power monitor.pdf
-
Upload
robertovm2002 -
Category
Documents
-
view
39 -
download
2
description
Transcript of power monitor.pdf
-
Powermonitor 3000Master Module
Catalog Numbers1404-M8
Installation Instru
Topic
Important User Information
About This Publication
Safety Considerations
About the Power Monitor
Catalog Number Explanation
Quick Start Guidelines
Install the Powermonitor 3000 Un
Product Dimensions
Wiring and Connecting the Powe
Wiring Diagrams
Interpret the Status Indicators
Specifications
Additional Resources 1404-M4, 1404-M5, 1404-M6,
ctions
Page
2
3
4
5
10
11
it 12
14
r Monitor 18
21
47
56
61
-
2 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the ApplicaSGI-1.1 available from your local http://literature.rockwellautomatequipment and hard-wired electrowide variety of uses for solid statsatisfy themselves that each inte
In no event will Rockwell Automaresulting from the use or applicat
The examples and diagrams in thvariables and requirements assocassume responsibility or liability f
No patent liability is assumed by equipment, or software described
Reproduction of the contents of tAutomation, Inc., is prohibited.
Throughout this manual, when ne
WARNINGIdentifies a hazardoudamage, o
IMPORTANT Identifies the produc
ATTENTIONIdentifies or death, pavoid a ha
SHOCK HAZARD
Labels mathat dange
BURN HAZARD
Labels mathat surfac- November 2009
tion, Installation and Maintenance of Solid State Controls (Publication Rockwell Automation sales office or online at ion.com) describes some important differences between solid state mechanical devices. Because of this difference, and also because of the
e equipment, all persons responsible for applying this equipment must nded application of this equipment is acceptable.
tion, Inc. be responsible or liable for indirect or consequential damages ion of this equipment.
is manual are included solely for illustrative purposes. Because of the many iated with any particular installation, Rockwell Automation, Inc. cannot or actual use based on the examples and diagrams.
Rockwell Automation, Inc. with respect to use of information, circuits, in this manual.
his manual, in whole or in part, without written permission of Rockwell
cessary, we use notes to make you aware of safety considerations.
information about practices or circumstances that can cause an explosion in s environment, which may lead to personal injury or death, property r economic loss.
information that is critical for successful application and understanding of t.
information about practices or circumstances that can lead to personal injury roperty damage, or economic loss. Attentions help you identify a hazard, zard and recognize the consequences.
y be on or inside the equipment, for example, drive or motor, to alert people rous voltage may be present.
y be on or inside the equipment, for example, drive or motor, to alert people es may reach dangerous temperatures.
-
Powermonitor 3000 Master Module 3
About This PublicationExcept as noted, refer to the Powermonitor 3000 User Manual, publication 1404-UM001, for
detailed information on the topics in this list. These installation instructions do not contain
the following information:
Information on mete
Use of the display mo
Discussion of comm
Setpoint configuratio
Discrete I/O configu
Data logging includin
Advanced features in
Detection
Powermonitor 3000 d
Sample ladder diagra
using various commu
Display Module Insta
This manual does not provid
master module, firmware rev
or Ethernet series B, firmwar
and 1404-UM001D-EN-E, a
http://literature.rockwellauto
Terms and ConventionsThe following terms and con
Terms and Conventions
Abbreviation
AWG
CSA
CT
DM
EMI
ID
IEC
NEMA
PLCPublication 1404-IN007F-EN-P - November 2009
ring functionality and measurements
dule for configuration, monitoring, and commands
unication options, functionality, configuration, and operation
n and operation
ration and operation
g Event Log, Trend Log, Min/Max Log, and Load Factor Log
cluding Oscillography, Harmonic Analysis, and Transient
ata tables
ms for communicating with the Powermonitor 3000 unit by
nication options
llation Instructions, see publication 1404-IN005
e information on functionality found in the Powermonitor 3000
ision 3.0 and earlier, or Ethernet series A, all firmware revisions,
e revision 2.0 earlier. Refer to publications 1404-IN007D-EN-E
vailable as downloads from
mation.com.
ventions are used in this manual.
Term
American Wire Gauge
Canadian Standards Association
Current transformer
Display module
Electromagnetic interference
Identification
International Electrotechnical Commission
National Electrical Manufacturers Association
Programmable logic controller
-
4 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Safety Consideratio
PT Potential transformer (also known as VT in some countries)
RAM
RFI
R I/O
RMS
SLC
SPDT
UL
VA
VAR
CIP
NAP
ATTENTION Only qualifservice theany work, dlocked out.property da
Never openWiring betterminal blpresent allprimary curdeath, prop
Terms and Conventions
Abbreviation Term- November 2009
ns
Random access memory
Radio frequency interference
Remote input/output
Rootmeansquare
Small logic controller
Single pole double throw
Underwriters Laboratories
Voltampere
Voltampere reactive
Control and information protocol
Network access port
ied personnel, following accepted safety procedures, should install, wire, and Powermonitor 3000 unit and its associated components. Before beginning isconnect all sources of power and verify that they are de-energized and
Failure to follow these instructions may result in personal injury or death, mage, or economic loss.
a current transformer (CT) secondary circuit with primary current applied. ween the CTs and the Powermonitor 3000 unit should include a shorting ock in the CT secondary circuit. Shorting the secondary with primary current ows other connections to be removed if needed. An open CT secondary with rent applied produces a hazardous voltage, which can lead to personal injury, erty damage, or economic loss.
-
Powermonitor 3000 Master Module 5
About the Power MoThe Bulletin 1404 Powermon
needs of both producers and
a master module that
an optional display m
an optional commun
networks.
optional external dev
control, and managem
IMPORTANT The Powermonitor 3000 unit is not designed for, nor intended for, use as a circuit protective device. Do not use this equipment in place of a motor overload relay or circuit protective r
The relay ounit may becan configu
Refer to theon configur
Be sure to process.
ATTENTION Electrostatguidelines
Touc
Wea
Do n
Use
KeepPublication 1404-IN007F-EN-P - November 2009
nitoritor 3000 unit is uniquely designed and developed to meet the
users of electric power. A power monitor system consists of:
provides metering and native RS-485 communication.
odule for configuration, commands, and data display.
ication port to serve data to other devices by using a choice of
ices and applications that display and use data for reporting,
ent of power and energy usage.
elay.
utput contacts and solid-state KYZ output contacts on the Powermonitor 3000 used to control other devices through setpoint control or communication. You re the response of these outputs to a communication failure.
Powermonitor 3000 User Manual, publication 1404-UM001 for information ing the outputs.
evaluate the safety impact of the output configuration on your plant or
ic discharge can damage integrated circuits or semiconductors. Follow these when you handle the module:
h a grounded object to discharge static potential.
r an approved wrist strap-grounding device.
ot open the module or attempt to service internal components.
a static safe workstation, if available.
the module in its static shield bag when not in use.
-
6 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
The Powermonitor 3000 unit is a microprocessor-based monitoring and control device ideally
suited for a variety of applications including these:
Load Profiling - Using the configurable trending utility to log power parameters, such
as real power, apparent power, and demand, for analysis of power usage by loads over
time.
Demand Managemen
make informed decis
Cost Allocation - Kn
efficiencies.
Distribution System M
system topology, and
Emergency Load She
the event of sudden u
Power System Contro
factor.
The power monitor is a soph
metering devices. A single po
meters. The power monitor p
compact economical package
Powermonitor 3000 MaThe master module contains
terminations for power syste
communication port, and a p
Configuration
Although the power monitor
configure it for your particula
the optional display module.
write configuration, operatio
native or optional communic
Refer to the Powermonitor 3
Optional external application
RSPower, RSPowerPlus, and
Contact your local Rockwell
http://www.rockwellautoma
software packages.- November 2009
t - Understanding when and why demand charges occur lets you
ions that reduce your electrical power costs.
owing your actual energy costs promotes manufacturing
onitoring - Using power parameters to show power flow,
distribution equipment status.
dding - Monitoring power usage to preserve system stability in
tility outage.
l - Managing system voltage, harmonic distortion, and power
isticated modern alternative for traditional electro-mechanical
wer monitor can replace many individual transducers and
rovides you with easy to understand, accurate information in a
.
ster Modulethe main microprocessor-based monitoring functions, including
m connections, status inputs, control outputs, a native RS-485
ort for the display module.
ships from the factory with default settings, you need to
r requirements. You may configure the power monitor by using
Alternately, you may use an external device or application to
nal parameters and commands to the master module through its
ation port.
000 User Manual, publication 1404-UM001, for additional detail.
s that you may use for power monitor configuration include
RSEnergyMetrix software operating on a personal computer.
Automation sales office or distributor, or visit
tion.com/rockwellsoftware for more information on available
-
Powermonitor 3000 Master Module 7
Communication
Every Powermonitor 3000 unit comes with a native RS-485 communication port. The native
port is suitable for communicating to devices including:
PLC-5, SLC 500, and
RSLinx software with
Modbus RTU Master
other third-party dev
software that you dev
You may also specify Powerm
the following:
Serial RS-232
Remote I/O
DeviceNet
EtherNet/IP
ControlNet
A power monitor may be int
control and monitoring systePublication 1404-IN007F-EN-P - November 2009
ControlLogix processors.
DDE/OPC server functionality.
devices.
ices.
elop.
onitor 3000 units with optional communication ports including
egrated into a programmable controller or computer-based
m by using any of the communication methods listed above.
-
8 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Master Module with Communication Options
Powermonitor 3000Powermonitor 3000
Removable Status Input Connector
Terminal Blocks
Optional RS-232 Port
OptiRem- November 2009
Powermonitor 3000wermonitor 3000 Powermonitor 3000 Powermonitor 3000
Status Indicators
Display Module Port
RS-485 (Native) Communication Port
onal ote I/O Port
Optional DeviceNet Port
Optional Ethernet 10BaseT Port
NAP Port
ControlNet Channel A
ControlNet Channel B
-
Powermonitor 3000 Master Module 9
Powermonitor 3000 Display ModuleThe display module is an optional user-interface device. The display module provides the
most economical and simplest method for setting up and configuring the master module for
operation.
The display module has a hig
tactile feedback. Use the butt
configuration, commands, an
The display module is shippe
power and serial communica
display module fits into a sta
Only one display module ma
display module to configure
Display ModulePublication 1404-IN007F-EN-P - November 2009
hly visible, two-line LED display and four operator buttons with
ons and display to navigate through a series of menus for
d data display.
d with a 3 m (10 ft) long, shielded four-pair cable that provides
tion between the master module and the display module. The
ndard ANSI four-inch analog meter cutout for panel mounting.
y be connected to a master module, although you may use one
and monitor any number of master modules; one at a time.
-
10 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Catalog Number ExplanationThe Powermonitor 3000 unit has the following catalog number possibilities.
140
Bulletin Number
1404 = Power Monitoring and Management Products
Type o
M4 = Master Mthree-phase msetpoints, I/O,logging.
M5 = M4 funcfirmware upgrM6 or M8.
M6 = M5 funcoscillography, detection, harmeasurement,setpoints and firmware upgr
M8 = M6 functransient captanalysis, harmmeasurement Transducer anmodes.
(1) In addition to Native RS-485 port.- November 2009
4 - M4 05 A - ENT - 02
f Device
odule with etering, and data
tionality, adeable to an
tionality plus sag/swell monics 141 additional logging, adeable to M8.
tionality plus ure and onics up to 63rd, d Energy Meter
Current Inputs05 = 5 A
Power Supply
A = 120240V AC 5060 Hz or 125250V DCB = 24V DC
000 = None232 = RS-232 SerialDNT = DeviceNetRIO = Remote I/OENT = EtherNet/IPCNT = ControlNet
Communication
Options(1)Revenue Accuracy Class
Blank = Class 1 or Class 0.5
02 = Class 0.2
-
Powermonitor 3000 Master Module 11
Quick Start GuidelinesThe Powermonitor 3000 unit may be used in many electric power monitoring and control
systems. Whether your power monitor is a complete power and energy monitor or a
component in a plant- or ent
steps to follow to make your
1. Install your Powermo
Refer to Install the P
2. Install your optional
Refer to the Bulletin
1404-IN005.
3. Determine your wirin
power system.
4. Connect control pow
5. If used, connect wirin
outputs.
Refer to Wiring and C
6. Configure the potent
match those used in y
7. Configure the Voltag
configuration.
8. Configure power mo
This step varies depe
9. Configure the power
10. Configure other optio
logging.
Refer to the Powermonitor 3
information on configuring aPublication 1404-IN007F-EN-P - November 2009
erprise-wide energy management system, there are a few basic
unit operational.
nitor 3000 master module within a suitable enclosure.
owermonitor 3000 Unit on page 12.
display module.
1404 Display Module Installation Instructions, publication
g mode and install wiring between the power monitor and your
er wiring, preferably from a separate source of control power.
g to the status inputs, Form C control relay, and KYZ solid-state
onnecting the Power Monitor on page 18.
ial transformer (PT) and current transformer (CT) ratios to
our power system connections.
e mode of the power monitor to match your power system
nitor communication.
nding upon the communication option you have selected.
monitor date and time.
nal performance features, such as setpoint control and data
000 User Manual, publication 1404-UM001, for complete
nd operating your power monitor.
-
12 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Install the Powermonitor 3000 UnitOnly qualified personnel should install, wire, service, and maintain this equipment. Refer to
and follow the safety guidelines and pay attention to all warnings and notices in these
instructions.
See Product Dimensions on
Mount the master module w
washers.
Mounting ConsideratioMount the Powermonitor 30
enclosure that protects the m
moisture, dust corrosive vapo
also protect against personal
The ambient temperature wit
Specifications, page 56.
Select an enclosure that prov
monitor and other equipmen
See Product Dimensions on
monitor.
When installed within a subs
monitor be mounted within a
circuits.
ATTENTION Electrostatguidelines
Touc
Wea
Do n
Use
Keep- November 2009
page 14 for mounting hole dimensions.
ith four No. 8-32 UNC or M4 screws with flat washers and lock
ns00 master module in a suitable protective enclosure. Select an
aster module from atmospheric contaminants, such as oil, water,
rs and other harmful airborne substances. The enclosure should
contact with energized circuits.
hin the enclosure must remain within the limits listed in the
ides adequate clearance for ventilation and wiring for the power
t to be installed within the enclosure.
page 14 for dimensions and spacing guidelines for the power
tation or switchgear lineup, we recommend that the power
low-voltage cubicle, isolated from medium- and high-voltage
ic discharge can damage integrated circuits or semiconductors. Follow these
when you handle the module:
h a grounded object to discharge static potential.
r an approved wrist strap grounding device.
ot open the module or attempt to service internal components.
a static safe work station, if available.
the module in its static shield bag when not in use.
-
Powermonitor 3000 Master Module 13
Mount the master module so that the metal grounding clips on the bottom of the mounting
feet make direct contact with the enclosure mounting panel. If the mounting panel is painted,
scrape or sand the paint down to bare metal. Use star washers to assure good long-term
electrical contact with the mounting panel. Be sure that the mounting panel is properly
connected to a low-impedanc
Mount the enclosure in a pos
master module with the vent
assure adequate free convect
IMPORTANT Use cautioobstructionPublication 1404-IN007F-EN-P - November 2009
e earth ground.
ition that allows full access to the master module. Install the
ilation slots in the bottom and top of the unit unobstructed to
ion cooling of its internal electronic components.
n not to block the ventilation slots of the master module. All wiring and other s must be a minimum of 50 mm (2.0 in.) from the top and bottom of the unit.
-
14 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Product DimensionsUse the dimensions in these drawings when mounting the master module.
Master Module Dimensions
14.66(0.577)
5.35(0.211)
125.0(4.921)
Mounting
114.30(4.50)
163.17 (6.Used With
Display Mo
All dimensions are in mm (in.).- November 2009
203.2 (8.000)Used With -232Communication
Options
Powermonitor 3000
114.30(4.50)85.0
(3.346)Mounting
4.57 (0.180)4 Places
10.43(0.411)
135.15(5.321)
184.15 (7.250)Used With
Display Module424)outdule
5.60(0.22)
-
Powermonitor 3000 Master Module 15
Master Module Spacing
50.8(2.00)
215.9 (8.50)
215.9 (8.50)
General Notes:
Recommended spacing
Maintain approximateelectrical equipment.
Do not block cooling vfrom top and bottom o
Mount with ventilation
Refer to Specifications
All dimensions are in mm (in.).Publication 1404-IN007F-EN-P - November 2009
Powermonitor 3000Powermonitor 3000
Powermonitor 3000 Powermonitor 3000
50.8(2.00)
50.8 (2.00)Minimum
50.8 (2.00)Minimum
101.6 (4.00)
101.6 (4.00)
provides reasonable wiring clearance and ventilation.
ly 102 mm (4.00 in.) clearance between master modules and other
ents. Wiring and other obstructions must be 50 mm (2.00 in.) minimum f unit.
opening in top and bottom to provide optimum free convection cooling.
for ambient temperature requirements.
-
16 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
System Accuracy ConsiderationsUser-supplied potential transformers (PTs) and current transformers (CTs), as well as wiring
from the CTs to the power monitor, may reduce the accuracy of your power monitor system.
The quality of the power mo
signals presented to its input
adequate for the desired met
ANSI/IEEE C57.13, Requir
transformer accuracy: class 1
transformer accuracy class us
PTs and CTs may introduce e
errors.
Ratio Errors
The voltage ratio of a PT is t
secondary turns. Manufacturi
design specifies, causing an e
Likewise, the current ratio of
the primary and secondary. S
and CTs.
Other errors include magnet
the transformer secondary. T
may compensate for Ratio E
PT and CT primary or secon
For a PT, the Ratio Error incr
impedance should be as high
voltage supported by the tran
including the impedance of t
low as possible. This is why 4
CTs with a 5 A secondary rat- November 2009
nitors measurements can be no better than the quality of the
terminals. It is your responsibility to select transformers that are
ering accuracy.
ements for Instrument Transformers, defines three classes of
.2, class 0.6, and class 0.3. The application should dictate the
ed.
rrors in three areas: ratio errors, phase errors, and bandwidth
he number of primary turns of wire divided by the number of
ng tolerances may cause the ratio to be slightly different than the
rror affecting the voltage input to the power monitor.
a CT is a function of the ratio of the number of turns of wire on
ome error in this ratio is quite common in commercial grade PTs
ic core losses, winding impedance, and the burden, or load, on
he combination of these errors is known as Ratio Error. You
rror, if known, by adjusting the Basic Configuration entries for
dary voltages.
eases as the transformers load current increases, so its total load
as possible. Conversely, a CTs Ratio Error increases as the
sformer secondary increases, so its total load impedance,
he wire connecting the CTs to the metering device, should be as
mm2 (12 AWG) or larger is usually recommended for wiring
ing.
-
Powermonitor 3000 Master Module 17
Phase Error
Phase shift between the primary to secondary signals is another source of inaccuracy
introduced by the user-supplied PTs and CTs. Phase shift is generally not of concern for
simple voltage or current mea
calculating line to line voltage
significant. The difference in
errors. If all the PTs and CTs
measured quantities. If, on th
phase error of 6, there woul
up as power factor and reacti
adjusting the power monitor
conditions of the power syste
A typical PT phase error vari
Applying higher than rated vo
and cause even larger errors.
The phase error in a CT incr
greater than 80% of the CT r
current is less than 20% of ra
used for metering.
The phase error of both PTs
secondary. For best accuracy,
CT loads as low as possible.
Bandwidth Error
For fundamental 50 or 60 Hz
However, for waveforms with
attenuate higher harmonics. M
to 3 kHz, or the 50th harmon
existing units, tend to be less
Hz) harmonic. Wide-band in
Bandwidth error cannot be c
In addition, operation of eith
saturation and resulting magn
For more detailed informatio
refer to Bulletin 1403 PowermPublication 1404-IN007F-EN-P - November 2009
surements. When these signals are combined, for instance when
or phase power, the effect of phase shift can become
phase error among different transformers causes measurement
introduced a 5 phase shift, there would be no error in the
e other hand, the PTs had a phase error of 1 and the CTs had a
d be a 5 phase error in the power calculation. This would show
ve power (VAR) errors. Phase errors cannot be corrected by
configuration since the errors change based on varying
m.
es from 10.25, depending on the PTs accuracy class.
ltage increases the phase error and may saturate the transformer
eases as its current decreases, and is lowest when the current is
ating. Because significant phase error can occur when CT
ted current, CTs sized for protection do not perform well when
and CTs are also affected by the power factor of the load on the
loads should be resistive, with PT loads as high as possible and
measurements, bandwidth error has no affect on accuracy.
significant harmonic content, the PTs and CTs you supply may
ost instrument quality PTs have a flat frequency response out
ic on a 60 Hz system. Current transformers, especially older,
linear, with a flat response only out to 300 Hz, or the fifth (60
strument CTs are available for improved frequency response.
orrected by adjusting the power monitor configuration.
er the PTs or CTs at extremely low frequencies may also cause
itude and phase errors.
n on instrument transformer accuracy and power measurement,
onitor II Tutorial, publication 1403-1.0.2.
-
18 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Wiring and Connecting the Power Monitor
Wiring of the power monitor
Connection of voltag
Connection of contro
Connection of status
Communication wirin
Follow these guidelines to he
Install and connect a
neatly and maintain a
ventilation slots to av
Furnish and install pr
Use 600V wiring rate
flame-retardant wire
Use a shorting termin
connected equipmen
de-energizing the pow
Use ring lugs or locki
additional wiring secu
Pay careful attention
Connect the master m
terminal and a dedica
current-carrying wire
short as possible. To
feet should make elec
Refer to Mounting C
Connect all equipmen
single point, low-imp
For information on wire size
Industrial Automation Wirin
National Electrical Code pub
ATTENTION Only qualifservice thedisconnectFailure to fdamage, or- November 2009
includes the following steps:
e and current signals from PTs and CTs
l power
inputs and status/control outputs
g
lp assure reliable, trouble-free operation of your power monitor:
ll wiring. Use wire tags to identify connections. Bundle wiring
minimum of 50 mm (2.0 in.) clearance from the master module
oid a buildup of heat within the unit.
operly-selected fuses for voltage signals and control power.
d at 75 C (167 F) or higher. We strongly recommend the use of
rated VW-1 by Underwriters Laboratories.
al block (you provide) for CT wiring, to permit servicing
t, such as the Powermonitor 3000 master module, without
er system.
ng spade lugs for voltage and current connections to provide
rity and safety.
to correct phasing and polarity for proper operation.
odule to a low-impedance earth ground by using its grounding
ted grounding wire at least as large as the largest
connected to the master module. Keep grounding wiring as
obtain maximum EMI immunity, the master module mounting
trical contact with the mounting panel.
onsiderations on page 12 for additional information.
t ground terminals (master module, PT, and CT secondary) to a
edance earth ground.
s and types for grounding electrical equipment, refer to
g and Grounding Guidelines, publication 1770-4.1, or the
lished by National Fire Protection Association (NFPA).
ied personnel, following accepted safety procedures, should install, wire, and power monitor and its associated components. Before beginning any work, all sources of power and verify that they are de-energized and locked out. ollow these instructions may result in personal injury or death, property economic loss.
-
Powermonitor 3000 Master Module 19
Wiring the Master ModuleObserve all wire lug sizes and screw torques for terminal blocks wire sizes and screw torques.
Refer to Specifications on page 56.
Voltage and Current InpThe following sections give i
Voltage Input and PT Select
The power monitor is design
line-to-line (347V line-to-neu
PTs. Typical secondary voltag
the nominal voltage of your p
Connect short circuit protect
monitor. If PTs are used, inst
Current Inputs and Current T
The current input on the pow
User-supplied CTs are requir
monitor. Select the CT prima
ATTENTION Never openbetween thCT secondaconnectionproduces adamage, orPublication 1404-IN007F-EN-P - November 2009
utsnformation on the selection of PTs and CTs.
ion
ed to connect directly to a power system rated up to 600V
tral). Higher system voltages require the use of user-supplied
e on a PT is 120V AC. Select the PT primary voltage to match
ower system.
ion, that you supply, between the power system and the power
all short circuit protection on the high-voltage side of the PTs.
ransformer (CT) Selection
er monitor is designed for a 5 A nominal current signal.
ed to connect your power system to the input of the power
ry current to match the nominal current of your power system.
a current-transformer secondary circuit with primary current applied. Wiring e CTs and the power monitor should include a shorting terminal block in the ry circuit. Shorting the secondary with primary current present allows other
s to be removed if needed. An open CT secondary with primary current applied hazardous voltage, which can lead to personal injury, death, property economic loss.
-
20 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
The shorting terminal block should be located adjacent to the Powermonitor 3000 master
module so that it is readily accessible should service be needed. Use 2.5 mm2 (14 AWG) wire
for the short run between the power monitor and the shorting terminal block. Use wiring of 4
mm2 (12 AWG) or larger between the shorting terminal block and the CT so that the
additional load of the wiring
Do not install fuses or other
Refer to System Accuracy Co
Refer to Specifications on pa
termination recommendation
The wiring diagrams depict w
need to configure your powe
operation.
Refer to the Powermonitor 3
instructions on unit configur
IMPORTANT You may involtage mo
Refer to the
Whether th
Refer to th- November 2009
does not overload the CT and reduce its accuracy.
overcurrent protection in the secondary circuit of a CT.
nsiderations on page 16 for guidelines on PT and CT selection.
ge 56 for information on voltage isolation levels and wire
s.
iring methods for a variety of power system configurations. You
r monitor to match the power system configuration for correct
000 Unit User Manual, publication 1404-UM001, for detailed
ation.
stall either two or three CTs for any of the Delta or Open Delta wiring or des.
wiring diagrams on pages 28, 30, and 33 for wiring of a two CT configuration.
ere are two or three CTs in a circuit does not affect the voltage wiring.
e Powermonitor 3000 Unit User Manual, publication 1404-UM001.
-
Powermonitor 3000 Master Module 21
Wiring Diagrams
Single-phase Direct Connection Wiring Diagram (Systems < 600V Nominal L-L)
Load
CustomeCT Shortin
Test
Fuse
Fuse
NL1 L2
LinePublication 1404-IN007F-EN-P - November 2009
CustomerChassisGround
r-suppliedg Switch or Block
Powermonitor 3000Master Module
R14
R11
R12
N/C N/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
L1(+)L2(-)
GRD
V1
V2
V3
N
Voltage Mode = Single Phase
Y K ZR14 R11 R12
-
22 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Single-phase with PTs Wiring Diagram
Load
CustomeCT Shortin
Test
Fuse
Fuse
NL1 L2
LineVoltage Mode = Single Phase- November 2009
CustomerChassisGround
r-suppliedg Switch or Block
Powermonitor 3000Master Module
R14
R11
R12
N/C N/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
L1(+)L2(-)
GRD
V1
V2
V3
N
Y K ZR14 R11 R12
-
Powermonitor 3000 Master Module 23
Three-phase Four-wire Wye Direct Connect Wiring Diagram(Systems < 600V Nominal L-L)
Load
Customer-sCT Shorting
Test B
Fuse
Fuse
Fuse
NL1 L2 L3
LineVoltage Mode = WyePublication 1404-IN007F-EN-P - November 2009
CustomerChassisGround
uppliedSwitch orlock
Powermonitor 3000Master Module
R14
R11
R12
N/C N/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
L1(+)L2(-)
GRD
V1
V2
V3
N
Y K ZR14 R11 R12
-
24 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Three-phase Four-wire with PTs Wiring Diagram
Load
Customer-sCT Shorting
Test B
Fuse
Fuse
Fuse
NL1 L2 L3
LineVoltage Mode = Wye- November 2009
CustomerChassisGround
uppliedSwitch orlock
Powermonitor 3000Master Module
R14
R11
R12
N/C N/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
L1(+)L2(-)
GRD
V1
V2
V3
N
Y K ZR14 R11 R12
-
Powermonitor 3000 Master Module 25
Three-phase Three-wire Grounded Wye Direct Connection Wiring Diagram (Systems < 600V Nominal L-L)
Load
Customer-CT Shorting
Test B
Fuse
Fuse
Fuse
L1 L2 L3
LineVoltage Mode = WyePublication 1404-IN007F-EN-P - November 2009
CustomerChassisGround
supplied Switch orlock
Powermonitor 3000Master Module
R14
R11
R12
N/C N/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
L1(+)L2(-)
GRD
V1
V2
V3
N
Y K ZR14 R11 R12
-
26 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Three-phase Three-wire Grounded Wye with PTs Wiring Diagram
Load
Customer-sCT Shorting
Test Bl
Fuse
Fuse
Fuse
L1 L2 L3
LineVoltage Mode = Wye- November 2009
CustomerChassisGround
uppliedSwitch orock
Powermonitor 3000Master Module
R14
R11
R12
N/C N/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
L1(+)L2(-)
GRD
V1
V2
V3
N
Y K ZR14 R11 R12
-
Powermonitor 3000 Master Module 27
Three-phase Three-wire Delta with Three PTs and Three CTs Wiring Diagram
Load
Customer-CT Shorting
Test B
Fuse
Fuse
Fuse
L1 L2 L3
LineVoltage Mode = Delta 3 CTPublication 1404-IN007F-EN-P - November 2009
CustomerChassisGround
supplied Switch orlock
Powermonitor 3000Master Module
R14
R11
R12
N/C N/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
L1(+)L2(-)
GRD
V1
V2
V3
N
Y K ZR14 R11 R12
-
28 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Three-phase Three-wire Delta with Three PTs and Two CTs Wiring Diagram
Load
Customer-sCT Shorting
Test B
L1 L2 L3
Line Voltage Mode = Delta 2 CT
Fuse
Fuse
Fuse- November 2009
CustomerChassisGround
uppliedSwitch orlock
Powermonitor 3000Master Module
R14
R11
R12
N/C N/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
L1(+)L2(-)
GRD
V1
V2
V3
N
Y K ZR14 R11 R12
-
Powermonitor 3000 Master Module 29
Three-phase Three-wire Open Delta with Two PTs and Three CTs Wiring Diagram
Load
Customer-sCT Shorting
Test Bl
Fuse
Fuse
L1 L2 L3
Line Voltage Mode = Open Delta 3 CTPublication 1404-IN007F-EN-P - November 2009
CustomerChassisGround
uppliedSwitch orock
Powermonitor 3000Master Module
R14
R11
R12
N/C N/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
L1(+)L2(-)
GRD
V1
V2
V3
N
Y K ZR14 R11 R12
-
30 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Three-phase Three-wire Open Delta with Two PTs and Two CTs Wiring Diagram
Load
Customer-sCT Shorting
Test Bl
Fuse
Fuse
L1 L2 L3
Line Voltage Mode = Open Delta 2 CT- November 2009
CustomerChassisGround
uppliedSwitch orock
Powermonitor 3000Master Module
R14
R11
R12
N/C N/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
L1(+)L2(-)
GRD
V1
V2
V3
N
Y K ZR14 R11 R12
-
Powermonitor 3000 Master Module 31
Three-phase Three-wire Grounded L2(B) Phase Open Delta Direct Connect with Three CTs Wiring Diagram (Systems < 600V Nominal L-L)
Load
CustomCT Shor
Te
F
F
L1 L3
Line Voltage Mode = Open Delta 3 CT
DistributionGround
Voltexc
(otherwtransformPublication 1404-IN007F-EN-P - November 2009
CustomerChassisGround
er-suppliedting Switch orst Block
Powermonitor 3000MasterModule
R14
R11
R12
N/C N/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
L1(+)L2(-)
GRD
V1
V2
V3
N
use
use
Y K ZR14 R11 R12
age must noteed 347V L-L
ise, step downers are required).
-
32 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Three-phase Three-wire Delta Direct Connect with Three CTs Wiring Diagram (Systems < 600V Nominal L-L)
Load
Customer-CT Shorting
Test B
Fuse
Fuse
Fuse
L1 L2 L3
Line Voltage Mode = Direct Delta 3 CT- November 2009
CustomerChassisGround
supplied Switch orlock
Powermonitor 3000MasterModule
R14
R11
R12
N/C N/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
L1(+)L2(-)
GRD
V1
V2
V3
N
Y K ZR14 R11 R12
-
Powermonitor 3000 Master Module 33
Three-phase Three-wire Delta Direct Connect with Two CTs Wiring Diagram(Systems < 600V Nominal L-L)
Load
Customer-suCT Shorting Sw
Test Bloc
Fuse
Fuse
Fuse
L1 L2 L3
LineVoltage Mode = Direct Delta 2 CTPublication 1404-IN007F-EN-P - November 2009
CustomerChassisGround
pplieditch or
k
Powermonitor 3000MasterModule
R14
R11
R12
N/C N/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
L1(+)L2(-)
GRD
V1
V2
V3
N
Y K ZR14 R11 R12
-
34 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Control PowerThe power monitor draws a nominal 15VA control power. Catalog numbers
1404-MxxxA-xxx require nominal control power of 120240V AC or
125250V DC. The power s
nominal control power of 24
Refer to Specifications on pa
termination information.
We strongly recommend that
system being monitored. For
consider the use of a user-sup
continues to operate during p
disturbances.
You are required to connect
disconnecting means and ove
Status Inputs
ATTENTION Do not appand are intassociated- November 2009
upply is self-scaling. Catalog numbers 1404-MxxxB-xxx require
V DC.
ge 56 for acceptable control-voltage ranges and wiring
you use a separate source of control power from the power
applications where power system information is critical,
plied uninterruptible power supply so that the power monitor
ower system events such as significant sags, swells, and transient
your power-monitor control power through user-supplied
rcurrent protection. We recommend a 1 A slow-blow fuse.
ly an external voltage to a Status Input. These inputs have an internal source ended for dry contact input only. Applying a voltage may damage the input or internal power supply.
L1
N/L2
LocalFrameGround
Powermonitor 3000Master Module
R14
R11
R12
N/CN/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
R14 R11 R12 Y K Z
L1(+)
L2(-)
GRD
V1
S1
S2
SCOM
V2
V3
N
DISPLAYMODULE
SHLD
RS-485
-
Powermonitor 3000 Master Module 35
All Status Inputs are common to an internal 24V DC source on the SCOM terminal. Status
input terminals S1 and S2 are positive polarity and SCOM is negative polarity.
For optimal EMC performance, we recommend wiring the status inputs by using shielded
cable, Belden 8771 or equivalent, with the cable shield grounded at both ends where possible.
Status Input Connections
Applied resistance versus sta
Condition 1 is 3.5 kW
Condition 2 is 5.5 kW
Isolation Voltage is 500V sta
circuitry.
Relay and KYZ OutputsControl Relay Connections o
example of customer wiring
connection, R14 is the norm
connection. You must supply
connected to the relay outpu
Refer to Specifications on pa
TIP Status InpuPowermoniPublication 1404-IN007F-EN-P - November 2009
tus state
or less = ON
or greater = Off
tus input to case and 500V status input to internal digital
n page 36 shows the Form C relay output connections and an
to a supply voltage and two loads. Terminal R11 is the common
ally-open connection, and R12 is the normally-closed
the wetting voltage and overcurrent protection for the circuit
t.
ge 56 for further information.
t S2 can be configured for external demand pulse input. See the tor 3000 User Manual, publication 1404-UM001, for more information.
Powermonitor 3000Master Module
-+
R14R14
R11
R12
N/CN/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
R14 R11 R12 Y K Z
L1(+)
L2(-)
GRD
V1
S1
S2
SCOM
V2
V3
N
DISPLAYMODULE
SHLD
RS-485
N.O.Contact
N.O.Contact
-
36 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
The KYZ output is a solid-state relay designed for low-current switching and long life. Its
normal application is to provide a pulse based on energy usage (or one of five other
parameters) to an external pulse accumulator. Terminal K is common, Y is normally-open,
and Z is normally-closed.
Refer to the Powermonitor 3
information on the applicatio
Control Relay Connection
Communication WiringMethods for connecting com
provides guidelines for instal
system.
ATTENTION You must sground potconnected injury or de
IMPORTANT You need tRefer to thecommunica
10AFuse- November 2009
000 Unit User Manual, publication 1404-UM001, for further
n and operation of relay and KYZ outputs.
s
munication wiring vary from option to option. This section
ling dependable communication wiring for your power monitor
upply and install special high-level isolation when the possibility of high ential differences exists. This may occur when communicating with a unit to a power ground mat. Failure to install such isolation may lead to personal ath, property damage, or economic loss.
o configure communication for each communication option.
Powermonitor 3000 Unit User Manual, publication 1404-UM001, for detailed tion configuration instructions.
L1 NPowermonitor 3000
Master Module
-+
R14
R11
R12
N/CN/C
I1-I1+
I2-I2+
I3-I3+
I4-I4+
Y
K
Z
R14 R11 R12 Y K Z
L1(+)
L2(-)
GRD
V1
S1
S2
SCOM
V2
V3
N
DISPLAYMODULE
SHLD
RS-485
-
Powermonitor 3000 Master Module 37
Native RS-485 Communication Wiring
The RS-485 communication standard supports multi-drop communication among as many as
32 stations or nodes.
The RS-485 port is also used
RS-485 communication wirin
recommend that you use Bel
maximum cable length is 121
recommended and will result
(star topology) or network (b
If required, install suitable ter
RS-485, install a 150 , 1/4 W
some RS-485 conversion dev
manufacturer of the converte
At one end of each cable seg
master module RS-485 port o
low-impedance ground for h
signals.
The RS-485 port in the mast
network, allowing the standa
Configuration options for th
the data rate. Defaults are:
auto-detect protocol.
device address = the
communication rate =
Use of RS-232 to RS-485 Co
You need a user-supplied RS-
monitor native RS-485 port a
controller RS-232 port. Exam
B&B Electronics, Inc
Allen-Bradley catalogPublication 1404-IN007F-EN-P - November 2009
for master module firmware upgrades in the field.
g should be installed in a daisy-chain configuration. We
den 9841 two-conductor shielded cable or equivalent. The
9 m (4000 ft). Use of a star or bridging topology is not
in signal distortion unless impedance is matched for each spur
ridge topology).
minating resistors at the ends of the daisy-chain cable. For
terminating resistor (refer to the wiring diagram). Note that
ices are equipped with internal terminating resistors. Contact the
r for additional information.
ment, connect the cable shield to the SHLD terminal of the
r the converter. The SHLD connection provides a
igh-frequency noise while attenuating DC or line-frequency
er module presents a standard load impedance to the RS-485
rd 32 nodes on a network.
e native RS-485 port include the protocol, device address, and
Device ID assigned at the factory in the range 1254.
9600 bps.
nverter
232 to RS-485 converter for communication between the power
nd an external device such as a computer or programmable
ples include:
. part number 485SD9TB (DB-9 connection).
number 1761-NET-AIC.
-
38 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
RS-485 Connections
Shield Connection(See Note 4)
IBM Compatible Personal Computer
OrPLC Processor
OrSLC Processor
OrControlLogix Processor
Notes:1)
2)
3)
4)
SHLD
Three-device network shown. Up to 31 DF1Slave Devices can be connected to aDF1 Master without the use of a repeater.Terminating resistors may be required fornetworks with long distances or high noiseenvironments. Consult the RS-232 to RS-485converter manufacturer for more informaiton.Examples:B&B ElectronicsPart Number 485SD9TB (DB9)Allen-Bradley Cat. No. 1761-NET-AICShields should be connected atone end only to avoid ground loops.- November 2009
Powermonitor 3000 Device #1
Powermonitor 3000 Device #2
Powermonitor 3000 Device #3 (Last)
RS-485
RS-485
RS-485
ExternalRS-232C to RS-485
Converter(See Note 3)
150 Terminating
Resistor(See Note 2)
150 Terminating
Resistor(See Note 2)
SHLD
_
+
SHLD
_
+
SHLD
_
+
A
B
-
Powermonitor 3000 Master Module 39
Optional RS-232 Communication
Powermonitor 3000 units with a catalog number ending in -232 are equipped with an RS-232
serial communication port in addition to the native RS-485 port. The RS-232 communication
standard supports point-to-p
select either optional RS-232
ports do not operate at the sa
The optional RS-232 commu
device. It requires a straight-t
programmable controller ser
requires a crossover cable for
resistor is required.
The maximum cable length i
cable pinout information for
connectors.
Connecting Powermonito
Powermo
Or PLC Processor
Or SLC Processor
Or ControlLogix Processor
IBM CompatiblePersonal ComputerPublication 1404-IN007F-EN-P - November 2009
oint communication among two stations or nodes. You must
communication or native RS-485 communication. The two
me time.
nication port is a data communication equipment (DCE) type
hrough RS-232 cable to connect with personal computers,
ial ports, and other data terminal equipment (DTE) devices. It
connection to a modem or other DCE devices. No terminating
s 15.24 m (50.0 ft). Refer to the following wiring diagrams for
constructing your own cable using DB-9 and/or DB-25
r 3000 Unit to Computer Communication Port
nitor 3000
5
9 6
1
2
1
3
4
7
8
9
6
5
TXD
No connect
No connect
No connect
RXD
RTS (See Note 1)
CTS (See Note 1)
DSR (See Note 2)
GND
3
2
4
5
7
3
2 2
3
8
7 7
8
55
TXD
RXD
CTS (See Note 1)
RTS (See Note 1)
GND
TXD
RXD
RTS (See Note 1)
CTS (See Note 1)
GND
DB9 Female
13
25 14
1
DB-25 Female
5
9 6
1
DB9 Female
5
9 6
1
DB9 Female
Powermonitor 3000 Device IBM Personal Computer IBM Personal Computer -
Notes:1) Required only if you have enabled hardware handshaking.2) Internally pulled active in this DCE device - function not supported.3) Straight-through RS-232 cable required.
RS-232
Output
Input
Ground
Output
Input
Output
(See Note 3)
SLC 500 Ch 0 PLC-5 Ch 0 - DB-25 Male
-
40 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Optional Remote I/O Communication
Powermonitor 3000 units with a catalog number ending in -RIO are equipped with a remote
I/O port in addition to the native RS-485 port. Allen-Bradley remote I/O is a robust, widely
used industrial data network
monitor emulates a logical qu
communication. The remote
simultaneously, although ove
Remote I/O communication
recommend that you use Bel
length is shown in the Remo
Use of a star or bridging topo
unless impendance is matche
Be sure that all devices on yo
communication rate. Certain
rate.
Install suitable terminating re
At each end of each cable seg
remote I/O port connector.
high-frequency noise while at
follow the standard blue/shie
Data Highway Plus (clear/sh
Remote I/O Communicati
Communication Rate
57.6 Kbps
115.2 Kbps
230.4 Kbps
TIP Some remo- November 2009
that uses twinaxial cable as its physical media. The power
arter rack and supports both polled I/O and block transfer
I/O port and the native RS-485 port may be used
rall data throughput may be reduced.
wiring should be installed in a daisy-chain configuration. We
den 9463 twinaxial cable or equivalent. The maximum cable
te I/O Communication Rates table and varies with the data rate.
logy is not recommended and will result in signal distortion
d for each spur (star topology) or network (bridge topology).
ur remote I/O network are capable of operation at the desired
legacy devices may not support a 230.4 Kbps communication
sistors at the ends of the remote I/O network.
ment, connect the cable shields to the SHLD terminal of the
The SHLD connection provides a low-impedance ground for
tenuating DC or line-frequency signals. We recommend that you
ld/clear color scheme for remote I/O to differentiate it from
ield/blue) cables.
on Rates
Distance, Max Terminating Resistor
3048 m (10,000 ft) 150 , 1/4 W
1542 m (5000 ft) 150 , 1/4 W
762 m (2500 ft) 84 , 1/4 W
te I/O devices are equipped with internal terminating resistors.
-
Powermonitor 3000 Master Module 41
Configuration options for optional remote I/O communication include the logical rack
address and module group (the power monitor is always one-quarter rack), and data rate.
Defaults are rack 1, group 0, 57.6 Kbps.
Refer to the Powermonitor 3
Refer to the note at the begin
Connecting PowermonitoIBM Compatible
Personal Computer With R I/O
Interface Card
OrPLC Processor/
PLC R I/O Scanner
Or
Or
SLC R I/O Scanner
ControlLogix R I/O Scanner
Notes:1) Three-device network port Up to 32 slave devices can be connected per master R I/O channel.2) Terminating Resistors must be connected to each end of the R I/O network. Omit the terminating resistors if the devices already are equipped with interna terminating resistors.Publication 1404-IN007F-EN-P - November 2009
000 Unit User Manual, publication 1404-UM001.
ning of Communication Wiring on page 36.
r 3000 Unit to Remote I/O Scanner
2
SHLD
1
2
SHLD
1
2
SHLD
1
2
SHLD
1
82 Terminating
Resistor(See Note 2)
82 Terminating
Resistor(See Note 2)
BlueShield
Clear
rayed.
l
R I/O
Powermonitor 3000 Device #3 (Last)
R I/O
Powermonitor 3000 Device #2
R I/O
Powermonitor 3000 Device #1
-
42 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Optional DeviceNet Communication
Powermonitor 3000 units with a catalog number ending in -DNT are equipped with a
DeviceNet port in addition to the native RS-485 port. The DeviceNet network is an
open-standard, multi-vendor
media. The DeviceNet netwo
network. The DeviceNet por
although overall data through
For detailed DeviceNet syste
placement of terminating res
DeviceNet Cable System Pla
publication DNET-UM072.
Refer to the note at the begin
Install suitable terminating re
Configuration options for op
(MAC ID) and data rate. Def
Refer to the Powermonitor 3
TIP Some Devi
IMPORTANT You must inthe DeviceN24V DC sup
DeviceNet Terminal Bloc
Terminal Signa
1 COM (
2 CAN_
3 SHIEL
4 CAN_
5 VDC+ - November 2009
, industrial device data network that uses a variety of physical
rk also provides 24V DC power to devices connected to the
t and the native RS-485 port may be used simultaneously,
put may be reduced.
m installation information, including cable lengths, the
istors, power supplies, and other media components, refer to the
nning and Installation Manual,
ning of Communication Wiring on page 36.
sistors at the ends of the DeviceNet cable.
tional DeviceNet communication include the node address
aults are node 63 and 125 Kbps.
000 Unit User Manual, publication 1404-UM001.
ceNet devices are equipped with internal terminating resistors.
stall and wire a suitable 24V DC power supply to the V+ and V- conductors in et cable. The power monitor consumes less than 100 mA from the DeviceNet
ply.
k Wiring Connections
l Function Color
V-) Common Black
L Signal Low Blue
D Shield Uninsulated
H Signal High White
(V+) Power Supply Red
-
Powermonitor 3000 Master Module 43
Connecting Powermonitor 3000 to Other DeviceNet Devices
Optional Ethernet Communi
Powermonitor 3000 units wi
industry standard Ethernet 1
The power monitor is design
switches using standard UTP
Ethernet Wiring Connection
Powermonitor 3000 Etherne
121 Terminating
Resistor
IBM Compatible Personal Comp1784 PCDPCMCIA Interface
Or1770-KFD Interface Bo
OrPLC With
1771-SDN Scanner
OrSLC With
1747-SDN Scanner
Powermonitor 3000 Device
V-
CAN_L
SHLD
Or Other DeviceNet Scanner DevicesPublication 1404-IN007F-EN-P - November 2009
cation
th catalog numbers ending in -ENT are equipped with an
0/100baseT port.
ed to connect easily to industry-standard Ethernet hubs and
(unshielded twisted-pair) cables with RJ-45 connectors. The
s table shows the cable and connector pin assignments and
t Network Example shows a typical star network topology.
(See Note 2)
121 Terminating
Resistor(See Note 2)
uter With Card
x
Notes:1) Example network protrayed. For detailed DeviceNet installations, including cable requirements, refer to the DeviceNet Cable System Planning and Installation Manual, publication DNET-UM072.2) Terminating Resistors must be connected to each end of the DeviceNet network. Omit the terminating resistors if the devices already are equipped with internal terminating resistors.
V+
CAN_H
V-
V+
CAN_L
SHLD
CAN_H
V-
V+
CAN_L
SHLD
CAN_H
V-
V+
CAN_L
SHLD
CAN_H
+
-
DeviceNet24V DC
Power Supply
-
44 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Powermonitor 3000 Ether
Ethernet Wiring Connections
Terminal Signal
1 TX+
2 TX-
3 RX+
4
5
6 RX-
7
8
LAN
Powermonitor 3000Master Module #1
Powermonitor 3000Master Module #2
PRRRS- November 2009
net Network Example
Function
TX+
TX-
RX+
RX-
Ethernet Switch
ersonal Computer with SLinx and SPower 32 orSEnergyMetrixoftware
PLC-5 Controller
ControlLogix Controller
SLC 500 Controller
-
Powermonitor 3000 Master Module 45
Refer to the note at the beginning of Communication Wiring on page 36.
Configuration options for optional Ethernet communication include the IP (Internet
Protocol) address, subnet mask, default gateway IP address, and protocol.
Defaults are:
IP address: 192.168.2
range 1247.
subnet mask: 255.255
default gateway IP ad
protocol: CSP (PCCC
Optional ControlNet Commu
Powermonitor 3000 units wi
ControlNet communication
single media or redundant m
redundant media is shown he
Powermonitor 3000 Unit C
17(in
Redundant Media(optional)Publication 1404-IN007F-EN-P - November 2009
54.xxx where xxx is the Device ID assigned at the factory in the
.0.0.
dress: 128.1.1.1.
) and CIP (EtherNet/IP network).
nication
th catalog numbers ending in -CNT are equipped with a
interface. The ControlNet power monitor can be connected in a
edia network. An example of a ControlNet network using
re.
ontrolNet Network Example
56-CNBR 1756-A4 chassis)
ControlNetNode
ControlNet Link
ControlNetNode
Powermonitor 3000 Device
Powermonitor 3000 Device
-
46 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Refer to the following documentation for ControlNet network wiring requirements and
general ControlNet information:
ControlNet Coax Media Planning and Installation Guide,
publication CNET-IN002
ControlNet Coax Tap
Connecting a Programming
To connect a programming t
following options:
Using a 1784-KTC, 1
cable
Using a 1770-KFC co
1786-CP cable
1Powermonitor 3000 Device
Powermonitor 3000 Device - November 2009
Installation Instructions, publication 1786-IN007
Terminal to the Network by Using a 1786-CP Cable
erminal to the network using a 1786-CP cable, you have the
784-KTCx, or 1784-PCC communication card and a 1786-CP
mmunication interface, a serial or parallel connection, and a
786-CP Cable1784-KTC, KTCx,PCIC, or PCC Card
ControlNet Link
1786-CP
ControlNet Link
Cable
1770-KFC
Serial or ParallelConnections
-
Powermonitor 3000 Master Module 47
The 1786-CP cable can be plugged into any ControlNet products NAP to provide
programming capability on the ControlNet network. A programming terminal connected
through this cable is counted as a node and must have a unique network address.
Interpret the Status The power monitor is equipp
The three status indicators o
modules with any communic
three status indicators on the
on the communication optio
ATTENTION Use a 1786NAPs. UsinPublication 1404-IN007F-EN-P - November 2009
Indicatorsed with six bi-color status indicators.
n the left display the same information on power monitor
ation option including native RS-485 communication only. The
right have different labels and different indications depending
n selected, as shown in these charts.
-CP cable when connecting a programming terminal to the network through g a commercially available RJ-style cable could result in network failure.
-
48 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Powermonitor 3000 Status Indicators
RS-485 Status Indicators
All Powermonitor 3000 M
Indicator Status
Module Status Off
Steady red
Steady gree
RS-485 RX Off
Flashing gre
RS-485 TX Off
Flashing gre
Native RS-485 Communic
Indicator Status
F1 Off
F2 Off
F3 Off
Powermonitor 3000
Powermonitor 3000
F1
F2
F3- November 2009
odels Status Indicators
Description
Control power is off or insufficient.
Major fault; internal self-test has failed. If a power cycle does not correct the problem, call customer support.
n Power monitor is operating normally.
The RS-485 bus is idle; no active data is present.
en Active data is present on the RS-485 bus.
Power monitor is not transmitting data onto the RS-485 bus.
en Power monitor is transmitting data onto the RS-485 bus.
ation Only (catalog numbers ending in -000)
Description
Not used.
Not used.
Not used.
RX
TXRS-485
MODULE STATUS
-
Powermonitor 3000 Master Module 49
RS-232 Status Indicators
Remote I/O Status Indica
RS-232 Optional Commun
Indicator Status
F1 Off
RS-232 RX Off
Flashing gre
RS-232 TX Off
Flashing gre
Remote I/O Optional Com
Indicator Status
F1 Off
F2 Off
R I/O Off
Flashing gre
Steady gree
Powermonitor 3000
F1
RX
TX}RS-2
Powermonitor 3000
F1
F2
R I/OPublication 1404-IN007F-EN-P - November 2009
tors
ication (catalog numbers ending in -232)
Description
Not used.
The RS-232 bus is idle; no active data is present.
en Power monitor is receiving data.
The power monitor is not transmitting any data onto the RS-232 bus.
en The power monitor is transmitting data.
munication (catalog numbers ending in -RIO)
Description
Not used.
Not used.
Remote I/O communication has not been established.
en Remote I/O communication has been established but there are errors.
n Remote I/O communication has been established.
32
-
50 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
DeviceNet Status Indicators
EtherNet/IP Status Indica
DeviceNet Optional Com
Indicator Status
F1 Off
F2 Off
Network Status Off
Flashing gre
Steady gree
Flashing red
Steady red
EtherNet/IP Optional Com
Indicator Status
LNK Off
Steady gree
ACT Strobing or
F1 Off
Powermonitor 3000
F1
F2
NETWORSTATUS
F1
LNK
ACT
F2
NETWORSTATUS
Powermonitor 3000wermonitor 3000- November 2009
tors
munication (catalog numbers ending in -DNT)
Description
Not used.
Not used.
Power is off or the power monitor is not online.
en Network status is OK, no connections established.
n Network status is OK, connections established.
Recoverable communication failure; port is restarting.
Nonrecoverable communication error; check wiring and configuration parameters.
munication (catalog numbers ending in -ENT)
Description
No valid physical EtherNet connection.
n Valid physical EtherNet connection.
solid yellow Power monitor transmitting onto the EtherNet/IP network.
Not used.
K
K
-
Powermonitor 3000 Master Module 51
ControlNet Status Indica
F2 Off Not used.
Network Status Off
Flashing gre
Steady gree
Flashing red
Steady red
Flashing gre
ControlNet Optional Com
Indicator Status
Chan A and Chan B Off
Steady red
Alternating
Alternating
Steady gree
Flashing gre
Flashing red
Flashing red
Status Off
Flashing gre
EtherNet/IP Optional Communication (catalog numbers ending in -ENT)
Indicator Status Description
CHAN A
CHAN B
NETWORSTATUS
Powermonitor 3000Publication 1404-IN007F-EN-P - November 2009
tors
No power.
en No established connections.
n Connected; has at least one established connection.
Connection timeout; one or more connections to this device has timed-out.
Duplicate IP; the IP address assigned to this device is already in use.
en/red Selftest; this device is performing a power-up self-test.
munication (catalog numbers ending in -ENT)
Description
No power or channel disabled.
Faulted unit.
red/green Self-test.
red/off Incorrect node configuration.
n Normal operation.
en/off Temporary errors or node is not configured to go online.
/off Media fault or no other nodes present on network.
/green Incorrect network configuration.
Normal operation.
en Communication card power-up self-test.
K
-
52 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Access Self-test and Diagnostic Data
You can access valuable diagnostic information by using the optional display module.
1. Connect the display m
2. Using the four contro
Enter.
The display module t
to step through the s
Display Module Status
Display Des
CAT NO The
ACC CLASS Disp
WIN NO The optio
HW REV Disp
FRN MASTER
MODULE
Show
DEVICE ID ShowusedEthe
SELFTEST
STATUS
Dispanom
CODE FLASH Indic
RAM Indic
DATA FLASH Indic
NVRAM Indic
D ACQ Indic
W DOG Indic
CLOCK Indic
COMM Disp
COMM Disp
COMM Dispnorm- November 2009
odule to the master module by using the display module cable.
l keys, navigate through the menus to Display - Status and press
hen displays the following data. Use the up and down arrow keys
tatus data.
cription
unit catalog number and series revision letter.
lays the revenue-meter accuracy class.
units unique Warranty Identification Number (needed for service and nal firmware enhancements).
lays details of the digital board, analog board, and ASIC revisions.
s the master-module firmware revision.
s the units device ID number assigned at the factory. This number is also in the default address for native RS-485, and optional RS-232 and rNet/IP communication.
lays a status code bitfield as a hex number. A non-zero value indicates an aly.
ates the health of the flash-memory code area.
ates the health of the random access memory.
ates the health of the flash-memory data area.
ates the health of the super-cap backed nonvolatile random-access memory.
ates the data-acquisition system health.
ates the system watchdog-timer status.
ates the health of the real-time clock.
lays the firmware revision of the optional communication card (if applicable).
lays the optional communication-card type.
lays the optional communication-status bitfield as a hex number (0000 hex is al for -232 and -RIO units, and 9001 hex is normal for -DNT and -ENT units).
-
Powermonitor 3000 Master Module 53
Refer to the Powermonitor 3
information on using the dis
CalibrationTo meet general operating re
For special customer requirem
for calibration or service info
DMSTA Displays the display-module status bitfield as a hex number. A non-zero value maymod
DM FRN Indic
MM/DD/YYYY Disp
HH/MM/SS Disp
RELAY Show
KYZ Show
S1 STATUS Show
S1 COUNT Show
S2 STATUS Show
S2 COUNT Show
OUTWD Disp
Display Module Status
Display DescriptionPublication 1404-IN007F-EN-P - November 2009
000 Unit User Manual, publication 1404-UM001, for
play module.
quirements, regular recalibration is not necessary.
ents, contact your local Rockwell Automation representative
rmation.
indicate an anomaly, although a non-zero value may appear if a display ule is connected to an operating master module.
ates the display-module firmware revision.
lays the current date.
lays the current time.
s the status of the Form 4C relay.
s the status of the KYZ output.
s the status of Status Input 1.
s the accumulated value of Status Input 1 counter, since last cleared.
s the status of Status Input 2, since last cleared.
s the accumulated value of Status Input 2 counter.
lays the output word bitfield as a hex number.
-
54 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Cleaning Instructions
1. Turn off all electrical
2. Clean the master mo
a. Remove all dust a
lower, and ends o
b. Be sure that the n
3. Clean the display mo
a. Remove all dust a
b. Be sure that the g
good condition.
ATTENTION Electrostatic discharge can damage integrated circuits or semiconductors. Follow these guidelines
Touc
Wea
Do n
Use
Keep
Discosecoperso- November 2009
power supplied to the master module.
dule with a dry, anti-static, lint-free cloth.
nd any obstructions from the cooling air vents on the upper,
f the module.
ameplate is clean and in good condition.
dule with a dry, anti-static, lint-free cloth.
nd foreign materials from the exterior of the module.
raphic front-panel overlay and back nameplate are clean and in
when you handle the module:
h a grounded object to discharge static potential.
r an approved wrist strap grounding device.
ot open the module or attempt to service internal components.
a static safe work station, if available.
the module in its static shield bag when not in use.
nnect and lock out all power sources and short all current transformer ndaries before servicing. Failure to comply with these precautions can lead to nal injury or death, property damage, or economic loss.
-
Powermonitor 3000 Master Module 55
Field Service ConsiderationsIf the power monitor requires servicing, contact your nearest Rockwell Automation sales
office. To minimize your inconvenience, the initial installation should be performed in a
manner that makes removal e
A CT shorting block
master-module curre
CTs an open circuit.
external protective re
All wiring should be
power-monitor termi
Firmware UpgradesPower monitor firmware upg
from time-to-time to improv
firmware enhancements that
an 1404-M6 or 1404-M8, or
Service upgrades may be ava
representative for informatio
Product upgrades are availab
representative for additional
Master module firmware upg
communication port. Firmw
monitor from its installation.
the power monitor and your
power monitor may be requi
Factory-installed CommThe RS-485 communication
or changing a second commu
and is not field upgradeable.
ATTENTION Never openWiring betin the CT sother connapplied prodamage, orPublication 1404-IN007F-EN-P - November 2009
asy.
should be provided to allow the Powermonitor 3000
nt inputs to be disconnected without making the user-supplied
The shorting block should be wired to prevent any effect on the
lays.
routed to allow easy maintenance at connections to the
nal strips and the power monitor itself.
rades are of two types. Service upgrades are those that occur
e operation and resolve issues. Product upgrades are optional
you may purchase to convert your 1404-M5 master module to
your 1404-M6 to an 1404-M8.
ilable at no charge. Contact your local Rockwell Automation
n or visit the Internet at http://www.ab.com/PEMS.
le for purchase. Contact your Rockwell Automation
information.
rades (of either type) are performed by using the native RS-485
are upgrades may be performed without removing the power
An RS-485 to RS-232 converter is required to connect between
personal computer communication port. Cycling power to the
red to complete the firmware upgrade.
unication Cardsis integral to the master module and cannot be removed. Adding
nication card to a power monitor must be done at the factory
a current transformer (CT) secondary circuit with primary current applied. ween the CTs and the power monitor should include a shorting terminal block econdary circuit. Shorting the secondary with primary current present allows ections to be removed, if needed. An open CT secondary with primary current duces a hazardous voltage, which can lead to personal injury, death, property economic loss.
-
56 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Specifications
Measurement Accuracy Powermonitor 3000 Mast
Parameter Accuracy inPower Faca
1404-M4
Voltage sense inputs: V1, V2, V3
0.2%
Current sense input: I1, I2, I3, I4
0.2%
Frequency 0.05 Hz
Power functions: kW, kVA, kVARDemand functions: kW, kVAEnergy functions: kWH, kVAH
ANSI C12.16andEN 61036 Cla1 Accuracy
Metering update rates
6590 ms
Input and Output Ratings
Attribute
Control power 1404-xxxxA-xxx
Control power 1404-xxxxB-xxx
Voltage sense inputs: V1, V2, V3- November 2009
and Rangeer Module - 1404-M4, 1404-M5, 1404-M6, 1404-M8
% of Full Scale at 25 C (77 F) 50/60 Hz Unity tor
Nominal/Range
1404-M5 1404-M6 1404-M8
0.05% 0.05% 0.05% 347V/15399V L-N rms 600V/26691V L-L rms
0.05% 0.05% 0.05% 5 A/50 mA10.6 A rms
0.05 Hz 0.05 Hz 0.05 Hz 50 or 60 Hz/4075 Hz
ss
ANSI C12.20 andEN 60687 Class 0.5 Accuracy (Class 0.2 is also available)
ANSI C12.20 andEN 60687 Class 0.5 Accuracy (Class 0.2 is also available)
ANSI C12.20 andEN 60687 Class 0.5 Accuracy (Class 0.2 is also available)
5580 ms 5585 ms 50100 ms
Value
102240V AC 4763 Hz or106250V DC(0.2 A max loading)
1850V DC (15V A max loading)
Input impedance: 1 M min, 399V AC max; V1, V2 and V3 to N
-
Powermonitor 3000 Master Module 57
Current sense inputs: I1, I2, I3, I4 Overload withstand: 15 A continuous, 200 A for 1 s
Status inputs
Control relayKYZ output
Control Relay(1)
(1) Meets ANSI/IEEE C37.90-1989 sta
Rating
Resistive load switching, max
Load switching, min
UL 508, CSA 22.2, IEC rating clas
Make values, max (inductive load
Break values, max (inductive load
Motor load switching, max
Input and Output Ratings
(1) Meets ANSI/IEEE C37.90-1989 sta
Attribute
Mechanical
Electrical
Input and Output Ratings
Attribute ValuePublication 1404-IN007F-EN-P - November 2009
Burden: 0.05VAImpedance: 0.002 Max crest factor at 5 A: 3Starting current: 5 mA
Contact closure (internal 24V DC)
(1) ANSI C37.90-1989 trip duty(1) Solid state KYZ - 80 mA at 240300V DC
ndards for trip duty.
50/60 Hz AC rms DC
10 A at 250V(2500VA)
10 A at 30V and 0.25 A at 250V
10 mA at 24V 10 mA at 24V
s B300 Q300
) 30 A at 120V15 A at 240V(3600VA)
0.55 A at 125V0.27 A at 250V(69VA)
) 3 A at 120V1.5 A at 240V(360VA)
0.55 A at 125V0.27 A at 250V(69VA)
1/3 HP at 125V1/2 HP at 250V
(1)
ndards for trip duty.
Number of Operations
5 x 106
1 x 105
-
58 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Technical Specifications - 1404-M4, 1404-M5, 1404-M6, 1404-M8
Attribute
Dielectric withstand
Terminal blocks
(1) Recommended ring lug: AMP part
Temperature, operating
Temperature, storage
Humidity
Vibration
Shock- November 2009
1404-M4, 1404-M5, 1404-M6, 1404-M8
Control power 2000V
Voltage inputs 2000V
Current inputs 2000V
Status inputs 500V
Control relays 1600V
Power supply and voltage input terminals
4 mm2 (12 AWG) max, 1.02 Nm (9 lbin) torque,75 C (167 F) or higher copper wire only
Relay, KYZ outputs, current input
terminals(1)
# 320634.
2.5 mm2 (14 AWG) max, 1.18 Nm (10.4 lbin) torque,75 C (167 F) or higher copper wire only
Status inputs, RS485 2.5 mm2 (14 AWG) max,0.56 Nm (5 lbin) torque
RIO, DNT (when present) 2.5 mm2 (14 AWG) max,0.56 Nm (5 lbin) torque
-2060 C (-40140 F) cat. no. 1404-DM, 1404-Mxxxx-000, 1404-Mxxxx-DNT055 C (32 131 F) cat. no. 1404-Mxxxx-232, -RIO, -ENT, -CNT
-4085 C (-40185 F)
595%, noncondensing
10500 Hz: 2 g operational (0.012 in.)
1/2 sine pulse, 11 ms duration: 30 g operational and nonoperational
-
Powermonitor 3000 Master Module 59
Product ApprovalsPowermonitor 3000 units have the following approvals and certifications.
EtherNet/IP Conformance Te
All products equipped with a
below. This mark indicates th
Association (ODVA) indepen
This test provides a level of a
conformance tested EtherNe
representative devices from t
1404-M405A-ENT/B and th
using EtherNet/IP Conform
(http://www.odva.org) main
one of their test labs.
ControlNet Conformance Te
All products equipped with a
This mark indicates the powe
independent test lab and has
level of assurance that the po
ControlNet devices (includin
the Powermonitor 3000 Con
1404-M805A-CNT/A modu
version 12. The CI website (h
have passed the conformanc
UL/CUL
UL 508 listed, File E96956, fPublication 1404-IN007F-EN-P - November 2009
sting
n EtherNet/IP communication port bear the mark shown
e power monitor has been tested at an Open Device Vendor
dent test lab and has passed the EtherNet/IP conformance test.
ssurance that the power monitor interoperates with other
t/IP devices (including devices from other vendors). Two
he Powermonitor 3000 EtherNet/IP family of devices, the
e 1404-M805A-ENT/B modules, have been tested by ODVA
ance Test version A2.8. The ODVA website
tains a list of products that have passed the conformance test at
sting
ControlNet communication port bear the mark shown below.
r monitor has been tested at a ControlNet International (CI)
passed the ControlNet conformance test. This test provides a
wer monitor interoperates with other conformance tested
g devices from other vendors). Two representative device from
trolNet family of devices, the 1404-M405A-CNT/A and the
les, have been tested by CI using ControlNet Conformance Test
ttp://www.ControlNet.org) maintains a list of products that
e test at one of their test labs.
or Industrial Control Equipment and CUL Certified.
-
60 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
CE Certification
If this product bears the CE marking, it is approved for installation within the European
Union and EEA regions. It has been designed to meet the following directives.
EMC Directive
This product is tested to mee
Compatibility (EMC) and the
construction file:
EN 50081-2 - Gener
EN 50082-2 - Gener
This product is intended for
Low Voltage Directive
This product is tested to mee
safety requirements of IEC 1
Measurement, Control, and L
This equipment is classified a
environmental and safety pro
application conditions. See N
applicable, for explanations o
enclosure.
International Standard IEC 5
The Powermonitor 3000 mas
International Standard IEC 5
The Powermonitor 3000 disp
International Standard IEC 5
Follow the recommended ins
ANSI/IEEE Tested
Meets or exceeds the Surge W
and relay systems on all powe- November 2009
t Council Directive 89/336/EEC Electromagnetic
following standards, in whole, documented in a technical
ic Emission Standard, Part 2 - Industrial Environment
ic Immunity Standard, Part 2 - Industrial Environment
use in an industrial environment.
t Council Directive 73/23/EEC Low Voltage, by applying the
010-1, Safety Requirements for Electrical Equipment for
aboratory Use.
s an open style device. Open style devices must be provided with
tection by proper mounting in enclosures designed for specific
EMA Standards publication 250 and IEC publication 529, as
f the degrees of protection provided by different types of
29 / NEMA / UL 508 Degree of Protection
ter module is rated as IP10 degree of protection per
29. It is considered an open device per NEMA and UL 508.
lay module is rated as IP65 degree of protection per
29. It is rated as Type 4 (Indoor) per NEMA and UL 508.
tallation guidelines to maintain these ratings.
ithstand Capability (SWC) C37.90.1 - 1989 for protective relays
r connection circuit terminations.
-
Powermonitor 3000 Master Module 61
Additional ResourcesRefer to these power and energy management documents for more information.
.
You can view or download p
To order paper copies of tech
distributor or sales represent
Documentation FeedYour comments will help us
suggestions on how to impro
available at http://www.rock
For this information
Powermonitor 3000 User Manual1404-UM001
Powermonitor 3000 Display ModuInstructions, publication 1404-IN0
Bulletin 1403 Powermonitor II Tutpublication 1403-1.0.2Publication 1404-IN007F-EN-P - November 2009
ublications at http://www.rockwellautomation.com/literature.
nical documentation, contact your local Rockwell Automation
ative.
backserve your documentation needs better. If you have any
ve this document, complete this form, publication RA-DU002,
wellautomation.com/literature/.
Refer to Publication
, publication Provides details about configuring and using the master module.
le Installation 05
Provides details about how to mount and wire the display module.
orial, Provides details about instrument transformer accuracy and power measurement
-
62 Powermonitor 3000 Master Module
Publication 1404-IN007F-EN-P
Notes:- November 2009
-
Powermonitor 3000 Master Module 63
Notes:Publication 1404-IN007F-EN-P - November 2009
-
Publication 1404-IN007F-EN-P Supersedes Publication 1404-IN007E-EN-P - October 20
Rockwell Automation SupportRockwell Automation provides technical information on the Web to assist you in using its
products. At http://www.rockwellautomation.com/support/, you can find technical manuals,
a knowledge base of FAQs, technical and application notes, sample code and links to software
service packs, and a MySupport feature that you can customize to make the best use of these
tools.
For an additional level of tech
troubleshooting, we offer Tec
your local distributor or Rock
http://www.rockwellautomat
Installation