Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama...
-
Upload
phungtuyen -
Category
Documents
-
view
231 -
download
2
Transcript of Power System Protection - UPRMlorama/Week8b.pdf · Power System Protection Dr. Lionel R. Orama...
Power System Protection
Dr. Lionel R. Orama Exclusa, PEWeek 8
Copyright L.R. Orama 2006 2
Distance Relays
• Mason– Chapter 4, pgs. 61-76
Copyright L.R. Orama 2006 3
Objectives
• R-X Diagrams• Operating Principles of:
– Impedance– Admittance (Mho)– Reactance
• Memory Action
Copyright L.R. Orama 2006 4
Distance Relays
• Respond to phasor ratio of input voltage & input current to relay (V/I)
• They are directional• They have high speed• Used to protect transmission lines• Usually induction cup design
Copyright L.R. Orama 2006 5
Construction
Copyright L.R. Orama 2006 6
R-X Diagram
• Can use impedance or R-X diagram to analyze relay operation
1. Plot relay characteristic
2. Plot impedance “seen” by the relay (Z relay)
Copyright L.R. Orama 2006 7
Copyright L.R. Orama 2006 8
Copyright L.R. Orama 2006 9
Copyright L.R. Orama 2006 10
Copyright L.R. Orama 2006 11
Copyright L.R. Orama 2006 12
Impedance Relay
Copyright L.R. Orama 2006 13
Admittance (Mho) Relay
Copyright L.R. Orama 2006 14
Offset Mho
Copyright L.R. Orama 2006 15
Offset Mho
Copyright L.R. Orama 2006 16
Angle Impedance Relay
Non-Directional
Not appropriate to work alone
Copyright L.R. Orama 2006 17
Reactance Relay
Non-Directional
Copyright L.R. Orama 2006 18
Distance Relays• Operating Time
– Induction Cup: High Speed
• Adjustments– Reach: Tapped
Transformer• Rises or lowers voltage on
restraining coil• Range of Z to cover down
the line
– Offset: Tapped Reactor• For offset Mho, adjust ZT
Copyright L.R. Orama 2006 19
Application of Distance Relays to Transmission Line Protection
• Phase distance relays• Ground distance relays (will not be
covered)• Step distance relays
– Usually 3 zones
• Distance better than overcurrent– Faster– Easier coordination– Permit higher line loading
Copyright L.R. Orama 2006 20
System Impedance on Relay Base
Copyright L.R. Orama 2006 21
System Impedance on Relay Base
Copyright L.R. Orama 2006 22
PT Connections-Phase Distance Relays
600577115
4.66
10115
115 3
→===
===
V
kV
V
VPTR
V
kV
V
VPTR
LGout
LGinLG
LLout
LLinLL
Copyright L.R. Orama 2006 23
CT Connection to Op Coils
Copyright L.R. Orama 2006 24
Impedances Detected by Phase Relays
3 Phase Fault
Phase-Phase Fault
Relay setting based on Positive Sequence Impedance (Z1)
Copyright L.R. Orama 2006 25
Step Distance Relaying
Objectives• Zones of protection• Effect of arc resistance• Effect of infeed• Methods to reduce size of distance relay
characteristic
Copyright L.R. Orama 2006 26
Zones of Protection-3 Zones
• 3 zones (Primary & Backup)Purpose: Provide high speed tripping for internal faults• Relay must be set to underreach• Does not cover entire line• Zone 1 settings:
– Reach:80-90%– Time: No time delay
Zone 1
Copyright L.R. Orama 2006 27
Zones of Protection
Purpose: Cover remaining 10-20% of AB segment• Zone 2 must reach beyond B• Will detect faults on CD segment• Must have time delay• Zone 2 settings:
– Reach:120%– Time: 0.2-0.4 seconds
Zone 2
Copyright L.R. Orama 2006 28
Zones of Protection
Purpose: Provides Backup protection for faults on adjacent line
• Do not set such that load can cause a trip• Zone 3 settings:
– Reach:120% of ZAB+ZCD
– Time: 0.4-1.0 seconds
Zone 3
Equivalent Relays at B and D looking on the other direction
Copyright L.R. Orama 2006 29
Three Zones of Protection Using Mho Relays
• Advantage– Lots of fault coverage
• Disadvantage– Characteristic gets
close to ZLOAD
GCY - GE Mho
Copyright L.R. Orama 2006 30
Relay Characteristic Vs Arc Resistance
• illustrates increase RF coverage with mho relay (GCY) & reactance relay (GCX)– O1 & M3 operate - Zone 1– O2 & M3 operate – Zone 2– M3 operate – Zone 3– M1 – Zone1 using mho
Copyright L.R. Orama 2006 31
Zone 3 Setting with Infeed
Copyright L.R. Orama 2006 32
Zone 3 Setting with Infeed
danger
Copyright L.R. Orama 2006 33
Use of Blinders where Impedance may cause incorrect tripping
Zone 3 so big that ZLOAD gets inside of it
Angle Impedance relays to blind
Copyright L.R. Orama 2006 34
Reverse Third ZoneZAB+ZCDIF/IA
Copyright L.R. Orama 2006 35
Reverse Third Zone
Load
Copyright L.R. Orama 2006 36
Admittance Relay Settings• Reach: Diameter of Mho
Circle– Maximum Z that makes
relay operate
Copyright L.R. Orama 2006 37
Admittance Relay Settings
• t varies from 0.10 to 1.00 (t higher, smaller circle)• k is called Basic Minimum Reach is adjustable• Angle of maximum torque is adjustable• Offset is adjustable
Copyright L.R. Orama 2006 38
Impedances Detected by all Relays During B-C Fault
B-C Relay
A-B Relay
C-A Relay
Copyright L.R. Orama 2006 39
Impedances Detected by all Relays During B-C Fault