Power Plant Controller for ConextTM Advisor 2

4
Your best companion for Grid Code compliance Solution at a glance Fully integrated in Conext™ Advisor 2 (CA2) the Power Plant Controller (PPC) is designed, provided and implemented by Schneider Electric Solar Business. The PPC is a dynamic system that commands SmartGen inverters and other compensation devices to fulfill the Grid Code and any Grid Utility requirements regarding active and reactive power control. The PPC is designed to get a fast and accurate response at the Point of Connection of the PV plant, and notably for the large Utility-scale PV plants, from few MW to hundreds of MW. The PPC offers the following functions: • Embedded reactive power operating modes • Embedded active power operating modes In hybrid power networks, the PPC controls the generating resources to maximize the economical/ profitable power source while ensuring load stability. Power Plant Controller for Conext TM Advisor 2 Extend Conext TM Advisor 2 features, adding PPC in your monitoring solution.

Transcript of Power Plant Controller for ConextTM Advisor 2

Page 1: Power Plant Controller for ConextTM Advisor 2

Your best companion for Grid Code compliance

Solution at a glance

Fully integrated in Conext™ Advisor 2 (CA2) the Power Plant Controller (PPC) is designed, provided and implemented by Schneider Electric Solar Business.

The PPC is a dynamic system that commands SmartGen inverters and other compensation devices to fulfill the Grid Code and any Grid Utility requirements regarding active and reactive power control.

The PPC is designed to get a fast and accurate response at the Point of Connection of the PV plant, and notably for the large Utility-scale PV plants, from few MW to hundreds of MW.

The PPC offers the following functions:• Embedded reactive power operating modes• Embedded active power operating modes

In hybrid power networks, the PPC controls the generating resources to maximize the economical/profitable power source while ensuring load stability.

Power Plant Controller for ConextTM Advisor 2

Extend ConextTM

Advisor 2 features, adding PPC in your

monitoring solution.

Page 2: Power Plant Controller for ConextTM Advisor 2

solar.schneider-electric.com | 2

Introducing Power Plant ControllerPower Plant Controller

Key features

Architecture

PERFORMANCE SCALABILITY ROBUSTNESS & GRID STABILITY

Grid Code compliance at Point Of

Interconnection

Fast and accurate responses

Strong robustness under any

scenario

Modular solution for fast and easy

adaptation to grid code worldwide

Compatibility with advanced

applications:

Hybrid plant (PV + Energy storage)

Pure energy storage plant

Energy management system

Fault Ride Through (LVRT / HVRT)

management

Loss of communication / Fallback

management

Ensures a high level of performance

and maximizes the revenue of your plant

Designed to be customized for

every plant around the world

Considers unexpected conditions on the

Grid or in the Plant to improve its integration

PPC system is based on: PLC Controller (Modicon M580)

in charge of the management of all control loops

ConextTM Advisor 2 Interface for monitoring and control

Power Meter connected at the Point of Connection of the PV plant or HV substation

Page 3: Power Plant Controller for ConextTM Advisor 2

Embedded power control loopsPower Plant Controller

solar.schneider-electric.com | 3

Reactive power operating modes

Voltage control Power factor control

Constant reactive power control

Active power operating modes

Active power curtailment Frequency control

For several reasons, like overload of the lines, excess of intermittent energy production, the Grid Utility may request to curtail the production. This kind of feature is presented in below figure. Active power curtailment can be applied with or without ramp rate control.

During an over-frequency event the PPC can quickly decrease the active power injection at POC proportionally to the frequency deviation.

Several control loops are implemented into the PPC to reach an accurate control of the power

and the voltage at the Point of Connection (POC) of the PV plant.

Maintains the grid voltage to the reference voltage at the POC by suppling or absorbing reactive power. The voltage control can be set without any droop or with a droop (between 0% and 10%).

Maintains a fix reactive power exchange at the POC, whatever the grid voltage and the PV plant production.

Maintains a constant Power Factor at the POC, whatever the grid voltage or the losses in the transformers of the PV plant.

U set point

Capacitive Q limit

Inductive Q limit

Del

ta U

min

Del

ta U

max

Capacitive droop

Inductive droop

Voltage deadband

Q

U

Q

P

Q

P

During an under-frequency event and when an active power limitation is in progress the PPC for PV plant can partially or fully release the active power limitation in order to participate to grid stability.

Potential PV production

Power snapshot at begin of frequency eventActual power injected at POCFrequency

P

t

tf

No freq. support

P limit start P limit stop

Potential PV production

P limit set pointActual power injected at POC

P

t

Page 4: Power Plant Controller for ConextTM Advisor 2

Two versions of PPCPower Plant Controller

solar.schneider-electric.com | 4

© 2018 Schneider Electric. All Rights Reserved. True Design for Service trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Ethernet/IP is a registered trademark of Odva, Inc. Specifications are subject to change without notice.

Designed for regular PV plants. It provides the basic control loop functions mentioned above. These functions can be set with the predefined parameters to meet the Grid Utility requirements of most PV plant projects.

Designed for large PV plants, challenging Grid Codes, or customer requests. It provides the basic control loop functions, and on request additional or more advanced functions depending of the PV plant specific needs.

PPC Universal PPC Evolution

PPC universal is integrated in the Gridbox main controller of ConextTM Advisor 2, therefore no additional controller is required.

To improve the response time of the PPC, the hardware and software architecture of the PPC Evolution includes an additional controller located in CA2 grid cabinet.

PPC Universal PPC Evolution

Functionalities

Total response time 2-5 s <1 s

Rea

ctiv

e P

ower

Con

trol

Reactive Power limitation

Power Factor

Reactive Power

Voltage Control

Capa bank, shunt reactor, STATCOM control -

Overnight reactive power or voltage control -

Act

ive

Pow

er

Con

trto

l PV

Pla

nt

Active Power LimitationOpen loop Close loop

Over Frequency -

Under Frequency -

Act

ive

Pow

er C

ontr

ol P

V +

E

SS

pla

nt/E

SS

pla

nt

Frequency support -

Power smoothing (ramp) -

SOC balancing for multiple storage system unit -

SOC Management -

Interface with an Energy Management System (EMS) -

Peak Power Shifting -

System

PLCEmbedded in the main controller

of the CA2 Grid MCCDedicated controller in the CA2 Grid MCC

Full integration in CA2 Cloud

Interface with inverters Modbus TCP/IPModbus TCP, 4-20 mA (through

Ethernet/IP distributed I/O) 

Interface with Utility

Compatible power meter ION7650, ION8650, ION8800 ION7650, ION8650, ION8800 (7)

Additional Services

There are some additional services that can be requested on-demand to complete the PPC offer, as design of new control loops, energy management system development, advanced modelling and simulation with grid integration study (PSSE, PSCAD, PowerFactory).

To have more information, please contact us at [email protected]

(1)

(1): Advanced control on request(2): Active Power reduction at POC(3): Release of active power limitation(4): Yes for over- and under-frequency

(2)

(3)

(4)

(5): Modbus TCP ou Analog and Digital Input / Ouput(6): Modbus TCP, DNP3 TCP, DNP3 Serial, IEC60870-5-101, IEC60870-5-104, Analog and Digital input / output, customization on request(7): More on request

(5)(5) (6)