Leakage Current and Harmonic Reduction in Transformerless Grid Connected PV Systems
Problems of harmonic voltage in the LV distribution grid
Transcript of Problems of harmonic voltage in the LV distribution grid
23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015
Paper 0403
CIRED 2015 1/5
PROBLEMS OF HARMONIC VOLTAGE IN THE LV DISTRIBUTION GRID
Martin KASPIREK David MEZERA Karel PROCHAZKA
E.ON Czech Republic – Czech Rep. E.ON Czech Republic – Czech Rep. EGC EnerGoConsult CB – Czech Rep.
[email protected] [email protected] [email protected]
ABSTRACT
The supply territory of the company E.ON Distribution in
the Czech Republic (operated by the company E.ON
Czech Republic) accounts for approximately 1.5 million
customers. One of the detected problems was with
harmonic voltage in approximately 7% LV (low voltage)
distribution grids. The survey is based on the evaluation
of approximately 600 voltage quality (VQ) measurements
which were made in points of the LV grid with known
phase-earth system impedance. This system impedance
was measured in each point of VQ measurement and was
compared with the reference value according to the IEC
60725 standard. The purpose of this paper is to
determine the average value of each harmonic voltage, to
compare this value with the limit value according to the
EN 50160 standard and to answer the questions: Which
harmonics create problems in the LV distribution grid? Is
the problem detected in the weak grids or even in the
grids with better network impedance than reference value
according to the IEC 60725standard? What is the reason,
that some harmonic voltages violate the limits according
to the EN 50 160 standard?
INTRODUCTION
The electricity market liberalisation brings considerable pressure on the introduction of penalties for insufficient voltage quality parameters. In case of poor voltage quality, these penalties should be of the electricity rebate payment nature. Another issue included in this paper is the responsibility for the poor voltage quality and the consequent damage. The analysis of VQ parameters in the distribution grid is necessary for a definition of an interface between the customer and the distribution network operator (DNO) under the terms of the responsibility for poor VQ. We make approximately nine hundred week VQ measurements a year so we have good practice with VQ measurements in the LV distribution grid. All measurements are systematically archived and it is possible to filter them for example according to the voltage level or exceeded VQ parameters. If possible, the system impedance phase-earth is measured in the point of the VQ measurement. A special measuring instrument Zerotest 46 N is used – see Fig. 1. The system impedance in all three phases is measured and the average value is calculated and used in the following graphs. Values of the measured system impedance are included in the archival system so that the link between VQ measurement, or more precisely values of VQ parameters and system impedance, is available for each VQ measurement.
Fig. 1: The measuring instrument Zerotest 46N for the system impedance (phase-earth) measurement
REFERENCE IMPEDANCE
IEC 60725 [1] sets the reference impedance value, or
more precisely, a reference (relative) short circuit
impedance (short circuit power) value for the LV
distribution network and electric equipment of nominal
current less than 16/75 A. It is assumed that if the
required impedance value is met at the point of network
connection, an electric appliance will not produce any
adverse retroactive impacts on the network therefore no
interference in the network will occur.
Electric equipment with
nominal current
Reference impedance
Zphase-earth
up to 16A 0,47 Ω
up to 75 A 0,35 Ω
Tab. 1: Reference impedance for equipment with current
ratings ≤16A/75A
The question is when the DNO and when the customer is
responsible for the poor voltage quality. . It can be used
as the guideline for the reference impedance according to
the IEC60725 standard [1] however keeping of this value
from the side of DNO will not guarantee a voltage quality
for all LV grids.
HARMONIC VOLTAGE DEPENDENCY ON
THE SYSTEM IMPEDANCE
The dependence of harmonics on phase-earth system
impedance can be demonstrated by means of graphs. The
survey is based on the evaluation of approximately 600
VQ measurements with known (measured) system
impedance phase-earth. The VQ measurements were
evaluated according to the EN 50160 standard [2] so
values of 95% percentile are evaluated in following
23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015
Paper 0403
CIRED 2015 2/5
graphs. The legend for the following graphs is: red
horizontal line – limit value for corresponding VQ
parameter, red vertical line – reference impedance 0.47Ω,
black vertical line - reference impedance 0.35Ω.
Fig. 2: Evaluation of 2
nd voltage harmonic
Fig. 3: Evaluation of 3
rd voltage harmonic
Fig. 4: Evaluation of 4
th voltage harmonic
Fig. 5: Evaluation of 5th
voltage harmonic
Fig. 6: Evaluation of 6th
voltage harmonic
Fig. 7: Evaluation of 7th
voltage harmonic
Fig. 8: Evaluation of 8th
voltage harmonic
Fig. 9: Evaluation of 9th
voltage harmonic
23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015
Paper 0403
CIRED 2015 3/5
Fig. 10: Evaluation of 10th
voltage harmonic
Fig. 11: Evaluation of 11th
voltage harmonic
Fig. 12: Evaluation of 12th
voltage harmonic
Fig. 13: Evaluation of 13
th voltage harmonic
Fig. 14: Evaluation of 14
th voltage harmonic
Fig. 15: Evaluation of 15th
voltage harmonic
Fig. 16: Evaluation of 16th
voltage harmonic
Fig. 17: Evaluation of 17th
voltage harmonic
23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015
Paper 0403
CIRED 2015 4/5
Fig. 18: Evaluation of 18
th voltage harmonic
Fig. 19: Evaluation of 19
th voltage harmonic
Fig. 20: Evaluation of 20
th voltage harmonic
Fig. 21: Evaluation of 21st voltage harmonic
Fig. 22: Evaluation of 22
nd voltage harmonic
Fig. 23: Evaluation of 23
rd voltage harmonic
Fig. 24: Evaluation of 24
th voltage harmonic
Fig. 25: Evaluation of 25
th voltage harmonic
23rd International Conference on Electricity Distribution Lyon, 15-18 June 2015
Paper 0403
CIRED 2015 5/5
HARMONIC CLASSIFICATION
Three groups of harmonics can be designed according to
the analysis in the previous caption.
Class A
Class A includes harmonics with the ample reserve to the
limit value according to the EN 50160 standard. The limit
value according to the EN 50160 standard is exceeded
only exceptionally and only in grids with the system
impedance worse than reference value. Class A includes
the 2nd, 7th, 11th, 13th, 17th, 20th, 22nd, 23rd, 24th and
25th harmonic.
Class B
Class B includes harmonics with the small reserve to the
limit value according to the EN 50160 standard. The limit
value according to the EN 50160 standard is exceeded
only exceptionally and but in grids with the system
impedance better than reference value too. Class B
includes the 3rd, 4th, 5th, 6th, 8th, 9th, 10th, 12th, 14th,
16th, 18th, 19th and 21nd harmonic.
Class C
Class C includes harmonics with zero reserve to the limit
value according to the EN 50160 standard. The limit
value according to the EN 50160 standard is exceeded in
many cases and in the grids with the system impedance
better than reference value too. Class C includes the 15th
harmonic.
CONCLUSION
In Fig. 15 you can see that the 15th harmonic voltage
differs from other voltage harmonics. The problem with
the 15th harmonic was detected in grids with better
system impedance than reference value. This could be
caused by high penetration of appliances producing 15th
harmonics current which isn’t our case, the measurement
was done in standard rural and small city area. The
second reason could be a low limit value for the 15th
voltage harmonic when measurement uncertainty for
generally used power quality analyzers (class S according
to the IEC 61000-4-30:2008 standard [3]) is +/- 0.5% of
nominal voltage. The standard IEC 62749 [5]
recommends limit values up to the 50th
voltage harmonic
and the limits for some harmonics (with the multiple of
three) are only 0.2% of the nominal voltage. Precise VQ
analyzers with low system noise should be used for
measuring of low harmonic voltage values. For some
measuring equipment the internal noise of the instrument
could disqualify VQ analyzer from measuring of such
low harmonic levels [4]. The experience of the DNO
shows that no complaints regarding harmonic voltage
were obtained up till now. Exceeding of the limit value
for the 15th harmonic voltage is hardly perceived by the
customer and has no influence on operation of commonly
used electrical devices. The goal of this paper is to point
out that there are problems with some non-standard VQ
parameters in LV distribution grids and that there are
problems in grids with good (better than reference)
system impedance. The value of reference impedance can
be used for a decision about the responsibility for poor
voltage quality in the distribution grid. If real value of the
system impedance in the delivery point of the customer is
better (smaller) than the reference value and problems
with voltage quality are detected, the customer is
responsible for the impermissible impact on the grid. If
real value of the system impedance in the delivery point
of the customer is worse (higher) than the reference
value, then DNO is responsible for poor voltage quality
in the distribution grid. Because the DNO has a duty to
meet the requirements according to the EN 50160
standard for all customers, the DNO has to do corrective
measures. These measures are based mostly on the
refurbishment of the grid and require investment cost
from the side of DNO. It is necessary to work out
analysis before the decision of VQ parameters. Such a
partial analysis is described in this paper but we suppose
that the working group IEC SC77A/WG8 (61000-2-2)
should define new limits of compatibility with the focus
on harmonics with the multiple of three.
REFERENCES [1] IEC/TR 60725:2012 Consideration of reference
impedances and public supply network impedances for use in determining the distrurbance characteristics of electrical equipment having a rated current ≤75A per phase, International electrotechnical commision, ISBN 978-2-83220-161-9
[2] EN 50160 Ed.3 Voltage characteristics of electricity supplied by public distribution systems. Brussels: European Committee for Electrotechnical Standardization, 2010. 20 p.
[3] IEC 61000-4-30 Ed.3.0 Electromagnetic compatibility (EMC): Part 4-30: Testing and measurement techniques – Power quality measurement methods. Geneva: International Electrotechnical Commission
[4] BILIK, Petr; ZIDEK, Jan. Precise Harmonic Component Analyzer based on Virtual Instrumentation. In Conference proceeding of the International Conference of Applied Electronics APPEL 2010, Pilsen, 8.-9.9.2010. Pilsen : Department of Applied Electronics and Telecommunications, FEE, ZCU Plzen, 2010, p. 39 - 42. ISBN 978-80-7043-865-7
[5] IEC/TS 62749 Ed.1 Assessment of power quality – Characteristics of electricity supplied by public networks