Post Tension BIJAN AALAMI
-
Upload
khaled-abdelbaki -
Category
Documents
-
view
407 -
download
18
Transcript of Post Tension BIJAN AALAMI
-
8/13/2019 Post Tension BIJAN AALAMI
1/14
The 10 Steps in Design ofThe 10 Steps in Design of
PostPost--Tensioned FloorsTensioned Floors
Dr Bijan O Aalami
Professor Emeritus,
San Francisco State University
Principal, ADAPT Corporation; [email protected]
www.adaptsoft.comwww.adaptsoft.com
301 Mission Street
San Francisco, California
High Seismic Force Region
Four Seasons Hotel; Florida
High Wind Force Region
Column supported multistory
building
Two-way flat slab construction
-
8/13/2019 Post Tension BIJAN AALAMI
2/14
Multi-level parking structures
One-way beam and slab design
(a) STRAND (b) TENDON
NOTE: * NOMINAL DIAMET
(0.5
"*)
CORROSIONINHIBITING
12.7mm
SHEATH
(c) ANCHORAGE ASSEMBLY
STRAND
PLASTIC
WIRECOATING
TUBE
GREASE FILLED PLASTIC CAP
SHEATH
Post-Tensioning SystemsUnbonded System
Example of a Floor System using the Unbonded
Post-tensioning System
An example of a grouted
system hardware with flat duct
Post-Tensioning Systems
Grouted System
-
8/13/2019 Post Tension BIJAN AALAMI
3/14
Example of a Floor System Reinforced
with Grouted Post-Tensioning System
Preliminary Considerations
Design of Post-Tensioned Floor
Dimensions (sizing) Optimum spans; optimum thickness
Structural system One-way/two-way; slab band
Boundary conditions; connections Service performance; strength condit
Load Path; Design strips
Design sections; design values
Preliminary Considerations
Design of Post-Tensioned Floors
Dimensions (sizing) Optimum spans; optimum thickness
An optimum design is one in which thereinforcement determined for servicecondition is used in its entirety forstrength condition.
PT amount in service condition is
governed mostly by: Hypothetical tensile stresses (USA), orcrack width (EC2)
Tendon spacing (USA)
Common spans: 25 30 ft (8 9 m)
Span/thickness ratios 40 - 45 for interior
35 for exterior with no overhang
Selection of load path for two-wasystems Design Strips
Preliminary Considerations
Design of Post-Tensioned Floors
Subdivide the structure into design
strips in two orthogonal directions(Nahid slab)
-
8/13/2019 Post Tension BIJAN AALAMI
4/14
X
Y
G
F
E
D
C
B
A
31 2 4 5
Subdivide the floor along support
lines in design strips
Preliminary Considerations
Design of Post-Tensioned Floors
X
Y
1 2 3 4 5
F
E
D
C
B
A
Subdivide slab along support lines in desig
strips in the orthogonal direction
An important aspect of load path selection in a
two-way system is that every point of the slab
should be assigned to a specific design strip.
portion of the slab should be left unassigned.
Preliminary Considerations
Design of Post-Tensioned Floors
Design sections Design sections extend over the entire
design strip and are considered at criticallocations, such as face of support andmid-span
Preliminary Considerations
Design of Post-Tensioned Floors
Design valuesActions, such as moments at each de
section are reduced to a singlerepresentative value to be used for des
559 is the area (total) value of bending
moment at face of support
-
8/13/2019 Post Tension BIJAN AALAMI
5/14
10 Steps
Design of Post Tensioned Floors
. Geometry and Structural System
2. Material Properties. Loads
. Design Parameters
. Actions due to Dead and Live Loads
. Post-Tensioning
. Code Check for Serviceability
. Code Check for Strength
. Check for Transfer of Prestressing
0. Detailing
Select design strip and Idealize Extract; straighten the support line;
square the boundary
Step 1
Geometry and Structural System
Select design strip and Idealize Extract; straighten the support line;
square the boundary
Model the slab frame with a row ofsupports above and below. Thisrepresents an upper level of multi-storyconcrete frame.
Assume rotational fixity at the farends;
Assume rollersupport at the farends
Step 1
Geometry and Structural System
View of idealized slab-frame
Step 2
Material Properties
ConcreteWeight 24 kN/m3
28 day cylinder 40 MPa
Elastic modulus 35,220 MPa
Long-term deflection factor 2
Non-Prestressed reinforcement fy 460 MPa
Elastic modulus 200,000 M
Prestressing Strand diameter 13 mm
Strand area 99 mm2
Ultimate strength 1,860 MPa
Effective stress 1,200 MPa
Elastic modulus 193,000 M
-
8/13/2019 Post Tension BIJAN AALAMI
6/14
Step 3
Loads
Selfweight Based on member volume
Superimposed dead load Min (partitions) 1 kN/m2
Live load Residential 2.0 kN/m2
Office 2.5 kN/m2
Shopping mall 3.5 kN/m2
Parking structure 2.0 kN/m2
Lateral loads
Wind
Earthquake
Example assumes Superimposed DL SDL= 2 kN/m2
Live load LL = 3 kN/m2
Step 4
Design Parameters
Applicable codeACI 318-11; EC2 EN 1992-1-1:2004
IBC 2012
Local codes, such as California BuildiCode (CBC 2011); or otherwise
Cover for protection against corros
Cover to rebar Not exposed to weather 20 mm Exposed to weather 50 mm
Cover to tendon
Not exposed to weather 20 mm Exposed to weather 25 mm
Step 4
Design Parameters
Cover for fire resistivity
Identify restrained and unrestrainedpanels.
Restrained or
UnrestrainedAggregate Type Cover Thickness, mm. for
Fire Endurance of
1 hr 1.5 hr 2 hr 3 hr 4 hr
Unrestrained Carbonate
SiliceousLightweight
-
--
-
--
40
4040
50
5050
-
Restrained CarbonateSiliceousLightweight
---
---
202020
252525
303030
--
For 2-hour fire resistivity Restrained 20 mm.
Unrestrained 40 mm
Step 4
Design Parameters
Cover for fire resistivity
Identify restrained and unrestraipanels.
-
8/13/2019 Post Tension BIJAN AALAMI
7/14
Step 4
Design Parameters
Allowable Stresses or Crack WidthSelection for Two-Way System
Based on ACI Total load case
Tension
Compression 0.60fc Sustained load case
Tension 0.5fcCompression 0.60 fc
Based on EC2 Frequent load case
Tension Ft = 0.30 fck(2/3)
Compression 0.60fck Quasi permanent load case
Tension Ft = 0.30 fck(2/3)
Compression 0.45fck Crack width normal exposure (?)
Unbonded
Bonded
0.5fc
Step 4
Design Parameters
Allowable deflections (EC2/ approx. A
For visual impact use total deflection Span/250
Use camber, if necessary
Total deflection subsequent to installationmembers that are likely to be damaged
Span/350
Immediate deflection due to live load
Span/500
Long-term deflection magnifier 2. This brinthe total long-term deflection to 3,
Step 5
Actions due to Dead and Live Loads
Analyze the design strip as a singlelevel frame structure with one row ofsupports above and below, using
In-house simple frame program(Simple Frame Method; SFM); or
in-house Equivalent Frame Program (EFM);
Specialty commercial software
All the three options yield safe designs.But, each will give a different amount ofreinforcement.
The EFM is suggested byACI-318. To someextent, it accounts for biaxial action of theprototype structure in the frame model.
Accuracy and ability of commercial softwarefor optimization varies
Step 5
Actions due to Dead and Live Loa
Analyze the design strip as a single levelframe structure with one row of supportsabove and below.
-
8/13/2019 Post Tension BIJAN AALAMI
8/14
Step 6
Post-Tensioning
Selection of design parameters
Selection of PT force and profile
Effective force/tendon selection option- force selection
Calculation of balanced loads;adjustments for percentage of loadbalanced
Calculation of actions due to balancedloads
Step 6
Post-Tensioning
Selection of PT force and profileTwo entry value assumptions must be mad
initiate the computations. Selectprecompression and % of DL to balance
Step 6
Post-Tensioning
Selection of design parameters Select average precompression 1 MPa
Target to balance 60% of DL
Selection of PT force and profileAssume simple parabola mapped within
the bounds of top and bottom covers
Force diagram of simple parabola
Step 6
Post-Tensioning
Assume simple parabola forhand calculation
-
8/13/2019 Post Tension BIJAN AALAMI
9/14
Calculation of balanced loads;
adjustment of % of DL balanced
STEP 6
Post-Tensioning
Select critical span
Select max drape
Calculate %of DL balanced (%DL)
%DL < 50%?
Reduce P/AReduce drape
Yes
Increase P/A
NoYes
No
No Yes
Yes No
Assume P/A =150psi[1MPa]
P /A 80%?
P/A>125psi [0.8MPa]?
Go to next span
1
2
F121_ACI_PT_2_way_082012
Member with widely
different spans
Calculation of balanced loads;
adjustment of % of DL balanced
STEP 6
Post-Tensioning
Select max drap e using tendons
from critical span
Calculate %of DL balanced (%DL)
Move to next span
Reduce P/A or tendons to%DL balanced ~ 60% ;
P/A >= 125 psi [0.8 MPa]
YesNo
No Yes
Is it practical to reduceP/A or tendons?
%DL > 80%?
Raise tendon to reach%DL ~ 60%
Exit after last span
F121_ACI_2-way_PT_force_0
Calculation of balanced loads Lateral forced from continuous tendons
Lateral force from terminated tendons
Moments from change in centroid of
member
Example of force from continuous tendon
STEP 6
Post-Tensioning
P = 500 k
a = 93 mm ; b = 186 mm ; L = 9 m ;
c = {[93/186]0.5/[1 + (93/186)0.5]} * 9.00 = 3.73 m
Wb/tendon = 2 P*a/c2 = 119.0 kN * (2*93/1000)/3.732
= 119.0 kN / tendon * 0.013 / m =1.59 kN/m / tendon
Calculation of balanced loads Lateral forced from continuous tendons
Lateral force from terminated tendons
Moments from change in centroid of mem
Force from terminated tendon
STEP 6
Post-Tensioning
L = 10 m ; a = 93 mm ; P = 119 kN; c =0.20*10 = 2.00
Wb = (3 * 119.0 * 2 * 93 / 1000) / 2.02 16.60 kN/m
Concentrated force at dead end = 2*16.60 = 33.20 k
-
8/13/2019 Post Tension BIJAN AALAMI
10/14
Calculation of balanced loads
Lateral forced from continuous tendons
Lateral force from terminated tendons
Moments from change in centroid of member
Example of force from change in membercentroid
STEP 6
Post-Tensioning
Moment at face of drop = M
M = P * shift in centroid =P * (Yt-Left Yt-Right)
P = 23*119 kN; Yt-Left = 120 mm ; Yt-Right =
146 mm
M= 23*119(120 146)/1000 = -71.16 kNm
Calculation of actions due to balanced load
Check balanced loads for static equilibrium
Determine moments/shears from balanced loads
applied the frame used for dead and
live loads
Note down reactions from balanced loads
STEP 6
Post-Tensioning
Calculation of actions due to balanced loads Obtain moments at face-of-supports and mid-spans
Note the reactions. The reactions are hyperstatic
actions.
Comments:
Moments and precompression will be used for serviceability check.
Reactions will be used for Strength check.
STEP 6
Post-Tensioning
Code requirements for serviceability Load combinations
Stress/crack width check
Minimum reinforcement
Deflection check.
Load combination
Frequent (Total) load condition
1.00DL + 0.50LL + 1.00PT
Quasi Permanent (Sustained) load condition
1.00DL + 0.30LL + 1.00PT
Stress check
STEP 7
Code Check for Serviceabil ity
Using engineering judgment, select the locatio
likely to be cr itical. Typically, these are at the f
and for hand calculation at mid-span
At each section selected for check, use the de
applicable to the entire design section and app
the entire cross-section of the design section
the hypothetical stresses used in code check.
= (MD + 0.5ML + MPT) / S + P/AS = I/Yc ; I = second moment of area of ;
Yc = distance to farthest tension fiber
-
8/13/2019 Post Tension BIJAN AALAMI
11/14
ACI Minimum Reinforcement
STEP 7
Code Check for Serviceabil ity
Yes
6
ACI Minimum Rebarfor two-way systems
F114_041112
BondedUnbonded
At supportsAs = 0.0075Acf
Add rebar to resistforce in tensile zone
No added rebarrequired
EXIT
Add rebar to increaseMoment capacity to
1.2 Mcr
5
4
3
2
1
11
10
9
PT system?
`
`
No
ft ?tension stress
In span calculatehypothetical tension
stress ft
ft > 2 root 'c[ft > 0.17 root f'c ]
ft =< 2 root 'c[ ft =< 0.17 root f'c ]
Does Mcr exceeed1.2xmoment capacity?
No added rebarrequired
Calculate the crackingmoment Mcr at
supports and spans
12
ACI 318-11 Minimum Reinforcement Rebar over support is function of geometry of t
design strip and the strip in the orthogonal
direction
Rebar in span is a function of the magnitude o
the hypothetical tensile stress
STEP 7
Code Check for Serviceabil ity
As = 0.00075 * Acf
As = Area of s teel required
Acf = Larger of cross-sectional area of the
strip in
direction of analysis and orthogonal to
ACI 318-11 Minimum Reinforcement Rebar in span is a function of the magnitude of the
hypothetical tensile stress
In span, provide rebar if the hypothetical
tensile
stress exceeds 0.166f cThe amount of reinforcement As is
given by:
As
= N / (0.5*fy
)
where N is the tensile force in tension
e
STEP 7
Code Check for Serviceabil ity
h = member thickness; b = design section
width
EC2 Minimum Reinforcement Minimum based on cross-sectional area
Minimum based on hypothetical tensile stress
Based on cross-sectional area of section
Asmin (0.26* fctm *bt*d / fyk) 0.0013
*d
STEP 7
Code Check for Serviceabil ity
Based on value of hypothetical tensile stressesfor crack control Check probable crack width Add rebar based using the code
-
8/13/2019 Post Tension BIJAN AALAMI
12/14
Read deflections from the frame analysis of thedesign strip for dead, live and PT; (DL , LL , and PT ).
. Make the following load combinations and
check against the allowable values for each case
Total Deflection
(1 + 2)(
DL +
PT + 0.3
LL ) + 0.7
LL < span/250This is on the premise of sustained load being 0.3
time the design live load. It is for visual effects;
Provide camberto reduce value, where needed and
practical
Immediate deflection from live load
immediate = 1.00L < span/500
This check is applicable, where non-structural
members are likely to be damaged. Otherwise,
span/240 applies
Presence of members likely to be damaged fromsustained deflection
(1+ 2)(0.3 LL ) + 0.7 LL < span/350
STEP 7
Deflection Check
Steps in strength check Load combinations
Determination of hyperstatic actions
Calculation of design moments (Mu)
Calculate capacity/rebarfor design moment Mu
Check for punching shear
Check/detail for unbalanced moment at support
Load combinations (EC2)
U1 = 1.35DL + 1.50LL + 1.0HYP
where, HYP is moment due to hyperstatic actions
from prestressing
Determination of Hyperstatic actions
Direct Method based on reactions from balan
loads
Indirect Method Using primary and post-tensi
moments
STEP 8
Strength Check
Determination of Hyperstatic actions
Direct Method based on reactions from balanced
loads
STEP 8
Strength Check
A comment on capacity versus demand Post-tensioned members possess both a positive
and negative moment capacity along the memb
length
Rebar needs to be added, where capacity falls sh
of demand
First, find the capacity and compare it with deman
STEP 8
Strength Check
-
8/13/2019 Post Tension BIJAN AALAMI
13/14
The figure below shows the forces on a PT member.
In calculating the force from PT tendons, use either
the code formulas or the following simplified
procedure, based on parametric study of common
building structures can be sued.
STEP 8
Strength Check
USING EC2
Assume tendon st ress under serv ice cond it ion 1,200 M
Assume tendon st ress at ul timate limi t s tate 1300 MPa
USING ACI
Tendon Length 38 m for single end stressing; ; length
35 m length 75 m double end stressing
fps is conservatively 1,480 MPa if span is less than 11
fps is conservatively 1,340 MPa if span is greater than
Check for adequate ductility
ACI
Ductility is deemed adequate, if c/dt
-
8/13/2019 Post Tension BIJAN AALAMI
14/14
STEP 9
Check for Transfer of Prestressing
Load combination
U = 1.00*Selfweight + 1.15*PT
Check for allowable stresses
Tension stress
Compression stress
If tension exceeds, provide rebar in tensile
zone to resist Nc
If compression exceeds, wait until concrete
gains adequate strength
Position of rebar
STEP 10
Detailing
STAGGER
SEE PLAN
EQ.
MID-SPAN
STAGGER
DROP CAP
COLUMN
SUPPORT
EQ. EQ.EQ.
SUPPORT TTOP REBAR
SUPPORT
EQ.
WALL
EQ.
SUPPORT LINE
POST-TENSIONED
COLUMN
DROP
Lc/6
Lc/3
Lc
SLAB
Lc/6
*
BOTTOM
PLAN
ELEVATION
Thank you for listening.
www.adaptsoft.com;