POWER | SENSYS : SYS 201 RT 2U
-
Upload
paulo-chong-santos -
Category
Engineering
-
view
59 -
download
8
Transcript of POWER | SENSYS : SYS 201 RT 2U
SYS 201 rt 2u
GROUP
Mission Critical Applications
INFINITE POWER
UPSUNINTERRUPTIBLE POWER SUPPLY
Double Conversion On-Line TechnologyRack Tower Convertible DesignVFI Voltage and Frequency IndependentWide Input Voltage and Frequency Windows
Active Harmonic Current ControlHot Swappable Battery
Unity Input Power Factor (PF=0.99)Battery Extension ModulesActive RS232 & USB & Extended Slot SimultaneouslySNMP Management Capability - Extend Slot
Mission Critical Servers, Telecommunications,Internet Servers, Network Components,
Local Area Networks, VOIP,Process & Telecom Equipment.
From 1000 VA to 3000 VA
02
UNITY INPUT POWER FACTOR
Meet today´s industry standard for energy saving and low reflected harmonic pollution to the utility.
SINGLE CHIP MICROPROCESSOR CONTROL
The SYS 201 RT 2U uses a field proven MPU to substantially reduce the component count. This provides greater reliability, functionality and smaller size than other designs. Using the latest high frequency techniques and quality components reliability is further increased. High system efficiency is achieved in all operating modes saving electricity.
powerfull LCDDisplay
SYSSYS 201 RT 2UFrom 1000 VA to 3000 VA
EASY COMMUNICATION PLUG & PLAY SELF DIAGNOSTICSEXTENDED BACK UP TIME
overview
In today´s world we are heavily reliant on technology and the power that drives it. If you do not have the correct protection you are putting your business at risk of downtime, lost data and evencomponent damage. The SYS 201 RT is a cost effective way of meeting your critical power needs and integrated seamlessly into the modern network environment.
User friendly display
An easy-to-read LED/LCD display provides real time indication of all major system parameters and status such as operation modes AC voltage, frequency, battery voltage, load level, temperature, etc.
SYS 201 RT 2U
The SYS 201 RT 2U is equipped with advanced digital tecnology, ideal for servers networks,storage, telecom and industrial application.
03
• Maximum flexibility- with the reversible screen can be usedin both tower and 19” rack configuration
• Enables integration into a wide variety of environments
• 2U compact design for alll range with built-in battery
• High power density solution
Battery
••
•
•
•
Remote reboot and load shedding reserving
backup power for critical loads.
Programble Receptables
Rack / Tower convertible DEsign
Convertible design
Extended runtime capability
Run like stabilizer
Powerful buit-in charger
Cold start function
Hot Swappable Battery
From 1000 VA to 3000 VA
Costumers Communications Interface
••
Standard- USB Port, RS232 Port, EPO (emergency off)
Intelligent Shutdown and Monitoring Software•• Patented Technology allows RS232, USB and SNMP slot to be activated simultaneously
Smart Slot Optionals - Internal 2nd RS232 Card, 2nd USB Card, Web / SNMP Card and Dry Contact Card
MODEL SYS 201 RT 2U RT 1kVA RT 2kVA RT 3kVA
INPUT
Voltage Window 160 - 280VAC
Frequency 50/60 Hz ± 5%
Phase Single Phase
Power Factor >0.99
OUTPUT
Voltage
Capacity
220 / 230 / 240VAC
2000 VA / 1600 W 3000 VA / 2400 W1000 VA / 800 W
Voltage Regulation ±%1
Frequency 50/60 Hz
Frequency Stability ± 0,1% unless synch to line
Crest Factor 3:1
Overload Capacity
Wave Form
100%-120% for 30 seconds 120%-150% for 10seconds
Sine Wave, ≤3% THD at linear load; ≤5% at Non-linear load
Inverter E�ciency
Transfer Time 0ms
BATTERY
Type Maintenance-free Sealed Lead Acid
Recharge Time 3 hours to 90%
DC Voltage 36V 72V
Internal Battery 3pcs 12V 7Ah 6pcs 12V 7Ah 6pcs 12V 9Ah
Built in max. Charge Current 1.8A 2.1A 2.7A
Back Up Time Full Load
Managment
5 min 4 min
Half Load 12 min
Advanced Battery Discharge Managment (A B D M)
10 min
Cold Start YES
DISPLAYLED Indicators
LCD Display
Audible and Visual
Hold Whole System
Input /Output Voltage and Frequency Values, Load%, Battery Voltage, Internal Temperature
ALARMS Line Failure, Battery Low, Over Load, Failure Events
PROTECTIONS Short circuit, over temperature, overload, high voltage, battery low, EPO
COMMUNICATIONInterface Type
EPO
Standard RS232 and USB
Contact for UPS Shutdown
Slots
Operating Compatible Platforms
Relay Contact Board, SNMP / WEB Card, 2nd RS323 CArd, 2nd USB Card
Windows 95/98/NT/2000/XP/Vista/Novell NetWare, Linux, etc...
ENVIRONMENT
Temparature 0°C - 40°C
Humidity 0% - 90% (without condensation)
Noise Level(1m distance) <50dBA (at 1 meter)
Protection Class IP 20
PHYSICAL
Outlets 6 pcs IEC or 2pcs Schuko 4pcs IEC or 2pcs Schuko
Dimensions (mm) WxDxH
Net Weight
440x405x88
16 28 30
440x650x88 440x650x88
STANDARDS EN 62040-1-1 (safety), EN 62040-2(EMC) CE, UL, CUL,FCC
Utility or Bypass, Battery Low, Battery Abnormal, Overload, Site Wiring Fault, Service Mode, UPS O�, UPS Abnormal
04
Model
SYS 201 RT 2UFrom 1000 VA to 3000 VA
www.sensysgroup.com
GROUP