Product Model Number Guide 12.04.17 1 PRODUCT MODEL NUMBER GUIDE

Transcript of PRODUCT MODEL NUMBER GUIDE - Data Aire · Product Model Number Guide 12.04.17 7 C - Auxillary...

Page 1: PRODUCT MODEL NUMBER GUIDE - Data Aire · Product Model Number Guide 12.04.17 7 C - Auxillary Chilled Water Coil DA A D 20 3 2 DATA AIRE D - Downf ow U --- Upf ow Nominal tons 3 -

Product Model Number Guide12.04.17 1

PRODUCT MODEL NUMBER

GUIDE

Page 2: PRODUCT MODEL NUMBER GUIDE - Data Aire · Product Model Number Guide 12.04.17 7 C - Auxillary Chilled Water Coil DA A D 20 3 2 DATA AIRE D - Downf ow U --- Upf ow Nominal tons 3 -

Product Model Number Guide12.04.172

TABLE OF FIGURES

Figure 1 - gForce Ultra Systems (Single & Dual Circuit) .........................................3

Figure 2 – gForce In-Row Systems (Single Circuit) ..................................................3

Figure 3 - GT Systems (Single Circuit) ......................................................................4

Figure 4 - gForce Systems (Dual Circuit) ..................................................................5

Figure 5 - Data Temp Systems (Single Circuit) ........................................................6

Figure 6 - Modular Data Temp Systems (Single Circuit) ........................................6

Figure 7 - Data Aire Systems (DX) .............................................................................7

Figure 8 - Data Aire Systems (Chilled Water) ..........................................................7

Figure 9 - Mini Ceiling Systems (Single Circuit) ......................................................8

Figure 10 - Mini-Plus Ceiling Systems (Single Circuit) ...........................................8

Figure 11 - Large Ceiling Systems (Single OR Dual Circuit) ..................................9

Figure 12 – Outdoor Remote Condensers (RC) ....................................................10

Figure 13 - Outdoor Condensing Units (CU) ........................................................10

Figure 14 - Indoor “Piggy-Back” Remote Condenser (RC + PB) .........................10

Figure 15 - Outdoor Fluid Coolers (FC) .................................................................11

Figure 16 – Indoor “Piggy-Back” Fluid Cooler (FC + PB) .....................................11

Figure 17 - Data Cool Systems (Single Circuit) .....................................................12

Figure 18 - Shelf Systems (Single Circuit) ..............................................................12

Page 3: PRODUCT MODEL NUMBER GUIDE - Data Aire · Product Model Number Guide 12.04.17 7 C - Auxillary Chilled Water Coil DA A D 20 3 2 DATA AIRE D - Downf ow U --- Upf ow Nominal tons 3 -

Product Model Number Guide12.04.17 3

FLOOR UNITS (VARIABLE SPEED COMPRESSOR)

Figure 1 - gForce Ultra Systems (Single & Dual Circuit)

RACK & ROW(FIXED/VARIABLE SPEED COMPRESSOR:

Figure 2 - gForce In-Row Systems (Single Circuit)

gForce Ultra

A U - 3GU 2022

gForce Ultra, Single and Dual Circuit

A----- Air CooledW - Water CooledG - Glycol Cooled

D - Downf ow U ---- Upf ow

Nominal Kilowatts022kW 036kW045kW070kW091kW125kW

Phase 3 - Three phase

Voltage2 - 208/230 V 4 - 460 V

CW - 3GI 4035

Data Aire gForce IR

AX------Air CooledWX - Water CooledGX - Glycol Cooled

035kW -AX, WX or GX **

020kW -AX *030kW -CW

010kW -AX *

060kW -CW

1 - Single Phase3 - Three phase

2 - 208/230 volt 4 - 460 volt

CW - Chilled Water

022kW -AX, WX or GX **

Note: Each image will hyperlink to our website and the product’s supporting documentation

MODEL NUMBER IDENTIFICATION

gForce IRMODEL NUMBER IDENTIFICATION

Single Circuit

Voltage

Phase

Nominal Kilowatts

single circuit: 022, 036, 045dual: 070, 091, 125

12” Cabinet:

24” Cabinet:

* Fixed speed compressor** Variable speed compressor

12” cabinet 24” cabinet

Page 4: PRODUCT MODEL NUMBER GUIDE - Data Aire · Product Model Number Guide 12.04.17 7 C - Auxillary Chilled Water Coil DA A D 20 3 2 DATA AIRE D - Downf ow U --- Upf ow Nominal tons 3 -

Product Model Number Guide12.04.174

FLOOR UNITS

A D - 3GT 4035

gForce Series Single Circuit

A------Air CooledW - Water CooledG - Glycol Cooled

D - Downf ow U ---- Upf ow

Nominal Kilowatts

1 - Single Phase3 - Three phase

2 - 208 or 230 V4 - 460 V5 - 575 V

CC - Auxillary Chilled Water Coil

E - Energy Saver Coil (Water/Glycol Cooled Units)

(Air or Water Cooled Units)

Figure 3 - GT Systems (Single Circuit)

GT SystemsMODEL NUMBER IDENTIFICATION

Voltage

Phase

007-046 kW

Page 5: PRODUCT MODEL NUMBER GUIDE - Data Aire · Product Model Number Guide 12.04.17 7 C - Auxillary Chilled Water Coil DA A D 20 3 2 DATA AIRE D - Downf ow U --- Upf ow Nominal tons 3 -

Product Model Number Guide12.04.17 5

C - Auxillary Chilled Water Coil A D - 3GF 4035

gForce Systems Dual Circuit

A ------ Air CooledW --- Water Cooled

G --- Glycol Cooled

D - Downf owU ---- Upf ow

Nominal Kilowatts

1 - Single Phase3 - Three phase

2 - 208 or 230 V

4 - 460 V

EC - Auxillary Chilled Water Coil

E - Energy Saver Coil (Water/Glycol Cooled Units)

(Air or Water Cooled Units)

DX Units (Link)

Figure 4 - gForce Systems (Dual Circuit)

gForce SystemsMODEL NUMBER IDENTIFICATION

Voltage

Phase

3 - 380 or 400 VC --- Chilled Water

021 - 106 kW

Chilled Water Units (Link)

Page 6: PRODUCT MODEL NUMBER GUIDE - Data Aire · Product Model Number Guide 12.04.17 7 C - Auxillary Chilled Water Coil DA A D 20 3 2 DATA AIRE D - Downf ow U --- Upf ow Nominal tons 3 -

Product Model Number Guide12.04.176

FLOOR UNITS (Cont.)

A D - 1DT 205

DATA TEMP

D - Downf owU ---- Upf ow

Nominal tons 1 - Single Phase3 - Three phase

2 - 208 or 230 V4 - 460 V5 - 575 V

CC - Auxillary Chilled Water Coil

E - Energy Saver Coil (Water/Glycol Cooled Units)

(Air or Water Cooled Units)

A--------Air Cooled

G --- Glycol CooledC --- Chilled Water

W --- Water Cooled

Figure 5 - Data Temp Systems (Single Circuit)

A D - 3DT 208

A ---- Air CooledW - Water CooledG - Glycol Cooled

D - Downf owU ---- Upf ow

3 - Three phase

DATA TEMP

Nominal tons

2 - 208 or 230 V 4 - 460 V 5 - 575 V

Figure 6 - Modular Data Temp Systems (Single Circuit)

Data Temp SystemsMODEL NUMBER IDENTIFICATION

Modular Data Temp SystemsMODEL NUMBER IDENTIFICATION

-

2-5 tons

8-13 tons

Phase

Voltage

Voltage

Phase

MODULAR

C - Chilled Water

Page 7: PRODUCT MODEL NUMBER GUIDE - Data Aire · Product Model Number Guide 12.04.17 7 C - Auxillary Chilled Water Coil DA A D 20 3 2 DATA AIRE D - Downf ow U --- Upf ow Nominal tons 3 -

Product Model Number Guide12.04.17 7

C - Auxillary Chilled Water CoilA D 3DA 220

DATA AIRE

D - Downf owU --- Upf ow

Nominal tons

3 - Three phase

2 - 208 or 230 V 4 - 460 V 5 - 575 V

C C - Auxillary Chilled Water Coil

E - Energy Saver Coil (Water/Glycol Cooled Units)

(Air or Water Cooled Units)

A------Air CooledW - Water CooledG - Glycol Cooled

Data Aire Systems (DX)MODEL NUMBER IDENTIFICATION

Figure 7 - Data Aire Systems (DX)

Figure 8 - Data Aire Systems (Chilled Water)

C D 3DA 415

D - Downf owU ---- Upf ow

3 - Three phase

DATA AIRE

Nominal tons

2 - 208 or 230 V4 - 460 V5 - 575 V

C - Chilled Water

Data Aire Systems (Chilled Water)MODEL NUMBER IDENTIFICATION

- -

-

Voltage

Phase

Voltage

Phase

06 - 30 tons

07 - 50 tons

Page 8: PRODUCT MODEL NUMBER GUIDE - Data Aire · Product Model Number Guide 12.04.17 7 C - Auxillary Chilled Water Coil DA A D 20 3 2 DATA AIRE D - Downf ow U --- Upf ow Nominal tons 3 -

Product Model Number Guide12.04.178

CEILING UNITS

A 01 2DAM P1

01, 1.5, 02 and 2.5

CEILING SYSTEM

1 - Single Phase

2 - 208, 230 or 270 V

DATA AIRE MINI

A ------ Air Cooled

W --- Water CooledC --- Chilled Water

G --- Glycol Cooled

Nominal tons

P - Package System

CO - Split system withoutdoor condenser(DARC)

AO - Split system withoutdoor condensing unit(DRCU)

AI - Split system withindoor condensing unit(DAAC)

CONDENSER - Condenser coil only, no compressorCONDENSING UNIT - Condenser coil and compressor

The order write up should have the condenser or condensing unit model number. Refer to applicable condenser or condensing model number identification.

Example: DATA AIRE MINI, air cooled, 1 ton, 10 - 230 volts, packaged system DAMA 0112 P

Figure 9 - Mini Ceiling Systems (Single Circuit)

A 2.5 2 CO1

2.5, 03, 04 and 05

CEILING SYSTEM

1 - Single Phase

DATA AIRE MINI-PLUS

A ------ Air Cooled

W -- Water CooledC --- Chilled Water

G --- Glycol Cooled

Nominal tons

P - Package System

CO - Split system withoutdoor condenser(DARC)

CI - Split systems withindoor condenser(DAIC)

AO - Split system withoutdoor condensing unit(DRCU)

AI - Split system withindoor condensing unit(DAAC)

3 - Three Phase

2 - 208 or 230 V 4 - 460 V5 - 575 V

E

C - Auxilary chilled

E - Energy SaverFigure 10 - Mini-Plus Ceiling Systems (Single Circuit)

Mini Ceiling SystemsMODEL NUMBER IDENTIFICATION

Mini-Plus Ceiling SystemsMODEL NUMBER IDENTIFICATION

- -

- - -

water coil

DAP

CO - Split system withindoor condenser(DAIC)

Phase

Voltage

Phase

Voltage

Page 9: PRODUCT MODEL NUMBER GUIDE - Data Aire · Product Model Number Guide 12.04.17 7 C - Auxillary Chilled Water Coil DA A D 20 3 2 DATA AIRE D - Downf ow U --- Upf ow Nominal tons 3 -

Product Model Number Guide12.04.17 9

CO - Split system with

outdoor condensing unit

CO - Split system with

CI - Split systems with

AO - Split system withoutdoor condensing unit

AI - Split system withindoor condensing unit

C - Auxilary chilled

E - Energy Saverwater coil

CO - Split system with

A 06 2DAL CO3

06, 08, 10 and 13

DATA AIRE LCS UNIT

Nominal tons

P - Package System

CO - Split system withoutdoor condenser(DARC)

AO - Split system withoutdoor condensing unit(DRCU) 3 - Three Phase

2 - 208 or 230 V4 - 460 V

E D

D - Dual CompressorS - Single Compressor

5 - 575 V

LCS units are not available in air cooled packaged configuration.

CONDENSER - Condenser coil only, no compressorCONDENSING UNIT - Condenser coil and compressor

The order write up should have the condenser or condensing unit model number. Refer to applicable condenser or condensing model number identification.

Example: DATA AIRE LCS UNIT, air cooled, 6 ton, 30 - 230 volts, split system with outdoor condenser and dual compressors - Evaporator model: DALA 0632 CO D Condenser model: DARC 0632

Figure 11 - Large Ceiling Systems (Single or Dual Circuit)

Large Ceiling SystemsMODEL NUMBER IDENTIFICATION

- - - -

A ------ Air Cooled

W --- Water CooledC --- Chilled Water

G --- Glycol Cooled

C - Auxilary chilled

E - Energy Saverwater coil

Single or Dual Circuit

Voltage

Phase

Page 10: PRODUCT MODEL NUMBER GUIDE - Data Aire · Product Model Number Guide 12.04.17 7 C - Auxillary Chilled Water Coil DA A D 20 3 2 DATA AIRE D - Downf ow U --- Upf ow Nominal tons 3 -

Product Model Number Guide12.04.1710

HEAT EXCHANGERS

RC 035 4GH LD3

1 - Single Phase

Remote Condenser - RC

gForce EC fans - GHPSC fans - DA

Nominal tons - Data Aire

3 - Three Phase

2 - 208 or 230 volt4 - 460 volt

LD - Low decibel

Figure 12 - Outdoor Remote Condensers (RC)

CU 05 2DR 1

1 - Single Phase

gForce EC fans - GHPSC fans - DA

Nominal tons - Data Aire

3 - Three Phase

2 - 208 or 230 volt4 - 460 volt

CU - Remote Condensing UnitHCU - Rejection Remote Condensing Unit

Kilowatts - gForce

Figure 13 - Outdoor Condensing Units (CU)

Figure 14 - Indoor “Piggy-Back” Remote Condenser (RC+PB)

Model DARC 07xx-PB

DARC 09xx-PB

DARC 11xx-PB

DARC 15xx-PB

DARC 17xx-PB

DARC 21xx-PB

DARC 24xx-PB

DARC 28xx-PB

DARC 07xx-PB to DARC 09xx-PB are single fan units.

DARC 11xx-PB to DARC 28xx-PB are dual fan units.

Outdoor Remote Condensers (RC)MODEL NUMBER IDENTIFICATION

Outdoor Condensing Units (CU)MODEL NUMBER IDENTIFICATION

- -

-

Voltage

Phase

Voltage

Phase

* Only on DA Series for for LD

Kilowatts - gForce

Page 11: PRODUCT MODEL NUMBER GUIDE - Data Aire · Product Model Number Guide 12.04.17 7 C - Auxillary Chilled Water Coil DA A D 20 3 2 DATA AIRE D - Downf ow U --- Upf ow Nominal tons 3 -

Product Model Number Guide12.04.17 11

FC 06 2DA LD1

1 - Single Phase

FC - Fluid Cooler

Nominal tons

3 - Three Phase

2 - 208 or 230 volt4 - 460 volt

LD - Low decibelPB - Indoor Centrifugal

Figure 15 - Outdoor Fluid Coolers (Dry Coolers) (FC)

Model • DAFC-06-PB

• DAFC-07-PB

• DAFC -09-PB

• DAFC -11-PB

• DAFC -15-PB

• DAFC -17-PB

• DAFC -21-PB

• DAFC-28-PB

Figure 16 - Indoor “Piggy-Back” Fluid Cooler (FC+PB) (Dry Coolers)

Outdoor Fluid Coolers (Dry Coolers)(FC)MODEL NUMBER IDENTIFICATION

- -

Phase

Voltage

PSC fans - DAgForce EC fans - GH

Page 12: PRODUCT MODEL NUMBER GUIDE - Data Aire · Product Model Number Guide 12.04.17 7 C - Auxillary Chilled Water Coil DA A D 20 3 2 DATA AIRE D - Downf ow U --- Upf ow Nominal tons 3 -

Product Model Number Guide12.04.1712

A 02 2DC AO1

02 and 03

1 - Single Phase

2 - 208, 230 volt

DATA COOL

Nominal tons

AO - Split system withoutdoor condensing unit(DRCU)

AI - Split system withindoor condensing unit(DAAC)

Figure 17 - Data Cool Systems (Single Circuit)

A 02 2DAS CO1

1 - Single Phase

Nominal tons

SHELF SYSTEMDATA AIRE

02, 03 and 04

3 - Three Phase

2 - 208 or 230 volt4 - 460 volt5 - 575 volt

P - Package System Fluid cooler identifi cation may be required for glycol cooled units. (DAFC)

SHELF SYSTEMS units are not available in air cooled packaged configuration.

CONDENSER - Condenser coil only, no compressorCONDENSING UNIT - Condenser coil and compressor

The order write up should have the condenser or condensing unit model number. Refer to applicable condenser or condensing model number identification.

Example: DATA AIRE SHELF SYSTEM, air cooled, 2 ton, 10 - 230 volts, split system with outdoor condenser Evaporator model: DASA 0212 CO Condenser model: DARC 0312

Figure 18 - Shelf Systems (Single Circuit)

Data Cool SystemsMODEL NUMBER IDENTIFICATION

Shelf SystemsMODEL NUMBER IDENTIFICATION

- -

- -

Single Circuit

Single Circuit

A ------ Air Cooled

W --- Water CooledC --- Chilled Water

G --- Glycol Cooled

A ------ Air Cooled

W --- Water CooledC --- Chilled Water

G --- Glycol Cooled

CO - Split system withoutdoor condenser(DARC)

CI - Split systems withindoor condenser(DAIC)

AO - Split system withoutdoor condensing unit(DRCU)

AI - Split system withindoor condensing unit(DAAC)

Voltage

Phase

Phase

Voltage

U

U - Upf ow

SPECIALTY UNITS