PIC Tutorials

download PIC Tutorials

of 93

Transcript of PIC Tutorials

  • 8/6/2019 PIC Tutorials

    1/93

    NEMA(1) Define various NEMA enclosure types.The purpose of this document is to providegeneral information on the definitions of NEMA(National Electrical Manufacturers Association)

    Enclosure Types to architects, engineers,installers, inspectors and other interested parties.[For more detailed and complete information,NEMA Standards Publication 250-1997,"Enclosures for Electrical Equipment (1000 VoltsMaximum)" should be consulted. This Standards

    Publication as well as all other NEMApublications are available from IHS @ 800 854-7179.]DefinitionsIn Non-Hazardous Locations, the specificenclosure Types, their applications, and the

    environmental conditions they are designed toprotect against, when completely and properlyinstalled, are as follows:Type 1 - Enclosures constructed for indoor use toprovide a degree of protection to personnel

  • 8/6/2019 PIC Tutorials

    2/93

    against incidental contact with the enclosedequipment and to provide a degree of protectionagainst falling dirt.

    Type 2 - Enclosures constructed for indoor use toprovide a degree of protection to personnelagainst incidental contact with the enclosedequipment, to provide a degree of protectionagainst falling dirt, and to provide a degree ofprotection against dripping and light splashing of

    liquids.Type 3 - Enclosures constructed for either indooror outdoor use to provide a degree of protectionto personnel against incidental contact with theenclosed equipment; to provide a degree ofprotection against falling dirt, rain, sleet, snow,

    and windblown dust; and that will be undamagedby the external formation of ice on the enclosure.Type 3R - Enclosures constructed for either

    indoor or outdoor use to provide a degree of

    protection to personnel against incidental contact

    with the enclosed equipment; to provide a degree

    of protection against falling dirt, rain, sleet, andsnow; and that will be undamaged by the

    external formation of ice on the enclosure.

  • 8/6/2019 PIC Tutorials

    3/93

    Type 3S - Enclosures constructed for either

    indoor or outdoor use to provide a degree of

    protection to personnel against incidental contact

    with the enclosed equipment; to provide a degree

    of protection against falling dirt, rain, sleet, snow,

    and windblown dust; and in which the external

    mechanism(s) remain operable when ice laden.

    Type 4 - Enclosures constructed for either indoor

    or outdoor use to provide a degree of protectionto personnel against incidental contact with the

    enclosed equipment; to provide a degree of

    protection against falling dirt, rain, sleet, snow,

    windblown dust, splashing water, and hose-

    directed water; and that will be undamaged bythe external formation of ice on the enclosure.

    Type 4X - Enclosures constructed for either

    indoor or outdoor use to provide a degree of

    protection to personnel against incidental contact

    with the enclosed equipment; to provide a degree

    of protection against falling dirt, rain, sleet, snow,

    windblown dust, splashing water, hose-directed

    water, and corrosion; and that will be

  • 8/6/2019 PIC Tutorials

    4/93

    undamaged by the external formation of ice on

    the enclosure.

    Type 5 - Enclosures constructed for indoor use to

    provide a degree of protection to personnel

    against incidental contact with the enclosed

    equipment; to provide a degree of protection

    against falling dirt; against settling airborne dust,

    lint, fibers, and flyings; and to provide a degree

    of protection against drippingand light splashing of liquids.

    Type 6 - Enclosures constructed for either indoor

    or outdoor use to provide a degree of protection

    to personnel against incidental contact with the

    enclosed equipment; to provide a degree ofprotection against falling dirt; against hose-

    directed water and the entry of water during

    occasional temporary submersion at a limited

    depth; and that will be undamaged by the

    external formation of ice on the enclosure.

    Type 6P - Enclosures constructed for either

    indoor or outdoor use to provide a degree of

    protection to personnel against incidental contact

    with the enclosed equipment; to provide a degree

  • 8/6/2019 PIC Tutorials

    5/93

    of protection against falling dirt; against hose-

    directed water and the entry of water during

    prolonged submersion at a limited

    depth; and that will be undamaged by the

    external formation of ice on the enclosure.

    Type 12 - Enclosures constructed (without

    knockouts) for indoor use to provide a degree of

    protection to personnel against incidental contact

    with the enclosed equipment; to provide a degreeof protection against falling dirt; against

    circulating dust, lint, fibers, and flyings; and

    against dripping and light splashing of liquids.

    Type 12K - Enclosures constructed (with

    knockouts) for indoor use to provide a degree ofprotection to personnel against incidental contact

    with the enclosed equipment; to provide a degree

    of protection against falling dirt; against

    circulating dust, lint, fibers, and flyings; and

    against dripping and light splashing of liquids.

    Type 13 - Enclosures constructed for indoor use

    to provide a degree of protection to personnel

    against incidental contact with the enclosed

    equipment; to provide a degree of protection

  • 8/6/2019 PIC Tutorials

    6/93

    against falling dirt; against circulating dust, lint,

    fibers, and flyings; and against the spraying,

    splashing, and seepage of water, oil, and

    noncorrosive coolants.

  • 8/6/2019 PIC Tutorials

    7/93

    (2) Summarize NEMA enclosure type 4

    hazardous and non-hazardous locations.

  • 8/6/2019 PIC Tutorials

    8/93

  • 8/6/2019 PIC Tutorials

    9/93

    (3) Describe IP (Ingress protection) classification

    course.

    An IP number is used to specify the

    environmental protection of enclosures around

    electronic equipment. These ratings are

    determined by specific tests. The IP number is

    composed of two numbers, the first referring tothe protection against solid objects and the

    second against liquids. The higher the number

    the better the protection.

  • 8/6/2019 PIC Tutorials

    10/93

    1. Degrees of Protection - First Digit

    The first digit of the IP code indicates the degree

    that persons are protected against contact with

    moving parts (other than smooth rotating shafts,

    etc.) and the degree that equipment is protected

    against solid foreign bodies intruding into an

    enclosure.

    0 No special protection

    1 Protection from a large part of the body such as

    a hand (but no protection from deliberate

    from solid objects greater than 50mm in diameter

    2 Protection against fingers or other objects notgreater than 80mm in length and 12mm

    in diameter

    3 Protection from entry by tools, wires, etc., with

    a diameter or thickness greater than

    2.5mm

    4 Protection from entry by solid objects with a

    diameter or thickness greater than 1.0mm

    5 Protection from the amount of dust that would

    interfere with the operation of the

  • 8/6/2019 PIC Tutorials

    11/93

    equipment

    6 Dust-tight

    2. Degrees of Protection - Second Digit

    Second digit indicates the degree of protection of

    the equipment inside the enclosure against the

    harmful entry of various forms of moisture (e.g.

    dripping, spraying, submersion, etc.).

    0 No special protection1 Protection from dripping water2 Protection from vertically dripping water3 Protection from sprayed water4 Protection from splashed water

    5 Protected against low-pressure jets from alldirections - limited ingress permitted6 Protected against direct sprays from alldirections - limited ingress permitted7 Protection against effects of immersion from15cm to 1m

    8 Protection against complete, continuoussubmersion in water from 15 meters or 50feet

  • 8/6/2019 PIC Tutorials

    12/93

    IP Code Symbols

    The chart below illustrates the use of specialsymbols in the IP classification system. In the "1st

    digit" columns, note the grid-like symbols next tonumbers 5 and 6. In the "2nd digit" columnsnumbers 3-8 are symbolized by teardrop shaped

    symbols, sometimes enclosed in a box or atriangle, sometimes unenclosed (7-8).

    Example:

    1st Digit Protection from solid objects 2nd DigitProtection from solid objects

  • 8/6/2019 PIC Tutorials

    13/93

    UL1.What do you mean by UL standards?

    Ans. UL means Underwriters Laboratories.

    UL 1:These requirements cover flexible

    aluminum and steel conduit designed for use as

    metal raceway for wires and cables in accordance

    with the National Electrical Code, NFPA 70.

    UL 6a:These requirements cover aluminum(ERMC-A) and stainless steel (ERMC-SS)

    electrical rigid metal conduit, nipples, elbows,and couplings in 12 - 155 (3/8 - 6) trade sizes foruse as metal raceway for the installation of wiresand cables in accordance with CSA C22.1,Canadian Electrical Code, Part 1, NOM-001-

  • 8/6/2019 PIC Tutorials

    14/93

    SEDE, Standard for Electrical Installations, andNFPA 70, It is the users responsibility todetermine the appropriate product for the

    application.

    These requirements also cover red brass (ERMC-RB) electrical rigid metal conduit, nipples,elbows, and couplings in 16 (1/2) trade size foruse as metal raceway for the installation of wiresand cables in direct burial and swimming pool

    applications in accordance with the applicablenational electrical installation codes.

    UL 13: These requirements cover 60 - 250C (140- 482F) single- and multiple-conductor power-limited circuit cables for use as fixed wiringwithin buildings (some are also marked for direct

    burial) principally for Class 3 and Class 2 circuitsas described in Article 725 and other applicableparts of the National Electrical Code (NEC).Cables covered by these requirements are:

    a) Types CL3P and CL2P (plenum cables),

    b) Types CL3R and CL2R (riser cables),

    c) Types CL3 and CL2 (commercial cables forother than plenum, riser, or tray uses),

    d) Types CL3X and CL2X (cables for limiteduse), and

  • 8/6/2019 PIC Tutorials

    15/93

    e) Type PLTC (cable for non-plenum and non-riser Class 3 and Class 2 circuits in general andin trays).

    UL 20: The requirements of this Standard applyto manually operated, general-use snap switchesfor connection to copper (Cu) or copper-cladconductors used in accordance with the NationalElectrical Code(NEC), ANSI/NFPA 70, or theCanadian Electrical Code (CEC), and intended

    for connection to wiring systems recognized bythe NEC or the CEC. In Canada, requirementsfor switches for connection to aluminum (Al)conductors used in accordance with the CEC,and intended for connection to wiring systemsrecognized by the CEC.

    This Standard applies to ac/dc rated switches forwhich the load ratings do not exceed 60 A at 250V or less, 30 A at 251 V - 600 V, and 2 hp at 125V - 600 V or less. This Standard also covers ac-only rated switches for which the load ratings donot exceed 30 A at 347 Vac or less.

    This Standard applies to switches constructed tobe installed readily in a flush device box or on anoutlet-box cover and intended for connection tobranch-circuit wiring.

  • 8/6/2019 PIC Tutorials

    16/93

    This Standard applies to pendant and through-cord switches intended for field installation onflexible cord and provided with one "on" and one

    "off" position.

    This Standard applies to switches intended forsurface mounting and provided with a separablebase and cover for connection to exposed wiringconsisting of nonmetallic sheathed cable or openwiring on insulators (knob and tube).

    This Standard applies to self-contained switchesintended for flush mounting without a separateoutlet box and for connection to branch-circuitwiring consisting of one or more non-metallicsheathed cables containing copper conductors.

    This Standard applies to ac/dc fixture switches

    intended to be installed in fixtures to controlincandescent lighting or fans for connection tobranch-circuit wiring.

    This Standard also applies to single-pole,momentary-contact door switches constructed tobe installed readily in a special-purpose device

    box or on an outlet-box cover for connection tobranch-circuit wiring.

    This Standard does not apply to:

  • 8/6/2019 PIC Tutorials

    17/93

    a) Clock operated switches specified in theStandard for Clock-Operated Switches, UL 917,and CSA Standard C22.2 No. 177;

    b) Dimmer switches specified in the Standardfor Solid-State Dimming Controls, UL 1472, andCSA Standard C22.2 No. 184.1;

    c) Industrial control equipment specified in theStandard for Industrial Control Equipment, UL508, and CSA Standard C22.2 No. 14;

    d) Solid-state, single-phase motor speedcontrols specified in the Standard for Solid-StateFan Speed Controls, UL 1917, and CSA StandardC22.2 No. 156;

    e) Special-use and ac-only fixture switchesspecified in the Standard for Special-UseSwitches, UL 1054, and CSA Standard C22.2 No.55; and

    f) Switches for use in hazardous locationsspecified in the Standard for Switches for Use inHazardous (Classified) Locations, UL 894, andCSA Standard C22.2 No. 159.

    For switches intended for connection to branch-circuit wiring containing aluminum conductors,refer to the Standard for Receptacles and

  • 8/6/2019 PIC Tutorials

    18/93

    Switches Intended for Use with Aluminum Wire,UL 1567.

    UL 25: These requirements cover positivedisplacement liquid meters for:

    a) Flammable and combustible liquids of thetype and size commonly used in the assembly ofmotor fuel dispensing devices and

    b) Liquefied petroleum gas (LP-Gas) of the type

    and size commonly used in the assembly of motorfuel dispensing devices and tank trucks.

    UL 33: These requirements cover heat responsivelinks used for fire-protection service. These linksconsist of devices intended for installation underload conditions such as for use with automaticfire suppression systems; or automatic closuredevices for doors, windows, dampers or smokerelief vents.

    UL 48: These requirements cover electric signs,referred to as signs, using incandescent lamps,fluorescent lamps, HID lamps, neon tubing andother combinations, for use in accordance withthe National Electrical Code, NFPA 70.

    UL 58: STANDARD FOR SAFETY FOR STEELUNDERGROUND TANKS FOR FLAMMABLEAND COMBUSTIBLE LIQUIDS

  • 8/6/2019 PIC Tutorials

    19/93

    Scope

    These requirements cover horizontalatmospheric-type steel tanks intended for thestorage underground of flammable andcombustible liquids.

    These requirements cover single wall tanks,secondary containment tanks, multiplecompartment single wall and multiplecompartment secondary containment tanks.

    These tanks are intended for installation and usein accordance with the Standard for theInstallation of Oil-Burning Equipment, NFPA 31,the Flammable and Combustible Liquids Code,NFPA 30, the Automotive and Marine ServiceStation Code, NFPA 30A, and the Standard for

    the Installation and Use of StationaryCombustion Engines and Gas Turbines, NFPA37, and the Uniform Fire Code, published by theInternational Fire Code Institute.

    Tanks covered by these requirements arecylindrical tanks that are fabricated, inspected,

    and tested for leakage before shipment from thefactory as completely assembled vessels.

    These requirements do not apply to tankscovered by the Standard for Welded Steel Tanks

  • 8/6/2019 PIC Tutorials

    20/93

    for Oil Storage, API 650, nor tanks intended foruse in chemical and petrochemical plants.

    This Standard does not cover corrosionprotection which may be required by local, stateor federal authorities. Corrosion protectionsystems installed at the factory on carbon steelunderground storage tanks are covered in UL1746, External Corrosion Protection System forSteel Underground Storage Tanks.

    A product that contains features, characteristics,components, materials, or systems new ordifferent from those in use when the Standardwas developed, and that involves a risk of fire,electric shock, or injury to persons, shall beevaluated using the appropriate additional

    component and end-product requirements asdetermined necessary to maintain the level ofsafety for the user of the product as originallyanticipated by the intent of this Standard.

    UL 65: These requirements cover wired cabinetsfor use in accordance with the National Electrical

    Code.These requirements cover display cases andspecial-purpose cabinets containing electricalwiring, with or without illumination.

  • 8/6/2019 PIC Tutorials

    21/93

    These requirements also cover wired cabinets ofsuch size that they must be sectionalized forshipping from the factory, and assembled and

    wired at the installation site.

    These requirements do not cover bathroomcabinets, cabinets provided with or designed foruse with refrigeration equipment, or general usecabinets or boxes intended for the enclosure ofelectrical equipment.

    UL 67: These requirements cover panel boards tobe employed in accordance with the NationalElectrical Code, NFPA 70.

    These requirements cover panel boards for thecontrol and protection of electric lighting andappliance branch circuits, and power circuits,

    including feeder distribution panel boards. Theyalso cover units specifically designed for panelboard assembly.

    These requirements do not cover:

    a) Distribution equipment which sole function isthe automatic or nonautomatic transferring ofone or more load conductor connections from onepower source to another. Reference the Standardfor Transfer Switch Equipment, UL 1008.

  • 8/6/2019 PIC Tutorials

    22/93

    b) Factory wired assemblies of industrialcontrol equipment intended to control industrialprocesses. Reference the Standard for Industrial

    Control Panels, UL 508A.

    c) Distribution equipment containing only onecircuit subdivision, unless also provided with ameter socket. See 5.5.1. Reference the Standardfor Molded-Case Circuit Breakers, Molded-CaseSwitches and Circuit-Breaker Enclosures, UL

    489.d) Distribution equipment intended to serve asa means for distributing power required tooperate mobile or temporarily installedequipment. Reference the Standard for PowerOutlets, UL 231.

    e) Factory wired assemblies of controllers,timers, temperature regulating equipment andsuch, intended for control of equipment for usewith swimming pools, hot tubs, and/or spas.Reference the Standard for Electric Spas,Equipment Assemblies, and Associated

    Equipment, UL 1563.f) Factory wired assemblies intended for thecontrol of Architectural and Floating Fountains.Reference the Standards for Motor-Operated

  • 8/6/2019 PIC Tutorials

    23/93

    Water Pumps, UL 778, Underwater Luminairesand Submersible Junction Boxes, UL 676 andIndustrial Control Panels, UL 508A.

    g) Portable power distribution equipment.Reference the Standard for Portable Power-Distribution Equipment, UL 1640

    UL 80: These requirements cover steel primary,steel secondary, and steel diked type atmosphericstorage tanks from 60 to 660 gallons (227 to 2500

    L) intended primarily for the storageand supply of heating fuels for oilburning equipment, or alternately forthe storage of diesel fuels forcompression ignition engines andmotor oils (new and used) forautomotive service stations, inaboveground applications.

    UL 96A: These requirements coverthe installation of lightningprotection systems on all types of

    structures other than structuresused for the production, handling, orstorage of ammunition, explosives,flammable liquids or gases, and

  • 8/6/2019 PIC Tutorials

    24/93

    other explosive ingredients includingdust.

    These requirements apply tolightning protection systems that arecomplete and cover all parts of astructure. Partial systems are notcovered by this standard.

    This standard does not cover

    lightning protection for:a) Electric transmission lines oropen air distribution racks,b) Outdoor substations or switchyards, andc) Electric generators unenclosed

    by a building other enclosedstructure.

    UL 132: These requirements coverpressure and safety relief valves andhydrostatic relief valves foranhydrous ammonia and liquefied

    petroleum gas (LP-Gas) for use oncontainers built in accordance withASME Pressure Vessel Code, in

  • 8/6/2019 PIC Tutorials

    25/93

    nonrefrigerated systems in facilitiescovered by the following standards:

    a) Safety Requirements for theStorage and Handling of AnhydrousAmmonia, (ANSI K61.1), ANSI/CGA G-2.1.

    b) Liquefied Petroleum Gas Code,NFPA 58.

    c) Utility LP-Gas Plant Code, NFPA59.

    SPECIAL TYPE

    UL 61010b-2-032: ElectricalEquipment for Measurement,Control, and Laboratory Use.

    Scope:

    Replace the text by the following:

    This International Standard appliesto hand-held and hand-manipulatedCURRENT CLAMPS. These CURRENTCLAMPS are for use in themeasurement of current without

  • 8/6/2019 PIC Tutorials

    26/93

  • 8/6/2019 PIC Tutorials

    27/93

    equipment and computing devicesfor:

    measurement and test; control;

    laboratory use;

    accessories intended for use withthe above (e.g. sample handlingequipment).

    This Part 1 of the standard applies to

    the equipment defined in a) to c)

    below, when used under the

    environmental condition.

    a) Electrical measurement and testequipment. This is equipment whichby electrical means measures,indicates or records one or moreelectrical or non-electricalquantities, also non-measuringequipment such as signalgenerators, measurement standards,power supplies, transducers,transmitters, etc. NOTE - Allindicating and recording electrical

  • 8/6/2019 PIC Tutorials

    28/93

    measuring instruments (except thoseexcluded in 1.1.2) fall within thescope of this standard unless theyare panel meters designed only forbuilding-in to other equipment. Built-in panel meters are considered ascomponents and only need to meetthe relevant requirements of IEC1010, or other standards, as part ofthe equipment into which they arebuilt.

    b) Electrical control equipment.This is equipment which controls oneor more output quantities to specific

    values, with each value determinedby manual setting, by local or remoteprogramming, or by one or moreinput variables.

    c) Electrical laboratory equipment.This is equipment which measures,

    indicates, monitors or analysessubstances, or is used to preparematerials. This equipment may also

  • 8/6/2019 PIC Tutorials

    29/93

    be used in areas other thanlaboratories.

    UL 61010c-1: Process ControlEquipment

    This International Standard specifiesgeneral safety requirements forelectrical equipment intended forprofessional, industrial process, and

    educational use, includingequipment and computing devicesfor:

    measurement and test;

    control;

    laboratory use;

    accessories intended for use withthe above (e.g. sample handlingequipment).

  • 8/6/2019 PIC Tutorials

    30/93

    This Part of the standard applies to

    the equipment defined in a) to c)

    below, when used under theenvironmental conditions.

    a) Electrical measurement and testequipmentThis is equipment whichby electrical means measures,indicates or records one or moreelectrical or non-electricalquantities, also non-measuringequipment such as signalgenerators, measurement standards,power supplies, transducers,transmitters, etc.NOTE - Allindicating and recording electricalmeasuring instruments fall withinthe scope of this standard unlessthey are panel meters designed onlyfor building-in to other equipment.Built-in panel meters are consideredas components and only need tomeet the relevant requirements ofIEC 1010, or other standards, as part

  • 8/6/2019 PIC Tutorials

    31/93

    of the equipment into which they arebuilt.

    b) Electrical control equipmentThisis equipment which controls one ormore output quantities to specificvalues, with each value determinedby manual setting, by local or remoteprogramming, or by one or more

    input variables.c) Electrical laboratoryequipmentThis is equipment whichmeasures, indicates, monitors oranalyses substances, or is used toprepare materials.This equipment

    may also be used in areas other thanlaboratories

    UL 61010-1: Electrical Equipment ForMeasurement, Control, andLaboratory Use;

    This part of IEC 61010 specifies

    general safety requirements forelectrical equipment intended forprofessional, industrial process, andeducational use, any of which may

  • 8/6/2019 PIC Tutorials

    32/93

    incorporate computing devices, asdefined in a) to d) below, when usedunder the environmental conditions.

    a) Electrical test and measurementequipmentThis is equipment whichby electrical means tests, measures,indicates or records one or moreelectrical or non-electrical

    quantities, also non-measuringequipment such as signalgenerators, measurement standards,power supplies, transducers,transmitters, etc.NOTE All indicatingand recording electrical measuring

    instrument fall within the scope ofIEC 61010 unless they are panelmeters designed only for building-into other equipment. Built-in panelmeters are considered to becomponents and only need to meet

    the relevant requirements of IEC61010, or other standards, as part ofthe equipment into which they arebuilt.

  • 8/6/2019 PIC Tutorials

    33/93

    b) Electrical control equipmentThisis equipment which controls one ormore output quantities to specificvalues, with each value determinedby manual setting, by local or remoteprogramming, or by one or moreinput variables.

    c) Electrical laboratory

    equipmentThis is equipment whichmeasures, indicates, monitors oranalyses substances, or is used toprepare materials, and includes invitro diagnostic (IVD) equipmentThisequipment may also be used in areas

    other than laboratories, for exampleself-test IVD equipment may be usedin the home.

    d) Accessories intended for usewith the above (for example, samplehandling equipment).

    UL-61010a-1:Electrical EquipmentFor Laboratory Use

    This International Standard specifiesgeneral safety requirements for

  • 8/6/2019 PIC Tutorials

    34/93

    electrical equipment intended forprofessional, industrial process, andeducational use, includingequipment and computing devicesfor:

    measurement and test;control; laboratory use; accessories intended for

    use with the above (e.g.sample handlingequipment).

    This Part 1 of the standard applies to

    the equipment defined in a) to c)below, when used under the

    environmental conditions.

    a) Electrical measurement and testequipmentThis is equipment whichby electrical means measures,indicates or records one or moreelectrical or non-electricalquantities, also non-measuringequipment such as signal

  • 8/6/2019 PIC Tutorials

    35/93

    generators, measurement standards,power supplies, transducers,transmitters, etc.NOTE - Allindicating and recording electricalmeasuring instrumet fall within thescope of this standard unless theyare panel meters designed only forbuilding-in to other equipment. Built-in panel meters are considered ascomponents and only need to meetthe relevant requirements of IEC1010, or other standards, as part ofthe equipment into which they arebuilt.

    b) Electrical control equipmentThisis equipment which controls one ormore output quantities to specificvalues, with each value determinedby manual setting, by local or remoteprogramming, or by one or more

    input variables.c) Electrical laboratoryequipmentThis is equipment whichmeasures, indicates, monitors or

  • 8/6/2019 PIC Tutorials

    36/93

  • 8/6/2019 PIC Tutorials

    37/93

    FMWhat do you mean by FM (FactoryMutual) Standards & Define thefollowing.

    FM 1110 :This standard sets

    performance requirements for indicator

    posts. Indicator posts are controls,

    extending above ground or through

    building walls, for operating gate valves

    used in fire protection systems. Animportant feature of their design is a

    target indicator, visible through an

    opening in the post, which is provided to

    show whether the valve is open or shut.

    FM 1221 :This standard sets

    performance requirements for backflow

    preventers which can be used in

  • 8/6/2019 PIC Tutorials

    38/93

    connections between public water

    supplies and fire protection systems to

    prevent reverse flow. Local healthauthorities usually recommend these

    devices to prevent contaminated water

    from entering public water supplies.

    FM 1321 : This standard encompasses

    the design and performancerequirements for controllers for electric

    motor driven and diesel engine driven

    fire pumps used in fire pump service

    that are designed and installed in

    accordance with the applicabledocuments and the FM Global Property

    Loss Prevention Data Sheets. The

    intended operation of a fire pump

    controller is to initiate and sustain the

    operation of the fire pump driver in the

    event of a fire. In addition, controllers

    are tested under specified overload and

    fault conditions. To this extent the fire

  • 8/6/2019 PIC Tutorials

    39/93

    pump controller is unique when

    compared to other industrial motor

    controllers, and system reliability isimproved by provisions for

    self testing and annunciation of

    conditions that could result in fire

    protection impairment.

    FM 1333 : This standard encompassesthe design and performance

    requirements for diesel engines used in

    fire pump service that are designed and

    installed in accordance with FM Global

    Property Loss Prevention Data Sheets.This Standard does not address National

    or Local Codes which require specific

    emission levels to be

    met by stationary diesel engine

    installations.FM 1635 : This standard encompasses

    the design and performance

    requirements for plastic pipe and

  • 8/6/2019 PIC Tutorials

    40/93

    fittings in light hazard occupancies for

    use in automatic wet sprinkler fire

    protection systems. Approval standardsare intended to verify that the product

    described will meet stated conditions of

    performance, safety, and quality useful

    to the ends of property conservation.

    FM 2000 : This standard states FMApprovals criteria for automatic control

    mode sprinklers for fire protection

    service. FM Approvals criteria may

    include, but are not limited to,

    performance requirements, markingrequirements, examination of

    manufacturing facility (ies), audit of

    quality assurance procedures, and a

    follow-up program.

    FM 2008 : These automatic sprinklersare intended for use in certain

    occupancies in which fire suppression is

    possible. They are not suitable for use in

  • 8/6/2019 PIC Tutorials

    41/93

    occupancies where fire cannot be

    suppressed by water (e.g., low flash

    point flammable liquids, oxidizingchemicals, etc.). Refer to the FM Global

    Property Loss Prevention Data Sheets

    for more specific information.

    FM 3260 : This standard sets

    performance requirements for radiantenergy-sensing fire detectors for the

    protection of occupants, building space,

    structure, area, or object.FM Approval

    Standards are intended to verify that

    the product described will meet statedconditions of

    Performance, safety and quality that are

    useful to the ends of property

    conservation.

    FM 3600 : This standard shall apply to:Electrical equipment or parts of

    electrical equipment rated for use in

    Hazardous (Classified) Locations as

  • 8/6/2019 PIC Tutorials

    42/93

    defined by the National Electrical Code

    (NEC), ANSI/NFPA 70;

    Associated equipment located outside ofthe Class I, II or III location whose design

    and construction may influence those

    parts of the equipment within the

    classified location.

    FM 3610 :This standard provides

    requirements for the construction and

    testing of electrical apparatus, or parts

    of such apparatus, whose circuits are

    incapable of causing ignition in:Classes

    I, II & III, Division 1 hazardous

    (classified) locations as defined in

    Article 500 of the National Electrical

    Code, ANSI/NFPA-70 (NEC).

    FM 3611 :

    This standard sets performancerequirements for the construction and

    testing of electrical apparatus, or parts

    of such apparatus, for use in Class I and

  • 8/6/2019 PIC Tutorials

    43/93

    II, Division 2, and Class III, Divisions 1

    and 2 hazardous (classified) locations.

    Electrical equipment intended for use inClass I and II, Division 2, and Class III,

    Divisions 1 and 2 hazardous (classified)

    locations is apparatus in which any

    spark or thermal effect, produced under

    normal conditions,

    is incapable of causing ignition of a

    specified mixture of flammable or

    combustible material in air.

    FM 3615 :

    This standard contains the basic

    requirements for the construction and

    testing of explosion proof electricalequipment. This standard is intended to

    be used in conjunction with Approval

    Standard 3600 which includes the

  • 8/6/2019 PIC Tutorials

    44/93

    general requirements that apply to all

    types of hazardous (classified) location

    protection methods.FM 3620 :

    This standard is intended to be used in

    conjunction with Class 3600 FM

    Approval Standard which includes the

    general requirements that apply to alltypes of protection for electrical

    equipment for use in hazardous

    (classified) locations.

    FM 3810 :

    This standard applies to

    electrical, electronic, or electro-

    mechanical equipment designed:

    to measure or observe, and indicate

    quantities of electrical or electronicphenomena, or

    to supply electrical or electronic

    quantities for measuring or indicating

  • 8/6/2019 PIC Tutorials

    45/93

    purposes, or

    to measure or control, directly or

    indirectly, an industrial process, orto measure or indicate electrical

    analogs of non-electrical phenomena, or

    to measure, indicate, monitor, analyze

    substances or prepare materials, i.e.,

    Laboratory Equipment.

    FM 3990 :

    This standard

    also applies to any component intended

    for use as a protective device and that

    is normally provided as part of thetransformer assembly. Use of

    components previously Approved as

    individual protective devices shall not

    automatically result in an Approved

    transformer assembly.

    FM 6051 : The

    requirements of this standard are

    intended as guidelines reflecting current

  • 8/6/2019 PIC Tutorials

    46/93

    FM Approval tests and practices.

    Containers, which do not precisely

    conform to these requirements may beApproved if they meet the intent of this

    standard. Similarly, items that do

    conform to these requirements may not

    be Approved if they do not meet the

    intent of these requirements or if other

    conditions govern.

    FM 6310 :

    This

    standard is concerned with the detailsof construction, performance and

    testing of portable, mobile and

    stationary electrical instruments that

    sense the presence of combustible gas

    or vapour concentrations in air. Based

    on associated requirements specified in

    Section 3, this standard considers the

    suitability of the instruments or parts

  • 8/6/2019 PIC Tutorials

    47/93

    thereof for use in Class I, hazardous

    (classified) locations as defined by the

    National Electrical Code (ANSI/NFPA70).

  • 8/6/2019 PIC Tutorials

    48/93

    Tender

    Specification forPower Plant

    (Diesel)

    Switchgear andControl System

    for the Electrical

    Equipment of a Diesel

    Power Station

    8 x 6500 kVA, 11 kV,50 Hz

    Drawings andDocumentation

  • 8/6/2019 PIC Tutorials

    49/93

    Drawings and documentation willbe issued to the above mentioned

    standards.

    3-fold in DIN A4 size, English

    language.

    Drawings will be generated with

    our engineering system CAE 33.

    Preparation of documents used in

    Electric Technology Part 2:

    Function-oriented diagrams acc. to

    DIN/EN 61082-1-3 (IEC 1082-1-3)

    Diagrams, charts, tables:

    Item designation acc. to DIN 40

    719-2 (IEC 750).

    Graphical symbols of diagrams acc.

    to DIN 40 900-1.....12

  • 8/6/2019 PIC Tutorials

    50/93

    (IEC 617-1.....12).

    Normal colour codes of the wiring

    as follows:

    Black - the 3 phases and

    normal control wiring

    and

    secondary

    winding of

    p.t.'s

    Light Blue - neutral

    Yellow / Green - earthing

    Red - DC-

    wiring 24 V+

    Blue - DC-

    wiring 24 V-

    Brown - DC-wiring 110 V+

    Violet - DC-

    wiring 110 V-

  • 8/6/2019 PIC Tutorials

    51/93

    Grey - secondary

    wiring of c.t.'s

    White - wiring forpotential free contacts.

    The Common Control Panel

    consisting of:

    1 Control and Monitoring Unit

    interface "CMC1" with 10.4" colour

    graphic

    display

    1 Secondary, freely programmable

    logic control system (PLC) for the

    common control specific features

    Interconnecting Remote Modules

    "IRM-1" for the common

  • 8/6/2019 PIC Tutorials

    52/93

    auxiliaries

    Depending on the configuration,

    the following modes of operation(see also

    page 3) and functions are available:

    Standby operation (gen.-sets are

    started only in case of mains

    failure)

    Prime power operation (permanent

    operation without connection to the

    mains)

    Mains parallel operation

    Mains parallel operation with

    automatic standby operation

    Black Start function

    Load management

    Interfaces for data transfer with:

    the Control and Monitoring units

    for Gen-Set type "CMG-2",mounted in

    alternator control panels (CAN-Bus)

    the offered Power Station Scada

  • 8/6/2019 PIC Tutorials

    53/93

  • 8/6/2019 PIC Tutorials

    54/93

    The Local Data Board additionally

    consists of:

  • 8/6/2019 PIC Tutorials

    55/93

    1 Programmable logic controller

    PLC, make SEGPLC with the following functions:

    Start preparation with engine-

    specific start-up program

    Control and supervision of the

    engine and its auxiliary drives

    Data collection of the analogue and

    digital signals of the actors and

    sensors of the engine

    Data transfer

    Shut-down of Diesel engine

    PLC consisting of:

    Compact housing with modules of

    required quantity

    Power supply

    Central controller (CPU)

    Digital input channels acc. to theengine manufacturers monitoring

    list

    Digital output channels

  • 8/6/2019 PIC Tutorials

    56/93

  • 8/6/2019 PIC Tutorials

    57/93

    Installation on mounting plate of:

    Engine electronic speed governor

    (issued free of charge by theengine

    supplier

    Alternator voltage regulator

    (outside dimensions max. 320 x 550

    mm)

  • 8/6/2019 PIC Tutorials

    58/93

  • 8/6/2019 PIC Tutorials

    59/93

    Power Station Scada System "PSS"

    The central communication

    interface of the power station

    consists of:

    1 Personal computer with

    Pentium processor with

    appropriate performance

    and memory capacity

    1 Colour graphic monitor, 19"

    with high resolution

    1 DIN A4 colour inkjet printer for

    event and graphic printout1 Ethernet network with

    Ethernet cards for insertion into

    the vacant slots of

    the "CMG-2" and "CMC-1"

    processorsOperating system Windows

    95/98

    Graphics software "InTouch" by

  • 8/6/2019 PIC Tutorials

    60/93

  • 8/6/2019 PIC Tutorials

    61/93

    Transmission of control and

    switching commands to the

    respectivesystems (with password

    protection)

    Long-term storage of the data and

    events stored in the individual

    subsystems "CMG-2" and "CMC-

    1"

    Tender

    Specificati

    on for

  • 8/6/2019 PIC Tutorials

    62/93

    PharmaIndustry

    1

    .

    Product andPacka

    ge

    Specificatio

    ns

    1

    .

    1

    The Goods to be

    purchased by the

    Purchaser under this

    Invitation for Bids are

    included in the

    Purchasers current

    national essential

    drugs list or national

    formulary. The required

    packing standards andlabel must meet the

    latest requirements of

    the World Health

  • 8/6/2019 PIC Tutorials

    63/93

    Organization (WHO)

    good manufacturing

    practices (GMP)

    standards in all

    respects. (These

    standards contained in

    Good Practices in the

    Manufacture and

    Quality Control ofDrugs.)

    1

    .

    2

    Product specifications

    indicate dosage form

    (e.g., tablet, capsules,dry syrup, liquid,

    ointment, injectable,

    emulsion suspension,

    etc.) and the drug

    content (exact number

    of mg or internationalunits [IU] or % v/v, wlw

    or v/w acceptable

    range). The Goods

  • 8/6/2019 PIC Tutorials

    64/93

    should conform to

    standards specified in

    the following

    compendia: [The

    procuring entity should

    specify an accept

    Pharmacopoeia

    standard from one of

    the following: theBritish Pharmacopoeia,

    the United States

    Pharmacopoeia, the

    French Pharmacopoeia,

    the International

    Pharmacopoeia ortheEuropean

    Pharmacopoeia, the

    latter particularly for

    raw materials.] The

    standards will be the

    latest edition unless

    otherwise stated by

    the Purchaser or other

    if applicable. In case

  • 8/6/2019 PIC Tutorials

    65/93

  • 8/6/2019 PIC Tutorials

    66/93

    and labelling) should

    also meet

    specifications suitable

    for distribution,

    storage, and use in a

    climate similar to that

    prevailing in the United

    Republic of Tanzania.

    All packaging must beproperly sealed and

    tamper-proofand

    packaging components

    must meet the latest

    compendium standards

    and be approved forpharmaceutical

    packaging by the

    manufacturer's

    national Regulatory

    Authority (RA). The

    Purchaser should

    specify any additional

    special requirements.

  • 8/6/2019 PIC Tutorials

    67/93

    1

    .4

    All labelling and

    packaging inserts shallbe in the language

    requested by the

    Purchaser or English if

    not otherwise stated.

    1

    .

    5

    Goods requiring

    refrigeration or

    freezing or those that

    should not fall below a

    certain minimum

    temperature forstability must

    specifically indicate

    storage requirements

    on labels and

    containers and be

    shipped in specialcontainers to ensure

    stability in transit from

    point of shipment to

  • 8/6/2019 PIC Tutorials

    68/93

    port of entry.

    1.

    6

    Upon award, thesuccessful Supplier

    shall, on demand,

    provide a translated

    version in the language

    of the bid of the

    prescriber's

    information for any

    specific goods the

    Purchaser may request.

    2

    .

    Labelli

    ng

    Instru

    ctions

    2

    .

    1

    The label of the

    primary container for

    each pharmaceutical

    and vaccine products

    shall meet the W210

    GMP standard and

    include:

    the international

  • 8/6/2019 PIC Tutorials

    69/93

    non-proprietaryname (INN) orgeneric name

    prominentlydisplayed and above

    the brand name,where a brand name

    has been given.Brand names should

    not be bolder orlarger than thegeneric name;

    dosage form, e.g.,tablet, ampoule,

    syrup, etc.;

    the activeingredient "per unit,

    dose, tablet orcapsule, etc.";

    the applicablepharmacopoeial

    standard;

  • 8/6/2019 PIC Tutorials

    70/93

    the Purchaser's logo

    and code numberand any specificcolour coding if

    required;

    content per pack;

    instructions for use;

    special storagerequirements;

    batch number;

    date of manufactureand date of expiry(in clear language,

    not code);

    name and addressof manufacture; and

  • 8/6/2019 PIC Tutorials

    71/93

    Any additional

    cautionarystatement.

    2

    .

    2

    The outer case or

    carton should also

    display the above

    information.

    3

    .

    Case

    Identif

    icatio

    n

    3

    .

    1

    All cases should

    prominently indicate

    the following:

    Purchaser's line andcode numbers;

    the generic name ofthe product;

    the dosage form

    (tablet, ampoule,syrup);

    date of manufactureand expiry (in clear

  • 8/6/2019 PIC Tutorials

    72/93

    language not code);batch number;

    quantity per case;

    special instructions forstorage;

    name and address ofmanufacture; and

    any additionalcautionary statements.

    3

    .

    2

    No case should contain

    pharmaceutical

    products from more

    than one batch.

    4

    .

    Uniqu

    e

    Identif

    iers

    4

    .

    1

    The Purchaser shall

    have the right to

    request the Supplier to

    imprint a logo, if the

    quantity so justifies it,

    on the labels of thecontainers used for

    packaging and in

    certain dosage forms,

  • 8/6/2019 PIC Tutorials

    73/93

    such as tablets, and

    ampoules andthis will

    be in the Technical

    Specifications. The

    design and detail will

    be clearly indicated at

    the time of biding, and

    confirmation of the

    design of such logoshall be provided to

    the Supplier at the

    time of contract award.

    5. Standards

    of

    Qualit

    y

    Contro

    l forSuppl

    y

    5.

    1

    The successful Supplierwill be required to

    furnish to the

    Purchaser:

    With eachconsignment, and foreach item a WHO

    certificate of qualitycontrol test results

  • 8/6/2019 PIC Tutorials

    74/93

    concerningquantitative assay,chemical analysis,

    sterility, pyrogencontent uniformity,microbial limit, and

    other tests, asapplicable to the Goodsbeing supplied and the

    manufacturer'scertificate of analysis;

    Assay methodology ofany or all tests if

    requested;

    Evidence of bio-availability and/or bio-equivalence for certain

    critical Goods uponrequest. This

    information would besupplied on a strictly

    confidential basis only;and

  • 8/6/2019 PIC Tutorials

    75/93

    Evidence of basis forexpiration dating andother stability data

    concerning thecommercial final

    package upon request.

    5

    .

    2

    The Supplier will also

    be required to provide

    the Purchaser withaccess to its

    manufacturing facilities

    to aspect the

    compliance with the

    GMP requirements and

    quality control

    mechanisms.

    TECHNICAL SPECIFICATION FOR

    PHARMACEUTICALS

    Product quality and Package

    Specifications

    Product specification should

  • 8/6/2019 PIC Tutorials

    76/93

    indicate dosage form (e.g., tablet,liquid, injection, emulsion,

    suspension, etc.) and the drug

    content (exact number of mg or %v/v per doses with acceptablerange). The product should

    conform to standards specified inthe latest edition of one of the

    following compendia: the BritishPharmacopoeia (BP), the United

    State Pharmacopoeia (USP)European Pharmacopoeia (EP) orthe International Pharmacopoeia

    (IP). In case the pharmaceutical isnot included in the specified

    compendium, the supplier must

    provide the reference standardsand testing protocols to allow for

    quality control testing.

    The following information must besubmitted with the bid:

    Certificates of pharmaceutical productsaccording to WHO 41.18 Certification

    scheme on the quality of

  • 8/6/2019 PIC Tutorials

    77/93

    pharmaceutical product moving ininternational commerce must be

    enclosed.

    Copies of registration

    certificates of registered

    products for human

    medicines for products

    tendered issued by theTanzania Food and Drug

    Authority (TFDA).

    Otherwise bidders shall submit copiesof the following documents:

    A receipt of registration fee

    issued by the Tanzania Food andDrug Authority (TFDA).

    A letter of acknowledgement

    from the TFDA that the drug

    dossier and sample have been

    received.Copy of certificate of

    pharmaceutical product from

  • 8/6/2019 PIC Tutorials

    78/93

    Drug Regulatory Authority (DRA)

    in the country of origin.

    The required packing standards andlabelling of pharmaceuticals must meetthe WHO Good Manufacturing Practices

    ("GMP") standard in all respects.

    Alternative specifications to meetfunctional requirements will be

    considered, but must be submittedseparate from, and not on the scheduleof quantities and must be limited to amaximum of two offers including the

    quoted offer.

    The packaging components (e.g.,bottles and closures) should meet

    specifications suitable for thepurpose and have no detrimental

    effects on the pharmaceuticalproduct Primary packing materials

    must give adequate protectionagainst external influence and

    potential contamination. All light

  • 8/6/2019 PIC Tutorials

    79/93

  • 8/6/2019 PIC Tutorials

    80/93

    100 ml bottles liquidsyrups/suspensions in not more than

    24 units per carton

    5 litres bottles in not more than 4 unitsper carton

    Eye drops should not be packedmore than 30 units per carton,and if more than 10 units, the

    box must be partitioned.Ampoules/ vials must be packed

    in units of 10 in sealed boxesand each ampoule/vials must bemarked with the product name,

    strength, batch number,manufacture and the expiry

    date. Instruction leaflets shouldbe inserted.

    All packing must be properly sealedand tamper-proof.

    Pharmaceuticals requiringrefrigeration of freezing for stability

    must specifically indicate storage

    requirements on labels and

  • 8/6/2019 PIC Tutorials

    81/93

    containers and be shipped in special

    container to ensure stability in

    transit from point of shipment to

    Medical stores Department (MSD).

    Manufacture and expiration date

    All products must indicate the dates

    of manufacture and expiry in a clearlanguage note codes. In additional

    all products must arrive at the

    port/airport of Dar es Salaam with a

    remaining shelf life of at least 80%

    of the total stipulated shelf life at

    the time of manufacture.

    Qualifications of Manufacturer

    The Supplier shall furnish a

    certificate from the competent

    authority such as Food and Drug

    Authority (FDRA) that the

    manufacturer of the

    pharmaceuticals is licensed to

  • 8/6/2019 PIC Tutorials

    82/93

    manufacture these products.

    Standards and Quality Assurance forSupply

    4.1All products must:

    Meet the requirements ofmanufacturing legislation and

    regulation of pharmaceuticals in thecountry of origin.

    Conform to all the specificationscontained herein.

    Be certified by a competent authority

    in the manufacturer's countryaccording to resolution WHO 28-65B, of

    the World Health Organization"Certifications Scheme on the Qualityof Pharmaceuticals Products Moving

    International Commerce"

    6.2The Supplier will also berequired, if requested, to providethe purchaser with access to its

    manufacturer facilities to inspect its

  • 8/6/2019 PIC Tutorials

    83/93

    facilities, quality control proceduresfor raw materials, test methods, in-process tests, and finished dosage

    forms.

    Recalls

    In the event any of the Goods are

    recalled, the Supplier shall notify the

    Purchaser within fourteen (14) days,providing full details of the reason for

    the recall and promptly replace, at its

    own cost, the items covered by the

    recall with Goods that fully meet the

    requirements of the Technical

    Specification and arrange for collectionor destruction of any defective Goods.

    If the Supplier fails to fulfil its recall

    obligation promptly, the Purchaser will,

    at the Suppliers expense, carry out

    the recall.

  • 8/6/2019 PIC Tutorials

    84/93

    Tender

    Specification for

  • 8/6/2019 PIC Tutorials

    85/93

    OilRef inerySCOPE :

    The Specification covers manufacture, testing, supply & delivery and therequirementsof new insulating oil of petroleum origin suitable for use as insulating and heattransfermedium and are quenching medium in Power/Distribution transformers and otherequipments used in West Bengal by WBSEDCL.

    The oils covered by this standard are of low viscosity type and completely free fromadditives. The oil should contain minimum amount of impurities including moisture,sludge and should have some specified physical and chemical properties as detailedinthe specification.

    SERVICE CONDITION :

    The transformer oil will be used in WBSEDCL'S Power/ Distribution Transformer andCircuit Breakers installed in outdoor sub-stations of various types subjected to allsortsof seasonal weather variations considering tropical and humid climate of WestBengaland rain, thunder-storms alongwith impact of dust particles on the transformers.

    Thetransformer oil should maintain the desired characteristics despite operation undersevere service conditions with all types of above transformers manufactured inIndiaincluding those fitted with on-load tap changing equipment. The temperature of the

    oilmay rise upto 95oC under extreme conditions. The manufacturer may cement onthevarnish preferred in insulation of coils etc. due to probable effect on the oil includingthe design feature for accessibility of air, if required.

    COMPOSITION :

    The oil shall be pure hydrocarbon mineral oil, without any additive, clean andsufficiently free from moisture and other foreign materials likely to impair its

  • 8/6/2019 PIC Tutorials

    86/93

    properties. Mineral insulating oil are made from selected fraction of crude oil. Thecrude oil composed of mainly hydrocarbon, which may differ in their content of themain classes or types of hydrocarbons alongwith non- hydrocarbons as impuritieslikeparaffins, napthenes and aromatics. The transformer oil should be free fromaromatichydrocarbons as they are unsaturated and hence less stable. By proper refining, thecrude oil consisting of above constituents, the desired characteristics are obtained.

    CHARACTERISTICS :

    The characteristics of the oil when it is sampled at the manufacturer`s works and /orat the point of delivery and tested in accordance with ISS: 335 1993 shouldcomplywith the results given in the IS specification (ISS : 335- 1993 alongwith its latestamendment will be applicable) except for certain characteristics for which the value

    applicable will be as shown in the specification sheet.

    SAMPLING AND TESTING :

    Sampling of the oil shall be done in accordance with IS:6855 1973 and the testsshallbe carried out in accordance with the test methods referred to IS:335-1993 withlatestamendments and modified limit of moisture content only, in the manufacturer's

  • 8/6/2019 PIC Tutorials

    87/93

    laboratory arranged by them.The list of instruments available in the manufacturers laboratory for rigoroustesting,should be furnished alongwith the quotation. Any test, which cannot be carried outintheir laboratory, should be clearly stated in the offer. Those who have no majortestingfacilities in their laboratories need not quote.

  • 8/6/2019 PIC Tutorials

    88/93

    For determination of rate of sludge formation by accelerated ageing test at whichsludge is formed at 115oC in the presence of the copper catalyst at controlled rates ofairflow, WBSEDCL shall prefer the test to run for 96 hours.

    The manufacturer may submit their own method of test referring to any national /international standard in the guaranteed technical particulars.

    All the tests will be conducted by the vender at their works as per ISS/WBSEDCL'STechnical Specification except for the following tests :

    i) Corrosive Sulferii) Accelerated ageingiii) Oxidation stability

    The above tests have to be done from any unit of CPRI and all the cost to be borne bythe vendor. For the tests the sample have to be collected in presence of therepresentative of WBSEDCL.

    According to General Conditions of Contract, WBSEDCL reserves the right to carry outinhouse testing of the supplied materials at destination stores, in presence ofauthorized representative of the Manufacturer. In case they do not be present,company shall Test unilaterally and their result will be binding on them. In case thetest results deviates from the inspection result carried out at Manufacturers Works(more than 2% tolerance as per IS where ever applicable), the Company reserves the

    right to cancel the specific lot and in that event materials are to be replaced by theManufacturer free of cost including the transportation from the site to their works andback.In case of EHV Grade Transformer Oil only, if the test results of the inhouse testingdeviates from the inspection results (only except for Breakdown Voltage and WaterContent) carried out at Manufacturers Works (more than 10% tolerance), theCompany reserves the right to cancel the specific lot and in that event materials are tobe replaced by the Manufacturer free of cost including the transportation from the siteto their works and back. If the test results of the inhouse testing for Electric Strength(Breakdown Voltage) of the new unfiltered oil become less than 45 KV or those forWater Content become more than 25 ppm., the Company reserves the right to cancelthe specific lot and in that event materials are to be replaced by the Manufacturer freeof cost including the transportation from the site to their works and back.

    CALIBRATION :

    According to General Conditions of Contract, the instruments/equipment required forInspection & Testing should have valid calibration as per following guideline :

    (a) Calibration Certificate issued by Laboratory accredited by NABL may beaccepted unconditionally provided the certificate bears an Accreditation bodyLogo.

    (b) For Testing equipments, where NABL Accreditation is not available, CalibrationCertificate from Educational Institutions like IITs, NITs, J.U., C.U., BHU onlycan be accepted provided they can demonstrate traceability.

    Necessary confirmation regarding above is to be given along with inspection offerfailing which the inspection offer will not be accepted.If during inspection & testing, the suppliers fail to produce Calibration Certificate asindicated above the offered lot may be rejected only except the following three tests.

    In case of following three tests only, Calibration of the instruments shall be shown bythe suppliers during inspection & testing according to the calibration method as statedbelow :

  • 8/6/2019 PIC Tutorials

    89/93

    Sl. No. Instrument Calibration Method

    1 Interfacial

    Tensiometer

    With weights as per instruction manual of the Interfacial

    Tensiometer according to test method of IS 6104.

    2 Viscometer With standard liquids supplied by :

    i) M/s. Merk Limited,

    ...56, New Timber Yard Layout,

    ...Bangalore 26.

    ii) M/s. Alliance Technologies,rd

    aaNo. 78, 3 Cross, Sunder nagar,

    aaGokul, Bangalore 54.

    3 Moisturemeter

    QUANTITY :

    The quantitY may vary upto maximum 25% subsequently in case of necessity.

    PACKING :

    The tenderer should indicate in their offer whether they could supply transformer oil inI.S.I. Marked barrels. If they are not in a position to supply transformer oil in ISImarked barrels, their offer may not be considered. The transformer oil should bedelivered in sealed non-returnable epoxy coated new steel barrels each containing209/210 litres of oil. The barrels should conform to Type A or B of ISS: 1783 1974.

    TEST REPORTS AND TYPE TESTS :

    The bidder shall submit complete test reports of all tests (including Type Test) asstipulated in relevant IS with complete identification and date, carried out in CentralPower Research Institute on the tendered item.Copies of Type Test Report as per latest IS, carried out within five (5) years from duedate of Tender, from Central Power Research Institute shall be submitted alongwith the

    offer as pre-requisites. Otherwise the offer may be rejected.

    CONSUMERS :

    List of reputed concerns to whom the transformer oils have been previously suppliedalongwith order nos. and quantities should be clearly mentioned in the offer.

    SOURCE OF SUPPLY :

    Name & address of the supplier of base product is to be mentioned in the offer.

    REFINERYCENTRE:

    Name and address of refinery where the base product is processed are also to bementioned in the offer.

    MARKING:

    Each drum shall be legibly and indelibly marked with the following :(a) Manufacturers name, (b) Name of the material, (c) Quantity in litres,(d)The words Low Viscosity Type , (e) Date and lot of manufacture,(f) ISI Certification mark as IS-335-1993, (g) Name of Consignee as WBSEDCL.

  • 8/6/2019 PIC Tutorials

    90/93

    0

    DECLARATION:

    The enclosed declaration sheet (Annexure III) shall have to be filled up and signed.

    PRICEVARIATIONFORMULA:

    For calculation of Price variation , the tenderer should furnish documents indicatingnecessary dates viz. Price of TOBS/ TOPS, Price of oil barrels, base date effective forthe quoted prices etc.

    DOCUMENTSTO BE SUBMITTED AT THE TIME OF PHYSICAL DELIVERY ATCONSIGNEE STORES :

    The following documents to be submitted by the venders to the consignee Stores at thetime of despatch to stores by the venders:-

    SL.

    a)b)c)

    d)e)f)

    g)h)i)

    Copy of purchase Order.Copy of Despatch InstructionInspection Test Certificate

    Guarantee CertificateProforma InvoiceCalculation Sheet for price Variation on the basis of IEEMA or CACMAI asapplicable with base date of order.Seal list and packing listChallan in triplicateWay bill, if applicable.

    REQUIRED SPECIFICATION OF NEW INSULATING OIL

    VALUES PROPOSED AS PER

    NO.

    1)

    2)

    3)

    4)

    5)

    6)

    7)

    CHARACTERISTICS

    Appearance

    Density at 29.5oC (Max) gm/cc

    Viscosity, Kinematic at 27oC (Max)

    Interfacial Tension at 27oC(Min)Newton / M

    Flash point, Pensky Marten(closed) in oC (min).

    Pour point in oC (Max)

    Neutralisation value

    a) Total acidity, mg KOH /gm

    (Max)

    TENDER SPECIFICATION

    Clear and transparentfree from suspendedmatter or sediments.

    0.89

    27

    0.04

    140

    - 06

    0.03

  • 8/6/2019 PIC Tutorials

    91/93

    b) Inorganic acidity / alkalinity Nil

    8)

    9)

    Corrosive sulphur (Copper strip)19 hours at 140 oC

    Electric strength (BreakdownVoltage )KV (rms).

    Non corrosive.

    a) New unfiltered oil (min).

    b) After filteration (min).

    60

    60

    10)

    11)

    Dielectric dissipation factor(Tan Delta) at 90oC (Max).

    Specific resistance (resistivity)

    0.002

    a)b)

    at 90oC , ohm-cms (Min )at 27oC , ohm-cms (Min)

    35 x 10 121500 x 10 12

    12) Oxidation stability.

    a) Neutralisation value, afterOxidation for 164 hours at 100mg KOH/gm (Max).

    b) Total sludge, after 164hours

    At 100 o C wt. % (max).

    C

    0.10

    0.40

    13) Ageing characteristics after accelerated

    Ageing (open beaker method withcopper Catalyst) for 96 hours at 115 o C

    a) Specific resistance (resistivity)

    i) at 27oC , ohm-cms (Min)

    ii) at 90oC , ohm-cms (Min)

    b) Dielectric dissipation factor(Tan Delta ) at 90oC (Max)

    2 . 5 x 1 0

    0.2 x 10

    0 . 2

    12

    12

    c)

    d)

    Total acidity, mg KOH/gm (max)

    Total sludge value, Wt. % (max)

    0.05

    0.05

    14)

    15)

    16)

    Presence of oxidation inhibitor

    Water content, ppm (max)

    SK value, % (max)

    The oil shall not containanti oxidant additives.

    20

    -

    The values are tentative and there is scope for further improvement in the stability

    characteristics of the oil, which may increase the service life of the oil.

    Tenderer shall furnish their guaranteed values along with method of tests for the above

  • 8/6/2019 PIC Tutorials

    92/93

    characteristics of Transformer oil, along with their offer.

  • 8/6/2019 PIC Tutorials

    93/93

    The tenderer shall also furnish :

    a) Proportion of classes of hydrocarbons in the crude oilincluding content of aromatic

    hydrocarbons.

    b) Details of barrel (Size, gauge inside/outsidecoating/weight of empty drum not less

    than 18 Kg.).

    c) List of equipments for testing of oil as per revised ISS

    d) Electric strength(breakdown voltage ) KV (Min)

    i) Value of the fresh sample in the supplied sealed drums KV(Min).

    ii) Value after filling in transformer upto & within 3 months (Min).