Placa Up Ste Cub
-
Upload
luis-felipe-moyano -
Category
Documents
-
view
213 -
download
1
description
Transcript of Placa Up Ste Cub
-
1LIEBERT INTELLISLOT 485 CARDS
Product Specification/Installation SheetDescriptionLiebert IntelliSlot 485 cards provides Liebert SiteScan Web or Building Management Systems monitoring and control of your Liebert equipment.
The card delivers Modbus or the Emerson Protocol via the RS-485 port.
Liebert IntelliSlot 485 Card Liebert IntelliSlot 485 Card-SLiebert IntelliSlot 485 Card-LBDS Liebert IntelliSlot 485 Card-XLiebert IntelliSlot 485 Card-L
Compatibility With Other Emerson Network Power ProductsThe Liebert IntelliSlot 485 Card family, formerly the Liebert OpenComms line, includes:
Liebert IntelliSlot Card Part Number Compatible with:
Liebert IntelliSlot 485 Card OC-485 Liebert GXT Liebert GXT 6kVA&10kVA Liebert GXT3
Liebert GXT2U Liebert Hinet Liebert Nfinity
Liebert NX Liebert PowerSure PSI
(before July 2008)
Liebert IntelliSlot 485 Card-LBDS OC485-LBDS
Units with Liebert iCOM Firmware prior to PA1.04.033.STD: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert PeX Liebert XDC with
Liebert iCOM Liebert XDF
Liebert IntelliSlot 485 Card-L IS-485L
Liebert APM Liebert CRV
Liebert HPC Liebert HPM
Liebert XDP withLiebert iCOM
Units with Liebert iCOM Firmware PA1.04.033.STD or later: Liebert Challenger 3000 Liebert Challenger ITR Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert PeX Liebert XDC with
Liebert iCOM
Liebert IntelliSlot 485 Card-S IS-485SUnits with Liebert IntelliSlot support only: Liebert FDC Liebert FPC
Liebert PPC Liebert RDC
Liebert RX
Liebert IntelliSlot 485 Card-X IS-485X Liebert NXL (SA, SR, SN, MM, CD), Alber BDSU
Liebert IntelliSlot Card Communication ProtocolsThe 485 cards support the following protocols:
Liebert IntelliSlot Card Part Number
Communication Protocol
MODBUS/485 IGM
Liebert IntelliSlot 485 Card OC-485 Liebert IntelliSlot 485 Card-LBDS OC485-LBDS Liebert IntelliSlot 485 Card-L IS-485L Liebert IntelliSlot 485 Card-S IS-485S Liebert IntelliSlot 485 Card-X IS-485X
DTE/DB9F serial port for configuration (requires null-modem connection)
RS-485 (for Modbus)
ORRS-422 (for IGM)Depends on configuration by user
-
2 2007 Liebert CorporationAll rights reserved throughout the world. Specifications subject to change without notice.
Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-28160_REV8_08-13
Liebert Corporation1050 Dearborn DriveP.O. Box 29186Columbus, OH 43229
Telephone: 1-800-877-9222Facsimile: 1-614-841-6022www.liebert.com
Wiring Specifications
Dimensions
Specifications
Connection Supported Wire Type Max. Wire Length
RS-422 (IGM) 18-22 AWG Stranded & Shielded18 AWG recommendedNon Plenum - Belden 9461Plenum - Belden 88761 1000 ft. (300m)
RS-485 (Modbus) 18-22 AWG Stranded & Shielded18 AWG recommendedNon Plenum - Belden 9461Plenum - Belden 88761 3000 ft. (915m)
RS-232DB-9F Connector
Null Modem CableDTE Null Modem Cable
Null Modem CableDTE Null Modem Cable 50 ft. (15.3m)
Power Requirements
AC Inputs 18 - 24 VAC; 50/60 HzDC Inputs 12 - 36VDCPower Consumption 6VA maximum (1.75W)
Dimensions - W x D x H: in. (mm) 3 x 5-1/4 x 1-1/2 (76 x 134 x 38)
WeightNet - oz. (kg) 7 (0.2)Shipping - lb. (kg) 1.3 (0.6)
Ambient Operating Environment, F (C) 32 to 104 (0 to 40); 10% to 90% RH (non-condensing)Ambient Storage Temperature, F (C) -4 to 140 (-20 to 60)Protection SELV Isolated User Connections, Watchdog Timer Circuitry
CommunicationPorts
Service Terminal (RS-232) DB9F, DTEModbus (RS-485) 2-Position Terminal BlockIGM (RS-422) 2-Position Terminal Block
RS485 RS232
- +
2-3/8"(60.3mm)
4-3/4"(121mm)
RS-232 port
1/2" (11mm)
1-1/2"(38mm)
3"(76mm)
FaceplateTOP VIEW
FRONT VIEW
DescriptionCompatibility With Other Emerson Network Power ProductsLiebert IntelliSlot Card Communication ProtocolsWiring SpecificationsDimensionsSpecifications