Product Guide REM611 Motor Protection and Control · Motor start blocking...

44
RELION® 611 SERIES Motor Protection and Control REM611 Product Guide

Transcript of Product Guide REM611 Motor Protection and Control · Motor start blocking...

Page 1: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

—RELION® 611 SERIES

Motor Protection and ControlREM611Product Guide

Page 2: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Contents

1. Description..................................................................... 3

2. Standardized configuration.............................................3

3. Protection functions........................................................6

4. Application..................................................................... 7

5. Supported ABB solutions............................................... 8

6. Control........................................................................... 9

7. Measurement................................................................. 9

8. Disturbance recorder......................................................9

9. Event log...................................................................... 10

10. Recorded data............................................................ 10

11. Trip circuit supervision ................................................10

12. Self-supervision...........................................................10

13. Access control............................................................ 10

14. Inputs and outputs...................................................... 10

15. Station communication................................................11

16. Technical data.............................................................16

17. Local HMI....................................................................32

18. Mounting methods...................................................... 32

19. Relay case and plug-in unit......................................... 33

20. Selection and ordering data.........................................34

21. Accessories and ordering data.................................... 35

22. Tools...........................................................................35

23. Cyber security............................................................. 36

24. Terminal diagram.........................................................37

25. Certificates.................................................................. 37

26. References..................................................................37

27. Functions, codes and symbols.................................... 38

28. Document revision history........................................... 39

Disclaimer

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors

that may appear in this document.

© Copyright 2019 ABB.

All rights reserved.

Trademarks

ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks

of their respective holders.

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

2 ABB

Page 3: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

1. DescriptionREM611 is a dedicated motor protection relay for theprotection, control, measurement and supervision ofasynchronous motors in manufacturing and process industry.Typically, the relay is used with circuit breaker or contactor-controlled medium-sized or small motors in a variety of drives,such as pumps and conveyors, crushers and choppers, mixersand agitators, and fans and aerators.

REM611 is a member of ABB’s Relion® product family and partof the 611 protection and control product series. The 611 seriesrelays are characterized by their compactness andwithdrawable-unit design.

The 611 series offers simplified yet powerful functionality formost applications. Once the application-specific parameter sethas been entered, the installed protection relay is ready to beput into service. The further addition of communicationfunctionality and interoperability between substationautomation devices offered by the IEC 61850 standard addsflexibility and value to end users as well as electrical systemmanufacturers.

The 611 series relays fully support the IEC 61850 standard forcommunication and interoperability of substation automationdevices, including fast GOOSE (Generic Object OrientedSubstation Event) messaging, and can now also benefit fromthe extended interoperability provided by Edition 2 of thestandard. The relays further support the parallel redundancyprotocol (PRP) and the high-availability seamless redundancy(HSR) protocol. The 611 series relays are able to use IEC 61850and Modbus® communication protocols simultaneously.

2. Standardized configurationREM611 is available in one configuration.

To increase the user-friendliness of the configuration and toemphasize the simplicity of usage of the relay, only theapplication-specific parameters need setting within the relay'sintended area of application.

The standard signal configuration can be altered by local HMI,Web HMI or optional application functionality of Protection andControl IED Manager PCM600.

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0 Issued: 2019-04-10

Revision: G

ABB 3

Page 4: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Is2t n<49, 66, 48, 51LR

I2>M46M

REMARKS

Optionalfunction

No. ofinstances

Alternative function to be defined when ordering

OR3×

Io/Uo

Calculatedvalue

CONDITION MONITORING AND SUPERVISION

CONTROL AND INDICATION 1) MEASUREMENT

- I, Io- Limit value supervision- Symmetrical components

MOTOR PROTECTION RELAY STANDARD CONFIGURATION

LOCAL HMI

A

COMMUNICATION

Protocols: IEC 61850-8-1 Modbus®

Interfaces: Ethernet: TX (RJ-45), FX (LC) Serial: RS-485

Redundant protocols: HSR PRP RSTP

4

-

Analog interface types 1)

Current transformer

Voltage transformer1) Conventional transformer inputs

Object Ctrl 2) Ind 3)

CB

DC

ES

1 -

- -

- -1) Check availability of binary inputs/outputs from technical documentation2) Control and indication function for primary object3) Status indication function for primary object

Master TripLockout relay

94/86

PROTECTION

3I

ALSO AVAILABLE

- Disturbance and fault recorders- Event log and recorded data- Local/Remote push button on LHMI- Self-supervision- Time synchronization: IEEE 1588 v2, SNTP, IRIG-B- User management- Web-HMI

3I>>>50P/51P

3I>/Io>BF51BF/51NBF

3I>51P-1

TCSTCM

IoIo>

51N-1Io>>

51N-2

ESTARTESTART

OPTSOPTM

M

3I<37

I2>>46R

3Ith>M49M

Ist>51LR

REM611

RL

ESCI

O

AControlEventsMeasurementsDisturbance records

GUID-5E2D4B1E-9287-4833-BB0A-BB310A16E2CD V2 EN

Figure 1. Functionality overview for configuration A

Table 1. Standardized configuration

Description Conf.

Motor protection A

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

4 ABB

Page 5: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 2. Supported functions

Function IEC 61850 A

Protection

Three-phase non-directional overcurrent protection, low stage PHLPTOC 1

Three-phase non-directional overcurrent protection, instantaneous stage PHIPTOC 1

Non-directional earth-fault protection, low stage EFLPTOC 11)

Non-directional earth-fault protection, high stage EFHPTOC 11)

Negative-sequence overcurrent protection for machines MNSPTOC 2

Loss of load supervision LOFLPTUC 1

Motor load jam protection JAMPTOC 1

Motor start-up supervision STTPMSU 1

Phase reversal protection PREVPTOC 1

Thermal overload protection for motors MPTTR 1

Circuit breaker failure protection CCBRBRF 1

Master trip TRPPTRC 1

Control

Circuit-breaker control CBXCBR 1

Emergency start-up ESMGAPC 1

Condition monitoring and supervision

Trip circuit supervision TCSSCBR 2

Runtime counter for machines and devices MDSOPT 1

Logging

Disturbance recorder RDRE 1

Fault recorder FLTRFRC 1

Measurement

Three-phase current measurement CMMXU 1

Sequence current measurement CSMSQI 1

Residual current measurement RESCMMXU 1

Other

Input switch group ISWGAPC 10

Output switch group OSWGAPC 20

Selector SELGAPC 6

Minimum pulse timer (2 pcs) TPGAPC 10

Minimum pulse timer (2 pcs, second resolution) TPSGAPC 1

Move (8 pcs) MVGAPC 11, 2, ... = Number of included instances. The instances of a protection function represent the number of identical protection function blocks available inthe standardized configuration.() = optional

1) Io selectable by parameter and default value is "Io measured"

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 5

Page 6: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

3. Protection functionsREM611 offers all functionalities needed to manage motorstarts and normal operation, including protection and faultclearance in abnormal situations. The relay includes thermaloverload protection, motor start-up time supervision, lockedrotor protection and protection against too frequent motorstarts. The relay also incorporates non-directional earth-fault,negative phase-sequence current unbalance and backupovercurrent protection. Further, the relay offers stall protection,loss-of-load supervision and phase-reversal protection.

Certain motor drives require a possibility to override the motorthermal overload protection to perform an emergency start of ahot motor. To enable the emergency hot start, the relay offers aforced start execution feature.

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

6 ABB

Page 7: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

4. ApplicationREM611 constitutes the main protection for asynchronousmotors and the associated drives. Typically, the relay is usedwith circuit-breaker or contactor-controlled medium or smallsized motors in a variety of drives, such as pumps andconveyors, crushers and choppers, mixers and agitators, andfans and aerators.

The relay is thoroughly adapted for earth-fault protection.Sensitive and reliable earth-fault protection can be achieved

using a cable current transformer. Phase current transformersin Holmgreen (summation) connection can also be used forearth-fault protection. In that case, possible unwantedoperations of the earth-fault protection at motor start-up, dueto current transformer saturation, can be prevented using therelay's internal interlocking features or a suitable stabilizingresistor in the common neutral return.

REM611Std. conf.

ANSI IEC

37

46M

46R

49,66,48,51LR

49M

50/51P

51BF

51LR

51NBF

51N-1

51N-2

51P-1

94/86

ESTART

3I<

I2>M

I2>>

Is2t n<

3Ith>M

3I>>>

3I>BF

Ist>

Io>BF

Io>

Io>>

3I>

Lockout relay

ESTART

A

Io

3I3I

Io

3I

REF611

Std. conf.

ANSI IEC

50/51P

50N

51BF

51NBF

51N(SEF)

51P-1

51P-2

68

94/86

3I>>>

Io>>>

3I>BF

Io>BF

Io>

3I>

3I>>

3I2f

Lockout relay

B

REM611Std. conf.

ANSI IEC

46M

46R

49,66,48,51LR

49M

50/51P

51BF

51LR

51NBF

51N-2

51P-1

94/86

ESTART

I2>M

I2>>

Is2t n<

3Ith>M

3I>>>

3I>BF

Ist>

Io>BF

Io>>

3I>

Lockout relay

ESTART

A

Motor start blocking

GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN

Figure 2. Motor protection and control of contactor and circuit-breaker controlled motors based on configuration A

Figure 4 shows an example of motor protection and control ofcontactor and circuit-breaker controlled motors based onconfiguration A. The motor start-up signal is used to

dynamically increase the setting level of the lowest overcurrentprotection stage of REF611 on the incoming feeder.

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 7

Page 8: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

5. Supported ABB solutionsThe 611 series protection relays together with the SubstationManagement Unit COM600S constitute a genuine IEC 61850solution for reliable power distribution in utility and industrialpower systems. To facilitate the system engineering, ABB'srelays are supplied with connectivity packages. Theconnectivity packages include a compilation of software andrelay-specific information and a full relay data model. The datamodel includes event and parameter lists. With the connectivitypackages, the relays can be readily configured using PCM600and integrated with COM600S or the network control andmanagement system MicroSCADA Pro.

The 611 series relays offer native support for the IEC 61850standard, including limited binary GOOSE messaging.Compared to traditional hard-wired, inter-device signaling,peer-to-peer communication over a switched Ethernet LANoffers an advanced and versatile platform for power systemprotection. The implementation of the IEC 61850 substationautomation standard enables access to distinctive featuresincluding fast software-based communication, continuoussupervision of the protection and communication system'sintegrity, and inherent flexibility for reconfiguration andupgrades.

At substation level, COM600S uses the data content of the bay-level devices to enhance substation level functionality.

COM600S features a Web browser-based HMI, which providesa customizable graphical display for visualizing single-linemimic diagrams for switchgear bay solutions. The Web HMI ofCOM600S also provides an overview of the whole substation,including relay-specific single-line diagrams, which makesinformation easily accessible. Substation devices andprocesses can also be remotely accessed through the WebHMI, which improves personnel safety.

In addition, COM600S can be used as a local data warehousefor the substation's technical documentation and for thenetwork data collected by the devices. The collected networkdata facilitates extensive reporting and analyzing of networkfault situations by using the data historian and event handlingfeatures of COM600S. The historical data can be used foraccurate monitoring of process and equipment performance,using calculations based on both real-time and historicalvalues. A better understanding of the process dynamics isachieved by combining time-based process measurementswith production and maintenance events.

COM600S can also function as a gateway and provideseamless connectivity between the substation devices andnetwork-level control and management systems, such asMicroSCADA Pro and System 800xA.

Table 3. Supported ABB solutions

Product Version

Substation Management Unit COM600S 4.0 SP1 or later

4.1 or later (Edition 2)

MicroSCADA Pro SYS 600 9.3 FP2 or later

9.4 or later (Edition 2)

System 800xA 5.1 or later

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

8 ABB

Page 9: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

PCM600Ethernet switch

Utility: IEC 60870-5-104Industry: OPC

COM600SWeb HMI

ABBMicroSCADA Pro/

System 800xA

Analog and binary horizontal GOOSE communication IEC 61850

PCM600Ethernet switch

COM600SWeb HMI

Analog and binary horizontal GOOSE communication IEC 61850

GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V4 EN

Figure 3. ABB power system example using Relion relays, COM600S and MicroSCADA Pro/System 800xA

6. ControlThe relay offers control of one circuit breaker or contactor withdedicated push buttons for opening and closing via the localHMI or a remote system, for example, PCM600.

By default, the relay is equipped with a single input interlockingscheme. Binary GOOSE messaging can be used in the creationof additional interlocking schemes, such as secured objectcontrol (SOC), blocking-based protection schemes or externaltripping.

These additional protection and control schemes required byspecific applications are configured using the local HMI, theWeb HMI and the optional application functionality of PCM600.The local HMI and the Web HMI can be utilized for signalconfiguration, while PCM600 is required for the configuration ofGOOSE messaging.

7. MeasurementThe relay continuously measures phase currents and neutralcurrent.

In addition, the relay calculates the symmetrical components ofthe currents and the maximum current demand value over auser-selectable preset time frame.

The measured values can be accessed via the local HMI orremotely via the communication interface of the relay. Thevalues can also be accessed locally or remotely using the WebHMI.

8. Disturbance recorderThe relay is provided with a disturbance recorder featuringpreconfigured analog and binary channels.The analog channelscan be set to record either the waveform or the trend of thecurrents and voltages measured.

The analog channels can be set to trigger the recording functionwhen the measured value falls below or exceeds the set values.

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 9

Page 10: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

The binary signal channels can be set to start a recording eitheron the rising or the falling edge of the binary signal or on both.

By default, the binary channels are set to record external orinternal relay signals, for example, the start or trip signals of therelay stages, or external blocking or control signals. Binary relaysignals, such as protection start and trip signals, or an externalrelay control signal via a binary input, can be set to trigger therecording. Recorded information is stored in a nonvolatilememory and can be uploaded for subsequent fault analysis.

9. Event logTo collect sequence-of-events information, the relay has anonvolatile memory capable of storing 1024 events with theassociated time stamps. The nonvolatile memory retains itsdata even if the relay temporarily loses its auxiliary supply. Theevent log facilitates detailed pre- and post-fault analyses offeeder faults and disturbances. The considerable capacity toprocess and store data and events in the relay facilitatesmeeting the growing information demand of future networkconfigurations.

The sequence-of-events information can be accessed either vialocal HMI or remotely via the communication interface of therelay. The information can also be accessed locally or remotelyusing the Web HMI.

10. Recorded dataThe relay has the capacity to store the records of the 128 latestfault events. The records enable the user to analyze the mostrecent power system events.

Each record includes current and angle values, start times ofthe protection blocks, time stamp, and so on.

The fault recording can be triggered by the start signal or thetrip signal of a protection block, or by both.

The available measurement modes include DFT, RMS andpeak-to-peak. In addition, the maximum demand current withtime stamp is recorded separately. By default, the records arestored in the non-volatile memory of the device.

11. Trip circuit supervisionThe trip circuit supervision continuously monitors the availabilityand operation of the trip circuit. It provides two open-circuit

monitoring functions that can be used to monitor the circuitbreaker’s control signal circuits. It also detects loss of circuit-breaker control voltage.

12. Self-supervisionThe relay’s built-in self-supervision system continuouslymonitors the state of the relay hardware and the operation ofthe relay software. Any fault or malfunction detected is used foralerting the operator.

A permanent relay fault blocks the protection functions toprevent incorrect operation.

13. Access controlTo protect the relay from unauthorized access and to maintaininformation integrity, the relay is provided with a four-level, role-based authentication system with administrator-programmableindividual passwords for the viewer, operator, engineer andadministrator levels. The access control applies to the localHMI, the Web HMI and PCM600.

14. Inputs and outputsThe relay is equipped with three phase-current inputs and oneresidual-current input. The phase-current inputs and theresidual current input are rated 1/5 A, that is, the inputs can beconnected to either 1 A or 5 A secondary current transformers.The optional residual current input of 0.2/1 A is normally used inapplications requiring sensitive earth-fault protection andfeaturing core-balance current transformers.

The rated currents of the analog inputs can be selected in therelay software. In addition, the binary input threshold (16…176V DC) can be selected by adjusting the relay’s parametersettings.

All binary input and output contacts are preconfiguredaccording to the configuration, but can be easily reconfiguredby setting application-based parameters using the signalconfiguration functionality of the local HMI and Web HMI.

See the input and output overview table and the terminaldiagram for more information about the inputs and outputs.

Table 4. Input/output overview

Conf. Analog channels Binary channels

CT VT BI BO

A 4 - 4 6

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

10 ABB

Page 11: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

15. Station communicationThe 611 series protection relays support the IEC 61850 and

Modbus® communication protocols. Operational informationand controls are available through these protocols. However,some communication functionality, for example, horizontalcommunication between the protection relays, is enabled onlyby the IEC 61850 communication protocol.

The IEC 61850 protocol is a core part of the relay as theprotection and control application is fully based on standardmodelling. The relay supports Edition 1 and Edition 2 versionsof the standard. With Edition 2 support, the relay has the latestfunctionality modelling for substation applications and the bestinteroperability for modern substations. It incorporates also fullsupport for standard device mode functionality supportingdifferent test applications. Control applications can utilize thenew safe and advanced station control authority feature.

The IEC 61850 communication implementation supportsmonitoring and control functions. Additionally, parametersettings, disturbance recordings and fault records can beaccessed using the IEC 61850 protocol. Disturbancerecordings are available to any Ethernet-based application inthe standard COMTRADE file format. The relay supportssimultaneous event reporting to five different clients on thestation bus. The relay can exchange data with other devicesusing the IEC 61850 protocol.

The relay can send binary and analog signals to other devicesusing the IEC 61850-8-1 GOOSE (Generic Object OrientedSubstation Event) profile. Binary GOOSE messaging can beemployed, for example, for protection and interlocking-basedprotection schemes. The relay meets the GOOSE performance

requirements for tripping applications in distributionsubstations, as defined by the IEC 61850 standard (<10 msdata exchange between the devices).

For redundant Ethernet communication, the relay offers twogalvanic Ethernet network interfaces. A third port with galvanicEthernet network interface is also available providingconnectivity for any other Ethernet device to an IEC 61850station bus inside a switchgear bay, for example connection ofa remote I/O. Ethernet network redundancy can be achievedusing the high-availability seamless redundancy protocol (HSR)or the parallel redundancy protocol (PRP) or with a self-healingring using Rapid Spanning Tree Protocol (RSTP) in managedswitches. Ethernet redundancy can be applied to Ethernet-based IEC 61850 and Modbus protocols.

The IEC 61850 standard specifies network redundancy whichimproves the system availability for substation communication.The network redundancy is based on two complementaryprotocols defined in the IEC 62439-3 standard: PRP and HSRprotocols. Both the protocols are able to overcome a failure of alink or switch with a zero switch-over time. In both theprotocols, each network node has two identical Ethernet portsdedicated for one network connection. The protocols rely onthe duplication of all transmitted information and provide a zeroswitch-over time if the links or switches fail, thus fulfilling all thestringent real-time requirements of substation automation.

In PRP, each network node is attached to two independentnetworks operated in parallel, thus providing zero time recoveryand continuous checking of redundancy to avoid failures. Thenetworks are completely separated to ensure failureindependence, and can have different topologies.

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 11

Page 12: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Managed

Ethernet switchIEC 61850 PRP Managed

Ethernet switch

GUID-AA005F1B-A30B-48F6-84F4-A108F58615A2 V1 EN

Figure 4. Parallel redundancy protocol (PRP) solution

HSR applies the PRP principle of parallel operation to a singlering. For each message sent, the node sends two frames, onethrough each port. Both the frames circulate in oppositedirections over the ring. Every node forwards the frames itreceives from one port to another to reach the next node. Whenthe originating sender node receives the frame it sent, it

discards the frame to avoid loops. The HSR ring with the 611series relays supports the connection of up to 30 relays. If morethan 30 relays are to be connected, it is recommended to splitthe network into several rings to guarantee the performance forreal-time applications.

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

12 ABB

Page 13: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

IEC 61850 HSR

Ethernet switch

Redundancy box

Redundancy box

Redundancy box

XX

Unicast traffic

Message is recognized as a duplicate and is

immediately forwarded

X Sending device removes the message from the ring

Devices not supporting HSR

Sen

der

Receiver

GUID-B24F8609-0E74-4318-8168-A6E7FCD0B313 V1 EN

Figure 5. High availability seamless redundancy (HSR) solution

The choice between the HSR and PRP redundancy protocolsdepends on the required functionality, cost and complexity.

The self-healing Ethernet ring solution enables a cost-efficientcommunication ring controlled by a managed switch withstandard RSTP support. The managed switch controls theconsistency of the loop, routes the data and corrects the data

flow in case of a communication switch-over. The relays in thering topology act as unmanaged switches forwarding unrelateddata traffic. The Ethernet ring solution supports the connectionof up to 30 relays. If more than 30 relays are to be connected, itis recommended to split the network into several rings. The self-healing Ethernet ring solution prevents single point of failureconcerns and improves the reliability of the communication.

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 13

Page 14: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Managed Ethernet switch

with RSTP support

Managed Ethernet switch

with RSTP support

Client A Client B

Network

Network

GUID-A19C6CFB-EEFD-4FB2-9671-E4C4137550A1 V2 EN

Figure 6. Self-healing Ethernet solution

All communication connectors, except for the front portconnector, are placed on integrated optional communicationmodules. The relay can be connected to Ethernet-basedcommunication systems via the RJ-45 connector (100Base-TX).

The Modbus implementation supports RTU, ASCII and TCPmodes. Besides the standard Modbus functionality, the relaysupports retrieval of time-stamped events, changing of theactive setting group and uploading of the latest fault records. Ifa Modbus TCP connection is used, five clients can beconnected to the relay simultaneously. Further, Modbus serialand Modbus TCP can be used in parallel and, if required, bothIEC 61850 and Modbus protocols can be run simultaneously.

When the relay uses the RS-485 bus for the serialcommunication, both 2-wire and 4-wire connections aresupported. Termination and pull-up/down resistors can beconfigured with jumpers on the communication card so externalresistors are not needed.

The relay supports several time synchronization methods with atime-stamping resolution of 1 ms. SNTP can be used inEthernet based time synchronization and IRIG-B is availablewith special time synchronization wiring.

For high accuracy time synchronization, the relay supports IEEE1588 v2 with a time-stamping resolution of 4 μs.• Ordinary Clock with Best Master Clock algorithm• One-step Transparent Clock for Ethernet ring topology• 1588 v2 Power Profile• Receive (slave): 1-step/2-step• Transmit (master): 1-step• Layer 2 mapping• Peer to peer delay calculation• Multicast operation

The required accuracy of grandmaster clock is +/-1 μs. Therelay can work as a master clock per the BMC algorithm if theexternal grandmaster clock is not available for short term.

The IEEE 1588 support is included in all variants having aredundant Ethernet communication module.

In addition, the relay supports time synchronization via Modbusserial communication protocol.

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

14 ABB

Page 15: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 5. Supported station communication interfaces and protocols

Interfaces/protocols Ethernet Serial

100BASE-TX RJ-45 100BASE-FX LC RS-485

IEC 61850 ● ● -

MODBUS RTU/ASCII - - ●

MODBUS TCP/IP ● ● -● = Supported

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 15

Page 16: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

16. Technical data

Table 6. Dimensions

Description Value

Width Frame 177 mm

Case 164 mm

Height Frame 177 mm (4U)

Case 160 mm

Depth 201 mm (153 + 48 mm)

Weight Complete protection relay 4.1 kg

Plug-in unit only 2.1 kg

Table 7. Power supply

Description Type 1 Type 2

Nominal auxiliary voltage Un 100, 110, 120, 220, 240 V AC, 50 and 60 Hz 24, 30, 48, 60 V DC

48, 60, 110, 125, 220, 250 V DC

Maximum interruption time in the auxiliary DCvoltage without resetting the relay

50 ms at Un

Auxiliary voltage variation 38...110% of Un (38...264 V AC) 50...120% of Un (12...72 V DC)

80...120% of Un (38.4...300 V DC)

Start-up threshold 19.2 V DC (24 V DC × 80%)

Burden of auxiliary voltage supply underquiescent (Pq)/operating condition

DC <12.5 W (nominal)/<15.0 W (max.)AC <13.5 W (nominal)/<16.0 W (max.)

DC <10.2 W (nominal)/<10.8 W (max.)

Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)

Fuse type T4A/250 V

Table 8. Energizing inputs

Description Value

Rated frequency 50/60 Hz

Current inputs Rated current, In 0.2/1 A1) 1/5 A2)

Thermal withstand capability:

• Continuously 4 A 20 A

• For 1 s 100 A 500 A

Dynamic current withstand:

• Half-wave value 250 A 1250 A

Input impedance <100 mΩ <20 mΩ

1) Ordering option for residual current input2) Residual current and/or phase current

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

16 ABB

Page 17: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 9. Binary inputs

Description Value

Operating range ±20% of the rated voltage

Rated voltage 24...250 V DC

Current drain 1.6...1.9 mA

Power consumption 31.0...570.0 mW

Threshold voltage 16...176 V DC

Reaction time <3 ms

Table 10. Signal output X100: SO1

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 5 A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R<40 ms, at48/110/220 V DC

1 A/0.25 A/0.15 A

Minimum contact load 100 mA at 24 V AC/DC

Table 11. Signal outputs and IRF output

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 5 A

Make and carry for 3.0 s 10 A

Make and carry 0.5 s 15 A

Breaking capacity when the control-circuit time constant L/R<40 ms, at48/110/220 V DC

1 A/0.25 A/0.15 A

Minimum contact load 10 mA at 5 V AC/DC

Table 12. Double-pole power output relays with TCS function

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 8 A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R<40 ms, at48/110/220 V DC (two contacts connected in series)

5 A/3 A/1 A

Minimum contact load 100 mA at 24 V AC/DC

Trip-circuit supervision (TCS):

• Control voltage range 20...250 V AC/DC

• Current drain through the supervision circuit ~1.5 mA

• Minimum voltage over the TCS contact 20 V AC/DC (15...20 V)

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 17

Page 18: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 13. Single-pole power output relays

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 8 A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R<40 ms, at48/110/220 V DC

5 A/3 A/1 A

Minimum contact load 100 mA at 24 V AC/DC

Table 14. Front port Ethernet interfaces

Ethernet interface Protocol Cable Data transfer rate

Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s

Table 15. Station communication link, fiber optic

Connector Fiber type1) Wave length Typical max.

length2)Permitted path attenuation3)

LC MM 62.5/125 or 50/125 μmglass fiber core

1300 nm 2 km <8 dB

1) (MM) multi-mode fiber, (SM) single-mode fiber2) Maximum length depends on the cable attenuation and quality, the amount of splices and connectors in the path.3) Maximum allowed attenuation caused by connectors and cable together

Table 16. IRIG-B

Description Value

IRIG time code format B004, B0051)

Isolation 500V 1 min

Modulation Unmodulated

Logic level 5 V TTL

Current consumption <4 mA

Power consumption <20 mW

1) According to the 200-04 IRIG standard

Table 17. Degree of protection of flush-mounted protection relay

Description Value

Front side IP 54

Rear side, connection terminals IP 20

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

18 ABB

Page 19: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 18. Environmental conditions

Description Value

Operating temperature range -25...+55ºC (continuous)

Short-time service temperature range -40...+85ºC (<16 h)1)2)

Relative humidity <93%, non-condensing

Atmospheric pressure 86...106 kPa

Altitude Up to 2000 m

Transport and storage temperature range -40...+85ºC

1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55ºC2) For relays with an LC communication interface, the maximum operating temperature is +70ºC

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 19

Page 20: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 19. Electromagnetic compatibility tests

Description Type test value Reference

1 MHz/100 kHz burst disturbance test IEC 61000-4-18IEC 60255-26, class IIIIEEE C37.90.1-2002

• Common mode 2.5 kV

• Differential mode 2.5 kV

3 MHz, 10 MHz and 30 MHz burst disturbancetest

IEC 61000-4-18IEC 60255-26, class III

• Common mode 2.5 kV

Electrostatic discharge test IEC 61000-4-2IEC 60255-26IEEE C37.90.3-2001

• Contact discharge 8 kV

• Air discharge 15 kV

Radio frequency interference test

10 V (rms)f = 150 kHz...80 MHz

IEC 61000-4-6IEC 60255-26, class III

10 V/m (rms)f = 80...2700 MHz

IEC 61000-4-3IEC 60255-26, class III

10 V/mf = 900 MHz

ENV 50204IEC 60255-26, class III

20 V/m (rms)f = 80...1000 MHz

IEEE C37.90.2-2004

Fast transient disturbance test IEC 61000-4-4IEC 60255-26IEEE C37.90.1-2002

• All ports 4 kV

Surge immunity test IEC 61000-4-5IEC 60255-26

• Communication 1 kV, line-to-earth

• Other ports 4 kV, line-to-earth2 kV, line-to-line

Power frequency (50 Hz) magnetic fieldimmunity test

IEC 61000-4-8

• Continuous• 1...3 s

300 A/m1000 A/m

Pulse magnetic field immunity test 1000 A/m6.4/16 µs

IEC 61000-4-9

Damped oscillatory magnetic field immunity test IEC 61000-4-10

• 2 s 100 A/m

• 1 MHz 400 transients/s

Voltage dips and short interruptions 30%/10 ms60%/100 ms60%/1000 ms>95%/5000 ms

IEC 61000-4-11

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

20 ABB

Page 21: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 19. Electromagnetic compatibility tests, continued

Description Type test value Reference

Power frequency immunity test Binary inputs only IEC 61000-4-16IEC 60255-26, class A

• Common mode 300 V rms

• Differential mode 150 V rms

Conducted common mode disturbances 15 Hz...150 kHzTest level 3 (10/1/10 V rms)

IEC 61000-4-16

Emission tests EN 55011, class AIEC 60255-26CISPR 11CISPR 12

• Conducted

0.15...0.50 MHz <79 dB (µV) quasi peak<66 dB (µV) average

0.5...30 MHz <73 dB (µV) quasi peak<60 dB (µV) average

• Radiated

30...230 MHz <40 dB (µV/m) quasi peak, measured at 10 mdistance

230...1000 MHz <47 dB (µV/m) quasi peak, measured at 10 mdistance

1…3 GHz <76 dB (µV/m) peak<56 dB (µV/m) average, measured at 3 mdistance

3…6 GHz <80 dB (µV/m) peak<60 dB (µV/m) average, measured at 3 mdistance

Table 20. Insulation tests

Description Type test value Reference

Dielectric tests 2 kV, 50 Hz, 1 min500 V, 50 Hz, 1 min, communication

IEC 60255-27

Impulse voltage test 5 kV, 1.2/50 μs, 0.5 J1 kV, 1.2/50 μs, 0.5 J, communication

IEC 60255-27

Insulation resistance measurements >100 MΩ, 500 V DC IEC 60255-27

Protective bonding resistance <0.1 Ω, 4 A, 60 s IEC 60255-27

Table 21. Mechanical tests

Description Requirement Reference

Vibration tests (sinusoidal) Class 2 IEC 60068-2-6 (test Fc)IEC 60255-21-1

Shock and bump test Class 2 IEC 60068-2-27 (test Ea shock)IEC 60068-2-29 (test Eb bump)IEC 60255-21-2

Seismic test Class 2 IEC 60255-21-3

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 21

Page 22: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 22. Environmental tests

Description Type test value Reference

Dry heat test • 96 h at +55ºC• 16 h at +85ºC1)

IEC 60068-2-2

Dry cold test • 96 h at -25ºC• 16 h at -40ºC

IEC 60068-2-1

Damp heat test • 6 cycles (12 h + 12 h) at +25°C…+55°C,humidity >93%

IEC 60068-2-30

Change of temperature test • 5 cycles (3 h + 3 h)at -25°C...+55°C

IEC60068-2-14

Storage test • 96 h at -40ºC• 96 h at +85ºC

IEC 60068-2-1IEC 60068-2-2

1) For relays with an LC communication interface the maximum operating temperature is +70oC

Table 23. Product safety

Description Reference

LV directive 2006/95/EC

Standard EN 60255-27 (2013)EN 60255-1 (2009)

Table 24. EMC compliance

Description Reference

EMC directive 2004/108/EC

Standard EN 60255-26 (2013)

Table 25. RoHS compliance

Description

Complies with RoHS directive 2002/95/EC

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

22 ABB

Page 23: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Protection functions

Table 26. Three-phase non-directional overcurrent protection (PHxPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz

PHLPTOC ±1.5% of the set value or ±0.002 × In

PHHPTOC1)

andPHIPTOC

±1.5% of set value or ±0.002 × In(at currents in the range of 0.1…10 × In)±5.0% of the set value(at currents in the range of 10…40 × In)

Start time 2)3) Minimum Typical Maximum

PHIPTOC:IFault = 2 × set Start valueIFault = 10 × set Start value

16 ms 11 ms

19 ms 12 ms

23 ms 14 ms

PHHPTOC1) and PHLPTOC:IFault = 2 × set Start value

22 ms

24 ms

25 ms

Reset time <40 ms

Reset ratio Typically 0.96

Retardation time <30 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 4)

Suppression of harmonics RMS: No suppressionDFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…Peak-to-Peak: No suppressionP-to-P+backup: No suppression

1) Not included in REM6112) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one phase

with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements3) Includes the delay of the signal output contact4) Includes the delay of the heavy-duty output contact

Table 27. Three-phase non-directional overcurrent protection (PHxPTOC) main settings

Parameter Function Value (Range) Step

Start value PHLPTOC 0.05...5.00 × In 0.01

PHHPTOC1) 0.10...40.00 × In 0.01

PHIPTOC 1.00...40.00 × In 0.01

Time multiplier PHLPTOC and PHHPTOC1) 0.05...15.00 0.01

Operate delay time PHLPTOC and PHHPTOC1) 40...200000 ms 10

PHIPTOC 20...200000 ms 10

Operating curve type2) PHLPTOC Definite or inverse timeCurve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

PHHPTOC1) Definite or inverse timeCurve type: 1, 3, 5, 9, 10, 12, 15, 17

PHIPTOC Definite time

1) Not included in this product2) For further reference, see the Operation characteristics table

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 23

Page 24: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 28. Non-directional earth-fault protection (EFxPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz

EFLPTOC ±1.5% of the set value or ±0.002 × In

EFHPTOCandEFIPTOC1)

±1.5% of set value or ±0.002 × In(at currents in the range of 0.1…10 × In)±5.0% of the set value(at currents in the range of 10…40 × In)

Start time 2)3) Minimum Typical Maximum

EFIPTOC1):IFault = 2 × set Start valueIFault = 10 × set Start value

16 ms11 ms

19 ms12 ms

23 ms14 ms

EFHPTOC and EFLPTOC:IFault = 2 × set Start value

23 ms

26 ms

29 ms

Reset time Typically 40 ms

Reset ratio Typically 0.96

Retardation time <30 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 4)

Suppression of harmonics RMS: No suppressionDFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…Peak-to-Peak: No suppression

1) Not included in this product2) Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on

statistical distribution of 1000 measurements3) Includes the delay of the signal output contact4) Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20

Table 29. Non-directional earth-fault protection (EFxPTOC) main settings

Parameter Function Value (Range) Step

Start value EFLPTOC 0.010...5.000 × In 0.005

EFHPTOC 0.10...40.00 × In 0.01

EFIPTOC 1) 1.00...40.00 × In 0.01

Time multiplier EFLPTOC and EFHPTOC 0.05...15.00 0.01

Operate delay time EFLPTOC and EFHPTOC 40...200000 ms 10

EFIPTOC1) 20...200000 ms 10

Operating curve type2) EFLPTOC Definite or inverse timeCurve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

EFHPTOC Definite or inverse timeCurve type: 1, 3, 5, 9, 10, 12, 15, 17

EFIPTOC1) Definite time

1) Not included in this product2) For further reference, see the Operation characteristics table

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

24 ABB

Page 25: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 30. Negative-sequence overcurrent protection for machines (MNSPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the measured current: fn±2 Hz

±1.5% of the set value or ±0.002 × In

Start time1)2) Minimum Typical Maximum

IFault = 2.0 × set Start value 23 25 ms 28 ms

Reset time Typically 40 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Negative-sequence current before = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements

2) Includes the delay of the signal output contact3) Start value multiples in range of 1.10...5.00

Table 31. Negative-sequence overcurrent protection for machines (MNSPTOC) main settings

Parameter Function Value (Range) Step

Start value MNSPTOC 0.01...0.50 × In 0.01

Operating curve type MNSPTOC ANSI Def. TimeIEC Def. TimeInv. Curve AInv. Curve B

-

Operate delay time MNSPTOC 100...120000 ms 10

Operation MNSPTOC 1 = on5 = off

-

Cooling time MNSPTOC 5...7200 s 1

Table 32. Loss of load supervision (LOFLPTUC)

Characteristic Value

Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz

±1.5% of the set value or ±0.002 × In

Start time Typically 300 ms

Reset time Typically 40 ms

Reset ratio Typically 1.04

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 25

Page 26: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 33. Loss of load supervision (LOFLPTUC) main settings

Parameter Function Value (Range) Step

Start value low LOFLPTUC 0.01...0.50 × In 0.01

Start value high LOFLPTUC 0.01...1.00 × In 0.01

Operate delay time LOFLPTUC 400...600000 ms 10

Operation LOFLPTUC 1 = on5 = off

-

Table 34. Motor load jam protection (JAMPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz

±1.5% of the set value or ±0.002 × In

Reset time Typically 40 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Table 35. Motor load jam protection (JAMPTOC) main settings

Parameter Function Value (Range) Step

Operation JAMPTOC 1 = on5 = off

-

Start value JAMPTOC 0.10...10.00 × In 0.01

Operate delay time JAMPTOC 100...120000 ms 10

Table 36. Motor start-up supervision (STTPMSU)

Characteristic Value

Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz

±1.5% of the set value or ±0.002 × In

Start time1)2) Minimum Typical Maximum

IFault = 1.1 × set Start detection A 27 ms 30 ms 34 ms

Operate time accuracy ±1.0% of the set value or ±20 ms

Reset ratio Typically 0.90

1) Current before = 0.0 × In, fn = 50 Hz, overcurrent in one phase, results based on statistical distribution of 1000 measurements

2) Includes the delay of the signal output contact

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

26 ABB

Page 27: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 37. Motor start-up supervision (STTPMSU) main settings

Parameter Function Value (Range) Step

Motor start-up A STTPMSU 1.0...10.0 × In 0.1

Motor start-up time STTPMSU 1...80 s 1

Lock rotor time STTPMSU 2...120 s 1

Operation STTPMSU 1 = on5 = off

-

Operation mode STTPMSU 1 = IIt2 = IIt, CB3 = IIt + stall4 = IIt + stall, CB

-

Restart inhibit time STTPMSU 0...250 min 1

Table 38. Phase reversal protection (PREVPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz

±1.5% of the set value or ±0.002 × In

Start time1)2) Minimum Typical Maximum

IFault = 2.0 × set Start value 23 ms 25 ms 28 ms

Reset time Typically 40 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Negative-sequence current before = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements

2) Includes the delay of the signal output contact

Table 39. Phase reversal protection (PREVPTOC) main settings

Parameter Function Value (Range) Step

Start value PREVPTOC 0.05...1.00 x In 0.01

Operate delay time PREVPTOC 100...60000 ms 10

Operation PREVPTOC 1 = on5 = off

-

Table 40. Thermal overload protection for motors (MPTTR)

Characteristic Value

Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz

Current measurement: ±1.5% of the set value or ±0.002 × In (at currentsin the range of 0.01...4.00 × In)

Operate time accuracy1) ±2.0% of the theoretical value or ±0.50 s

1) Overload current > 1.2 × Operate level temperature

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 27

Page 28: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 41. Thermal overload protection for motors (MPTTR) main settings

Parameter Function Value (Range) Step

Overload factor MPTTR 1.00...1.20 0.01

Alarm thermal value MPTTR 50.0...100.0% 0.1

Restart thermal Val MPTTR 20.0...80.0% 0.1

Weighting factor p MPTTR 20.0...100.0% 0.1

Time constant normal MPTTR 80...4000 s 1

Time constant start MPTTR 80...4000 s 1

Env temperature mode MPTTR 1 = FLC Only2 = Use input3 = Set Amb Temp

-

Env temperature Set MPTTR -20.0...70.0°C 0.1

Operation MPTTR 1 = on5 = off

-

Table 42. Circuit breaker failure protection (CCBRBRF)

Characteristic Value

Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz

±1.5% of the set value or ±0.002 × In

Operate time accuracy ±1.0% of the set value or ±20 ms

Reset time1) Typically 40 ms

Retardation time <20 ms

1) Trip pulse time defines the minimum pulse length

Table 43. Circuit breaker failure protection (CCBRBRF) main settings

Parameter Function Value (Range) Step

Current value CCBRBRF 0.05...2.00 × In 0.05

Current value Res CCBRBRF 0.05...2.00 × In 0.05

CB failure mode CCBRBRF 1 = Current2 = Breaker status3 = Both

-

CB fail retrip mode CCBRBRF 1 = Off2 = Without check3 = Current check

-

Retrip time CCBRBRF 0...60000 ms 10

CB failure delay CCBRBRF 0...60000 ms 10

CB fault delay CCBRBRF 0...60000 ms 10

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

28 ABB

Page 29: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Control functions

Table 44. Emergency start-up (ESMGAPC)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.5% of the set value or ±0.002 × Un

Table 45. Emergency start-up (ESMGAPC) main settings

Parameter Function Value (Range) Step

Motor stand still A ESMGAPC 0.05...0.20 × In 0.01

Operation ESMGAPC 1 = on5 = off

-

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 29

Page 30: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Condition monitoring and supervision functions

Table 46. Runtime counter for machines and devices (MDSOPT)

Description Value

Motor runtime measurement accuracy1) ±0.5%

1) Of the reading, for a stand-alone relay, without time synchronization

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

30 ABB

Page 31: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Measurement functions

Table 47. Three-phase current measurement (CMMXU)

Characteristic Value

Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz

±0.5% or ±0.002 × In(at currents in the range of 0.01...4.00 × In)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…RMS: No suppression

Table 48. Sequence current measurement (CSMSQI)

Characteristic Value

Operation accuracy Depending on the frequency of the measured current: f/fn = ±2 Hz

±1.0% or ±0.002 × Inat currents in the range of 0.01...4.00 × In

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

Table 49. Residual current measurement (RESCMMXU)

Characteristic Value

Operation accuracy At the frequency f = fn

±0.5% or ±0.002 × In(at currents in the range of 0.01...4.00 × In)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…RMS: No suppression

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 31

Page 32: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

17. Local HMIThe relay is equipped with a four-line liquid crystal display.Depending on the chosen font and language, the number ofvisible lines may vary. The display is designed for enteringparameter settings of the protection and control functions. It isalso suited for remotely controlled substations where the relayis only occasionally accessed locally via the front panel userinterface.

The display offers front-panel user interface functionality withmenu navigation and menu views. Depending on theconfiguration, the relay displays the related measuring values.

The local HMI includes a push button (L/R) for local/remoteoperation of the relay. When the relay is in the local mode, it canbe operated only by using the local front-panel user interface.When the relay is in the remote mode, it can executecommands sent from a remote location. The relay supports theremote selection of the local/remote mode via a binary input.This feature facilitates, for example, the use of an externalswitch at the substation to ensure that all relays are in the localmode during maintenance work and that the circuit breakerscannot be operated remotely from the network control center.

GUID-8DC31119-E1C4-42DA-848B-968FBF8F8F53 V1 EN

Figure 7. Front panel of 611 series relays

Table 50. Small display

Character size1) Rows in the view Characters per row

Small, mono-spaced (6 × 12 pixels) 5 20

Large, variable width (13 × 14 pixels) 3 8 or more

1) Depending on the selected language

18. Mounting methodsBy means of appropriate mounting accessories, the standardrelay case can be flush mounted, semi-flush mounted or wallmounted. The flush mounted and wall mounted relay cases canalso be mounted in a tilted position (25°) using specialaccessories.

Further, the relays can be mounted in any standard 19”instrument cabinet by means of 19” mounting panels availablewith cut-outs for one or two relays.Alternatively, the relays canbe mounted in 19” instrument cabinets by means of 4UCombiflex equipment frames.

For routine testing purposes, the relay cases can be equippedwith test switches, type RTXP 18, which can be mounted sideby side with the relay cases.

Mounting methods• Flush mounting• Semi-flush mounting• Semi-flush mounting in a 25° tilt• Rack mounting• Wall mounting• Mounting to a 19" equipment frame• Mounting with an RTXP 18 test switch to a 19" rack

Panel cut-out for flush mounting• Height: 161.5 ±1 mm• Width: 165.5 ±1 mm

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

32 ABB

Page 33: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

48153

160

177

177164

GUID-0ED32BE0-C610-4171-81A9-321735932451 V1 EN

Figure 8. Flush mounting

98

160

186

177

103

GUID-2B67CC71-7A0E-4EC8-86AA-9E94EE3C0BAF V1 EN

Figure 9. Semi-flush mounting

230

133107

25°

190

GUID-78E3ECC3-F2C7-4EFE-BC94-CAF89B5CA6D0 V1 EN

Figure 10. Semi-flush mounting in a 25º tilt

19. Relay case and plug-in unitThe relay cases are assigned to a certain type of plug-in unit.For safety reasons, the relay cases for current measuring relaysare provided with automatically operating contacts for short-circuiting the CT secondary circuits when a relay unit iswithdrawn from its case. The relay case is further provided witha mechanical coding system preventing the current measuringrelay units from being inserted into relay cases intended forvoltage measuring relay units.

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 33

Page 34: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

20. Selection and ordering dataThe relay type and serial number label identifies the protectionrelay. The label is placed above the local HMI on the upper partof the plug-in-unit. An order code label is placed on the side ofthe plug-in unit as well as inside the case. The order codeconsists of a string of letters and digits generated from therelay's hardware and software modules.

Use ABB Library to access the selection and orderinginformation and to generate the order number.

Product Selection Tool (PST), a Next-Generation Order NumberTool, supports order code creation for ABB DistributionAutomation IEC products with emphasis on, but not exclusivelyfor, the Relion product family. PST is an easy-to-use, online toolalways containing the latest product information. The completeorder code can be created with detailed specification and theresult can be printed and mailed. Registration is required.

# Description

1-2 Product Series, Size, Plug-in

Relay RE

3 Main application

Motor protection and control M

4-6 IED series

611 series 611

7 IED case, plugin unit, test switch

Complete relay H

Complete Relay with test switch installed and wired in 19” cover plate K

Complete Relay with test switch installed and wired for CombiFlex

rack mountingL

8 Standard

IEC B

CN C

R E M 6 1 1 H B A A A A 1 N N 1 1 G

GUID-CC0B4158-3448-440E-B4E4-225AE126A34C V4 EN

# Description

9-

10

Standard configuration / Analog Inputs

Motor protection [4I + 4BI (Io 1/5A)] AA

11 Communication module

Ethernet 100Base FX (LC) A

RS485 (including IRIG-B) C

12 Communication (Protocol)

IEC 61850 A

Modbus B

IEC 61850+Modbus C

13 Language

English 1

English and Chinese 2

Motor protection [4I + 4BI (Io 0.2/1A)] AB

Ethernet 100Base TX (RJ45)

None N

Ethernet 100Base TX (3xRJ45) with HSR/PRP

B

D

R E M 6 1 1 H B A A A A 1 N N 1 1 G

GUID-9787276D-05CF-4538-97EC-6271C4CAF69E V4 EN

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

34 ABB

Page 35: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

# Description

14 Option 1

None

15 Option 2

None N

16 Power supply

48-250 Vdc; 100-240 Vac 1

24-60 Vdc 2

17-

18

Version

Product version 2.0 1G

N

R E M 6 1 1 H B A A A A 1 N N 1 1 G

GUID-73E4C093-EA58-456B-9708-962D9AFC1C4B V3 EN

Example code: R E M 6 1 1 H B A A A A 1 N N 1 1 G

Your ordering code:

Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Code

GUID-CED8B9E7-26EF-429A-BACD-995B41278BD9 V3 EN

Figure 11. Ordering key for complete relays

21. Accessories and ordering data

Table 51. Mounting accessories

Item Order number

Semi-flush mounting kit 1MRS050696

Wall mounting kit 1MRS050697

Inclined semi-flush mounting kit 1MRS050831

19” rack mounting kit with cut-out for one relay 1MRS050694

19” rack mounting kit with cut-out for two relays 1MRS050695

Mounting bracket for one relay with test switch RTXP in 4U Combiflex (RHGT 19” variant C) 2RCA022642P0001

Mounting bracket for one relay in 4U Combiflex (RHGT 19” variant C) 2RCA022643P0001

19” rack mounting kit for one relay and one RTXP18 test switch (the test switch is not included in the delivery) 2RCA021952A0003

19” rack mounting kit for one relay and one RTXP24 test switch (the test switch is not included in the delivery) 2RCA022561A0003

22. ToolsThe protection relay is delivered as a preconfigured unit. Thedefault parameter setting values can be changed from the front-panel user interface (local HMI), the Web browser-based userinterface (Web HMI) or Protection and Control IED ManagerPCM600 in combination with the relay-specific connectivitypackage.

PCM600 offers extensive relay configuration functions. Forexample, depending on the protection relay, the relay signals,application, graphical display and single-line diagram, and IEC61850 communication, including horizontal GOOSEcommunication, can be modified with PCM600.

When the Web HMI is used, the protection relay can beaccessed either locally or remotely using a Web browser(Internet Explorer). For security reasons, the Web HMI is

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 35

Page 36: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

enabled by default but it can be enabled via the local HMI. TheWeb HMI functionality can be limited to read-only access.

The relay connectivity package is a collection of software andspecific relay information, which enables system products andtools to connect and interact with the protection relay. Theconnectivity packages reduce the risk of errors in system

integration, minimizing device configuration and setup times.Further, the connectivity packages for protection relays of thisproduct series include a flexible update tool for adding oneadditional local HMI language to the protection relay. Theupdate tool is activated using PCM600, and it enables multipleupdates of the additional HMI language, thus offering flexiblemeans for possible future language updates.

Table 52. Tools

Description Version

PCM600 2.7 or later

Web browser IE 8.0, IE 9.0, IE 10.0 or IE 11.0

REM611 Connectivity Package 2.0 or later

Table 53. Supported functions

Function Web HMI PCM600

Relay parameter setting ● ●

Saving of relay parameter settings in the relay ● ●

Signal monitoring ● ●

Disturbance recorder handling ● ●

Alarm LED viewing ● ●

Access control management ● ●

Relay signal configuration ●1) ●2)

Modbus® communication configuration (communication management) - ●

Saving of relay parameter settings in the tool - ●

Disturbance record analysis - ●

XRIO parameter export/import ● ●

IEC 61850 communication configuration, GOOSE (communicationconfiguration) - ●

Phasor diagram viewing ● -

Event viewing ● ●

Saving of event data on the user's PC ● ●

Online monitoring - ●● = Supported

1) Relay input/output signal configuration2) For horizontal GOOSE signals only

23. Cyber securityThe relay supports role based user authentication andauthorization. It can store 2048 audit trail events to a nonvolatilememory. The nonvolatile memory is based on a memory typewhich does not need battery backup or regular componentexchange to maintain the memory storage. FTP and Web HMI

use TLS encryption with a minimum of 128 bit key lengthprotecting the data in transit. In this case the usedcommunication protocols are FTPS and HTTPS. All rearcommunication ports and optional protocol services can bedeactivated according to the required system setup.

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

36 ABB

Page 37: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

24. Terminal diagram

REM611

16

17

1918

X100

67

89

10

111213

15

14

2

1

3

45

22

212324

SO2

TCS2

PO4

SO1

TCS1

PO3

PO2

PO1

IRF

+

-Uaux

20

1) The protection relay features an automatic short-circuit mechanism in the CT connector when plug-in unit is detached

1)

X120

12

3

4

567

89

1011

12

14Io

IL1

IL2

BI 4

BI 3

BI 2

BI 1

IL3

1/5A

N1/5A

N1/5A

N1/5A

N

13

GUID-BCAF17E3-F7C4-49B1-B09D-95A963354E3B V2 EN

Figure 12. Terminal diagram of configuration A

25. CertificatesDNV GL has issued an IEC 61850 Edition 2 Certificate Level A1

for Relion® 611 series. Certificate number: 10010221-OPE/INC15-2723.

DNV GL has issued an IEC 61850 Edition 1 Certificate Level A1

for Relion® 611Y5 series. Certificate number: 10010221-OPE/INC 15-2736.

Additional certificates can be found on the product page.

26. ReferencesThe www.abb.com/substationautomation portal providesinformation on the entire range of distribution automationproducts and services.

The latest relevant information on the REM611 protection relayis found on the product page. Scroll down the page to find anddownload the related documentation.

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 37

Page 38: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

27. Functions, codes and symbols

Table 54. Functions included in the relay

Function IEC 61850 IEC 60617 IEC-ANSI

Protection

Three-phase non-directional overcurrent protection, lowstage, instance 1 PHLPTOC1 3I> (1) 51P-1 (1)

Three-phase non-directional overcurrent protection,instantaneous stage, instance 1 PHIPTOC1 3I>>> (1) 50P/51P (1)

Non-directional earth-fault protection, low stage,instance 1 EFLPTOC1 Io> (1) 51N-1 (1)

Non-directional earth-fault protection, high stage,instance 1 EFHPTOC1 Io>> (1) 51N-2 (1)

Negative-sequence overcurrent protection formachines, instance 1 MNSPTOC1 I2>M (1) 46M (1)

Negative-sequence overcurrent protection formachines, instance 2 MNSPTOC2 I2>M (2) 46M (2)

Loss of load supervision LOFLPTUC1 3I< 37

Motor load jam protection JAMPTOC1 Ist> 51LR

Motor start-up supervision STTPMSU1 Is2t n< 49,66,48,51LR

Phase reversal protection PREVPTOC1 I2>> 46R

Thermal overload protection for motors MPTTR1 3Ith>M 49M

Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF

Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)

Other

Input switch group1) ISWGAPC ISWGAPC ISWGAPC

Output switch group2) OSWGAPC OSWGAPC OSWGAPC

Selector3) SELGAPC SELGAPC SELGAPC

Minimum pulse timer (2 pcs)4) TPGAPC TP TP

Minimum pulse timer (2 pcs, second resolution),instance 1 TPSGAPC TPS (1) TPS (1)

Move (8 pcs), instance 1 MVGAPC MV (1) MV (1)

Control

Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB

Emergency start-up ESMGAPC1 ESTART ESTART

Condition monitoring and supervision

Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)

Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)

Runtime counter for machines and devices MDSOPT1 OPTS OPTM

Logging

Disturbance recorder RDRE1 DR (1) DFR(1)

Fault recorder FLTRFRC1 - FR

Measurement

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

38 ABB

Page 39: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

Table 54. Functions included in the relay, continued

Function IEC 61850 IEC 60617 IEC-ANSI

Three-phase current measurement, instance 1 CMMXU1 3I 3I

Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0

Residual current measurement, instance 1 RESCMMXU1 Io In

1) 10 instances2) 20 instances3) 6 instances4) 10 instances

28. Document revision history

Document revision/date Product version History

A/2011-11-18 1.0 First release

B/2012-05-04 1.0 Content updated

C/2012-05-23 1.0 Content updated

D/2014-06-17 1.0 Content updated

E/2016-02-22 2.0 Content updated to correspond to the product version

F/2017-10-31 2.0 Content updated

G/2019-04-10 2.0 Content updated

Motor Protection and Control 1MRS757469 GREM611 Product version: 2.0

ABB 39

Page 40: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

40

Page 41: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker
Page 42: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker
Page 43: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker
Page 44: Product Guide REM611 Motor Protection and Control · Motor start blocking GUID-16710A62-D0E5-4D3C-B2CB-5EAE7C1F8D9E V2 EN Figure 2. Motor protection and control of contactor and circuit-breaker

ABB Distribution SolutionsDistribution AutomationP.O. Box 699FI-65101 VAASA, FinlandPhone +358 10 22 11

www.abb.com/mediumvoltagewww.abb.com/relion

© Copyright 2019 ABB. All rights reserved. 1MR

S75

7469

G