the user with plain English messages of the available configuration options. Configurations options available on the PROFIBUS- DP interface include the following - Drive type selection - I/O data length - Parameterisation options There are no DIP switches for the user to adjust. All user settings are done with the configuration tool and are stored in internal EEPROM. Diagnostics Extensive use has been made of the PROFIBUS Diagnostic telegrams to indicate both module and drive faults back to the PROFIBUS master immediately, this significantly simplifies any remote fault finding effort. Based on the diagnostic information the PROFIBUS master can determine the appropriate response required thereby minimising any production down time. Three Local LED indicators provide power and PROFIBUS status information while an additional seven segment status display is used to indicate the interface status. The local status display provides indication of the node address number, drive fault codes, hardware fault codes and the status of the communication link from the drive to the interface. Key Features - SPC-3 ASIC - 12Mb bus interface - PROFIDRIVE interface - Extensive Diagnostics both local and remote 4811-086 Rev A Bardac drives

Transcript of PROFIBUS Interface - Bardac · 2017. 1. 17. · Data Exchange green LED (DE) Bus Fault red LED (BF)...

Page 1: PROFIBUS Interface - Bardac · 2017. 1. 17. · Data Exchange green LED (DE) Bus Fault red LED (BF) Interface status 7 segment red LED PROFIBUS-DP INTERFACE Interface PROFIBUS-DP

PROFIBUS Interface

PROFIBUS-DP Interface

The PROFIBUS-DP Interface allows the Elite or XtravertSeries of AC motor controllers to be connected directly to a PROFIBUSnetwork.

The interface is based around the Siemens SPC-3 ASIC (PROFIBUS-DP slave ASIC), this in combination with the latest bus interfacecomponents ensures device compatibility with the latest 12 Mbtechnology. Use of the standard D-SUB 9 connector on the bus interfacereduces the wiring effort by allowing standard 12Mb Bus connectors tobe used.

The I/O data interface has also been simplified by the users of thePROFIDRIVE profile for AC Drives. This ensures that uses need onlylearn one common interface for products from multiple vendors.

Configuration

Full use of the PROFIBUS GSD file is made to simplify the setup andcommissioning of the interface during the network configuration stage.Standard PROFIBUS configuration tools such as COM PROFIBUS fromSiemens use the GSD file to present the user with plain Englishmessages of the available configuration options.

Configurations options available on the PROFIBUS-DP interface include the following

- Drive type selection- I/O data length- Parameterisation options

There are no DIP switches for the user to adjust. All user settings aredone with the configuration tool and are stored in internal EEPROM.

Diagnostics

Extensive use has been made of the PROFIBUS Diagnostic telegramsto indicate both module and drive faults back to the PROFIBUS masterimmediately, this significantly simplifies any remote fault finding effort.Based on the diagnostic information the PROFIBUS master candetermine the appropriate response required thereby minimising anyproduction down time.

Three Local LED indicators provide power and PROFIBUS statusinformation while an additional seven segment status display is used toindicate the interface status. The local status display provides indicationof the node address number, drive fault codes, hardware fault codesand the status of the communication link from the drive to the interface.

Key Features

- SPC-3 ASIC- 12Mb bus interface- PROFIDRIVE interface- Extensive Diagnostics both local and remote

4811-086 Rev A

Bardacdrives

Page 2: PROFIBUS Interface - Bardac · 2017. 1. 17. · Data Exchange green LED (DE) Bus Fault red LED (BF) Interface status 7 segment red LED PROFIBUS-DP INTERFACE Interface PROFIBUS-DP

4203

-030

Rev

. A

PDL ELECTRONICS PDL ELECTRONICS PDL ELECTRONICS PDL ELECTRONICS

Specifications are subject to change without notice.

TECHNICAL DATA

MECHANICAL CONSTRUCTIONFormat (height x width x depth) 281 x 35 x 87.5mm, metal enclosureType of mounting DIRECTDegree of ingress protection IP20

INTERFACESPROFIBUS-DP 9 Pin D-SUB / FPower 3 way 45° screw terminal/plugRS232 3 way 45° screw terminal/plugXtravert 3 way 45° screw terminal/plug

POWER SUPPLYNominal value 24VdcAllowable range (including ripple) 18 to 28VdcMaximum power consumption 250mA

ELECTRICAL INSULATIONPROFIBUS-DP / RS232 connection 500VacPROFIBUS-DP / Xtravert connection 500VacLOCAL INDICATIONSOperating voltage green LED (UL)Data Exchange green LED (DE)Bus Fault red LED (BF)Interface status 7 segment red LED

PROFIBUS-DP INTERFACEInterface PROFIBUS-DPBaudrate Auto detected to 12 MbDiagnostic Data Length 13 Bytes (max.)Parameterisation Data Length 230 Bytes (max.)Configuration Data Length 1 Byte (max.)Polled Data Length 12 Bytes (max.)Supported services Freeze, Sync, Set slave addressGSD file PDL-04B6.GSDProfile PROFIDRIVE

MOTOR CONTROLLERS SUPPORTED

E Series, software revision 2.5 or greater.

Xtravert Series, software revision 2.1 or greater.

4811-085 Rev A

PROFIBUS

CONNECTOR

PLUG TERMINALS

87.5 60

CUSTOMER SUPPLIED

WIRING

35

241.

5

281

5.25

(PBUS)

X

X

RS

232

XT

RA

VE

RT

T

R

0V

+24V

0V

DE

BF

UL

STATUS

PR

OF

IBU

S-D

P IN

TE

RF

AC

E

270.

5

Bardacdrives

Bardac Corporation40 Log Canoe Circle

Stevensville, MD 21666 USAPhone: (410)604-3400 Fax: (410)604-3500

www.bardac.com