power monitor.pdf

64
Powermonitor 3000 Master Module Catalog Numbers 1404-M4, 1404-M5, 1404-M6, 1404-M8 Installation Instructions Topic Page Important User Information 2 About This Publication 3 Safety Considerations 4 About the Power Monitor 5 Catalog Number Explanation 10 Quick Start Guidelines 11 Install the Powermonitor 3000 Unit 12 Product Dimensions 14 Wiring and Connecting the Power Monitor 18 Wiring Diagrams 21 Interpret the Status Indicators 47 Specifications 56 Additional Resources 61

description

Manual tecnico

Transcript of power monitor.pdf

  • Powermonitor 3000Master Module

    Catalog Numbers1404-M8

    Installation Instru

    Topic

    Important User Information

    About This Publication

    Safety Considerations

    About the Power Monitor

    Catalog Number Explanation

    Quick Start Guidelines

    Install the Powermonitor 3000 Un

    Product Dimensions

    Wiring and Connecting the Powe

    Wiring Diagrams

    Interpret the Status Indicators

    Specifications

    Additional Resources 1404-M4, 1404-M5, 1404-M6,

    ctions

    Page

    2

    3

    4

    5

    10

    11

    it 12

    14

    r Monitor 18

    21

    47

    56

    61

  • 2 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Important User Information

    Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the ApplicaSGI-1.1 available from your local http://literature.rockwellautomatequipment and hard-wired electrowide variety of uses for solid statsatisfy themselves that each inte

    In no event will Rockwell Automaresulting from the use or applicat

    The examples and diagrams in thvariables and requirements assocassume responsibility or liability f

    No patent liability is assumed by equipment, or software described

    Reproduction of the contents of tAutomation, Inc., is prohibited.

    Throughout this manual, when ne

    WARNINGIdentifies a hazardoudamage, o

    IMPORTANT Identifies the produc

    ATTENTIONIdentifies or death, pavoid a ha

    SHOCK HAZARD

    Labels mathat dange

    BURN HAZARD

    Labels mathat surfac- November 2009

    tion, Installation and Maintenance of Solid State Controls (Publication Rockwell Automation sales office or online at ion.com) describes some important differences between solid state mechanical devices. Because of this difference, and also because of the

    e equipment, all persons responsible for applying this equipment must nded application of this equipment is acceptable.

    tion, Inc. be responsible or liable for indirect or consequential damages ion of this equipment.

    is manual are included solely for illustrative purposes. Because of the many iated with any particular installation, Rockwell Automation, Inc. cannot or actual use based on the examples and diagrams.

    Rockwell Automation, Inc. with respect to use of information, circuits, in this manual.

    his manual, in whole or in part, without written permission of Rockwell

    cessary, we use notes to make you aware of safety considerations.

    information about practices or circumstances that can cause an explosion in s environment, which may lead to personal injury or death, property r economic loss.

    information that is critical for successful application and understanding of t.

    information about practices or circumstances that can lead to personal injury roperty damage, or economic loss. Attentions help you identify a hazard, zard and recognize the consequences.

    y be on or inside the equipment, for example, drive or motor, to alert people rous voltage may be present.

    y be on or inside the equipment, for example, drive or motor, to alert people es may reach dangerous temperatures.

  • Powermonitor 3000 Master Module 3

    About This PublicationExcept as noted, refer to the Powermonitor 3000 User Manual, publication 1404-UM001, for

    detailed information on the topics in this list. These installation instructions do not contain

    the following information:

    Information on mete

    Use of the display mo

    Discussion of comm

    Setpoint configuratio

    Discrete I/O configu

    Data logging includin

    Advanced features in

    Detection

    Powermonitor 3000 d

    Sample ladder diagra

    using various commu

    Display Module Insta

    This manual does not provid

    master module, firmware rev

    or Ethernet series B, firmwar

    and 1404-UM001D-EN-E, a

    http://literature.rockwellauto

    Terms and ConventionsThe following terms and con

    Terms and Conventions

    Abbreviation

    AWG

    CSA

    CT

    DM

    EMI

    ID

    IEC

    NEMA

    PLCPublication 1404-IN007F-EN-P - November 2009

    ring functionality and measurements

    dule for configuration, monitoring, and commands

    unication options, functionality, configuration, and operation

    n and operation

    ration and operation

    g Event Log, Trend Log, Min/Max Log, and Load Factor Log

    cluding Oscillography, Harmonic Analysis, and Transient

    ata tables

    ms for communicating with the Powermonitor 3000 unit by

    nication options

    llation Instructions, see publication 1404-IN005

    e information on functionality found in the Powermonitor 3000

    ision 3.0 and earlier, or Ethernet series A, all firmware revisions,

    e revision 2.0 earlier. Refer to publications 1404-IN007D-EN-E

    vailable as downloads from

    mation.com.

    ventions are used in this manual.

    Term

    American Wire Gauge

    Canadian Standards Association

    Current transformer

    Display module

    Electromagnetic interference

    Identification

    International Electrotechnical Commission

    National Electrical Manufacturers Association

    Programmable logic controller

  • 4 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Safety Consideratio

    PT Potential transformer (also known as VT in some countries)

    RAM

    RFI

    R I/O

    RMS

    SLC

    SPDT

    UL

    VA

    VAR

    CIP

    NAP

    ATTENTION Only qualifservice theany work, dlocked out.property da

    Never openWiring betterminal blpresent allprimary curdeath, prop

    Terms and Conventions

    Abbreviation Term- November 2009

    ns

    Random access memory

    Radio frequency interference

    Remote input/output

    Rootmeansquare

    Small logic controller

    Single pole double throw

    Underwriters Laboratories

    Voltampere

    Voltampere reactive

    Control and information protocol

    Network access port

    ied personnel, following accepted safety procedures, should install, wire, and Powermonitor 3000 unit and its associated components. Before beginning isconnect all sources of power and verify that they are de-energized and

    Failure to follow these instructions may result in personal injury or death, mage, or economic loss.

    a current transformer (CT) secondary circuit with primary current applied. ween the CTs and the Powermonitor 3000 unit should include a shorting ock in the CT secondary circuit. Shorting the secondary with primary current ows other connections to be removed if needed. An open CT secondary with rent applied produces a hazardous voltage, which can lead to personal injury, erty damage, or economic loss.

  • Powermonitor 3000 Master Module 5

    About the Power MoThe Bulletin 1404 Powermon

    needs of both producers and

    a master module that

    an optional display m

    an optional commun

    networks.

    optional external dev

    control, and managem

    IMPORTANT The Powermonitor 3000 unit is not designed for, nor intended for, use as a circuit protective device. Do not use this equipment in place of a motor overload relay or circuit protective r

    The relay ounit may becan configu

    Refer to theon configur

    Be sure to process.

    ATTENTION Electrostatguidelines

    Touc

    Wea

    Do n

    Use

    KeepPublication 1404-IN007F-EN-P - November 2009

    nitoritor 3000 unit is uniquely designed and developed to meet the

    users of electric power. A power monitor system consists of:

    provides metering and native RS-485 communication.

    odule for configuration, commands, and data display.

    ication port to serve data to other devices by using a choice of

    ices and applications that display and use data for reporting,

    ent of power and energy usage.

    elay.

    utput contacts and solid-state KYZ output contacts on the Powermonitor 3000 used to control other devices through setpoint control or communication. You re the response of these outputs to a communication failure.

    Powermonitor 3000 User Manual, publication 1404-UM001 for information ing the outputs.

    evaluate the safety impact of the output configuration on your plant or

    ic discharge can damage integrated circuits or semiconductors. Follow these when you handle the module:

    h a grounded object to discharge static potential.

    r an approved wrist strap-grounding device.

    ot open the module or attempt to service internal components.

    a static safe workstation, if available.

    the module in its static shield bag when not in use.

  • 6 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    The Powermonitor 3000 unit is a microprocessor-based monitoring and control device ideally

    suited for a variety of applications including these:

    Load Profiling - Using the configurable trending utility to log power parameters, such

    as real power, apparent power, and demand, for analysis of power usage by loads over

    time.

    Demand Managemen

    make informed decis

    Cost Allocation - Kn

    efficiencies.

    Distribution System M

    system topology, and

    Emergency Load She

    the event of sudden u

    Power System Contro

    factor.

    The power monitor is a soph

    metering devices. A single po

    meters. The power monitor p

    compact economical package

    Powermonitor 3000 MaThe master module contains

    terminations for power syste

    communication port, and a p

    Configuration

    Although the power monitor

    configure it for your particula

    the optional display module.

    write configuration, operatio

    native or optional communic

    Refer to the Powermonitor 3

    Optional external application

    RSPower, RSPowerPlus, and

    Contact your local Rockwell

    http://www.rockwellautoma

    software packages.- November 2009

    t - Understanding when and why demand charges occur lets you

    ions that reduce your electrical power costs.

    owing your actual energy costs promotes manufacturing

    onitoring - Using power parameters to show power flow,

    distribution equipment status.

    dding - Monitoring power usage to preserve system stability in

    tility outage.

    l - Managing system voltage, harmonic distortion, and power

    isticated modern alternative for traditional electro-mechanical

    wer monitor can replace many individual transducers and

    rovides you with easy to understand, accurate information in a

    .

    ster Modulethe main microprocessor-based monitoring functions, including

    m connections, status inputs, control outputs, a native RS-485

    ort for the display module.

    ships from the factory with default settings, you need to

    r requirements. You may configure the power monitor by using

    Alternately, you may use an external device or application to

    nal parameters and commands to the master module through its

    ation port.

    000 User Manual, publication 1404-UM001, for additional detail.

    s that you may use for power monitor configuration include

    RSEnergyMetrix software operating on a personal computer.

    Automation sales office or distributor, or visit

    tion.com/rockwellsoftware for more information on available

  • Powermonitor 3000 Master Module 7

    Communication

    Every Powermonitor 3000 unit comes with a native RS-485 communication port. The native

    port is suitable for communicating to devices including:

    PLC-5, SLC 500, and

    RSLinx software with

    Modbus RTU Master

    other third-party dev

    software that you dev

    You may also specify Powerm

    the following:

    Serial RS-232

    Remote I/O

    DeviceNet

    EtherNet/IP

    ControlNet

    A power monitor may be int

    control and monitoring systePublication 1404-IN007F-EN-P - November 2009

    ControlLogix processors.

    DDE/OPC server functionality.

    devices.

    ices.

    elop.

    onitor 3000 units with optional communication ports including

    egrated into a programmable controller or computer-based

    m by using any of the communication methods listed above.

  • 8 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Master Module with Communication Options

    Powermonitor 3000Powermonitor 3000

    Removable Status Input Connector

    Terminal Blocks

    Optional RS-232 Port

    OptiRem- November 2009

    Powermonitor 3000wermonitor 3000 Powermonitor 3000 Powermonitor 3000

    Status Indicators

    Display Module Port

    RS-485 (Native) Communication Port

    onal ote I/O Port

    Optional DeviceNet Port

    Optional Ethernet 10BaseT Port

    NAP Port

    ControlNet Channel A

    ControlNet Channel B

  • Powermonitor 3000 Master Module 9

    Powermonitor 3000 Display ModuleThe display module is an optional user-interface device. The display module provides the

    most economical and simplest method for setting up and configuring the master module for

    operation.

    The display module has a hig

    tactile feedback. Use the butt

    configuration, commands, an

    The display module is shippe

    power and serial communica

    display module fits into a sta

    Only one display module ma

    display module to configure

    Display ModulePublication 1404-IN007F-EN-P - November 2009

    hly visible, two-line LED display and four operator buttons with

    ons and display to navigate through a series of menus for

    d data display.

    d with a 3 m (10 ft) long, shielded four-pair cable that provides

    tion between the master module and the display module. The

    ndard ANSI four-inch analog meter cutout for panel mounting.

    y be connected to a master module, although you may use one

    and monitor any number of master modules; one at a time.

  • 10 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Catalog Number ExplanationThe Powermonitor 3000 unit has the following catalog number possibilities.

    140

    Bulletin Number

    1404 = Power Monitoring and Management Products

    Type o

    M4 = Master Mthree-phase msetpoints, I/O,logging.

    M5 = M4 funcfirmware upgrM6 or M8.

    M6 = M5 funcoscillography, detection, harmeasurement,setpoints and firmware upgr

    M8 = M6 functransient captanalysis, harmmeasurement Transducer anmodes.

    (1) In addition to Native RS-485 port.- November 2009

    4 - M4 05 A - ENT - 02

    f Device

    odule with etering, and data

    tionality, adeable to an

    tionality plus sag/swell monics 141 additional logging, adeable to M8.

    tionality plus ure and onics up to 63rd, d Energy Meter

    Current Inputs05 = 5 A

    Power Supply

    A = 120240V AC 5060 Hz or 125250V DCB = 24V DC

    000 = None232 = RS-232 SerialDNT = DeviceNetRIO = Remote I/OENT = EtherNet/IPCNT = ControlNet

    Communication

    Options(1)Revenue Accuracy Class

    Blank = Class 1 or Class 0.5

    02 = Class 0.2

  • Powermonitor 3000 Master Module 11

    Quick Start GuidelinesThe Powermonitor 3000 unit may be used in many electric power monitoring and control

    systems. Whether your power monitor is a complete power and energy monitor or a

    component in a plant- or ent

    steps to follow to make your

    1. Install your Powermo

    Refer to Install the P

    2. Install your optional

    Refer to the Bulletin

    1404-IN005.

    3. Determine your wirin

    power system.

    4. Connect control pow

    5. If used, connect wirin

    outputs.

    Refer to Wiring and C

    6. Configure the potent

    match those used in y

    7. Configure the Voltag

    configuration.

    8. Configure power mo

    This step varies depe

    9. Configure the power

    10. Configure other optio

    logging.

    Refer to the Powermonitor 3

    information on configuring aPublication 1404-IN007F-EN-P - November 2009

    erprise-wide energy management system, there are a few basic

    unit operational.

    nitor 3000 master module within a suitable enclosure.

    owermonitor 3000 Unit on page 12.

    display module.

    1404 Display Module Installation Instructions, publication

    g mode and install wiring between the power monitor and your

    er wiring, preferably from a separate source of control power.

    g to the status inputs, Form C control relay, and KYZ solid-state

    onnecting the Power Monitor on page 18.

    ial transformer (PT) and current transformer (CT) ratios to

    our power system connections.

    e mode of the power monitor to match your power system

    nitor communication.

    nding upon the communication option you have selected.

    monitor date and time.

    nal performance features, such as setpoint control and data

    000 User Manual, publication 1404-UM001, for complete

    nd operating your power monitor.

  • 12 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Install the Powermonitor 3000 UnitOnly qualified personnel should install, wire, service, and maintain this equipment. Refer to

    and follow the safety guidelines and pay attention to all warnings and notices in these

    instructions.

    See Product Dimensions on

    Mount the master module w

    washers.

    Mounting ConsideratioMount the Powermonitor 30

    enclosure that protects the m

    moisture, dust corrosive vapo

    also protect against personal

    The ambient temperature wit

    Specifications, page 56.

    Select an enclosure that prov

    monitor and other equipmen

    See Product Dimensions on

    monitor.

    When installed within a subs

    monitor be mounted within a

    circuits.

    ATTENTION Electrostatguidelines

    Touc

    Wea

    Do n

    Use

    Keep- November 2009

    page 14 for mounting hole dimensions.

    ith four No. 8-32 UNC or M4 screws with flat washers and lock

    ns00 master module in a suitable protective enclosure. Select an

    aster module from atmospheric contaminants, such as oil, water,

    rs and other harmful airborne substances. The enclosure should

    contact with energized circuits.

    hin the enclosure must remain within the limits listed in the

    ides adequate clearance for ventilation and wiring for the power

    t to be installed within the enclosure.

    page 14 for dimensions and spacing guidelines for the power

    tation or switchgear lineup, we recommend that the power

    low-voltage cubicle, isolated from medium- and high-voltage

    ic discharge can damage integrated circuits or semiconductors. Follow these

    when you handle the module:

    h a grounded object to discharge static potential.

    r an approved wrist strap grounding device.

    ot open the module or attempt to service internal components.

    a static safe work station, if available.

    the module in its static shield bag when not in use.

  • Powermonitor 3000 Master Module 13

    Mount the master module so that the metal grounding clips on the bottom of the mounting

    feet make direct contact with the enclosure mounting panel. If the mounting panel is painted,

    scrape or sand the paint down to bare metal. Use star washers to assure good long-term

    electrical contact with the mounting panel. Be sure that the mounting panel is properly

    connected to a low-impedanc

    Mount the enclosure in a pos

    master module with the vent

    assure adequate free convect

    IMPORTANT Use cautioobstructionPublication 1404-IN007F-EN-P - November 2009

    e earth ground.

    ition that allows full access to the master module. Install the

    ilation slots in the bottom and top of the unit unobstructed to

    ion cooling of its internal electronic components.

    n not to block the ventilation slots of the master module. All wiring and other s must be a minimum of 50 mm (2.0 in.) from the top and bottom of the unit.

  • 14 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Product DimensionsUse the dimensions in these drawings when mounting the master module.

    Master Module Dimensions

    14.66(0.577)

    5.35(0.211)

    125.0(4.921)

    Mounting

    114.30(4.50)

    163.17 (6.Used With

    Display Mo

    All dimensions are in mm (in.).- November 2009

    203.2 (8.000)Used With -232Communication

    Options

    Powermonitor 3000

    114.30(4.50)85.0

    (3.346)Mounting

    4.57 (0.180)4 Places

    10.43(0.411)

    135.15(5.321)

    184.15 (7.250)Used With

    Display Module424)outdule

    5.60(0.22)

  • Powermonitor 3000 Master Module 15

    Master Module Spacing

    50.8(2.00)

    215.9 (8.50)

    215.9 (8.50)

    General Notes:

    Recommended spacing

    Maintain approximateelectrical equipment.

    Do not block cooling vfrom top and bottom o

    Mount with ventilation

    Refer to Specifications

    All dimensions are in mm (in.).Publication 1404-IN007F-EN-P - November 2009

    Powermonitor 3000Powermonitor 3000

    Powermonitor 3000 Powermonitor 3000

    50.8(2.00)

    50.8 (2.00)Minimum

    50.8 (2.00)Minimum

    101.6 (4.00)

    101.6 (4.00)

    provides reasonable wiring clearance and ventilation.

    ly 102 mm (4.00 in.) clearance between master modules and other

    ents. Wiring and other obstructions must be 50 mm (2.00 in.) minimum f unit.

    opening in top and bottom to provide optimum free convection cooling.

    for ambient temperature requirements.

  • 16 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    System Accuracy ConsiderationsUser-supplied potential transformers (PTs) and current transformers (CTs), as well as wiring

    from the CTs to the power monitor, may reduce the accuracy of your power monitor system.

    The quality of the power mo

    signals presented to its input

    adequate for the desired met

    ANSI/IEEE C57.13, Requir

    transformer accuracy: class 1

    transformer accuracy class us

    PTs and CTs may introduce e

    errors.

    Ratio Errors

    The voltage ratio of a PT is t

    secondary turns. Manufacturi

    design specifies, causing an e

    Likewise, the current ratio of

    the primary and secondary. S

    and CTs.

    Other errors include magnet

    the transformer secondary. T

    may compensate for Ratio E

    PT and CT primary or secon

    For a PT, the Ratio Error incr

    impedance should be as high

    voltage supported by the tran

    including the impedance of t

    low as possible. This is why 4

    CTs with a 5 A secondary rat- November 2009

    nitors measurements can be no better than the quality of the

    terminals. It is your responsibility to select transformers that are

    ering accuracy.

    ements for Instrument Transformers, defines three classes of

    .2, class 0.6, and class 0.3. The application should dictate the

    ed.

    rrors in three areas: ratio errors, phase errors, and bandwidth

    he number of primary turns of wire divided by the number of

    ng tolerances may cause the ratio to be slightly different than the

    rror affecting the voltage input to the power monitor.

    a CT is a function of the ratio of the number of turns of wire on

    ome error in this ratio is quite common in commercial grade PTs

    ic core losses, winding impedance, and the burden, or load, on

    he combination of these errors is known as Ratio Error. You

    rror, if known, by adjusting the Basic Configuration entries for

    dary voltages.

    eases as the transformers load current increases, so its total load

    as possible. Conversely, a CTs Ratio Error increases as the

    sformer secondary increases, so its total load impedance,

    he wire connecting the CTs to the metering device, should be as

    mm2 (12 AWG) or larger is usually recommended for wiring

    ing.

  • Powermonitor 3000 Master Module 17

    Phase Error

    Phase shift between the primary to secondary signals is another source of inaccuracy

    introduced by the user-supplied PTs and CTs. Phase shift is generally not of concern for

    simple voltage or current mea

    calculating line to line voltage

    significant. The difference in

    errors. If all the PTs and CTs

    measured quantities. If, on th

    phase error of 6, there woul

    up as power factor and reacti

    adjusting the power monitor

    conditions of the power syste

    A typical PT phase error vari

    Applying higher than rated vo

    and cause even larger errors.

    The phase error in a CT incr

    greater than 80% of the CT r

    current is less than 20% of ra

    used for metering.

    The phase error of both PTs

    secondary. For best accuracy,

    CT loads as low as possible.

    Bandwidth Error

    For fundamental 50 or 60 Hz

    However, for waveforms with

    attenuate higher harmonics. M

    to 3 kHz, or the 50th harmon

    existing units, tend to be less

    Hz) harmonic. Wide-band in

    Bandwidth error cannot be c

    In addition, operation of eith

    saturation and resulting magn

    For more detailed informatio

    refer to Bulletin 1403 PowermPublication 1404-IN007F-EN-P - November 2009

    surements. When these signals are combined, for instance when

    or phase power, the effect of phase shift can become

    phase error among different transformers causes measurement

    introduced a 5 phase shift, there would be no error in the

    e other hand, the PTs had a phase error of 1 and the CTs had a

    d be a 5 phase error in the power calculation. This would show

    ve power (VAR) errors. Phase errors cannot be corrected by

    configuration since the errors change based on varying

    m.

    es from 10.25, depending on the PTs accuracy class.

    ltage increases the phase error and may saturate the transformer

    eases as its current decreases, and is lowest when the current is

    ating. Because significant phase error can occur when CT

    ted current, CTs sized for protection do not perform well when

    and CTs are also affected by the power factor of the load on the

    loads should be resistive, with PT loads as high as possible and

    measurements, bandwidth error has no affect on accuracy.

    significant harmonic content, the PTs and CTs you supply may

    ost instrument quality PTs have a flat frequency response out

    ic on a 60 Hz system. Current transformers, especially older,

    linear, with a flat response only out to 300 Hz, or the fifth (60

    strument CTs are available for improved frequency response.

    orrected by adjusting the power monitor configuration.

    er the PTs or CTs at extremely low frequencies may also cause

    itude and phase errors.

    n on instrument transformer accuracy and power measurement,

    onitor II Tutorial, publication 1403-1.0.2.

  • 18 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Wiring and Connecting the Power Monitor

    Wiring of the power monitor

    Connection of voltag

    Connection of contro

    Connection of status

    Communication wirin

    Follow these guidelines to he

    Install and connect a

    neatly and maintain a

    ventilation slots to av

    Furnish and install pr

    Use 600V wiring rate

    flame-retardant wire

    Use a shorting termin

    connected equipmen

    de-energizing the pow

    Use ring lugs or locki

    additional wiring secu

    Pay careful attention

    Connect the master m

    terminal and a dedica

    current-carrying wire

    short as possible. To

    feet should make elec

    Refer to Mounting C

    Connect all equipmen

    single point, low-imp

    For information on wire size

    Industrial Automation Wirin

    National Electrical Code pub

    ATTENTION Only qualifservice thedisconnectFailure to fdamage, or- November 2009

    includes the following steps:

    e and current signals from PTs and CTs

    l power

    inputs and status/control outputs

    g

    lp assure reliable, trouble-free operation of your power monitor:

    ll wiring. Use wire tags to identify connections. Bundle wiring

    minimum of 50 mm (2.0 in.) clearance from the master module

    oid a buildup of heat within the unit.

    operly-selected fuses for voltage signals and control power.

    d at 75 C (167 F) or higher. We strongly recommend the use of

    rated VW-1 by Underwriters Laboratories.

    al block (you provide) for CT wiring, to permit servicing

    t, such as the Powermonitor 3000 master module, without

    er system.

    ng spade lugs for voltage and current connections to provide

    rity and safety.

    to correct phasing and polarity for proper operation.

    odule to a low-impedance earth ground by using its grounding

    ted grounding wire at least as large as the largest

    connected to the master module. Keep grounding wiring as

    obtain maximum EMI immunity, the master module mounting

    trical contact with the mounting panel.

    onsiderations on page 12 for additional information.

    t ground terminals (master module, PT, and CT secondary) to a

    edance earth ground.

    s and types for grounding electrical equipment, refer to

    g and Grounding Guidelines, publication 1770-4.1, or the

    lished by National Fire Protection Association (NFPA).

    ied personnel, following accepted safety procedures, should install, wire, and power monitor and its associated components. Before beginning any work, all sources of power and verify that they are de-energized and locked out. ollow these instructions may result in personal injury or death, property economic loss.

  • Powermonitor 3000 Master Module 19

    Wiring the Master ModuleObserve all wire lug sizes and screw torques for terminal blocks wire sizes and screw torques.

    Refer to Specifications on page 56.

    Voltage and Current InpThe following sections give i

    Voltage Input and PT Select

    The power monitor is design

    line-to-line (347V line-to-neu

    PTs. Typical secondary voltag

    the nominal voltage of your p

    Connect short circuit protect

    monitor. If PTs are used, inst

    Current Inputs and Current T

    The current input on the pow

    User-supplied CTs are requir

    monitor. Select the CT prima

    ATTENTION Never openbetween thCT secondaconnectionproduces adamage, orPublication 1404-IN007F-EN-P - November 2009

    utsnformation on the selection of PTs and CTs.

    ion

    ed to connect directly to a power system rated up to 600V

    tral). Higher system voltages require the use of user-supplied

    e on a PT is 120V AC. Select the PT primary voltage to match

    ower system.

    ion, that you supply, between the power system and the power

    all short circuit protection on the high-voltage side of the PTs.

    ransformer (CT) Selection

    er monitor is designed for a 5 A nominal current signal.

    ed to connect your power system to the input of the power

    ry current to match the nominal current of your power system.

    a current-transformer secondary circuit with primary current applied. Wiring e CTs and the power monitor should include a shorting terminal block in the ry circuit. Shorting the secondary with primary current present allows other

    s to be removed if needed. An open CT secondary with primary current applied hazardous voltage, which can lead to personal injury, death, property economic loss.

  • 20 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    The shorting terminal block should be located adjacent to the Powermonitor 3000 master

    module so that it is readily accessible should service be needed. Use 2.5 mm2 (14 AWG) wire

    for the short run between the power monitor and the shorting terminal block. Use wiring of 4

    mm2 (12 AWG) or larger between the shorting terminal block and the CT so that the

    additional load of the wiring

    Do not install fuses or other

    Refer to System Accuracy Co

    Refer to Specifications on pa

    termination recommendation

    The wiring diagrams depict w

    need to configure your powe

    operation.

    Refer to the Powermonitor 3

    instructions on unit configur

    IMPORTANT You may involtage mo

    Refer to the

    Whether th

    Refer to th- November 2009

    does not overload the CT and reduce its accuracy.

    overcurrent protection in the secondary circuit of a CT.

    nsiderations on page 16 for guidelines on PT and CT selection.

    ge 56 for information on voltage isolation levels and wire

    s.

    iring methods for a variety of power system configurations. You

    r monitor to match the power system configuration for correct

    000 Unit User Manual, publication 1404-UM001, for detailed

    ation.

    stall either two or three CTs for any of the Delta or Open Delta wiring or des.

    wiring diagrams on pages 28, 30, and 33 for wiring of a two CT configuration.

    ere are two or three CTs in a circuit does not affect the voltage wiring.

    e Powermonitor 3000 Unit User Manual, publication 1404-UM001.

  • Powermonitor 3000 Master Module 21

    Wiring Diagrams

    Single-phase Direct Connection Wiring Diagram (Systems < 600V Nominal L-L)

    Load

    CustomeCT Shortin

    Test

    Fuse

    Fuse

    NL1 L2

    LinePublication 1404-IN007F-EN-P - November 2009

    CustomerChassisGround

    r-suppliedg Switch or Block

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Voltage Mode = Single Phase

    Y K ZR14 R11 R12

  • 22 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Single-phase with PTs Wiring Diagram

    Load

    CustomeCT Shortin

    Test

    Fuse

    Fuse

    NL1 L2

    LineVoltage Mode = Single Phase- November 2009

    CustomerChassisGround

    r-suppliedg Switch or Block

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • Powermonitor 3000 Master Module 23

    Three-phase Four-wire Wye Direct Connect Wiring Diagram(Systems < 600V Nominal L-L)

    Load

    Customer-sCT Shorting

    Test B

    Fuse

    Fuse

    Fuse

    NL1 L2 L3

    LineVoltage Mode = WyePublication 1404-IN007F-EN-P - November 2009

    CustomerChassisGround

    uppliedSwitch orlock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • 24 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Three-phase Four-wire with PTs Wiring Diagram

    Load

    Customer-sCT Shorting

    Test B

    Fuse

    Fuse

    Fuse

    NL1 L2 L3

    LineVoltage Mode = Wye- November 2009

    CustomerChassisGround

    uppliedSwitch orlock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • Powermonitor 3000 Master Module 25

    Three-phase Three-wire Grounded Wye Direct Connection Wiring Diagram (Systems < 600V Nominal L-L)

    Load

    Customer-CT Shorting

    Test B

    Fuse

    Fuse

    Fuse

    L1 L2 L3

    LineVoltage Mode = WyePublication 1404-IN007F-EN-P - November 2009

    CustomerChassisGround

    supplied Switch orlock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • 26 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Three-phase Three-wire Grounded Wye with PTs Wiring Diagram

    Load

    Customer-sCT Shorting

    Test Bl

    Fuse

    Fuse

    Fuse

    L1 L2 L3

    LineVoltage Mode = Wye- November 2009

    CustomerChassisGround

    uppliedSwitch orock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • Powermonitor 3000 Master Module 27

    Three-phase Three-wire Delta with Three PTs and Three CTs Wiring Diagram

    Load

    Customer-CT Shorting

    Test B

    Fuse

    Fuse

    Fuse

    L1 L2 L3

    LineVoltage Mode = Delta 3 CTPublication 1404-IN007F-EN-P - November 2009

    CustomerChassisGround

    supplied Switch orlock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • 28 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Three-phase Three-wire Delta with Three PTs and Two CTs Wiring Diagram

    Load

    Customer-sCT Shorting

    Test B

    L1 L2 L3

    Line Voltage Mode = Delta 2 CT

    Fuse

    Fuse

    Fuse- November 2009

    CustomerChassisGround

    uppliedSwitch orlock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • Powermonitor 3000 Master Module 29

    Three-phase Three-wire Open Delta with Two PTs and Three CTs Wiring Diagram

    Load

    Customer-sCT Shorting

    Test Bl

    Fuse

    Fuse

    L1 L2 L3

    Line Voltage Mode = Open Delta 3 CTPublication 1404-IN007F-EN-P - November 2009

    CustomerChassisGround

    uppliedSwitch orock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • 30 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Three-phase Three-wire Open Delta with Two PTs and Two CTs Wiring Diagram

    Load

    Customer-sCT Shorting

    Test Bl

    Fuse

    Fuse

    L1 L2 L3

    Line Voltage Mode = Open Delta 2 CT- November 2009

    CustomerChassisGround

    uppliedSwitch orock

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • Powermonitor 3000 Master Module 31

    Three-phase Three-wire Grounded L2(B) Phase Open Delta Direct Connect with Three CTs Wiring Diagram (Systems < 600V Nominal L-L)

    Load

    CustomCT Shor

    Te

    F

    F

    L1 L3

    Line Voltage Mode = Open Delta 3 CT

    DistributionGround

    Voltexc

    (otherwtransformPublication 1404-IN007F-EN-P - November 2009

    CustomerChassisGround

    er-suppliedting Switch orst Block

    Powermonitor 3000MasterModule

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    use

    use

    Y K ZR14 R11 R12

    age must noteed 347V L-L

    ise, step downers are required).

  • 32 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Three-phase Three-wire Delta Direct Connect with Three CTs Wiring Diagram (Systems < 600V Nominal L-L)

    Load

    Customer-CT Shorting

    Test B

    Fuse

    Fuse

    Fuse

    L1 L2 L3

    Line Voltage Mode = Direct Delta 3 CT- November 2009

    CustomerChassisGround

    supplied Switch orlock

    Powermonitor 3000MasterModule

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • Powermonitor 3000 Master Module 33

    Three-phase Three-wire Delta Direct Connect with Two CTs Wiring Diagram(Systems < 600V Nominal L-L)

    Load

    Customer-suCT Shorting Sw

    Test Bloc

    Fuse

    Fuse

    Fuse

    L1 L2 L3

    LineVoltage Mode = Direct Delta 2 CTPublication 1404-IN007F-EN-P - November 2009

    CustomerChassisGround

    pplieditch or

    k

    Powermonitor 3000MasterModule

    R14

    R11

    R12

    N/C N/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    L1(+)L2(-)

    GRD

    V1

    V2

    V3

    N

    Y K ZR14 R11 R12

  • 34 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Control PowerThe power monitor draws a nominal 15VA control power. Catalog numbers

    1404-MxxxA-xxx require nominal control power of 120240V AC or

    125250V DC. The power s

    nominal control power of 24

    Refer to Specifications on pa

    termination information.

    We strongly recommend that

    system being monitored. For

    consider the use of a user-sup

    continues to operate during p

    disturbances.

    You are required to connect

    disconnecting means and ove

    Status Inputs

    ATTENTION Do not appand are intassociated- November 2009

    upply is self-scaling. Catalog numbers 1404-MxxxB-xxx require

    V DC.

    ge 56 for acceptable control-voltage ranges and wiring

    you use a separate source of control power from the power

    applications where power system information is critical,

    plied uninterruptible power supply so that the power monitor

    ower system events such as significant sags, swells, and transient

    your power-monitor control power through user-supplied

    rcurrent protection. We recommend a 1 A slow-blow fuse.

    ly an external voltage to a Status Input. These inputs have an internal source ended for dry contact input only. Applying a voltage may damage the input or internal power supply.

    L1

    N/L2

    LocalFrameGround

    Powermonitor 3000Master Module

    R14

    R11

    R12

    N/CN/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    R14 R11 R12 Y K Z

    L1(+)

    L2(-)

    GRD

    V1

    S1

    S2

    SCOM

    V2

    V3

    N

    DISPLAYMODULE

    SHLD

    RS-485

  • Powermonitor 3000 Master Module 35

    All Status Inputs are common to an internal 24V DC source on the SCOM terminal. Status

    input terminals S1 and S2 are positive polarity and SCOM is negative polarity.

    For optimal EMC performance, we recommend wiring the status inputs by using shielded

    cable, Belden 8771 or equivalent, with the cable shield grounded at both ends where possible.

    Status Input Connections

    Applied resistance versus sta

    Condition 1 is 3.5 kW

    Condition 2 is 5.5 kW

    Isolation Voltage is 500V sta

    circuitry.

    Relay and KYZ OutputsControl Relay Connections o

    example of customer wiring

    connection, R14 is the norm

    connection. You must supply

    connected to the relay outpu

    Refer to Specifications on pa

    TIP Status InpuPowermoniPublication 1404-IN007F-EN-P - November 2009

    tus state

    or less = ON

    or greater = Off

    tus input to case and 500V status input to internal digital

    n page 36 shows the Form C relay output connections and an

    to a supply voltage and two loads. Terminal R11 is the common

    ally-open connection, and R12 is the normally-closed

    the wetting voltage and overcurrent protection for the circuit

    t.

    ge 56 for further information.

    t S2 can be configured for external demand pulse input. See the tor 3000 User Manual, publication 1404-UM001, for more information.

    Powermonitor 3000Master Module

    -+

    R14R14

    R11

    R12

    N/CN/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    R14 R11 R12 Y K Z

    L1(+)

    L2(-)

    GRD

    V1

    S1

    S2

    SCOM

    V2

    V3

    N

    DISPLAYMODULE

    SHLD

    RS-485

    N.O.Contact

    N.O.Contact

  • 36 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    The KYZ output is a solid-state relay designed for low-current switching and long life. Its

    normal application is to provide a pulse based on energy usage (or one of five other

    parameters) to an external pulse accumulator. Terminal K is common, Y is normally-open,

    and Z is normally-closed.

    Refer to the Powermonitor 3

    information on the applicatio

    Control Relay Connection

    Communication WiringMethods for connecting com

    provides guidelines for instal

    system.

    ATTENTION You must sground potconnected injury or de

    IMPORTANT You need tRefer to thecommunica

    10AFuse- November 2009

    000 Unit User Manual, publication 1404-UM001, for further

    n and operation of relay and KYZ outputs.

    s

    munication wiring vary from option to option. This section

    ling dependable communication wiring for your power monitor

    upply and install special high-level isolation when the possibility of high ential differences exists. This may occur when communicating with a unit to a power ground mat. Failure to install such isolation may lead to personal ath, property damage, or economic loss.

    o configure communication for each communication option.

    Powermonitor 3000 Unit User Manual, publication 1404-UM001, for detailed tion configuration instructions.

    L1 NPowermonitor 3000

    Master Module

    -+

    R14

    R11

    R12

    N/CN/C

    I1-I1+

    I2-I2+

    I3-I3+

    I4-I4+

    Y

    K

    Z

    R14 R11 R12 Y K Z

    L1(+)

    L2(-)

    GRD

    V1

    S1

    S2

    SCOM

    V2

    V3

    N

    DISPLAYMODULE

    SHLD

    RS-485

  • Powermonitor 3000 Master Module 37

    Native RS-485 Communication Wiring

    The RS-485 communication standard supports multi-drop communication among as many as

    32 stations or nodes.

    The RS-485 port is also used

    RS-485 communication wirin

    recommend that you use Bel

    maximum cable length is 121

    recommended and will result

    (star topology) or network (b

    If required, install suitable ter

    RS-485, install a 150 , 1/4 W

    some RS-485 conversion dev

    manufacturer of the converte

    At one end of each cable seg

    master module RS-485 port o

    low-impedance ground for h

    signals.

    The RS-485 port in the mast

    network, allowing the standa

    Configuration options for th

    the data rate. Defaults are:

    auto-detect protocol.

    device address = the

    communication rate =

    Use of RS-232 to RS-485 Co

    You need a user-supplied RS-

    monitor native RS-485 port a

    controller RS-232 port. Exam

    B&B Electronics, Inc

    Allen-Bradley catalogPublication 1404-IN007F-EN-P - November 2009

    for master module firmware upgrades in the field.

    g should be installed in a daisy-chain configuration. We

    den 9841 two-conductor shielded cable or equivalent. The

    9 m (4000 ft). Use of a star or bridging topology is not

    in signal distortion unless impedance is matched for each spur

    ridge topology).

    minating resistors at the ends of the daisy-chain cable. For

    terminating resistor (refer to the wiring diagram). Note that

    ices are equipped with internal terminating resistors. Contact the

    r for additional information.

    ment, connect the cable shield to the SHLD terminal of the

    r the converter. The SHLD connection provides a

    igh-frequency noise while attenuating DC or line-frequency

    er module presents a standard load impedance to the RS-485

    rd 32 nodes on a network.

    e native RS-485 port include the protocol, device address, and

    Device ID assigned at the factory in the range 1254.

    9600 bps.

    nverter

    232 to RS-485 converter for communication between the power

    nd an external device such as a computer or programmable

    ples include:

    . part number 485SD9TB (DB-9 connection).

    number 1761-NET-AIC.

  • 38 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    RS-485 Connections

    Shield Connection(See Note 4)

    IBM Compatible Personal Computer

    OrPLC Processor

    OrSLC Processor

    OrControlLogix Processor

    Notes:1)

    2)

    3)

    4)

    SHLD

    Three-device network shown. Up to 31 DF1Slave Devices can be connected to aDF1 Master without the use of a repeater.Terminating resistors may be required fornetworks with long distances or high noiseenvironments. Consult the RS-232 to RS-485converter manufacturer for more informaiton.Examples:B&B ElectronicsPart Number 485SD9TB (DB9)Allen-Bradley Cat. No. 1761-NET-AICShields should be connected atone end only to avoid ground loops.- November 2009

    Powermonitor 3000 Device #1

    Powermonitor 3000 Device #2

    Powermonitor 3000 Device #3 (Last)

    RS-485

    RS-485

    RS-485

    ExternalRS-232C to RS-485

    Converter(See Note 3)

    150 Terminating

    Resistor(See Note 2)

    150 Terminating

    Resistor(See Note 2)

    SHLD

    _

    +

    SHLD

    _

    +

    SHLD

    _

    +

    A

    B

  • Powermonitor 3000 Master Module 39

    Optional RS-232 Communication

    Powermonitor 3000 units with a catalog number ending in -232 are equipped with an RS-232

    serial communication port in addition to the native RS-485 port. The RS-232 communication

    standard supports point-to-p

    select either optional RS-232

    ports do not operate at the sa

    The optional RS-232 commu

    device. It requires a straight-t

    programmable controller ser

    requires a crossover cable for

    resistor is required.

    The maximum cable length i

    cable pinout information for

    connectors.

    Connecting Powermonito

    Powermo

    Or PLC Processor

    Or SLC Processor

    Or ControlLogix Processor

    IBM CompatiblePersonal ComputerPublication 1404-IN007F-EN-P - November 2009

    oint communication among two stations or nodes. You must

    communication or native RS-485 communication. The two

    me time.

    nication port is a data communication equipment (DCE) type

    hrough RS-232 cable to connect with personal computers,

    ial ports, and other data terminal equipment (DTE) devices. It

    connection to a modem or other DCE devices. No terminating

    s 15.24 m (50.0 ft). Refer to the following wiring diagrams for

    constructing your own cable using DB-9 and/or DB-25

    r 3000 Unit to Computer Communication Port

    nitor 3000

    5

    9 6

    1

    2

    1

    3

    4

    7

    8

    9

    6

    5

    TXD

    No connect

    No connect

    No connect

    RXD

    RTS (See Note 1)

    CTS (See Note 1)

    DSR (See Note 2)

    GND

    3

    2

    4

    5

    7

    3

    2 2

    3

    8

    7 7

    8

    55

    TXD

    RXD

    CTS (See Note 1)

    RTS (See Note 1)

    GND

    TXD

    RXD

    RTS (See Note 1)

    CTS (See Note 1)

    GND

    DB9 Female

    13

    25 14

    1

    DB-25 Female

    5

    9 6

    1

    DB9 Female

    5

    9 6

    1

    DB9 Female

    Powermonitor 3000 Device IBM Personal Computer IBM Personal Computer -

    Notes:1) Required only if you have enabled hardware handshaking.2) Internally pulled active in this DCE device - function not supported.3) Straight-through RS-232 cable required.

    RS-232

    Output

    Input

    Ground

    Output

    Input

    Output

    (See Note 3)

    SLC 500 Ch 0 PLC-5 Ch 0 - DB-25 Male

  • 40 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Optional Remote I/O Communication

    Powermonitor 3000 units with a catalog number ending in -RIO are equipped with a remote

    I/O port in addition to the native RS-485 port. Allen-Bradley remote I/O is a robust, widely

    used industrial data network

    monitor emulates a logical qu

    communication. The remote

    simultaneously, although ove

    Remote I/O communication

    recommend that you use Bel

    length is shown in the Remo

    Use of a star or bridging topo

    unless impendance is matche

    Be sure that all devices on yo

    communication rate. Certain

    rate.

    Install suitable terminating re

    At each end of each cable seg

    remote I/O port connector.

    high-frequency noise while at

    follow the standard blue/shie

    Data Highway Plus (clear/sh

    Remote I/O Communicati

    Communication Rate

    57.6 Kbps

    115.2 Kbps

    230.4 Kbps

    TIP Some remo- November 2009

    that uses twinaxial cable as its physical media. The power

    arter rack and supports both polled I/O and block transfer

    I/O port and the native RS-485 port may be used

    rall data throughput may be reduced.

    wiring should be installed in a daisy-chain configuration. We

    den 9463 twinaxial cable or equivalent. The maximum cable

    te I/O Communication Rates table and varies with the data rate.

    logy is not recommended and will result in signal distortion

    d for each spur (star topology) or network (bridge topology).

    ur remote I/O network are capable of operation at the desired

    legacy devices may not support a 230.4 Kbps communication

    sistors at the ends of the remote I/O network.

    ment, connect the cable shields to the SHLD terminal of the

    The SHLD connection provides a low-impedance ground for

    tenuating DC or line-frequency signals. We recommend that you

    ld/clear color scheme for remote I/O to differentiate it from

    ield/blue) cables.

    on Rates

    Distance, Max Terminating Resistor

    3048 m (10,000 ft) 150 , 1/4 W

    1542 m (5000 ft) 150 , 1/4 W

    762 m (2500 ft) 84 , 1/4 W

    te I/O devices are equipped with internal terminating resistors.

  • Powermonitor 3000 Master Module 41

    Configuration options for optional remote I/O communication include the logical rack

    address and module group (the power monitor is always one-quarter rack), and data rate.

    Defaults are rack 1, group 0, 57.6 Kbps.

    Refer to the Powermonitor 3

    Refer to the note at the begin

    Connecting PowermonitoIBM Compatible

    Personal Computer With R I/O

    Interface Card

    OrPLC Processor/

    PLC R I/O Scanner

    Or

    Or

    SLC R I/O Scanner

    ControlLogix R I/O Scanner

    Notes:1) Three-device network port Up to 32 slave devices can be connected per master R I/O channel.2) Terminating Resistors must be connected to each end of the R I/O network. Omit the terminating resistors if the devices already are equipped with interna terminating resistors.Publication 1404-IN007F-EN-P - November 2009

    000 Unit User Manual, publication 1404-UM001.

    ning of Communication Wiring on page 36.

    r 3000 Unit to Remote I/O Scanner

    2

    SHLD

    1

    2

    SHLD

    1

    2

    SHLD

    1

    2

    SHLD

    1

    82 Terminating

    Resistor(See Note 2)

    82 Terminating

    Resistor(See Note 2)

    BlueShield

    Clear

    rayed.

    l

    R I/O

    Powermonitor 3000 Device #3 (Last)

    R I/O

    Powermonitor 3000 Device #2

    R I/O

    Powermonitor 3000 Device #1

  • 42 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Optional DeviceNet Communication

    Powermonitor 3000 units with a catalog number ending in -DNT are equipped with a

    DeviceNet port in addition to the native RS-485 port. The DeviceNet network is an

    open-standard, multi-vendor

    media. The DeviceNet netwo

    network. The DeviceNet por

    although overall data through

    For detailed DeviceNet syste

    placement of terminating res

    DeviceNet Cable System Pla

    publication DNET-UM072.

    Refer to the note at the begin

    Install suitable terminating re

    Configuration options for op

    (MAC ID) and data rate. Def

    Refer to the Powermonitor 3

    TIP Some Devi

    IMPORTANT You must inthe DeviceN24V DC sup

    DeviceNet Terminal Bloc

    Terminal Signa

    1 COM (

    2 CAN_

    3 SHIEL

    4 CAN_

    5 VDC+ - November 2009

    , industrial device data network that uses a variety of physical

    rk also provides 24V DC power to devices connected to the

    t and the native RS-485 port may be used simultaneously,

    put may be reduced.

    m installation information, including cable lengths, the

    istors, power supplies, and other media components, refer to the

    nning and Installation Manual,

    ning of Communication Wiring on page 36.

    sistors at the ends of the DeviceNet cable.

    tional DeviceNet communication include the node address

    aults are node 63 and 125 Kbps.

    000 Unit User Manual, publication 1404-UM001.

    ceNet devices are equipped with internal terminating resistors.

    stall and wire a suitable 24V DC power supply to the V+ and V- conductors in et cable. The power monitor consumes less than 100 mA from the DeviceNet

    ply.

    k Wiring Connections

    l Function Color

    V-) Common Black

    L Signal Low Blue

    D Shield Uninsulated

    H Signal High White

    (V+) Power Supply Red

  • Powermonitor 3000 Master Module 43

    Connecting Powermonitor 3000 to Other DeviceNet Devices

    Optional Ethernet Communi

    Powermonitor 3000 units wi

    industry standard Ethernet 1

    The power monitor is design

    switches using standard UTP

    Ethernet Wiring Connection

    Powermonitor 3000 Etherne

    121 Terminating

    Resistor

    IBM Compatible Personal Comp1784 PCDPCMCIA Interface

    Or1770-KFD Interface Bo

    OrPLC With

    1771-SDN Scanner

    OrSLC With

    1747-SDN Scanner

    Powermonitor 3000 Device

    V-

    CAN_L

    SHLD

    Or Other DeviceNet Scanner DevicesPublication 1404-IN007F-EN-P - November 2009

    cation

    th catalog numbers ending in -ENT are equipped with an

    0/100baseT port.

    ed to connect easily to industry-standard Ethernet hubs and

    (unshielded twisted-pair) cables with RJ-45 connectors. The

    s table shows the cable and connector pin assignments and

    t Network Example shows a typical star network topology.

    (See Note 2)

    121 Terminating

    Resistor(See Note 2)

    uter With Card

    x

    Notes:1) Example network protrayed. For detailed DeviceNet installations, including cable requirements, refer to the DeviceNet Cable System Planning and Installation Manual, publication DNET-UM072.2) Terminating Resistors must be connected to each end of the DeviceNet network. Omit the terminating resistors if the devices already are equipped with internal terminating resistors.

    V+

    CAN_H

    V-

    V+

    CAN_L

    SHLD

    CAN_H

    V-

    V+

    CAN_L

    SHLD

    CAN_H

    V-

    V+

    CAN_L

    SHLD

    CAN_H

    +

    -

    DeviceNet24V DC

    Power Supply

  • 44 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Powermonitor 3000 Ether

    Ethernet Wiring Connections

    Terminal Signal

    1 TX+

    2 TX-

    3 RX+

    4

    5

    6 RX-

    7

    8

    LAN

    Powermonitor 3000Master Module #1

    Powermonitor 3000Master Module #2

    PRRRS- November 2009

    net Network Example

    Function

    TX+

    TX-

    RX+

    RX-

    Ethernet Switch

    ersonal Computer with SLinx and SPower 32 orSEnergyMetrixoftware

    PLC-5 Controller

    ControlLogix Controller

    SLC 500 Controller

  • Powermonitor 3000 Master Module 45

    Refer to the note at the beginning of Communication Wiring on page 36.

    Configuration options for optional Ethernet communication include the IP (Internet

    Protocol) address, subnet mask, default gateway IP address, and protocol.

    Defaults are:

    IP address: 192.168.2

    range 1247.

    subnet mask: 255.255

    default gateway IP ad

    protocol: CSP (PCCC

    Optional ControlNet Commu

    Powermonitor 3000 units wi

    ControlNet communication

    single media or redundant m

    redundant media is shown he

    Powermonitor 3000 Unit C

    17(in

    Redundant Media(optional)Publication 1404-IN007F-EN-P - November 2009

    54.xxx where xxx is the Device ID assigned at the factory in the

    .0.0.

    dress: 128.1.1.1.

    ) and CIP (EtherNet/IP network).

    nication

    th catalog numbers ending in -CNT are equipped with a

    interface. The ControlNet power monitor can be connected in a

    edia network. An example of a ControlNet network using

    re.

    ontrolNet Network Example

    56-CNBR 1756-A4 chassis)

    ControlNetNode

    ControlNet Link

    ControlNetNode

    Powermonitor 3000 Device

    Powermonitor 3000 Device

  • 46 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Refer to the following documentation for ControlNet network wiring requirements and

    general ControlNet information:

    ControlNet Coax Media Planning and Installation Guide,

    publication CNET-IN002

    ControlNet Coax Tap

    Connecting a Programming

    To connect a programming t

    following options:

    Using a 1784-KTC, 1

    cable

    Using a 1770-KFC co

    1786-CP cable

    1Powermonitor 3000 Device

    Powermonitor 3000 Device - November 2009

    Installation Instructions, publication 1786-IN007

    Terminal to the Network by Using a 1786-CP Cable

    erminal to the network using a 1786-CP cable, you have the

    784-KTCx, or 1784-PCC communication card and a 1786-CP

    mmunication interface, a serial or parallel connection, and a

    786-CP Cable1784-KTC, KTCx,PCIC, or PCC Card

    ControlNet Link

    1786-CP

    ControlNet Link

    Cable

    1770-KFC

    Serial or ParallelConnections

  • Powermonitor 3000 Master Module 47

    The 1786-CP cable can be plugged into any ControlNet products NAP to provide

    programming capability on the ControlNet network. A programming terminal connected

    through this cable is counted as a node and must have a unique network address.

    Interpret the Status The power monitor is equipp

    The three status indicators o

    modules with any communic

    three status indicators on the

    on the communication optio

    ATTENTION Use a 1786NAPs. UsinPublication 1404-IN007F-EN-P - November 2009

    Indicatorsed with six bi-color status indicators.

    n the left display the same information on power monitor

    ation option including native RS-485 communication only. The

    right have different labels and different indications depending

    n selected, as shown in these charts.

    -CP cable when connecting a programming terminal to the network through g a commercially available RJ-style cable could result in network failure.

  • 48 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Powermonitor 3000 Status Indicators

    RS-485 Status Indicators

    All Powermonitor 3000 M

    Indicator Status

    Module Status Off

    Steady red

    Steady gree

    RS-485 RX Off

    Flashing gre

    RS-485 TX Off

    Flashing gre

    Native RS-485 Communic

    Indicator Status

    F1 Off

    F2 Off

    F3 Off

    Powermonitor 3000

    Powermonitor 3000

    F1

    F2

    F3- November 2009

    odels Status Indicators

    Description

    Control power is off or insufficient.

    Major fault; internal self-test has failed. If a power cycle does not correct the problem, call customer support.

    n Power monitor is operating normally.

    The RS-485 bus is idle; no active data is present.

    en Active data is present on the RS-485 bus.

    Power monitor is not transmitting data onto the RS-485 bus.

    en Power monitor is transmitting data onto the RS-485 bus.

    ation Only (catalog numbers ending in -000)

    Description

    Not used.

    Not used.

    Not used.

    RX

    TXRS-485

    MODULE STATUS

  • Powermonitor 3000 Master Module 49

    RS-232 Status Indicators

    Remote I/O Status Indica

    RS-232 Optional Commun

    Indicator Status

    F1 Off

    RS-232 RX Off

    Flashing gre

    RS-232 TX Off

    Flashing gre

    Remote I/O Optional Com

    Indicator Status

    F1 Off

    F2 Off

    R I/O Off

    Flashing gre

    Steady gree

    Powermonitor 3000

    F1

    RX

    TX}RS-2

    Powermonitor 3000

    F1

    F2

    R I/OPublication 1404-IN007F-EN-P - November 2009

    tors

    ication (catalog numbers ending in -232)

    Description

    Not used.

    The RS-232 bus is idle; no active data is present.

    en Power monitor is receiving data.

    The power monitor is not transmitting any data onto the RS-232 bus.

    en The power monitor is transmitting data.

    munication (catalog numbers ending in -RIO)

    Description

    Not used.

    Not used.

    Remote I/O communication has not been established.

    en Remote I/O communication has been established but there are errors.

    n Remote I/O communication has been established.

    32

  • 50 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    DeviceNet Status Indicators

    EtherNet/IP Status Indica

    DeviceNet Optional Com

    Indicator Status

    F1 Off

    F2 Off

    Network Status Off

    Flashing gre

    Steady gree

    Flashing red

    Steady red

    EtherNet/IP Optional Com

    Indicator Status

    LNK Off

    Steady gree

    ACT Strobing or

    F1 Off

    Powermonitor 3000

    F1

    F2

    NETWORSTATUS

    F1

    LNK

    ACT

    F2

    NETWORSTATUS

    Powermonitor 3000wermonitor 3000- November 2009

    tors

    munication (catalog numbers ending in -DNT)

    Description

    Not used.

    Not used.

    Power is off or the power monitor is not online.

    en Network status is OK, no connections established.

    n Network status is OK, connections established.

    Recoverable communication failure; port is restarting.

    Nonrecoverable communication error; check wiring and configuration parameters.

    munication (catalog numbers ending in -ENT)

    Description

    No valid physical EtherNet connection.

    n Valid physical EtherNet connection.

    solid yellow Power monitor transmitting onto the EtherNet/IP network.

    Not used.

    K

    K

  • Powermonitor 3000 Master Module 51

    ControlNet Status Indica

    F2 Off Not used.

    Network Status Off

    Flashing gre

    Steady gree

    Flashing red

    Steady red

    Flashing gre

    ControlNet Optional Com

    Indicator Status

    Chan A and Chan B Off

    Steady red

    Alternating

    Alternating

    Steady gree

    Flashing gre

    Flashing red

    Flashing red

    Status Off

    Flashing gre

    EtherNet/IP Optional Communication (catalog numbers ending in -ENT)

    Indicator Status Description

    CHAN A

    CHAN B

    NETWORSTATUS

    Powermonitor 3000Publication 1404-IN007F-EN-P - November 2009

    tors

    No power.

    en No established connections.

    n Connected; has at least one established connection.

    Connection timeout; one or more connections to this device has timed-out.

    Duplicate IP; the IP address assigned to this device is already in use.

    en/red Selftest; this device is performing a power-up self-test.

    munication (catalog numbers ending in -ENT)

    Description

    No power or channel disabled.

    Faulted unit.

    red/green Self-test.

    red/off Incorrect node configuration.

    n Normal operation.

    en/off Temporary errors or node is not configured to go online.

    /off Media fault or no other nodes present on network.

    /green Incorrect network configuration.

    Normal operation.

    en Communication card power-up self-test.

    K

  • 52 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Access Self-test and Diagnostic Data

    You can access valuable diagnostic information by using the optional display module.

    1. Connect the display m

    2. Using the four contro

    Enter.

    The display module t

    to step through the s

    Display Module Status

    Display Des

    CAT NO The

    ACC CLASS Disp

    WIN NO The optio

    HW REV Disp

    FRN MASTER

    MODULE

    Show

    DEVICE ID ShowusedEthe

    SELFTEST

    STATUS

    Dispanom

    CODE FLASH Indic

    RAM Indic

    DATA FLASH Indic

    NVRAM Indic

    D ACQ Indic

    W DOG Indic

    CLOCK Indic

    COMM Disp

    COMM Disp

    COMM Dispnorm- November 2009

    odule to the master module by using the display module cable.

    l keys, navigate through the menus to Display - Status and press

    hen displays the following data. Use the up and down arrow keys

    tatus data.

    cription

    unit catalog number and series revision letter.

    lays the revenue-meter accuracy class.

    units unique Warranty Identification Number (needed for service and nal firmware enhancements).

    lays details of the digital board, analog board, and ASIC revisions.

    s the master-module firmware revision.

    s the units device ID number assigned at the factory. This number is also in the default address for native RS-485, and optional RS-232 and rNet/IP communication.

    lays a status code bitfield as a hex number. A non-zero value indicates an aly.

    ates the health of the flash-memory code area.

    ates the health of the random access memory.

    ates the health of the flash-memory data area.

    ates the health of the super-cap backed nonvolatile random-access memory.

    ates the data-acquisition system health.

    ates the system watchdog-timer status.

    ates the health of the real-time clock.

    lays the firmware revision of the optional communication card (if applicable).

    lays the optional communication-card type.

    lays the optional communication-status bitfield as a hex number (0000 hex is al for -232 and -RIO units, and 9001 hex is normal for -DNT and -ENT units).

  • Powermonitor 3000 Master Module 53

    Refer to the Powermonitor 3

    information on using the dis

    CalibrationTo meet general operating re

    For special customer requirem

    for calibration or service info

    DMSTA Displays the display-module status bitfield as a hex number. A non-zero value maymod

    DM FRN Indic

    MM/DD/YYYY Disp

    HH/MM/SS Disp

    RELAY Show

    KYZ Show

    S1 STATUS Show

    S1 COUNT Show

    S2 STATUS Show

    S2 COUNT Show

    OUTWD Disp

    Display Module Status

    Display DescriptionPublication 1404-IN007F-EN-P - November 2009

    000 Unit User Manual, publication 1404-UM001, for

    play module.

    quirements, regular recalibration is not necessary.

    ents, contact your local Rockwell Automation representative

    rmation.

    indicate an anomaly, although a non-zero value may appear if a display ule is connected to an operating master module.

    ates the display-module firmware revision.

    lays the current date.

    lays the current time.

    s the status of the Form 4C relay.

    s the status of the KYZ output.

    s the status of Status Input 1.

    s the accumulated value of Status Input 1 counter, since last cleared.

    s the status of Status Input 2, since last cleared.

    s the accumulated value of Status Input 2 counter.

    lays the output word bitfield as a hex number.

  • 54 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Cleaning Instructions

    1. Turn off all electrical

    2. Clean the master mo

    a. Remove all dust a

    lower, and ends o

    b. Be sure that the n

    3. Clean the display mo

    a. Remove all dust a

    b. Be sure that the g

    good condition.

    ATTENTION Electrostatic discharge can damage integrated circuits or semiconductors. Follow these guidelines

    Touc

    Wea

    Do n

    Use

    Keep

    Discosecoperso- November 2009

    power supplied to the master module.

    dule with a dry, anti-static, lint-free cloth.

    nd any obstructions from the cooling air vents on the upper,

    f the module.

    ameplate is clean and in good condition.

    dule with a dry, anti-static, lint-free cloth.

    nd foreign materials from the exterior of the module.

    raphic front-panel overlay and back nameplate are clean and in

    when you handle the module:

    h a grounded object to discharge static potential.

    r an approved wrist strap grounding device.

    ot open the module or attempt to service internal components.

    a static safe work station, if available.

    the module in its static shield bag when not in use.

    nnect and lock out all power sources and short all current transformer ndaries before servicing. Failure to comply with these precautions can lead to nal injury or death, property damage, or economic loss.

  • Powermonitor 3000 Master Module 55

    Field Service ConsiderationsIf the power monitor requires servicing, contact your nearest Rockwell Automation sales

    office. To minimize your inconvenience, the initial installation should be performed in a

    manner that makes removal e

    A CT shorting block

    master-module curre

    CTs an open circuit.

    external protective re

    All wiring should be

    power-monitor termi

    Firmware UpgradesPower monitor firmware upg

    from time-to-time to improv

    firmware enhancements that

    an 1404-M6 or 1404-M8, or

    Service upgrades may be ava

    representative for informatio

    Product upgrades are availab

    representative for additional

    Master module firmware upg

    communication port. Firmw

    monitor from its installation.

    the power monitor and your

    power monitor may be requi

    Factory-installed CommThe RS-485 communication

    or changing a second commu

    and is not field upgradeable.

    ATTENTION Never openWiring betin the CT sother connapplied prodamage, orPublication 1404-IN007F-EN-P - November 2009

    asy.

    should be provided to allow the Powermonitor 3000

    nt inputs to be disconnected without making the user-supplied

    The shorting block should be wired to prevent any effect on the

    lays.

    routed to allow easy maintenance at connections to the

    nal strips and the power monitor itself.

    rades are of two types. Service upgrades are those that occur

    e operation and resolve issues. Product upgrades are optional

    you may purchase to convert your 1404-M5 master module to

    your 1404-M6 to an 1404-M8.

    ilable at no charge. Contact your local Rockwell Automation

    n or visit the Internet at http://www.ab.com/PEMS.

    le for purchase. Contact your Rockwell Automation

    information.

    rades (of either type) are performed by using the native RS-485

    are upgrades may be performed without removing the power

    An RS-485 to RS-232 converter is required to connect between

    personal computer communication port. Cycling power to the

    red to complete the firmware upgrade.

    unication Cardsis integral to the master module and cannot be removed. Adding

    nication card to a power monitor must be done at the factory

    a current transformer (CT) secondary circuit with primary current applied. ween the CTs and the power monitor should include a shorting terminal block econdary circuit. Shorting the secondary with primary current present allows ections to be removed, if needed. An open CT secondary with primary current duces a hazardous voltage, which can lead to personal injury, death, property economic loss.

  • 56 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Specifications

    Measurement Accuracy Powermonitor 3000 Mast

    Parameter Accuracy inPower Faca

    1404-M4

    Voltage sense inputs: V1, V2, V3

    0.2%

    Current sense input: I1, I2, I3, I4

    0.2%

    Frequency 0.05 Hz

    Power functions: kW, kVA, kVARDemand functions: kW, kVAEnergy functions: kWH, kVAH

    ANSI C12.16andEN 61036 Cla1 Accuracy

    Metering update rates

    6590 ms

    Input and Output Ratings

    Attribute

    Control power 1404-xxxxA-xxx

    Control power 1404-xxxxB-xxx

    Voltage sense inputs: V1, V2, V3- November 2009

    and Rangeer Module - 1404-M4, 1404-M5, 1404-M6, 1404-M8

    % of Full Scale at 25 C (77 F) 50/60 Hz Unity tor

    Nominal/Range

    1404-M5 1404-M6 1404-M8

    0.05% 0.05% 0.05% 347V/15399V L-N rms 600V/26691V L-L rms

    0.05% 0.05% 0.05% 5 A/50 mA10.6 A rms

    0.05 Hz 0.05 Hz 0.05 Hz 50 or 60 Hz/4075 Hz

    ss

    ANSI C12.20 andEN 60687 Class 0.5 Accuracy (Class 0.2 is also available)

    ANSI C12.20 andEN 60687 Class 0.5 Accuracy (Class 0.2 is also available)

    ANSI C12.20 andEN 60687 Class 0.5 Accuracy (Class 0.2 is also available)

    5580 ms 5585 ms 50100 ms

    Value

    102240V AC 4763 Hz or106250V DC(0.2 A max loading)

    1850V DC (15V A max loading)

    Input impedance: 1 M min, 399V AC max; V1, V2 and V3 to N

  • Powermonitor 3000 Master Module 57

    Current sense inputs: I1, I2, I3, I4 Overload withstand: 15 A continuous, 200 A for 1 s

    Status inputs

    Control relayKYZ output

    Control Relay(1)

    (1) Meets ANSI/IEEE C37.90-1989 sta

    Rating

    Resistive load switching, max

    Load switching, min

    UL 508, CSA 22.2, IEC rating clas

    Make values, max (inductive load

    Break values, max (inductive load

    Motor load switching, max

    Input and Output Ratings

    (1) Meets ANSI/IEEE C37.90-1989 sta

    Attribute

    Mechanical

    Electrical

    Input and Output Ratings

    Attribute ValuePublication 1404-IN007F-EN-P - November 2009

    Burden: 0.05VAImpedance: 0.002 Max crest factor at 5 A: 3Starting current: 5 mA

    Contact closure (internal 24V DC)

    (1) ANSI C37.90-1989 trip duty(1) Solid state KYZ - 80 mA at 240300V DC

    ndards for trip duty.

    50/60 Hz AC rms DC

    10 A at 250V(2500VA)

    10 A at 30V and 0.25 A at 250V

    10 mA at 24V 10 mA at 24V

    s B300 Q300

    ) 30 A at 120V15 A at 240V(3600VA)

    0.55 A at 125V0.27 A at 250V(69VA)

    ) 3 A at 120V1.5 A at 240V(360VA)

    0.55 A at 125V0.27 A at 250V(69VA)

    1/3 HP at 125V1/2 HP at 250V

    (1)

    ndards for trip duty.

    Number of Operations

    5 x 106

    1 x 105

  • 58 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Technical Specifications - 1404-M4, 1404-M5, 1404-M6, 1404-M8

    Attribute

    Dielectric withstand

    Terminal blocks

    (1) Recommended ring lug: AMP part

    Temperature, operating

    Temperature, storage

    Humidity

    Vibration

    Shock- November 2009

    1404-M4, 1404-M5, 1404-M6, 1404-M8

    Control power 2000V

    Voltage inputs 2000V

    Current inputs 2000V

    Status inputs 500V

    Control relays 1600V

    Power supply and voltage input terminals

    4 mm2 (12 AWG) max, 1.02 Nm (9 lbin) torque,75 C (167 F) or higher copper wire only

    Relay, KYZ outputs, current input

    terminals(1)

    # 320634.

    2.5 mm2 (14 AWG) max, 1.18 Nm (10.4 lbin) torque,75 C (167 F) or higher copper wire only

    Status inputs, RS485 2.5 mm2 (14 AWG) max,0.56 Nm (5 lbin) torque

    RIO, DNT (when present) 2.5 mm2 (14 AWG) max,0.56 Nm (5 lbin) torque

    -2060 C (-40140 F) cat. no. 1404-DM, 1404-Mxxxx-000, 1404-Mxxxx-DNT055 C (32 131 F) cat. no. 1404-Mxxxx-232, -RIO, -ENT, -CNT

    -4085 C (-40185 F)

    595%, noncondensing

    10500 Hz: 2 g operational (0.012 in.)

    1/2 sine pulse, 11 ms duration: 30 g operational and nonoperational

  • Powermonitor 3000 Master Module 59

    Product ApprovalsPowermonitor 3000 units have the following approvals and certifications.

    EtherNet/IP Conformance Te

    All products equipped with a

    below. This mark indicates th

    Association (ODVA) indepen

    This test provides a level of a

    conformance tested EtherNe

    representative devices from t

    1404-M405A-ENT/B and th

    using EtherNet/IP Conform

    (http://www.odva.org) main

    one of their test labs.

    ControlNet Conformance Te

    All products equipped with a

    This mark indicates the powe

    independent test lab and has

    level of assurance that the po

    ControlNet devices (includin

    the Powermonitor 3000 Con

    1404-M805A-CNT/A modu

    version 12. The CI website (h

    have passed the conformanc

    UL/CUL

    UL 508 listed, File E96956, fPublication 1404-IN007F-EN-P - November 2009

    sting

    n EtherNet/IP communication port bear the mark shown

    e power monitor has been tested at an Open Device Vendor

    dent test lab and has passed the EtherNet/IP conformance test.

    ssurance that the power monitor interoperates with other

    t/IP devices (including devices from other vendors). Two

    he Powermonitor 3000 EtherNet/IP family of devices, the

    e 1404-M805A-ENT/B modules, have been tested by ODVA

    ance Test version A2.8. The ODVA website

    tains a list of products that have passed the conformance test at

    sting

    ControlNet communication port bear the mark shown below.

    r monitor has been tested at a ControlNet International (CI)

    passed the ControlNet conformance test. This test provides a

    wer monitor interoperates with other conformance tested

    g devices from other vendors). Two representative device from

    trolNet family of devices, the 1404-M405A-CNT/A and the

    les, have been tested by CI using ControlNet Conformance Test

    ttp://www.ControlNet.org) maintains a list of products that

    e test at one of their test labs.

    or Industrial Control Equipment and CUL Certified.

  • 60 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    CE Certification

    If this product bears the CE marking, it is approved for installation within the European

    Union and EEA regions. It has been designed to meet the following directives.

    EMC Directive

    This product is tested to mee

    Compatibility (EMC) and the

    construction file:

    EN 50081-2 - Gener

    EN 50082-2 - Gener

    This product is intended for

    Low Voltage Directive

    This product is tested to mee

    safety requirements of IEC 1

    Measurement, Control, and L

    This equipment is classified a

    environmental and safety pro

    application conditions. See N

    applicable, for explanations o

    enclosure.

    International Standard IEC 5

    The Powermonitor 3000 mas

    International Standard IEC 5

    The Powermonitor 3000 disp

    International Standard IEC 5

    Follow the recommended ins

    ANSI/IEEE Tested

    Meets or exceeds the Surge W

    and relay systems on all powe- November 2009

    t Council Directive 89/336/EEC Electromagnetic

    following standards, in whole, documented in a technical

    ic Emission Standard, Part 2 - Industrial Environment

    ic Immunity Standard, Part 2 - Industrial Environment

    use in an industrial environment.

    t Council Directive 73/23/EEC Low Voltage, by applying the

    010-1, Safety Requirements for Electrical Equipment for

    aboratory Use.

    s an open style device. Open style devices must be provided with

    tection by proper mounting in enclosures designed for specific

    EMA Standards publication 250 and IEC publication 529, as

    f the degrees of protection provided by different types of

    29 / NEMA / UL 508 Degree of Protection

    ter module is rated as IP10 degree of protection per

    29. It is considered an open device per NEMA and UL 508.

    lay module is rated as IP65 degree of protection per

    29. It is rated as Type 4 (Indoor) per NEMA and UL 508.

    tallation guidelines to maintain these ratings.

    ithstand Capability (SWC) C37.90.1 - 1989 for protective relays

    r connection circuit terminations.

  • Powermonitor 3000 Master Module 61

    Additional ResourcesRefer to these power and energy management documents for more information.

    .

    You can view or download p

    To order paper copies of tech

    distributor or sales represent

    Documentation FeedYour comments will help us

    suggestions on how to impro

    available at http://www.rock

    For this information

    Powermonitor 3000 User Manual1404-UM001

    Powermonitor 3000 Display ModuInstructions, publication 1404-IN0

    Bulletin 1403 Powermonitor II Tutpublication 1403-1.0.2Publication 1404-IN007F-EN-P - November 2009

    ublications at http://www.rockwellautomation.com/literature.

    nical documentation, contact your local Rockwell Automation

    ative.

    backserve your documentation needs better. If you have any

    ve this document, complete this form, publication RA-DU002,

    wellautomation.com/literature/.

    Refer to Publication

    , publication Provides details about configuring and using the master module.

    le Installation 05

    Provides details about how to mount and wire the display module.

    orial, Provides details about instrument transformer accuracy and power measurement

  • 62 Powermonitor 3000 Master Module

    Publication 1404-IN007F-EN-P

    Notes:- November 2009

  • Powermonitor 3000 Master Module 63

    Notes:Publication 1404-IN007F-EN-P - November 2009

  • Publication 1404-IN007F-EN-P Supersedes Publication 1404-IN007E-EN-P - October 20

    Rockwell Automation SupportRockwell Automation provides technical information on the Web to assist you in using its

    products. At http://www.rockwellautomation.com/support/, you can find technical manuals,

    a knowledge base of FAQs, technical and application notes, sample code and links to software

    service packs, and a MySupport feature that you can customize to make the best use of these

    tools.

    For an additional level of tech

    troubleshooting, we offer Tec

    your local distributor or Rock

    http://www.rockwellautomat

    Installation