SoP 001 Fatal & Non Fatal Accident Report Yearly Report
SoP 002 Action taken report for safety measures complied for the accidents occurred Yearly Report
SoP 003 Register for compiling the complaints classificationwise Yearly Report
SoP 004 Actons or steps carried out by distribution licensee towards public awareness in the year Yearly Report
SoP 005 Action taken report by the Redressal Committee Yearly Report
SoP 006 Failure of Distribution Transformer. Yearly Report
SoP 007 Failure of Power Transformer. Not Pertaining to DISCOMs
SoP 008 Sample Test result for Neutral Voltage Yearly Report
SoP 009 Sample result for Voltage Variations Yearly Report
SoP 010 Sample Test result for Harmonics Yearly Report
SoP 011 A System Average Interruption Frequency Index (SAIFI) Yearly Report
SoP 011 B System Average Interruption Duration Index (SAIDI) Yearly Report
SoP 011 C Momentary Average Interruption Frequency Index (MAIFI) Yearly Report
SoP 012 System Losses at EHT / 11 KV and below Yearly Report
SoP 013 Meter Faults Yearly Report
SoP 014 Statement Showing the AT&C losses, Collection Efficiency and Billing Efficiency Reports Yearly Report
SoP 015 Release of New Connections Yearly Report
SoP 016 Compensation Details Yearly Report
INDEX
FH NFH FH FA NFH FH FA NFH
1 Sabarmati1 1 1 2 3 14 23 15
2 Mehsana0 2 4 1 3 20 13 11
3 Palanpur0 1 1 1 0 10 10 5
4 Himatnagar0 0 1 2 0 19 24 12
TOTAL 1 4 7 6 6 63 70 43
Uttar Gujarat Vij Company Ltd ,Mehsana
Performa - SOP 001 : Fatal and Non-fatal Accident report for the year 2012-13
NUMBER OF ACCIDENTS FOR THE YEAR (APRIL-12 TO MARCH-13)
Sr. No. Name of area
No.of accidents in the quarterCumulative since the first
quarter of the current FY
yearDepartmental Outsider
C:\Users\ubchauhan5032\Desktop\YEARLY SOP Report 2012-13.xls
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
1 HMT Chorivad
1) Panchal
Pravinkumar
Keshavlal & 2)
Zala Ratansinh
Kansinh
NFH Dept 17.04.12 Chorivad Bhiloda
Maintenence Of 11 kv Akshar jgy feeder was arranged. Necessary line clear was
taken. Loc between 34&35 one 11 kv Goral feeder was crossing. Clearance
between these two feeders was about half feet, whily carrying out tree cutting tree
branch fallen on Akshar JGY feeder due to that conductor jumped and touch with
Goral AG feeder. Hence, return power came momentarily on Akshar JGY feeder.
Due to this two helpers working on SS gentry,got shocked.Goral fdr LC was not
taken by supervisor
CEI Report not received
field offices are
instructed to such type
of location is rectified by
providing Guarding &
proper clearance
maintenance
No
2 HMT Isari
Asari
Bhurabhai
Nathabhai,
Helper
NFH Dept 10.5.12 Meghraj Modasa
To attend the complain of No Power & to repair the Jumper,the Victim climed on
live line of 11 KV Sarkilimdi Jgy feeder whereas he got managed the LC permit on
11 KV Galpur Jgy feeder being under impression of 11 KV Galpur feeder. He
touched the live line and non fatal accident occured.
CEI Report not received
Line staff were educated to
conform the line must be
made off before starting of
work. Also proper earthing
must be done on both the side
of the section in which work
has to be done
No
3 HMT Punasan
Pravinbhai K
Kharadi
Vill.Helper
Baman
NFH Dept 6.9.12 Gambhoi Hmt
While attending the PF of vavdi JGY fdr Shri P K Kharadi,Victim by blunder tried to
isolate AB switch of 11kv Himatpur Agr feeder by hand without using operating rod
instead of 11kv Vavdi JGY with illusion that the said vavdi feeder is isolated from
initial position and there was 3 ph power supply on himatpur agr feeder so his
hand comes into induction zone and fall down to earth & got injuries
CEI Report not received
Inform to linestaff to avoid this
type of miskate in future &
use safety equipments while
working on line & line on
which work has to carried out
and also nearby line must be
made dead by earthing on
both the side
No
4 HMT Waghpur
H M
Prajapati,Line
Helper
FH Dept 9.9.12 Prantij Hmt
For attending the complain of broken LT cond.of Surykund TC loc.at vill.waghpur,
on stringing the top side conductor,the said conductor in the earlier span comes up
due to tension through stringing and touches with live conductor of 11kv line of
Galteshwar agr fdr.which is crossing in the said span and the victim got electric
shock due to this touching of LT line to the live 11kv line conductor and fall down
and got injuries.Then after during the further treatment at Appolo hospital the
victim got died on dated;30.9.12
CEI Report not received Particular HT<
crossing is removedNo
5 HMT Savgadh
Sureshbhai
Dungarbhai
Varsat
FH O/S 4.04.12 M'pura Hmt
On construction side of Tanishk Bunglows at vill Savagsh after Temp. conn.,Temp
LT line on iron pipe with cable is laid in the party premises & Light & other switch is
fixed on said iron pipes,the victim while going to drinking the water from water tap
adjacent to the iron pipe,came into the contact to the said pipe & got electric
shock through the pipe due to any reason and immediately hospitalised & during
treatment the victim get dead thereafter
CEI Report not received
Consumers was awared
for the installation of
ELCB in his premisesNo
6 HMT Bhiloda
Sharma
Nishanbhai
Shantilal
NFH O/S 12.04.12 Bhiloda-1 BhilodaOn dated 12.04.12 at time 18:30 o'clock victim was climed up on neem tree to take
neem flowers suddenly the tree branch was broken and victim fallen down with the
tree branch on 11kv Bhiloda Urban feeder and got shocked.
victim climbed on neem
tree branch which is
touched with live 11 kv
line & got electrocuted.
periodically Tree cutting
should be done by field
office.
Yes,it is
complied
Maintenance & tree
cutting carried outNo
7 HMT Hmt
Mehta
Manishaben
Hemantkumar
FH O/S 30.04.12 Hmt(T) Hmt
The out going cable feeding the supply from starter to motor was damaged &
insulation is opened ,the same is in contact with metal box holding the starter,so
while starting the same submersible motor at home ,on operating the starter by
vicitim the leakage current flows into the box through damaged insulation part of
cable & box became electrcally charged and the vicitm came into this charged box
& got electric shock
leackage current passes
due to opening of
insulation of submersible
cable due to rushing of
cable at galvenise box
consumer shold take
care to keep the
electric appliances in
healthy contdition for
safety
Yes,it is
complied
safety awareness
programme arrangedNo
8 HMT Lusadiya
1).Suvera
Eliyabhai
Chimanbhai &
2). Suvera
Hermeshbhai
Timotibhai
NFH O/S 18.5.12 Bhiloda-2 Bhiloda
1).Two conductor of JGY LT line & 11 KV lusadiya AG fdr line touch & fixed with
eachother , so that short circuit the LT network & meter & service & wiring at
consumer end. During that incident both victim was gone to switched off the main
switch of own house wiring at that time both victim are came in contact in electric
shock& met with NFH accident.While detail verification of site observed that from
anautohirised source that an out sider while removing anauthorsied lungariya from
ground, Due to force that LT conductor of JGY feeder was jumped & touched with
11 KV AG Lusadiya Feeder
Two conductor of JGY
LT line & 11 KV lusadiya
AG fdr line touch & fixed
with eachother , so that
short circuit the LT
network & meter &
service & wiring at
consumer end. During
that incident both victim
was gone to switched off
the main switch of own
house wiring at that time
both victim are came in
contact in electric shock
Guarding is required
between LT line & HT
line
Yes,it is
complied
field offices are
instructed to such type
of location is rectified by
providing Guarding &
proper clearance
maintenance
No
9 HMT Jitpur
Jayeshbhai
Sureshbhai
Valand
FH O/S 24.5.12 Choila TalodVictim try to start the table fan in his home and he used open ended wires without
pin plug to switch Board. During switched on the Table Fan victim came in contact
with open ends of wire and got electocuted & resulted into fatal accident.
CEI Report not received
Consumers was awared
for the installation of
ELCB in his premisesNo
10 HMT Kashipura
GITABEN
GIRISHBHAI
PATEL
FH O/S 10.06.12 Bayad Talod
The victim was came in the direct contact of the live part on the three pin plug pin
male contact while going to fix plug in female contact for starting the single phase
motor by temporary cable at his residence.The victim got electric shock and
died.The accident has occured in private premises of the resedential
connection.The police department has informed very late regarding accident prior
to that no intimation was given by anyone to sdn office.
CEI Report not received
Consumers was awared
for the installation of
ELCB in his premisesNo
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
11 HMT Butal
Dipak
Jayantibhai
Vaghari at
17.00
FH O/S 13.6.12 Dhansura Talod
Looking the site of accident it is found that a service wire is passing from LT line
to victim premise at meter. From meter to approximately 4 to 5 ft away service
phase wire is opened by removing insulation for the purpose of theft also found
spark spot on the phase wire. The height of accident location is approximately 5ft
above from the ground level. As per discussed with the relatives of victim he tried
to protect his house from the rain so he provide TADPATREE at the roof of house
and at that time he may came in contact at with open phase wire of service and
got electrical shocked & fatal accident occured.
victim he tried to protect
his house from the rain
so he provide
TADPATREE at the roof
of house and at that time
he may came in contact
at with open phase wire
of service ,removing
insulation for the purpose
of theft
According to the rule
no. 30 of the
Electricity act 1956,
all the field officers
are instructed to take
care of all the electric
parts which are
under the consumer
premises.
Yessafety awareness
programme arranged for
consumer No
12 HMT Gopalpura
VIJAYBHAI
BABUBHAI
KHANT
FH O/S 20.06.12 Bayad Talod
At village gopalpura real stone industry con no: 23657/00002/0 khant vijaybhai
babubhai was making welding to new structure of quarry works and directly
contact with live welding wire and got electric shock and met with fatal accident
and died.The accident has occured in private premises of the industrial
connection.
khant vijaybhai babubhai
was making welding to
new structure of quarry
works and directly
contact with live welding
wire and got electric
shock
According to the rule
no. 30 of the
Electricity act 1956,
all the field officers
are instructed to take
care of all the electric
parts which are
under the consumer
premises.
Yessafety awareness
programme arrangedNo
13 HMT Helodar
Patel
Nischalkumar
Sureshbhai
FH O/S 4.7.12 Malpur Modasa
The said accident place is a cattle shad with roof is made of iron roof sheet, other
iron rod and iron grill is fixed on the place of accident. The cattle shed is siyuated
back of the resident. It is 35 mtr far away. A private yellow alluminium two core pvc
cable is laid down from resident to cattke shed over head for ltg. purpose the
phage wire's inulation is damage where it touch with cattle shed iron roof sheet.
Leakage current flow from open alluminium wire to iron roof sheet, iron rod & iron
grill. A victim touch with this iron grill & got electrical accident & fallen into the
cement open water filled tank & died on the spot.
CEI Report not received
Consumers was awared
for the installation of
ELCB in his premisesNo
14 HMT Karoli
Sohilbhai
Isubbhai
Ganchi(Chad
di)
FH O/S 8.07.12 Dhansura Talod
The Driver parked his truck under HT Line, meantime victim climbed on cabin of
the truck and stood on cabin to see whether greet in truck was filled properly, at
that time he came in contact with HT line passing over the cabin and got
electroculated and died. The hight of both PSC poles from top of the Pole to the
ground is 20 Ft.and 20.4 ft.respectively. At the accident point ground clearance
reduced due to filling of quarry waste. Sag of line conductor is found satisfactory at
accident location.
CEI Report not received
People was awared to inform the
concern SDO while working
nearer to the electeric line
.Notice issued to Arbuda Quarry
pvt.ltd vide letter no
2821/10.7.12
No
15 HMT Kankrol
Parmar
Rangusinh
Udesinh
NFH O/S 18.7.12 Hmt® Hmt
The victim was working as labour on the under construction building of shri Patel
Dharmeshbhai Gordhanbhai at loc.19,Shyam sunder soc.,Kankrol Hmt.While
dropping the iron road from 2nd floor to ground ,he came into the contact with live
cond. of 11kv line of Nikunj Urban fdr passing nearby through touching of of the
said iron road to the live cond uctor and got electric shocked and same time he fell
down from the 2nd floor to the ground and got injured.
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
16 HMT KathvadaUnknown
personFH O/S 11.8.12 Talod-2 Talod
The site of fatal accident of human unknown person at village Kathvada Ta.Talod
was visited on Dt.11/8/12. on inspection of Ag.Conne.of Shri Ambalal Danabhai
Patel having of Load of 10HP. The consu.having conne.from tapping pole of X'mer
to his own private box. the box having three fuses where three phases came.
among three phases the consumer has used red and blank flexible wires. the rewd
wire is taken from incoming of blue phase. and black is neutral wire. which goes
to the holder of a lamp. the lamp is provided on wooden sticks. due to rainy season
the wooden stick fallen on the ten wire fencing of the farm. the red phase touches
the top most wire of fencing and current is distributed through whole fencing area.
the UNKNOWN PERSON came near the fencing area which is around one sixty
meters from the existing conne. of the consumer. the UNKNOWN PERSON
touches the fencing wire and met with fatal accident on spot.
current is distributed
through whole fencing
area due to unauthorised
work by AG consumer.
the UNKNOWN
PERSON came near the
fencing area,met with
fatal accident
According to the rule
no. 30 of the
Electricity act 1956,
all the field officers
are instructed to take
care of all the electric
parts which are
under the consumer
premises.
Yessafety awareness
programme arrangedNo
17 HMTNava
Bakarpu,Prantij
1.Ranjitsinh
Halusinh Zala
2.Mukesh
Balusinh
Pramar
NFH O/S 4.9.12 Prantij Hmt
HT Pole of balisan Agr feeder was broken & during rectification work of said line
,While stringing of the conductor of Balisana agr fdr by the victims the top
conductor on stringing came into contact with live conductor of Raslod agr. Feeder
which is crossed to said Balisana agr. after the three span from this location.
CEI Report not received
field offices are
instructed to such type
of location is rectified by
providing Guarding &
proper clearance
maintenance
No
18 HMT Juna untarda
Parmar
Subhashsinh
Bhavansinh
FH O/S 05.09.12 Talod-2 Talod
The house bathroom construction was going on under the 11 KV Ag Limb feeder
without any kind of information to sdn office.During that time victim went to the
said site to watch the work & came in contact with live wire & met with fatal
accident.
The house bathroom
construction was going
on under the 11 KV Ag
Limb feeder without any
kind of information to sdn
office.During that time
victim went to the said
site to watch the work &
came in contact with live
wire
Avoid any type of
work nearer or below
the electric line and
maintain the safe
distance between the
electric line and any
type of construction.
Yes
The accident has
occurred due to the
victim's own mistake
No
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
19 HMT Aambagam
Smt. Khant
Savitaben
Vitthalbhai
NFH O/S 15.9.12 Bayad Talod
Victim has extended insulated wire from his house to outsider room from above
iron roof.Because of iron roof the insulated wire insulation was broken & the iron
roof became live conductor.The same iron roof was connected with GI wire for
cloth dry.Mean time while removing the dust by victim with the help of tagara
putted on his head.The tagara was contaced with this GI wire.So the leakage
current flows from iron roof to GI wire & NFH accident occured.
CEI Report not received Victim himself responsible No
20 HMT Rajpur
Tarar
radhabhai
jemabhai
FA(Buffalo) 31.5.12 Dhansura TalodDue to heavy wind tree branches fallen on LT line. Then LT line got shorted & one
wire broken & fallen on the buffalo & met with fatal accident
Accident occurred due to
snapping of the LT line
conductor due to fallen
of the tree on the live LT
line
periodically Tree cutting
should be done by field
office.
Yes,it is
complied
Maintenance & tree
cutting carried out
5000
21 HMT Modasa
Bharvad
Jayeshbhai
Manekbhai
FA (Cow) 11.6.12 Modasa-T ModasaIn 11 KV Modasa Urban Feeder, the bird nest is on LT line Girder Pole. Due to rain
the nest became wet and the leakage current flows through the Pole. Meanwhile
the Cow came in contact with this pole & got electric shocked & died.
CEI Report not received 2000
22 HMT Moyad
Rathod
Kiritsinh
Natwarsinh
FA(Buffalo) 14.6.12 Salal HMT
At vill:Moyad(Nathaji) on loc. Of Sump vali T/C the said buffalo was passing
through the Double pole structure & touched to MMB of DTC meter .In the said
DTC Meter incoming cable was fired due to some reason & PT cable of R-phase
was opened & touched to MMB so the current is leakged through PT cable to MMB
of DTC meter. Mean time the said buffalo e passing under the structure of TC &
came into contact to the said electrically charged MMB & got electric shocked.
Due to leakage current
passes from MMB box to
earthing wire to victim.
Maintenance of LT line
& Fencing is required
surrounding at
transformer center
Yes,it is
complied
Such type of location is
rectified by providing
fencingNo
23 HMT SonisarZala hathisinh
KansinhFA(Buffalo) 31.8.12 Talod-2 Talod
Due to Cyclone HT pole of Sonisar fdr is broken & conductor snapped on the
ground. Mean while buffalo passing near that conductor & came in contact with
live wire, got shocked & died.
CEI Report not receivedMaintenance carried
out5000
24 HMT Alana
Desai
Shaharbhai
Mashabhai
FA( Baby
Buffalo)10.9.2012 Choila Talod
Due to water works body short leakage current coming to transformer center.Mean
time Babybuffalow was passing & came in contact with trnsformer neutral wire &
died on the spot.
CEI Report not received No
25 HMT JAYALA
Kharadi
Natvarbhai
Vechatbhai
(owner)
FA(Buffalo) 9.7.12 Bhiloda-1 Bhiloda
Due to very heavy wind pressure, an LT line of 11KV Virpur JGY feeder was
touched to telephone line. A stay is at the 1st pole of this telephone line. And due
to leakge path goes through telephone line to stay, a buffalo(female) was came in
contact with this stay wire and got electrocuted.
leakage current passes
due to gethering LT wire
& telephone wire through
iron telephone pole &
stay wire.
Guarding is required
between Telephone
line & company's LT
line
Yes,it is
complied
Such type of location is
rectified by providing
Guarding5000
26 HMT
JUNA
AAKODIYA
(DEMAI)
Zala Gitaben
JeshingbhaiFA(Buffalo) 13.7.12 Bayad Talod
On dtd. 13/7/2012, A buffalo of Zala Gitaben Jeshingbhai at:village : Juna
Aakodiya (Demai) Ta: Bayad came at near village transformer center & broken G.I.
wire of transformer neutral earthing by horn, hence leakage current of neutral
earthing passing througn the body & accident occurred as fatal.
Leakage current passes
in neutral wire due to
unbalancing load.
Fencing is required
surrounding at
transformer center
Yes,it is
complied
Such type of location is
rectified by providing
fencingNo
27 HMTNanasamera
Tarar
Nanjibhai
Becharbhai
TARAR
NANAJIBHAI
BECHARBHA
I
FA(Buffalo) 16.7.12 Bhiloda-2 BHILODADue to cyclone the LT conductor slipout from LT shackle insulator & leakage
current flow from D-clamp to earth wire & buffalo came in contact with earth wire
got shocked & died.
CEI Report not receivedMaintenance carried
outNo
28 HMT Khalikpur
Patel
Rakeshbhai
Rameshbhai
FA(Buffalo) 7.08.12 Modasa-T ModasaIN 3P4W LT line Due to rain the momentary leakage current might have passed
through earth wire.Mean while the buffalo came in contact with this earth wire &
got electric shocked & died.
CEI Report not receivedMaintenance carried
outNo
29 HMT Kolavada
Patel
Manguben
Nathabhai
FA(Buffalo) 11.08.12 Modasa-T Modasa
In Transformer center Due to rain & The street light phase touch to the neutral
and the momentary leakage current flows through neutral to earthing wire.Mean
while the buffalo came in contact with this earth wire & got electric shocked &
died.
CEI Report not receivedMaintenance carried
outNo
30 HMTHafsabad
Chhapra
Makwana
Kiritbhai
Ramanbhai
FA(Buffalo) 15.08.12 Modasa-T Modasa Due to rain the momentary leakage current might have passed through earth wire
at Transformer center.Mean while the buffalo came in contact with this earth wire
& got electric shocked & died.
CEI Report not receivedMaintenance carried
out5000
31 HMT Desaipura
Solanki
Sursinh
Nansinh
FA(Buffalo) 4.9.12 Sathamba TalodDue to heavy wind & rain L.V four line wire (440 V) were break down , mean time
Buffalo was passing near that line & came in contact with live wire & met with fatal
accident.
CEI Report not receivedMaintenance carried
outNo
32 HMTNavalpur(Ranas
an)
Smt.Bhuriben
Bhavansinh
Makawana
FA(Buffalo) 15.9.12 Gambhoi Hmt
As reported, due some reason the piece of centing wire fallen between B-phase
& neutral on lt side so leakage current flows through the earthing wire of x'mer
centre.Mean time the victimise buffalo passing nearby the TC & came into
contact with this earthing wire through its horn and got electric shocked and died.
CEI Report not receivedMaintenance carried
outNo
33 HMT Punsari
Barot
Mohanbhai
Trikambhai
FA(Buffalo) 8.8.12 Talod-2 Talod
The site for fatal accident to Buffalo of Shri Barot Mohanbhai Trikambhai At
,Village : Punsari ,Ta:- Talod was visited on Dt.:-08.08.12 . On Inspection of
L.T. Line the Incoming Service Wire Which is Connected to Streetlight
Fixtures Which is Opened and Touched to the Sideclamp (fixture Clamp)
and leakage Current Passed Through Pole – There was light rain on date:-
08.08.12 – Night hours and pole surface land was wet in condition- Due to
momentarily touching of Open incoming Service wire to Fixtures Clamp at
that time Buffalo Nearby pole might have got electrocuted and fatal
accident occurred.
leackage current passes
from service wire to
street lighrt fixtures
through iron road of
deterioted psc pole at
bottom side.
periodically
maintenance is
required for service
wire & street light
fixture.
Yes,it is
rectified
Maintenance carried
out10000
34 HMT Meghraj
Bharvad
Mayurbhai
Rajubhai
FA(Buffalo) 15.09.12 Meghraj ModasaConnection of Sh. Devabhai Karmabhai's house was fell down during rainy season
with meter,mmb & wall . After that due to broken service wire and buffalo was
touched with the service wire, hence fatal animal accident occur.
CEI Report not received
Service wire was
replaced by new
service wire
No
35 HMTLalji na
Pahadiya
Khant
Pratapbhai
Bhemabhai
FA(Buffalo) 07.09.12 Malpur Modasa
Due to short ckt in electrical instrument(fan) in the house of sh. Patel Haribhai
Moghabhai,leakage current flows to the LT line and Transformer centre earthing
and meantime buffalo was touched with the earth wire, hence fatal animal
accident occur.
CEI Report not received
Consumers was awared
for the installation of
ELCB in his premises5000
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
36 HMTVantada(Kabola
)
Chauhan
Sabaji MalajiFA(Bullock) 6.7.12 Modasa-R Modasa
Due to heavy cyclone & rain , one LT conductor of 11 KV Gadha AG feeder has
been snapped & the Bullock was came in contact with this live conductor and got
shocked and died.
accident occurred due to
touch with the broken LT
line live wire
periodically
maintenance is
required
Yes,it is
rectified
Maintenance carried
outNo
37 HMT AnjanaPatel Abalal
ShababhaiFA(Bullock) 12.7.12 Talod-1 Talod
Bullock is died due to electrical or not it is not justified. So after getting pm report
actual reason wii be justified.CEI Report not received No
38 HMT Dhansura
Rabari
Nikulbhai
Sankabhai
FA(Cow
,Goat)04.07.12 Dhansura Talod
At the time of rain falling leakage current passed from deterioted service wire to
girder pole and that time cows was sitted near the girder pole and the fatal
accident occurred
CEI Report not receivedMaintenance carried
outNo
39 HMT Hmt
Rabari
Karamshibhai
Nagjibhai
FA(Cow) 7.9.12 Hmt(T) Hmt
At " khada vistar" of mehtapura area, the compound wall of nagarpalica garden fall
on a supoort pole of LT line & the LT pole broken and 1ph 3w lT line also broken &
Live conductor of said LT line fall down and lies on the ground, same time the
victimised cow came into contact with this live broken conductor and got electric
shock and died
CEI Report not receivedMaintenance carried
out2000
40 HMT Gambhirpura
Rabari
Somabhai
Lilabhai
FA(Cow) 11.9.12 Idar-T IdarDue to heavy rain and wind Lt pole B-phase jumper touched to D-clamp so,
leakage current passsing through pole to earth wire. Meantime cow came in
contact of leakege path current and animal(cow) fatal accident occurred.
CEI Report not receivedMaintenance carried
outNo
41 MSH Kharna
Arvindbhai
kavabhai
Asari, ALM
NFH Dept 19.06.12 Gozariya Vijapur
A single phase two wire LT line was there on 10 mtr PSC Pole just near the
Kharna-Amarpura bus stand over the road crossing of Gozariya-Gandhinagar
Highway. Also 11 KV Boru Ag Dom feeder emanating from 66 KV boru s/s was
crossing the single phase two wire LT line. On dated 19/6/12, a programme was
given to remove the 8 mtr nacked psc pole just near the 10 mtr psc pole at Kharna-
Amarpura bus stand. On the said 10 mtr psc pole two service wire was connected.
To remove the nacked pole, the service wire was removed. After removing nacked
pole victim shri A K Asari climbed on 10 mtr psc pole to reconeect the service wire.
The ground staff had binded the single phase service with 2 core service wire and
gave to Shri A.K.Asari . He had hold the service and tried to bind with 10 meter
PSC pole. During Binding work jerk took place and GI wire of single phase service
touched to conductor of 11 KV Boru AG feeder and victim felt down and met with
non-fatal electrical accident.
Due to the some jerk
recieved by A K Asari,
a GI wire binded with
the service wire was
touched to the 11 KV
Boru feeder and victim
got electric shock and
fallen on the groung.
Take the Line clear of
the nearby electric
line before the
starting of the work
and use safety
equipments while
working on the line.
Yes
Inform to linestaff to
avoid this
type of miskate in
future & use safety
equipments while
working on line & line
on which work has to
carried out and also
nearby line must be
made dead by
earthing on both the
side
No
42 MSH Charup
Non fatal
Electrical
Accident
occurred to
D.R.Bhagora
Helper
NFH Dept 6.07.12 Jangral Patan
The work for conversion LT line for street light connection under MP/MLA fund at
Village Charup was Alloted to Sub Division gang under supervision of N.S.Patel
Line Inspector They have isolated the LT line before starting the work. Our helper
Shree D.R.Bhagora was on pole for stringing of conductor. while stringing work at
10:45 AM, the new conductor Jumped and came in inductin zone of 11KV Balva
JGY Feeder which is passing over the LT line. our Helper had got Electric shock
and fall down on ground. He injured on his left shoulder and admitted to Janta
Hospital, PATAN for treatment.
CEI Report not received
All the line staff was
informerd to work with
safety equipments onlyNo
43 MSH Soneripura
Harjivandas
Shankarlal
Rathod,
Helper
NFH Dept 11.07.12 Dhinoj Mehsana
According to the details, the accident took place on Dt. 11/7/12 at 11:30 AM
approx. The Victim Shri. H.S.Rathod went to Shri.Patel Jayntibhai Ambaram's
house at Soneripura for attending No Power Complaint. He checked the
connection and found no supply at the out going terminals of the meter. Revealing
the service might be faulty, he climbed on the roof of house. He checked the
service line and found it broken somewhere under the insulation. He detected the
exact place of breakage and cut the cable skillfully, to prepare for the new joint. He
started applying joint and made a first joint at the neutral. While providing Lt tap on
the joint to the phase - which was live at the time,- suddenly and accidentally, he
touched the live part of the phase wire. As he was standing on the iron sheet roof,
he received electrical shock and fell down there only, shouting for the help.
CEI Report is not
received
Victim & other line
staff were instructed
to use safety tools
while working & also
given the guideline
regarding safety
awareness
No
44 MSH Amarpura
1. Ganpat A
Patel(Helper)
2. Dilip D
Sadhu(Helper
NFH Dept 13.07.12 Kadi-2 Kadi
For givining single phase service wire to LT line near t/c center for releasing
lighting connection, service wire was connected to the first pole from the t/c center
& other end was pulled up by the helper who was climbed on the DP structure for
connecting it to the LT stud of the t/c,During this course said naked end of the
service jumped upward and touched the live HT line. And hence HT power passed
through the service cable to LT line side where two victims had climbed on the two
sequenceal poles, one for giving service wire on the first pole and other for binding
LT shackle, who were met electric current.
CEI Report is not received
Inform to linestaff to avoid this
type of miskate in future &
use safety equipments while
working on line & line on
which work has to carried out
and also nearby line must be
made dead by earthing on
both the side
No
45 MSH Madrisana
Jyantibhai
Maganbhai
Asari(V/S
Helper)
NFH Dept 1.09.12 Detroj Kadi
On dated 1/9/2012, a victim shri Jyantibhai Maganbhai Asari Village helper
climbed on Madrisana villlage T/C for repairing of some fault on lt side of
transformer centre at village madrisana. Before climbing on transformer centre
victim removed the 11 KV fuse link of transformer. Then after while repairing of LT
lug of LT Bushing of transfome, Victim's right hand toched to the 11 KV bushing of
transformer. Thus a not fatal electrical accident took place.
CEI Report is not received
Inform to linestaff to avoid this
type of miskate in future &
use safety equipments while
working on line & line on
which work has to carried out
and also nearby line must be
made dead by earthing on
both the side
No
46 MSH Vareda
Smt. Vijuben
Chhanaji
Thakor
FH O/S 14.04.12 Patan-R Patan
The victim Shrimati Vijuben Chenaji aged 37 years(aprox) resi. of Vareda Ta.
Patan she was living at farm of Shree Chemaji Ravaji Thakor Ag. Conn.
No.24410/00077/6. as per eye witness oral statement there is our transformer
center at consumer premises. The water was logged near by transformer. The
victim was passed thought the logged water & got Electrocuted due to leakage
current and died. but Dy.Engr. of Patan(R) S/dn has visited the accident site but no
sign of leakage current is found.
leakage current passes
in the T/C earthing wire
due to short ckt in party's
motor fault
This can be avoided by
providing quality
earthing at T/C center
.The neutral & body
earthing is also
provided separately at
T/C center
Yes,it is
complied
Quality earthing may be
provided at each
Transformer No
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
47 MSH Mansa
Thakor
Kishanbhai
Chunthaji
FH O/S 13.06.12 Mansa Vijapur
A single phase commercial connection having consumer no. 21601/05457/2 in
favour of shri Thakor Rameshbhai Ishvarji has given to Pan Parlour. The wiring of
the tube light from the left hand holder to starter was connected by open joint wire.
On dated 13.06.12 at about 11:50 PM, there was a heavy rain and this open joint
touches to the tube light patti and so it became live. Also the bottom surface of the
pan parlour was become wet due to heavy rain and suddenly victim's head came
in contact with this live patti and so victim got electric shock and died.
An insulation of the
electric wire giving
power to the tube light
inside the victim's
parlour was damaged
and have in naked
condition. This open
part of the wire was
touched to the iron
patti of the tube light
fixture. A victim's head
came in contact with
the iron patti and
hence got electric
shock.
To install the ELCB in
every residential and
commercial
installtion.
Yes
Consumer was
suggested to rectify
the wiring of his shop
No
48 MSH Ajol
Divakar
Rameshbhai
Balrambhai
FH O/S 4.07.12 Lodra Vijapur
At village Ajol, there is “ Pearl villa “ housing scheme developed by private party.
The site is on Ajol-Lodra Road –Right-hand side. The scheme is under
construction. He has made plotting & houses are being constructed. He has
developed common Amenities like internal road, garden, st. light, C. C .TV
Camera etc. The victim was doing the work of painting on Tabular poles which are
erected for C C.TV Camera on the side of main internal road. The victim was doing
this work using sliding ladder. To get proper height he had tied four bamboos on
four legs of ladder and put this structure on the tractor trolley. The victim has
climbed up on trolley and holds the structure. While driver was driving the tractor.
One 11 KV Veda Ag. Feeder passes through these primacies and cross the
internal road. As soon as, the tractor along with trolly passed under our electric
line, the top portion of structure touched the 11 KV line & victim meet with fatal
electrical accident. Here it is to inform that total height of the moving structured
with tractor was measured about 22 ft. Distance between lower condition of 11 KV
line & RCC road is 19 ft 4 inch. The RCC road is newly constructed with refilling of
earth about 1 ft from original ground level.
An alluminium ladder
was arranged on the
tracter trolley for
painting approximately
30 feet height of the
pole. While adjusting
the location of the
ladder by moving the
tractor the upper part
of the ladder touched
to the 11 KV Veda line
and hence victim gor
electric shock.
Avoid any type of
work nearer or below
the electric line and
maintain the safe
distance between the
electric line and any
type of construction.
Yes
The accident has
occurred due to the
victim's own mistake
No
49 MSHChaveli, Sardar
Avas
Shri
Jayantibhai
Ramsibhai
Raval
Aged
about 50
Years
FH O/S
5/7/2012 at
about
19:30 Hrs
Chanasma Patan
On Dated 05/07/2012 a late night telephonic message received from a local
person by Dy Engineer that a human fatal accident is occurred at village Chaveli
Ta:- Chanasma. On dated 06/07/2012 the Deputy Engineer of Chanasma has
visited the site & found that the accident was occured to Shri Jayantibhai
Ramsibhai Raval in the premises of Shri Raval Rameshbhai Vithalbhai. As per the
Raval Rameshbhai Vithalbhai statement the accident occured while fixing the bulb
on holder & died. While site inspection no any leakage of current or any sign of
electrical accident has been noted. The Dy Engr has visited the doctor of PHC
Lanva who has carried out the post mortom The doctor has personnelly told that
he is not be able to say any thing about perfect cause of death hence he has send
some sample to FSL for further investigation for detail report of cause of accident.
At this time we should wait for P.M.Report before concluding the cause of accident
CEI Report not received
Consumers was awared
for the installation of
ELCB in his premisesNo
50 MSH Jepur
Senma
Mangalbhai
dhudabhai
FH O/S 13.07.12 Vijapur Vijapur
Consmer single phase service cable 2.5 mm2 Cable was passing through metal
sheet of roof.At the junction point of cable & metal sheet insulation of service cable
was breaked(Punctured) by birds/khiskoli.The nest was made by birds at this
place. Due to rainy seasson the nest & surrounding area was wet.At the house of
victim the varagani of iron wire was binded one side at metal sheet & other side
with wooden limb.Leakage curruent was passing through breaked cable to
varagani throgh wetnest The victim came in contact with varani & elecrocute.
A single phase
connection was given
to Shri Mangalbhai by
Vijapur S/Dn ,UGVCL,
whose consumer no.
is 21717/00751/1. The
insulation of the 2 core
2.5 mm2 service wire
might be damaged
either by long service
life or by birds. So that
the live service wire
was came in contact
with the iron Patra. An
iron wire was also
binded with this iron
patra for cloth hanging
purpose. So that a
leakage current was
also passing through
this iron wire. While
taking towel from this
According to the rule
no. 30 of the
Electricity act 1956,
all the field officers
are instructed to take
care of all the electric
parts which are
under the consumer
premises.
Yes
Service wire was
replaced by new
service wire
No
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
51 MSH
Silver Ozon flat,
near Avsar
Party Plot
Shri
Shubhashbhai
Ruplal Damor
FH O/S 25.06.12 Mehsana Ind. Mehsana
For construction of new residential flat scheme, a 3-phase temporary connection
was given to Silver Ozon by Mehsana Ind. S/Dn. On dated 25/06/2012 at the site
of Silver Ozon, Shri Shubhashbhai Ruplal Damor was cutting the mild steel bars
with the help of electric cutter. The wire of this electric cutter had the open joint
nearer to the elctric cutter machine and said joint may be opened. Hence the mild
steel bars might be touch to the said open joint and hence victim might have got
electric shock and died. The occurance of the said accident was informed by the
Electric Inspector. As no one from the silver ozon site had informed regarding the
accident, the said accident is reported very late.
On dtd. 25/6/2012,
victim shri
Shubhashbhai Ruplal
Damor was working to
cut the iron saliya with
the help of hitachi
make 2.0 KW single
phase electric cutter
machine. The said
maching was supplied
by two core flexible
cable wire, which have
open live joint. So
while working, victim
might have came in
contact with this open
live joint and got an
electric shock.
According to the rule
no. 30 of the indian
electricity act 1956,
all the field officers
are instructed to
aware all the
consumers to make
their electric goods
with electic safety.
safety
measures
adopted by
the party.
safety measures
adopted by the party.No
52 MSHHinglachahcar
Chowk,Patan
Bhangi
Hareshbhai
Dahyabhai &
Bhangi
Dilipbhai
Saburbhai
NFH O/S 7.08.12 Patan City-1 Patan
Bhangi Hareshbhai Dahyabhai age 30 years & Bhangi Dilipbhai Saburbhai age 40
years both are Safai kamdar. On dated 7/8/12, both these victims were engaged
for removal of Hording nearer to Hinglachachar transformer centre. The said
hording was fitted with bamboo. While removing the hording victims lost his
balance and so the hording get contacted with DO fuse of Hinglachachar
transformer centre and thus non fatal accident occured.
CEI Report not received
People was awared to
inform the concern SDO
while working nearer to
the electeric line
No
53 MSH DetrojKhumaji
Jugaji Thakor FH O/S 23.09.12 Detroj Kadi
AT Village Detroj (Gayatrinagar) shri Khumaji Jugaji Thakor (outsider) was taking
bath at outside of his house in open space. A steel wire was install for cloth
hanging which was passing over open space.When shri Khumaji touch with this
steel wire he feel current & met with fatal electrical accident. Steel wire was fit with
steel pipe.Steel pipe was fit below steel roof.Steel roof was touchig with service
line support wire( Alluminium wire).This support wire other end was fit with psc
pole.It is posibility that from that support wire current was leakage from pole to
steel wire .
CEI Report is not received
Consumer was instructed to
use non conductive wire for
cloth hanging purpose ans
also service wire has been
replaced
No
54 MSH Kadi
Buffalow of
Shri Jyantiji
Babuji Thakor
FA(Buffalo) 15.04.12 Kadi R-2 Kadi
Due to some fault in submersible motor there is a leakage current flowing in
neutral & earthing of TC when the load is running(Motor is ON), but in case of No
Load condition ( Motor is OFF) there is no any leakage current flowing through the
neutral & earthing of TC. Thus during running of motor & load, a buffalo passed
nearby the TC and came in contact with earthing wire of TC and got electrocuted &
died.
CEI Report is not received
Consumer was intructed to
repair the motor and also TC
earthing has been reactivatedNo
55 MSH Dadhana
FA to
Buffalow total
Thee nos
Edels & Two
nos of Child
buffalow Of
Vishnubha
Narshibha
Zala
FA ( 3 NO.
OF Buffalo &
2 NO. OF
Child buffalo)
11/06/2012
, At 6.15
AM
Detroj kadi
on dt: 11/06/2012 morning at 6:15 AM three buffalo & two child buffalow passing
from a farm. Where a conductor of 11kv Vincchan (Ag) feeder was sanp & was fall
on ground. All 5 buffelow concact with live conductor & met with fatal electrical
accident. The owner of buffelow is Vishnubha Narshibha Zala Vill:Dadhana
tal:Mandal
An 11 KV Vinchhan Ag feeder
was passing nearer to the
Gidhabhai Parsottambhai
Patel's farm. On dated
11/6/2012, shri vishnubha
Narsinh Zala was passing from
this area with three nos. Od
edels and two nos. of child
buffalo. The conductor of the
sais feeder was broken
between pole no. 189/36/13
and 189/36/14 and lying on the
ground. While passing from
this area all these five animals
came in contact with this live
11 KV conductor and died.
As per the regulation no. 41
of the electricity act 2010,
proper earthing shuld be
done and also periodic
maintenance of the line
should be done.
YesLT line conductor of that
portion has been replacedNo
56 MSH Gambhu
FA to 2 No.s
of CAMEL of
Rabari
Bharatbhai
Chhaganbhai
FA(2 no.OF
camel)
14.06.12 at
8.amBechraji kadi
At site verification 3 phase 4 wire LT line goes to w/w connection. At the second
number of LT pole LT conductors broken due to heavy cyclone and rain in village.
One phase conductor and neutral conductor were found broken and laying on the
ground. During site verifaction one phase condutor found under the body of two
camel. Due to heavy rain, ground under the LT line was wet and at that time camel
passes through broken conductor so at that time there is a chance of leakage
current on ground so camel may be electroculated.
CEI Report is not receivedMaintenance of the LT line
has been doneNo
57 MSH Jangral
Cow of Shri
Rameshbhai
Kesharbhai
Rabari
FA (cow)
21.06.12 at
about
16:30 Hrs
Jangral Patan
11 Kv morpa Ag feeder give Power Supply to agriculture consumers of village
morpa.vagdod.&vadani.under jangral s/dn . At the time of incidant, conductor of 11
kv morpa feeder is broken due to pin punchar on loc no-6. When conductor fall
down on ground level, at that time 11 KV Morpa feeder is tripped. After snapping
of conductor , cow pass through between loc. no. 5 & 6 of 11 kv morpa feeder &
becomes in contact with brocken conductor. At that time second times try of 11 kv
morpa feeder is taken from 66 kv Jangral S/s. and hence current pass through cow
and fetal accident occured.
CEI Report not receivedMaintenance carried
outNo
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
58 MSH Vijapur
Rabari
Ishwarbhai
Mafabhai
FA(Cow) 16.06.12 Vijapur Vijapur
B phase of L T line was shorted with Channel fitted on LT railpole due to centing
wire placed by bird on the fabrication.Hence leakage current flow through rail to
ground.due to rain ground was wet.the cow came in this area and meet with
elecrocute.
A LT line was passing
nearer to the Chhabila
Hanumanji Temple in
the Bhatwada area.
On the said LT line on
the pole no.
MVR/VJN/15/01/00105
a centring wire was
placed and this
centring wire was in
touch with the cross
arm of the girder pole
and hence electric
current was passing
from the girder pole. A
cow of the owner
came in contact with
the said girder pole
and hence got electric
shock and died.
Field offices were
instructed to carry out
periodic maintenance
of the electric line.
YesMaintenance of the
line has been doneNo
59 MSH
Mehsana Town,
Near Eklavya
Society
Owner of
Buffalo Shri
Mukeshbhai
Harjibhai
Rabari
FA(Buffalo)5/7/2012 at
9:30 AMMehsana City Mehsana
ON DATED 05/07/2011 9:30 AM, AT EKALAVYANAGAR SOCIETY ON LT LINE
POLE WHICH IS NEAR TRANSFORMER CENTER ,DUE TO LEAKAGE
CURRENT FOUND ON EARTHING OF LT LINE POLE AND THE BUFFALO CAME
IN CONTACT WITH THE LEAKAGE CURRENT THE FATAL ACCIDENT
OCCURRED.
CEI Report is not
received
LT line maintenance
has been carried outNo
60 MSH Khakhadi
Two No. of
buffalo of
Thakor Kalaji
Natvarji &
Thakor
Alpeshji Dinaji
FA(Buffalo)15/08/12 at
10:40 HrsHarij Patan
The two nos of buffalo came nearer to W/W transformer centre of village khakhadi
and horn of one of the buffalo got fixed with the stay wire of the said transformer
centre. So the buffalo tried to remove its horn from the stay wire and while doing
so the anchor rod of the stay wire came out so the stay wire became loose and
suddenly it touched to the incoming jumpers of the transformer centre and the
buffalo got electrocuted. The another buffalo near by also came in contact with the
electrocuted buffalo and so it also got electrocuted and so both the buffallo died on
the spot.
CEI Report not receivedN/A as CEI report is not
received
N/A as CEI
report is
not
received
New stay and earthing
providedNo
61 MSH VidajShri Vaghela
Kaluji AnadujiFA(Buffalo) 14.09.12 Kadi R-1 Kadi
At village-Vidaj, under Kadi-1 sub division, on dated-14-09-2012, at between 1:30
to 2:30 P.M., bufffalow of Waghela Kaluji Anduji was dead near water works T/C of
vidaj village. This office has visited the site on 15-9-2012, but at that time no
leakage was found at that transformer center. Also the dead body of bufflow was
not there, so the exact reason for the death of buffalow can be concluded after
P.M. Report.
CEI Report is not receivedEarthing of the W/W TC has
been reactivatedNo
62 MSH
Tulsidham
Society
Common
Plot,Mehsana
No One FA(Cow)
10.07.12 at
appro.
21:15 Hrs
MSH-Ind MehsanaAnimal fatal accident occurred to cow due to leakage current passed through st.
ltg. Fixture, which became short circuited due to rainy water falling from the exit
pipe of nearby house terrace - to earthing wire & got electrocuted.
CEI Report is not
received
Mehsana,
Nagarpalika was
instructed to change
their faulty fixture
No
63 MSH Sonvad
Shri Thakor
Becharji
Gandaji
FA(Cow) 7.09.12 Kadi R-1 Kadi
At village-Sonvad, Taluka-Kadi, on dated :- 07-09-2012, at between 4:00 to 4:30
p.m., buffalo of Thakor Becharji Gandaji was passing from pastured land for
grazing. Conductor of 1-ph. 2 wire L.T. line toward Indirapara Vistar was broken
due to heavy rain and wind. Due to continuous rain Land was wet and some water
was accumulated a there place. Buffalo comes in contact with live wire and it got
electriculated & died on the spot.
CEI Report is not receivedMaintenance of the LT line
has been doneNo
64 MSH Vasai
Shri
Bhikhabhai
Ramabhai
Rabari
FA(Cow) 25.08.12 Gozariya Vijapur
Due to some fault in 11 KV Vasai Jgy feede, conductor were broken at seven
different locations and due to this fault, lt line cable giving supply to vasai railway
staiton was short circuited . Therefore a leackege current was passing from neutral
of the transformer and at the same time a cow was passing near from this
transformer centre and due leakage current the cow got electrocuted and died.
A leakage current was
passing from the
neutral of the
transformer due to the
lt line cable fired, so
the cow of the Rabari
Bhikhabhai Ramabhai
Rabari came in
contact with the
transformer neutral
and got electric shock
and died.
All the field offices
were instructed to
carry out double pole
earthing of the
transformer centre
Yes
Faulty cable has been
replaced and also
earthing of the tc has
been reactivated
No
65 MSH Khareda
Shri Savdanji
Sardarji
Thakor
FA(Cow) 10.09.12 Jangral Patan
On Dated 10.09.12 at about 12:30 hours the 11KV conductor of 11KV Untwada
feeder was broken near by Agriculture Consumer at Village Khareda due to fault
on 11KV feeder at Loc. No 103.The Conductor was fall down on
ground.Meanwhile a cow of Shree Thakor Savdanji Sardarji of village Khareda
was passed near by the conductor and came in contact with live conductor. Hence
It got electrocuted and died immediately.
CEI Report not receivedLine conductor of that portion
has been replacedNo
66 PLN Brahmadvada
Premaram
Koslaram
Chaudhary-25
years old
FH O/S
25.02.12
reporting
dated
30.04.12
Sidhpur-Rural SidhpurWhile victim was climbed on a water tank (which is located under the 11kv
Zamzam feeder )to clean the dust with use of iron pipe ,the pipe may be came in
contact to the line & he falls to earth.The accident to know by police station
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
67 PLN Ambaji
(1) Devubhai
Shaileshbhai
Joshi, Age-8
years, (2)
Hariben
Shaileshbhai
Joshi, Age 10
years
FH O/S 13.06.12 Palanpur-2 Palanpur
There is a compound wall around Vahivatdar sri bunglow. North and west side of
bunglow there is a fencing on compound wall. On that fencing two nos of tubelight
fixture directly fitted with angle of fencing. one of that tubelight fixture short and
leakage current pass on that fencing. At the time of accident above two children
contact with that fencing and electrocuted.
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
68 PLN Ranpur a vas
Dangi
Dineshkumar
Amarsingh-50
years old
NFH O/S 15.07.12Deesa-Rural-
1Deesa-1
A Fatal accident occurred to victim at Ranpur a vas during replacement of fail
Distribution Transformer of consumer named Koli Bijolji Jagmalji, at that time
victim come with contact with live line & got electrical shock.
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
69 PLN Vajegadh
Shri
Pravinbhai
Ashokbhai
sharma-24
years old
FH O/S 08.08.12 Tharad DeesaA fatal accident occurred to victim at vajegadh village ,while victim was fitting the
Hindustan petrolium signboard without switchoff the power at that time signboard
wire broken and tought with signboard angle & got shocked .
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
70 PLN
Place:-
Jayotindra
International
Factory
premises,, At
Vill:Jagana
(1) Rajendra
Jagdishbhai
Rajput-Fatal
Human & (2)
Kalubhai
Gulabbhai
Pathan-
Nonfatal
Human
FH O/S 17.08.12Palanpur-
RuralPalanpur-1
On dated:17-08-2012,Time:17:45 hours While doing colourworks in factoty of
Jayotindra International AT Vill:Jagana,Tal:palanpur by Labours Named
Rajendra(urfe Farute) Jagdishbhai Rajput & Kalubhai Gulabbhai Pathan by using
alliminium ladder And this ladder sliped and touched to live conductor of 11 kv
Swati feeder and this two persons are electocuted and met with Fatal & Non-Fatal
Human Electric Accident.
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
71 PLN Vedancha
Shri
Maheshkumar
Karsanbhai
Bhangi.
NFH O/S 18.08.12 Gadh Palanpur-2Victim him self climbed on Village T/C at village vedancha & got electrocuted and
met with Non-Fatal Human Electric Accident.CEI Report not received
Consumers were educated to
avoid direct or indirect contact
with the elecric lineNo
72 PLN
At-Deesa
city,N.R.Park
society
Smt.
Ramilaben
Rameshbhai
mali
FH O/S 2.09.12 Deesa City Deesa-1Victim came with contact of Leakage current ,which is flow on electric motor
pump and found victim died due to internal fault of motor.CEI Report not received
Consumer was informed to
check out the proper house
wiring of his premisesNo
73 PLN Mamana
Prajapati
Gangaram
Hemrajbhai-
55 years old
FH O/S 11.09.12 WAV Deesa-1A Fatal accident occurred to victim,while victim entered plug socket in his house
and found victim came with contact of plug wire which insulation is open and got
electric shock.
CEI Report not receivedConsumer was informed to
check out the proper house
wiring of his premisesNo
74 PLN ATARNESH
Owner of
Buffalows shri
RAUMA
RAGHUBHAI
MELUBHAI-2
nos buffalows
FA (2 No.of
buffalo)3.06.12 VARAHI
RADHANP
UR
In this matter one phase of 11 kv naliya ag fdr is snaped due to salty area at that
time two buffalo s are passing from there & snaped conductor is falling down on
two buffalos are coming contact with wire and get shocked and immediatly died at
place.
CEI Report not receivedMaintenance carried
out
10000
75 PLN Baspa
Owner of
Buffalows shri
-9 nos
buffalows
FA (9 no. of
Buffalo)7.06.12 Sami
RADHANP
UR
H.T. line one phase conductor broken and fall on ground near baspa village of 11
kv khodiyar jgy feeder eminating from sami s/s& 9 nos buffalows came into
contact with live conductor and expired on the spot. at that time this feeder not
tripped.
CEI Report not receivedMaintenance carried
out
76 PLN Bavarda
Owner of
Cow- Shri
AYAR RANI
BEN
DUDABHAI
FA(Cow) 13/6/2012 VarahiRadhanpu
r
IN THIS MATTER LT LINE OF SINGLE TWO WIRE OF VILLEGE TC OF
BAVARDA IS SNAPED WITH POLE DUE TO HEAVY CYCLONE . AT THAT TIME
SINGLE PHASE TWO WIRE FALL ON COW & COW WAS EXPIRED
IMMEDETIALLY.
CEI Report not receivedMaintenance carried
out
5000
77 PLN GOTRAKA
Owner of
camel
JEMALBHAI
VARJANGBH
AI RABARI
FA(Camel) 17.07.12 VARAHIRADHANP
UR
IN THIS MATTER A GROUP OF CAMEL'S OF MALDHARI PASSING THROUGH
ON GOTRAKA -CHHANIYATAR ROAD GOING AT HOME VILL. RAU TA. RAPAR
AT THAT TIME ONE OF THE CAMEL TRYING TO EAT LEAVES OF KHIJDO
THEN ITS MOUTH CAME IN CONTACT WITH ONE OF THE LIVE COND. OF 11
KV GOTRKA AG FEEDER & GOT ELECTRICAL SHOCKED & DIED AT THAT
TIME.
CEI Report not receivedMaintenance carried
out
5000
78 PLN Unava
Shri Rabari
Motibhai
Kurabhai
FA(Cow) 04.07.12 Unjha-Rural Sidhpur
A Fatal accident occurred to Cow due to leakage current flow surrounding T/C &
Cow come near current flow area near T/C, At site observed Motor of w/w
connection found short ,so leakage current flow through neutral of Transformer.&
got electrical shock
CEI Report not receivedMaintenance carried
outNo
79 PLN Arniwada
Owner of
COW- shri
Bhil
Bhagvanbhai
Haribhai
FA(Cow) 13.07.12 IQBALGADHPALANPU
R-2
A Fatal accident occurred to COW due to broken conductor of 11kv Awala AG
Feeder near P.H.Patel T/C at village Arniwada & fallown on ground while cow
came with contact of broken conductor & got electrical shock.
CEI Report not receivedMaintenance carried
out
5000
80 PLN Suigam
Owner of
COW- shri
Rabari
Maghabhai
Kalabhai
FA(Cow) 10.09.12 WAV Deesa-1A Fatal accident occurred to Cow due to Snnapping of LT conductor in village
suigam & cow came with contact of broken conductor and got electric shock.CEI Report not received
Maintenance carried
outNo
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
81 SBT Dehgam
Rabari
Karmenbhai
Kalyanbhai
FA(Buffalo) -6.7.12 at
12.30hrsDehgam T
Gandhinag
ar
Insulation of AB cable broken,Due to this live wire touched to D-clamp.Which was
earthed by GI wire.Due to this leakage current pass through GI wire.CEI Report not received
Maintenance carried
outNo
82 SBT Kathwada
Shri Shailesh
Lalabhai
damor
(V/S helper).
NFH Dept 14.04.12 Bareja Sabarmati
On dtd. 14.4.12, program of T/C replacement was given and Shri H R Waghela
ALM was the supervisor. Shri D.K.BHAGORA had gone to isolate the switch and
Shri H R Waghela and Shri D.K.BHAGORA were communicating, meanwhile Shri
S L Damor(victim) due to some misunderstanding (as per other present staff
nivedan) climbed on T/C structure before the AB switch was isolated. Suddenly
Shri S L Damor fallen from T/C structure to ground victim may came in contact
with live contacts of HT line or may be victim came in induction zone & due to that
accident occurred to Shri S L Damor (V/S helper).
CEI Report not received
Inform to linestaff to avoid this
type of miskate in future &
use safety equipments while
working on line & line on
which work has to carried out
and also nearby line must be
made dead by earthing on
both the side
No
83 SBT Dhandhuka
Shri Parmar
Popatbhai
Somabhai ,
V/S Helper
NFH Dept 04.05.12 Dhandhuka Bavla
On Dated 04.05.2012, Heavy wind flow passed through Dhandhuka at 6.00 pm.
Due to it 11 kv feeders were tripped. Among these feeders, 11 kv zanzarka feeder
was also tripped. Shri R.S.Ganderi (LI), Shri R.K.Ninama (v/s Helper),Shri
H.L.Pandor(v/s Helper),Shri P.S.Parmar(v/s Helper), went to attend fault on 11 kv
zanzarka feeder. First they cut the 1st AB switch on Limbadi road and charged
zanzarka feeder from S/S and after testing at AB switch they found one phase was
not coming.So, they were making patrolling from first AB swith to towards jaliya
S/S.While petrolling they found that one zamper was burnt on 42' gurder pole,
which is shackle pole in the compound of D.A.ENGLISH medium highschool near
S/S. Also two nos of feeders are passing on these shackle pole. The one burnt
jumpure found on upper side feeder of shackle pole, which was 11kv Zanzarka
feeder. All of them discussed about taking line clear of two feeders to repaire burnt
jumper. Shri R.S.Ganderi took line clears of 11 kv Zanzarka feeder & 11 kv Rojka
feeder on mobile phone. Actually, upper feeder is 11 kv zanzarka feeder and lower
is 11 kv zankhi feeder of 66 kv jaliya S/S. Shri P.S.parmar climed on shackle pole
for repairing of jumper & falled down. immediately sent him to RMS hospital and
then shifted to CIMS ahmedabad.
Wrong feeder LC taken
by Supervisor ,not use
safety tools & not proper
earthing on working
place
As per the regulation
no. 41 of the electricity
act 2010, proper
earthing shuld be done
& egulation no. 19 use
safety equipments
while working on the
line.
Inform to linestaff to avoid this
type of miskate in future &
use safety equipments while
working on line & line on
which work has to carried out
and also nearby line must be
made dead by earthing on
both the side
No
84 SBT
HK FINECHEM
URBAN FDR'S
GANRTY NEAR
SANAND SS
Harshandbhai
Parsottambha
i Vegada
NFH Dept
08.05.12
AT @
11.00 HRS
Sanand-1 Bopal
During maintenance of HK Finechem fdr, H P Vegada was working on Cross
boundary switch of Gantry of HK Finechem feeder and suddenly electric power
came in the 11 kv line and he was burnt at palmer(b/h palm) of left hand . He was
taken for treatment at hospital. . Electric power might be came from any generator
of consumer end.
CEI Report not received
Explanation asked to A
C patel ALM vide letter
no
Sanand/Tech/2278/21.0
5.12
No
85 SBT Valad
(1)Shri.
Santoshkuma
r Khanabhai
Charel,(2)Shri
.Ismailmiya
K Parmar
NFH Dept 21.05.12 Chiloda-1 G 'nagarAlthough the L.C. on 11KV Limbadiya AG feeder taken but the outsider cut the tree
which fallen on 11Kv line & the top part jumping and touch with conductor of
132KV Chiloda Ranasan line & Accident occurred.
outsider cut the tree
which fallen on 11Kv
line & the top part
conductor broken
&jumping and touch with
conductor of 132KV
Chiloda Ranasan line
which is above the 11 kv
line
periodically Tree cutting
should be done by field
office.
Yes,it is
rectified
Maintenance carried
outNo
86 SBT Chaloda
SHRI.CHAND
RAKANT
LAXMANBHA
I PANDAV ,
Helper
NFH DEPT 21.07.12 Dholka ( R ) Bavla
SHRI.CHANDRAKANT LAXMANBHAI PANDAV WORKING IN DHOLKA(R)SUBDIVISON
AS HELPAR AT VILLAGE CHALODA .WORKING ON LT LINE HIS LEFT HAND
TOUCHED 11KV H.T LINE FEEDAR CONDUCTOR OF KHANSARI(BADARKHA)
FEEDAR NEAR TO LT LINE AND MATE WITH MINOURE NON FATAL ACCIDENT AT
16:40 P.M ON 21-JULY-2012
WORKING ON LT LINE
HIS LEFT HAND
TOUCHED 11KV H.T LINE
FEEDAR CONDUCTOR
OF
KHANSARI(BADARKHA)
FEEDAR NEAR TO LT
LINE
Take the Line clear of
the nearby electric
line before the
starting of the work
and use safety
equipments while
working on the line.
Inform to linestaff to
use safety
equipments while
working on line and
also nearby line must
be made dead
No
87 SBT Kanotar
Shri
B.V.Ghatiya ,
Helper
NFH Dept 12.8.12 Koth Bavla
During attending Kalyangadh JGY Feeder Fault work, on disconnecting the AB
Switch behind Bhamsara village by keeping one helper there and near Kanotar
village a doutful Transformer without D.O. Unit, Shri B.V.Ghantiya, Helper was
isolating the Transformer from H.T. Line a returned current passed through his
right hand and and went out from his right thigh. This incidence was occured
during disconnecting the last Jumper (B Phase) of H.T. from Transformer Centre
and only Y Phase had given earth by earthing rod.
CEI Report not received
As per MRI report
taken, we have issued
notice to the BSNL
Company for return
power which is shown in
his DTC meter
No
88 SBT
Kathwada (
Shed no.c-65
Zaveri estate)
Shri
Rakeshbhai
Rameshbhai
Parmar
NFH O/S 12.04.12 Kujad SBT
The victim was working as a labour for work of digging of dranage line , on dt
12.04.12 at aprox. 11:00 am the victim was standing near the transformer centre
and same time the work of digging dranage line was going on . A metal rod was
laying near the T/C , when the victim put the metal rod from one side to other side
accidently one end of rod came in contact with live portion of D.O. of T/C .
Another end of rod was hold by the victim hence he got electric shock and fell on
ground.
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
89 SBT Palwada
Shri.
Arvindbhai
Revabhai
Raval (NFH)
& Shri.
Rameshji
Jugnathsinh
Dabhi (NFH)
NFH O/S 12.04.12 Bavla Ind Bopal
High stringing of AB (Areal bunch) conductor and removal of LT open conductor in
LT span where 11 kv Moraiya feeder line crossing, During stringing of LT line
came in contact with 11 KV Moraiya feeder line and both the victims got
electrocuted shock.
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
90 SBT Sagdalpur
SHRI
FULARAM .N
.DAMOR O/S
FH O/S 20.5.12 Rakhiyal G' nagar
On date 20.5.12 at approx 19:00 hrs the victim was sprinkling the water to the
bricks in umiya mojek tiles factory by 1 phase motor during sprinkling the pipe
from motor was remove at that time the victim was trying to fit the pipe of wet
motor and he direct contact with leakage current of faulty internal wiring motor and
got shocked and fatel accident occured.
victim was trying to fit the
pipe of wet motor and he
direct contact with
leakage current of faulty
internal wiring motor
To install the ELCB in
every residential and
commercial
installtion.
YesConsumers was awared
for the installation of
ELCB in his premisesNo
91 SBT Uvarsad
(1)Shree.Nare
shbhai
Manganbhai
Dantani(Cond
uctor),(2)
Chetanbhai
Chhababhai
Dantani(Drive
r)
NFH O/S 23.5.12 Adalaj G' nagar
On dt.23.5.12 approx. 10:30 am truck with hydrolick jack had came to contact with
11 kv HT line of preksha feeder coming from Adalaj s/s & at the time of uploading
the sand electric current flow due to hydrolick dumper to 11kv line & victim got
electric shock at time & NFH accident occured.
truck with hydrolick jack
had came to contact
with 11 kv HT line of
preksha feeder coming
from Adalaj s/s & at the
time of uploading the
sand electric current
flow due to hydrolick
dumper to 11kv line
Accident occurred due to
lack of knowledge of Victim
Victim
responsible
Consumers were educated to
avoid direct or indirect contact
with the elecric lineNo
92 SBT Dhanaj
Jayantibhai
Bababhai
Parmar(45
years)
FH O/S
06.06.12
@
12:30hrs
Santej Kalol
outsider Victim had climbed on T/C structure of ONGC well in village Dhanaj to
repair H.G. Fuse of outgoing jumper of horngap fuse at T/C center & Victim had
remove the D.O. fuse.While binding the jumper, binding wire touched the upper
bushing D.O.fuse & Victim got electric shock & fell on the plinth below T/C
structure.R.G.Nai Vs helper was supervising the work.First Victim was shifted to
Kalol & than Ahmedabad Civil hospital where he was declare dead.
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
93 SBT Changodar
Shri.Anilbhai
Danaji Thakor
(30 years)
FH O/S
11.06.12
@
10:10hrs
Changodar Bopal
On dated 11.06.12 ,a dumper truck GJ-1 BV 1924 came with sand filled trolly at
the 37/1,Ashawmegh ind.Estate in the premises of HT connection Sun Electro
Grovers,HT 18504 to unload the sand as the construction work inside the factory is
going on at 10.00 AM.After unloading the sand using hydraulic system,the driver
tried to drive his truck in forward direction towards gate keeping the hydraulic
system rod in upholding position so the upper part of the trolly trepped in one live
conductor of 11KV Satluj feeder.Then driver of the truck jumped from the truck
while cleaner of the truck tried to come down by keeping one foot on ground & one
hand with handle of cabin of the truck.The electric current passed from conductor
to truck body to the victim's body and to ground.At the same time the
cleaner(victim) got electrocuted and at the same time feeder was tripped at 10:10
AM.Victim died at 10:55 after hospitalization during treatment.
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
94 SBT
Swastik
Residency
,Manipur
Shri.Rakeshb
hai
Rameshbhai
Raval,14
years
FH O/S16.6.12 at
12:00 Hrs.Bopal Bopal
On dated16.6.12 at about 12=00 Hrs. (noon) a 14 year old boy Shri. Rakeshbhai
Rameshbhai Raval of village Manipur Ta. Sanand was passing near House No:18
of Swastik Residency ,opposite Manipur Primary school somehow came in contact
with MSP of Swastik Residency supplying power to its consumers.It was raining
and due to leakage current on MSP(metal box) the victim got electrocuted and
died.
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
95 SBT BarejadiVijaybhai K
TadviFH O/S
30.06.12
@ 09:30 Barejadi sabarmati
on 30.06.2012, at about 9:30 am, the victim & other 4 persons passed through this
road in vehicle no. GJ 9V 7321 near the well of Jasvantsinh N Waghela. One
conductor at this location having very low hight from ground and the driver
(Pravinbhai G Bharvad) has seen the conductor but anyhow the vehicle came in
contact with live conductor and instantly the vehicle stopped & driver could not
restart the vehicle. So victim & other 4 person tried to came down from the vehicle
but victim could not balance his body while came down & his left hand touched the
dala (rear part of vehicle) & fallen on the ground & got electrocuted. One of them
named Jigneshbhai R Tadvi tried to save the victim but he himself got electrocuted
but found ok later. The other 4 persons came down safely.
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
96 SBT Kathwada
Shri
Rakeshbhai
Hakuji Thakor
NFH O/S
Reporting
date
5.07.12
Kujad Sabarmati
There is no intimation about the accident to Sub-Division office. On dtd. 5.7.12,
AEI informed telephonically to DE, Kujad S/Dn who carried out site inspection on
6.7.12. Victim was doing work of roff fitting in Shed No. 55, Tribhuvan Estate
Kathwada. The Plastic roof/Shed is made of plastic material with metallic thread
inside. Victim climed the iron gate to fix the roof which came in contact with live
cond of 11KV Tribhuvan feeder due to which he got shock and fell on ground
injuring himself. Furthr no tripping of feeder was recorded in S/S from 4-5 PM
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
97 SBT Trent
Govindbhai
Akhuji
Waghela
FH O/S8.7.12 at
16:40 PMMandal Sabarmati
A human fatal accident had occurred to Shri..Govindbhai Akhuji Waghela(outsider
labour of contractor of Hemali electricals)lived in Village:Robas,Ta.Dessa,Age;20
Approx due to come in contact with live wire of 1phase 2 wire LT line at village
Trent Ta. Mandal around 12:30 noon.He was replacing armoured service at
kumbharvas (trent village) without removing DO of bhaktinagar village T/C.
CEI Report not receivedConsumers were educated to
avoid direct or indirect contact
with the elecric lineNo
98 SBT GODHAVI
ROSHANSIN
G M
RATHOD
NFH O/S
09.07.2012
@ 6.30
AM
SANAND I BOPALSecurity gard of Zaydus centre with the iron road about 5ft long,one side with huq
touch the 11KV line of nidharad JGY feeder by iron rod when trying to jump the
wall with the fencing.
Security gard of Zaydus
centre with the iron road
about 5ft long,one side
with huq touch the 11KV
line of nidharad JGY
feeder by iron rod when
trying to jump the wall
with the fencing.
Victim responsibleVictim
responsible
Consumers were educated to
avoid direct or indirect contact
with the elecric lineNo
99 SBT Dehgam
Smt Minaben
sanjaybhai
shah Age 36
yrs
FH O/S 8.8.12 Dehgam(T)Gandhinag
ar
Victim Smt. Minaben Sanjaybhai Shah was while putting clothes on steel wire for
drying ,got Electrict shock & died, in deatil investigation it was found that, due to
defect in freez & internal wiring , leakage current passed through galvanise sheet
on roof of house,which was supported by the pipe, to which steel wire was tied.
CEI Report not receivedConsumer was informed to
check out the proper house
wiring of his premisesNo
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
100 SBTBHAGUJINA
MUVADA
VIJAYSINH
R. ZALAFH O/S 20.9.12 RAKHIYAL
Gandhinag
ar
On dated 20-09-2012 at 22:00 hours Shri Vijaysinh has gone to river for loading
sand in tractor. After few hours one villager focusing the torchlight on tractor hence
the victim and other young boys understand that the government officer ( royalty
officer ) are coming, hence the all boys to ran away from river and at that time Shri
Vijaysinh was also ran away and might be contact with live fencing wire that
provided in farm of Hathisinh Dulsinh Zala which is near by river for saving the
crops from the Neel cow and victim got electric shock.
CEI Report not received
Consumers were
educated to avoid direct
or indirect contact with
the elecric line or
equipment
No
101 SBT Bakrol
Shri
Khumansinh
Agarsinh
Chauhan
FA(Buffalo)
19.03.12
reporting
late
Changodar Bopal
On dated 20.3.2012, police station ,Aslali has inform to S/Dn office that a fatal
animal accident occurred to a buffalo at village: Bakrol ondated 19.3.12. DE,
Changodar has visited the site on 20.3.2012. As per owner's statement buffalo
died due to conact with stay wire (Stay insulator was bypassed)of Ag T/C which
was tied there near T/C. On date of site visit no any leakage current found on stay
wire.
CEI Report not receivedMaintenance carried
outNo
102 SBT VIRAMGAM
Shri Kanabhai
Vasibhai
rabari
FA(Cow)
16/6/2012
@10:30P
M
VIRAMGAM
TOWNKALOL
An electrical Accident 16.6.12 at 10.30 pm hrs occure to a cow of shri Kanabhai
Vasibhai rabari at Viramgam near V choksi bazar . Their is Leakage Current in LT
Round Pole due to Faulty Street Light Fixture.When cow was passing near the LT
Round Pole due to sarounding wet area due to monsoon electrical fatal Animal
accident occured.(City-2 Feeder,66KVFulwadi S/S)
Their is Leakage Current
in LT Round Pole due
to Faulty Street Light
Fixture
As per CEA regulation 12
,periodically maintenance
should be done by field
office.
Yes,it is
rectified
Maintenance carried
out2000
103 SBT Tintoda Nanpura
Shri.Dayaji
Gabhaji
Thakor
FA(Buffalo) 16.6.12 AdalajGandhinag
ar
BUFFLOW CONTECT WITH TRANSFORMER STRUCTURE AND GOT
ELECTIRC SHOCK AND DIED.(11KV Moti Adaraj feeder/63KVA TC Nanpura-
Tintoda road)
CEI Report not receivedMaintenance carried
outNo
104 SBT kathwada gidc unknown cow
/ no ownerFA(Cow) 16.6.12 naroda Sabarmati
Due to switch short at plot no 378 con no 26002014446 return power come to
transformer earthig through neutral & cow come in contact with earthing wire of
transformer & get shocked
CEI Report not receivedMaintenance carried
outNo
105 SBT Vadsar
Vaghjibhai
Maljibhai
Rabari
FA ( He-
Buffalo)26.09.12 Santej Kalol
Fatal Animal Accident occurred to A He- buffalo, due to current passing through
Stay wire touching with live jumper ,Due to less clearance between stay wire &
jumper.(Only 3 inches)
CEI Report not receivedMaintenance carried
out5000
106 SBT BOPAL
SURESHBHA
I
BHIKHABHAI
BHARVAD
FA (2 no.s of
Buffalo)09.09.12 BOPAL BOPAL
DUE TO HEAVY RAIN & WIND PRESSURE CONDUCTOR OF LT LINE IS
SNAPPED & FELL DOWN ON BARBERED WIRE OF FENCINGOF THE PLOT.
THE BUFALLOWS GRAZING IN THE PLOT CAME IN CONTACT WITH THE
LEAKAGE CURRENT & DIED ON THE SPOT
CEI Report not receivedMaintenance carried
outNo
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
107 SBT Shilaj
GAFURBHAI
NAGARBHAI
RABARI&DE
VABHAI
SURABHAI
BHARVAD
FA (1
No.Cow & 1
no. Buffallo )
13.08.12 Bopal BopalTHERE WAS LEAKAGE CURRENT IN EARTHING WIRE OF TRANSFORMER
CENTRE OF TEMP. CONN. SO WHILE PASSING NEAR BY THE T/C, TWO
ANIMAL COME IN CONTACT WITH EARTH WIRE & DIED ON SPOT
CEI Report not receivedMaintenance carried
outNo
108 SBT Kalol(T) No owner
FA To 2
nos,of
ox(Akhala)
12.8.12 at
3.15 AMKalol(T) Kalol
Fatal Animal Accident to Two nos. of Ox occurred, due to a leakage current found
on LT Line tubular steel pole due to streetlight fixture fault
leakage current found on
LT Line tubular steel pole
due to streetlight fixture
fault
As per CEA regulation 12
,periodically maintenance
should be done by field
office.
Yes,it is
rectified
Maintenance carried
outNo
109 SBT Kathwada GIDC
Karmanbhai
talajabhai
Rabari
FA( 2 nos of
Cow)29.09.12 Naroda Sabarmati
as per investigation report due to LT pole broken by pvt vehicle no GJ - 18 8438
opp. Plot no:489 & LT conductor snapped & 2nos of Cows came in contact of live
wire ,got electrolucted & died
CEI Report not receivedMaintenance carried
outNo
110 SBT RampurShri.Juhabhai
P.BharwadFA(Buffalo) 3.07.12 Dhodaka Bavla
At about 16:00PM group of buffallows passing near to pole quarelled with each
other and collide with pole and due to impact LT line pole (1Ph 2wire) fallen down
& also line broken .The buffalow passing nearby came in contact with line and met
with the accident.
group of buffallows
passing near to pole
quarelled with each other
and collide with pole and
due to impact LT line
pole (1Ph 2wire) fallen
down & also line broken
.The buffalow passing
nearby came in contact
with line
As per CEA regulation 12
,periodically maintenance
should be done by field
office.
Yes,it is
rectified
Maintenance carried
outNo
111 SBT Aakru
Mundhva
Harjibhai
Jadavbhai
FA(Buffalo) 04.07.12 Dhandhuka Bavla
Due to heavy rain and cyclone one LT conductor broken down and laid down at
the road,Same time buffalow and other buffalow came outside of the house due to
cyclone .Buffalow came in contact with live LT wire which is laid down on the road
and got shock.
one LT conductor broken
, laid down on the
road,Buffalow came in
contact with live LT wire
As per the regulation no. 41
of the electricity act 2010,
proper earthing shuld be
done and also periodic
maintenance of the line
should be done.
YesMaintenance carried
out5000
112 SBTDehgam ITI
Road
Bhemanbhai
Hirabhai
Rabari
FA(Buffalo)15.7.12 @
10:30amDehgam T Sabarmati
Insulation of R-ph of pvc cable passing from LT bushingof transformer to LT line
take off pole was worn out.which was touching to the support angle of
transformer.as all metal parts of transformers were earthed but the earth wire was
broken from ground and was tied with stay wire of tranformer centre. due to this
current passed in stay wire & as buffalo came in to contact with stay wire and died.
CEI Report not receivedMaintenance carried
outNo
113 SBT Chankheda
Rabari
Somabhai
Lilabhai
FA(Buffalo)13.8.2012
16.30 HRSChankheda
Gandhinag
ar
Due to failure of earthing retuned power came on neutral. So when the buffalow
came in contact with the earthing wire she got electric shocked and died.CEI Report not received
Maintenance carried
outNo
114 SBT khoraj
shri
Yasinmiya
Rasulmiya
Malek
FA(Buffalo) 17.8.12 AdalajGandhinag
ar
L T line live conductor snapped due to tree fallen on LT line & live wire falled on
buffalow which was bound under LT line.CEI Report not received
Maintenance carried
outNo
115 SBT Dholka
Anishbhai
Ushmanbhai
Vora
FA(Buffalo) 11.09.12 Dholka-T BavlaLooking to the situation of site , it is found that LT wire broken due to big branch of
tree fallen due to heavy wind and buffalow came in connect to live LT wire and
got electrocuted & died
CEI Report not receivedMaintenance carried
out10000
116 SBT VadsarRajaji Mathurji
ThakorFA(Buffalo) 08.09.12 Santej Kalol
Fatal Animal Accident occurred to A buffelo, due to current passing through
fencing, through live conductor ,snapped from line, due to service cable of nearby
AG consumer fired'
CEI Report not receivedMaintenance carried
outNo
117 SBT Viramgam
Cow of
Bhathibhai
Lilabhai Desai
& Goat of Tai
Abbas
Gulamrasul
FA(Cow) 04.07.12viramgam
TownSabarmati
There was Leakage Current in LT Round Pole due to open joint of streetlight
connection which touched LT round pole & flew current, The cow & Goat passing
near the LT Round Pole touched Lt round pole, fatal Animal accident occured.
There was Leakage
Current in LT Round
Pole due to open joint of
streetlight connection
which touched LT round
pole
As per CEA regulation 12
,periodically maintenance
should be done by field
office.
Yes,it is
rectified
Maintenance carried
outNo
118 SBT GIDC,Chhatral
Prabhatbhai
Jesangbhai
Rabari
FA(Cow)
10/7/2012
At 12.00
PM
Chhatral KalolNeutral leakege current of LT Consumer was returned to x'mer centre The rain
was continuing & A Crowd of cows were passes near the x'mer centre.One of
those cow touches to the X'mer centre & got electrocuted & died
CEI Report not receivedMaintenance carried
outNo
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
119 HMT Dhamboliya
1)Gadasha
Bachubhai
Thavaraji-Fatal
2)Gadasha
Jagdishbhai
Virajibhai-Non fatal
FH & NFH O/S 1.10.12 Bhiloda-2 Bhiloda
Both victim were working themselves on LT network .Both are outsider and are not authorised to work
on distribution network.while working on LT network they came in live contact in distribution line and
met with Fatal and Non fatal accident respectively.
CEI Report is awaited
Consumers were educated to
avoid direct or indirect contact
with the elecric line
No
120 HMT Akrund
Amarsinh J.
Makwana(Assi.
L.M.)
NFH Dept 5.10.12 Dhansura Talod
At the location of the 11kv Akrund AG Feeder loc.no.154/17 where accident occurred ,66kv Dhansura-
Ambaliyara line is passing over the said 11kv line at loc.no.154/20 & on the Dt.when accident
occurred Amp.loading on 66kv line is high and ambient temp.was arround 35Cent.,due to the loading
& temp.effect conductor of 66kv line might have lowered.When victim climbed on the pole for repairing
of jumper at loc.no.154/17 during this time 66kv conductor may lowering & due to this ,distance
between 66kv & 11kv line may reduce & victim might have come in induction zone at that time and
further resulting electrocution and victim falling on the ground & accident may occured.At the same
time 66kv line tripping is observed.This is our primary observation,detail investigation report finally
given after taking nivedan of victim.
CEI Report is awaitedSdn has lower the 11 kv line
after the incidentNo
121 HMT Ambabar
Baranda
Champaben
Prakashbhai
FH O/S 2.10.12 Bhiloda-2 Bhiloda
In consumer premises,leakage current came through in house damage wiring at load side.Victim while
working her house ,she came in contact with internal private wiring of her premises and got
Electrocuted.
CEI Report is awaited
Consumer was informed to
check out the proper house
wiring of his premises
No
122 HMT Jesingpur
Chauhan Ramsinh
Movatsinh,Village
helper
NFH Dept 12.10.12 Bhiloda-2 s/dn Bhiloda
Victim has climbed on dead 11 kV line of Mehru JGY feeder, which was having two spans. He has
climbed on second and last pole of this line for removing 11 kv pin insulator. While he tested the
power supply by back palm of right hand, group of birds which were sit on tapping pole, fly away due
to which top conductor vibrated & momentary current passed to right hand back palm. It is reported
that victim was not fallen from pole. There was no any serious injury except burns on palm of right
hand & chest. He is already discharged from hospital on same day.
CEI Report is awaited
Dead spans removed
immediately. Warning memo
issued to victim.
No
123 HMT VasnirelManjuben Surabhai
ZalaFH O/S 22.10.12 Choila Talod
The Victim was washing clothes in her premises and for that she used electric motor to lift water.After
washing clothes she forgot to switch off the switch first & By mistake she touched to the open live wire
of motor And electrocuted & She died after some medical treatment...
CEI Report is awaited
Consumer was informed to
check out the proper house
wiring of his premises
No
124 HMT ModasaAkramhusen K
JamadarFH O/S 20.10.12 Mod-Town Modasa
Victim was cleaning the top of truck cabin. Truck was parked under 11 kv line of college fdr. Victim'
head was came in to contact with 11 kv line.The distance is 15 ft between ground and
line(vertical).The cause of low distanc is earth filling due to digging of gutter & RCC road during last
year . there was no T.T. of college fdr.
CEI Report is awaited
Consumers were educated to
avoid direct or indirect contact
with the elecric line
No
125 HMT Savagadh
FH to Kiranbhai
manubhai palasva
& NFH
toTufanbhai
Rupsinhbhai
Dindor
FH & NFH O/S 2.11.12 Mehtapura Himatnagar
To release New Ind connection two nos pole required to erect for transformer centre.one pole was
erected by the gang while digging pit for second pole stone come in pit so location of pit changed
which was near to 11KV feeder line.pole was erected by the victim(Labour of contractor)in the pit.while
adjusting the pole in the pit, pole was tilted & touched/came in induction zone of nearby Dhandha
Urban live feeder conductor. So current might have passed through G.I. wire of the pole. The victim
holding pole for work got electric shock and died while other get electric shock but survived with minor
injury of burnt.
CEI Report is awaited
Explanation asked to concern
helper by
MSD/2352/dtd:.3.11.12 all the
line staff has been awared
accordingly.
No
126 HMT Hathikhant Na Muvada
Khant Bhailalbhai
Somabhai Age; 16
Years
NFH O/S 1.12.12 Bayad Talod
At the time of removing mobile charger from the plug at the same time pin insulator of do unit fired on
jgy village transformer & leakage current passed through earth to neutral wire to village consumer
installation.So that Victim got electrocuted & injured on right hand finger & also bottom side of leg.
CEI Report is awaited Necessary maintance done No
127 HMT Salal
Gavariya
Navganbhai
Rameshbhai 12
years old
NFH O/S 6.12.12 Salal Hmt
The incident occurred at market yard vali TC at vill. Salal,while making attemp of catching kite, victim
climbed up from said transformer & he any how unknowingly came into contact with HT bushing
through his hand and got electric shock .
CEI Report is awaited
Consumers were educated to
avoid direct or indirect contact
with the elecric line
No
128 HMT Nanasamera Owner -Suvera
Mukesh BabuFA(Cow) 17.12.12 Bhiloda-2 Bhiloda
Due to pin puncture 11 kv conductor of Galpur JGY fdr snapped.Meantime cow passing near that
conductor & came in contact with that wire & got electrocuted.
Due to pin puncture 11 kv
conductor of Galpur JGY fdr
snapped
As per CEA regulation 12
,periodically maintenance
should be done by field
office.
Yes,it is
compliedRestringing of conductor done No
129 HMT ZanzariSolanki Makanbhai
SomabhaiFH O/S 27.12.12 Choila Talod
A tractor was parked near by 11 kv line of fdr narsipurAg to pull out motor from bore and while raising
trolly by mistake of driver it came in contact with HT line victim got electrocuted & died.CEI Report is awaited
Consumers were educated to
avoid direct or indirect contact
with the elecric line
No
130 HMT Jaswantpura
Khant
Dineshkumar
Madhusingh
FH O/S 30.12.12 Bayad Talod
At the consumer premises due to body short of 3 ph motor of conveyer belt,leakage current passing
through the whole metal fabrication of conveyer belt. When victim touched the same fabrication he
was electrocuted.
CEI Report is awaitedConsumers were educated for
install ELCB in his premises.No
131 HMT Lei
Owner -Patel
Sureshbhai
Maganbhai
FA(Bullock) 15.2.13 Idar-T IdarDue to Heavy Cyclone & Rain Conductor broken. Meanwhile bullock came in Contact of Live LT
Conductor & got died.
Accident occurred due to touch
with the broken LT line live wire
As per CEA regulation 12
,periodically maintenance
should be done by field
office.
Yes,it is
rectifiedRestringing of conductor done No
132 HMT BayadAshiben Abdulbhai
MalparaFH O/S 25.3.13 Bayad Talod
While victim was connecting 1ph electric motor through 1 ph-2wire cable at one side male pin at plug
side & other at motor side.During such type of connection , victim came in contact with live part of
wire & got electroculated & met with fatal accident.
CEI Report is awaitedConsumers were educated for
install ELCB in his premises.No
133 HMT HimatpurOwner -Ninama
Jivaji MehajiFA(Cow) 15.2.13 Bhiloda-2 Bhiloda
Due to Heavy Cyclone & Rain pin insulator punctured & Conductor broken and fallen down on
ground. Meanwhile cow came in Contact of Live Conductor & got died.
Due to pin puncture ,live
conductor snapped on Cow.
As per CEA regulation 12
,periodically maintenance
should be done by field
office.
Yes,it is
rectifiedRestringing of conductor done No
134 MSH Khadalpur
Patel
Mahendrabhai
Manilal Age 52
years
FH O/S 1.10.12 Visnagar-1 Visnagar
Ag connection of Shree Panchal Atmaram Madhavlal Ag Conn no 21104/00259/0 Khadalpur 52 HP
is located on 11 kv Chhogala feeder eminating from 66kv Umata s/s.This AG connection is given on
100 kva transformer center & 3 phase Power supply schedule is 23.15 to 9.15. AG premises (ordi) is
about 8to9 meter away from transformer center . On 1-10-2012 in morning at about 8.00 hrs Shri
Mahendrabhai Manilal Patel bore operator is to start the motor by starter for doing piyat in AG land.
By site inspection & investigation No body was present in AG premises (ordi) at the time of incident
but looking to the site Shri Mahendrabhai Manibhai Patel came in AG primises( Ordi) for reparing or
to start the starter. Window cover of starter is found open & black spots found on below side of starter
window cover it may be Shri Mahendrabhai Manibhai came in contact of Live wire & he got electric
shock& he fell down on the ground& thus Fatal electrical accident occured.By site verification incident
occured in party's Own premises by his mistake.
CEI Report is awaited
Consumers were educated to
use proper size of and proper
rating of starter(electric
appliances) in his premises
No
135 MSH MadhiPatel Veenitkumar
JyantibhaiFH O/S 1.10.12 Ladol Vijapur
Due to wrong sequence of phase and neutral in consumer's installation the phase is live in off
condition of switches hence while plugging of single phase water pump victim's hand came in contact
to plug pin and accident took place.
Phase wire was direct in the
switch board of the victim's
house due to this in both the
ON-OFF position of the swich
current was coming in the twi
pin plug
As per CEA Regulation 29
,consumer should get wiring
of house through licences
contractor .
Yes,it is
rectified
Consumer was informed to
check out the proper house
wiring of his premises
No
136 MSH Mehsana
Kantibhai
Shankarbhai
Rathod,Age 25
years
FH O/S21.09.12
(reporting late)Mehsana Highway Mehsana
Victim was working on iron structure at modhera circle for providing hording for advertisement & while
working on iron structure ,his back side touched to the live open LT conductor passing just 3 feet
away from the structure and got electric shock and met with the fatal accident. Information about the
accident was recieved from electrical inspector mehsana.
During the work of removal of
hording victim's body came in
contact with the electric line.
Not suggested
Maintain proper safe
clearance from the electric
line while working nearer to
the electric line
No
137 MSH Mehsana
Shokhaliben
Kalubhai Damor,
Age 46 years
FH O/S29.09.12
(reporting late)Mehsana Highway Mehsana
Victim might have gone for toilet on open ground of ST compound at modhera circle at where
consumer's armour cable having joints at 4 different places was lying open on the ground. While
passing through this area victim might came in contact with the live open joint and got electric shock
and dead on the spot. Information about the accident was recieved from the letter of Mehsana B
Division police station.
CEI Report is awaited
Consumer was informed to
insulate open joint of the
electric cable and use only
standard guage of electric
wires only.
No
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
138 MSH AlusanaMukeshji Ganpatji
ThakorFH O/S 8.10.12 Kadi R-1 Kadi
At corridor of his house, refrigerator was there. He has put his mobile for charging on refrigerator.
Victim tried to collect his mobile from there, and due to any leakage current on refrigerator, he got
electroculated. His family member brought him to nearer hospital for treatment, and there he got died.
So, the reason for the death of Victim is due to leakage current came from faulty refrigerator and also
there were no any protection for earth leakage current.
CEI Report is awaitedConsumer was educated to
install ELCB in his premises.No
139 MSH Pindharrupa
Goswami
Bharatpuri
Ishvarpuri
FH O/S 7.10.12 Dhinoj Mehsana
Victim kept his camel cart below the neem tree nearer to Gokulnagar Society at Pinddharpura. An 11
KV Pinddharpura Ag feeder was passing just 4-5 feet away from this neem tree. Victim climbed on the
neem tree for cutting the fresh neem tree branches. After cutting on of the fresh neem tree branch,
victim had holded on end of the freshly cut neem tree branch and the other leafy end of the branch
came in contact with the 11 KV line, causing a path for flow of leakage current. So victim got an
electric shock and died.
Victim climbed on tree for
cutting the fresh neem tree
branches. During victim had
holded on end of the freshly cut
neem tree branch and the other
leafy end of the branch came in
contact with the 11 KV
line.Accident occurred due to
lack of knowledge of Victim
Accident occurred due to
lack of knowledge of Victim
Branches of the neem tree
was cut down in order to
maintain proper clearance
between tree branches and
electric line
No
140 MSH DenapAlpeshji Chehraji
ThakorFH O/S
26.09.12(repor
ting late)Visnagar-1 Visnagar
As per the statement of victim's father, his son came from the school on dtd. 26/09/2012 about 15:00
hrs. and touched the switch of light and he fell down on the floor and died. During investigation, an
open switch board was found in victim's house. Also there was no any leakage current and any sign of
burning spot on switch board or on wall of the house. So it was the suspicious case for electrical
accident and we can only conclude the cause of the death after recieving the PM report. On reciept of
the PM report on dtd. 10/10/2012, it was concluded that the death has occured due to cardiac arrest
due to electric shock.
CEI Report is awaitedConsumers were educated for
install ELCB in his premises.No
141 MSH NarsinhpuraSenma Mehulbhai
ChandubhaiFH O/S 12.11.12 Kadi R-1 Kadi
Victim's brother was sprinkling water on wall of his shed and the victim was near water tank. The
water pipe from electric motor came out and the motor failed down to wet land near water tank. The
insulation of phase wire connected to shocket of motor was cut and water was spread on motor and
to earth. Victim tried to reinstall the water pipe connection, and due to leakage current, he got shock.
Then victim was transferred to Hospital where he got died. Morever, ON-OFF switch of switch board
to which the plug of motor was connected was not working properly, means even in OFF position,
phase was ON.
CEI Report is awaited
Consumer was educated to
use only standrd electric wire
and standard elctric switch
board with ELCB installed in
the premises.
No
142 MSH MehsanaThakor Motiji
MadhajiFH O/S 23.11.12 Vadnagar Juna Aspa
On dt 23-11-2012 D.E Kheralu visited the place of Fatal accident occurred to Shri Motiji Madhaji
Thakor at Juna Aspa village. A single phase lighting connection was existing in r/oShri Somaji
Bhikhaji Thakor conn no 22612/00342/8 given by 2 core 2.5mm2 yellow colour pvc cable . A house of
Shri Somaji Bhikhaji Thakor & a house of Shri Motiji Madhaji Thakor is located near to each other .
There is no Lighting connection in Motiji Madhaji Thakor's house. A illegal connection was taken from
Somaji BhikhajiThakor's house by flexible wire approximate 10 mtr. 12 watt lamp was connected. The
flexible wire was jointed& broken & comes from the door in his house. It is asummed that Shri Motiji
Madhaji open the door & by mistake he touch the broken flexible wire & he got the electric shock & fell
down on ground .There is no any Eye wittness at the time of accident .Near by people Shri Jehaji
Dhulaji Thakor might have seen the accident & they made a notice of it then theycame & call 108 &
brought him at Vadnagar Civil hospital & Doctor has declared he is died & sends the dead body for
Post mortem. During visiting the place of accident panchnama done. For An illlegal connection given
by Somaji Bhikaji Thakor a pannelty bill isssued to him.We have checked the UGVCL installation with
line tester that there is no any leakage current on MMB, or on wall at consumer premises. There is no
any spot of burns at consumer premises or on door
CEI Report is awaited
Consumers were educated to
use only proper guage wire of
standard
No
143 MSH MehsanaKum. Vaibhaviben
Rameshbhai DarjiNFH O/S
25.12.12 (late
reporting ) Mehsana IND Mehsana
A 200 KVA Distribution transformer is existing nearer the wall between Ratnadeep and Bhairavkripa
society. The height of the wall is up to the DO fuse link of the transformer centre. Hence the distance
between the Do fuse link and the wall is approximately 3.5 feet. On Dtd. 25.12.2012 at 16:25 pm,Kum.
Vaibhaiben R Darji returning from Ratnadeep Society, she climbed on Said Society's wall & crosses
towards Bhairavkrupa Society and at that time she touches 11 KV live wire from DO fuse to
transformer bushing & got electric shock & fallen down on ground.
CEI Report is awaited
On the top of the wall broken
glass pieses are fixed with
cement by contractor of
Ratnadeep society so that
now onwards nobody climb up
on said wall. As well as Do
fuse direction change from
wall side to open space side
on Dtd.10.01.2013
No
144 MSH Khanusa
Senma Jasubhai
Punjabhai,worker
of contractor's
gang
NFH O/S 22.01.13 Vijapur Vijapur
On Dt;- 22/01/13 line stringing work was arranged. On this day the 11 kv chadasana feeder 3-phase
power supply time started from 12:30 to 22:30. So, line clear by shree D.B. Tadvi has been taken of
this feeder at 9.55 a.m , earthing at work place on feeder has carried out & started the work on this
feeder of removing old line . But victim Shree senma Jasubhai Punjabhai, worker of contractor's gang
climbed on pole of 11 kv Vihar feeder , location no 11, having 3- phase supply starting from 3:45 to
13:45 p.m So, non fatal electrical occured to the victim at 10:35A.M. with heavy flash over occure &
one jumper on sub station gantry switch was burned.
CEI Report is awaited
Conform the line must be
dead before executing any
work in the electric line
No
145 MSH Vasai
Owner -Rabari
Jivanbhai
Mankabhai
FA(Cow) 15.02.13 Gozariya Vijapur
A single phase service line with GI wire giving power supply to school was short circuited. Therefore a
leakage current passing through GI wire, which was touched the LT line & girder pole. A cow was
passing near girder pole and due to leakage current got electrocuted and died.
Due to leakage current passes
from Girder pole due to
damage of insulation of single
phase service line .
As per CEA regulation 12
,periodically maintenance
should be done by field
office.
Yes,it is
rectified
Deteriorated service wire has
been replaced by by new
service cable with new GI
Wire and binding
No
146 MSH Vajapur
Thakor Dineshbhai
Mafaji,Electrical
Assistant
NFH Dept 25.02.13 Satlasana Visnagar
Shri D. M. Thakor during jumpering work on new 11 kv line of Mumanvas Ag feeder for releasing
new Ag connection at Vajapur Ag area .During that time victim came in 11 kv power induction zone
and he fall down on ground.
During investigation actually matter is found that,they have cut off the AB switch of wrong section
tape line. So power is continue from existing line and D. M. Thakor had not done proper earthing at
working place and not use any safety equipments. Hence the non fatal accident is occurred to Shri
D.M. Thakor during jumpering work.
CEI Report is awaited
Line staff were educated to
conform the line must be
made off before starting of
work. Also proper earthing
must be done on both the side
of the section in which work
has to be dong
No
147 MSH SurajThakor Rinkiben
RajujiFH O/S 18.02.13 Kadi-2 Kadi
Detail report will follow ,but as per primary report; victim was hanging the clothes on metal wire, which
was tide between the LT pole & 'chabutara' appr. 15 to 20 feet away from LT pole and got electric
shock. Reason may be the leakage current, which may be comes from the channel wire having weak
insulation tide on the same LT pole to earth wire and from earth wire to metal wire, on which the victim
was working.
CEI Report is awaited
Sharapanch of gram
panchayat was instructed to
caary out the mainenance and
to replace the electric wire of
the strret light fixture. Also,
Consumer was wducated to
not tide the metal wire with the
electric pole or nearer to
electric pole.
No
148 MSH Tintodan
Prafulbhai
Bharatbhai
Kher,Village Helper
Tintodan
NFH Dept 11.01.13 Kukarwada VijapurWhen victim was climbed on psc pole for attending the 1Q Lighting complain at that time victim
came in contact with live part of the cable & get shocked.CEI Report is awaited
Line staff ws educted to use
safety equipments while
working on the electric line
also they were instructed to
make the line dead before
starting of the work.
No
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
149 MSH DagawadiyaSohanbhai
Martabhai DamorFH O/S 24.01.13 Kukarwada Vijapur
on dtd. 23.1.13 , in the farm of Chaudhary Jashubhai D., Vill. Dagawadia, Ta:Vijapur, Di: Mehsana, a
victim was stacking down the column pipe in the bore, completing the work,the roller (Charkhi) of
boring apparatus touch the 11 kv Umiya feeder. Due to this a victim Damor Sohanbhai Martabhai was
operate the appratus came in contact with 11 kv line and current passes through lower part of
stomach and admitted to hospital at Visnagar. the incident occured on dtd 23.1.13 & police inform us
on dtd.24.1.13 at 5.00 P.M.
CEI Report is awaited
Consumers was educated to
avoid any work below the
electric line and carry out their
work with safe clearance from
the electric line
No
150 MSH BiliyaThakor Bharatji
Mahendraji NFH O/S 8.03.13 Ladol Vijapur
An eight year old, victim climbed on transformer centre of telephone exchange and hold jumper on
bushing side &spark shown on channel of support & jumper ,got electrocuted ,met with non fatal
accident.
CEI Report is awaited
people were educated to avoid
direct or indirect contact with
electric line
No
151 MSH Badarpur
Vaghari
Sureshbhai
Motibhai
FH O/S 20.03.13 Vadanagar Visangar
Victim self climbed on PSC Shackle pole ( near Rajebhai Ibrahimbhai Dharkhad farm)
of 11 KVBadarpur jgy feeder emanating from 66 KV Vadnagar Sub Station. He touched to
jumper of live Line & got shocked. CEI Report is awaited
Consumers were educated to
avoid direct or indirect contact
with the elecric line
No
152 MSH HarijThakor Anilbhai
ManajiFH O/S 20.03.13 Harij Patan
While carrying out masonry work of new house of Desai Hargovanbhai Bababhai, victim tried to
remove cotton string (used for Kadiya kam) lying on the conductor of 11kv Dantarvada Ag feeder.
While doing so he came in contact with live conductor and got electrocuted & met with fatal accident.
CEI Report is awaited
Consumer was awared to
maintain safe clearance from
the electric line and avoid
direct or indirect contact with
the electric line
No
153 PLN Kundi
Damor Sankarbhai
Khatarabhai-V/S
Helper
NFH Dept 12.10.12 Dhanera-2 Deesa-2While victim was attending complain of consumer ,he climbed on pole without switch off the power &
came in to the contact of live 3-phase 4-wire LT Line conductor and got electric shock.C.E.I report is awaited
Memo issue vide letter no-
UGVCL/Dhanera-
2/Tech/accident/8373/15-10-
2012 dtd, and required action
under process
No
154 PLN AT-Makadchampa
owner : Parmar
Jagabhai
Galbabhai
FA(Buffalo) 13-10-2012 AMBAJI PALANPUR-2
At Makadchampa, Agriculture consumer sri Parmar Mohanbhai Panabhai has 5 hp conection. & Ag
consumer no is 71030502714. His motor is short. so Return leakage current flow into 3 phase 4 wire
LT to Transformer from 3 ph elecric motor. He buffalow is contact with transformer Earthing (GI) wire
and got electocuted.
C.E.I report is awaited Use ISI Mark motor 5000
155 PLN Sidhpur.
Prajapati Gopalbhai
Kantilal-42 years &
Prajapati
Jyotsnaben
Gopalbhai-40 years
FH O/S 3.11.12 Sidhpur-City Sidhpur
smt. Jyotsnaben gopalbhai prajapati ( outsider) aged approx. 40 years,at 27 of k.b. complex society
b/h vishwas hotel, sidhpur highway was carrying approx. 22 feet long iron box pipe for some work.
While she was lifting/carrying the iron box pipe near compound wall of height approx. Five feet of her
residence, due to approx 22 feet length of that pipe, one side end of the iron box pipe was out of the
wall whose top side touched to 11kv ankvi ag. Feeder, which is passing out side the compound wall
approx. Five feet away from 11kv line and ground clearance of that 11kv line is approx. 19 feet.
Electric current passed through the iron box pipe & she got electoculated. Her husband shri
gopalbhai kantilal prajapati (outsider) aged about 42 years old rushed to save her & he also got
electoculated. Thus couple got electoculated & died on the spot. It is found that there was tripping on
11kv ag. Ankvi feeder at 8:42 a.m. & spark spots were found on the top end of the iron box pipe.
C.E.I report is awaited
Consumer was awared to
maintain safe clearance from
the electric line and avoid
direct or indirect contact with
the electric line
No
156 PLN Delwada
Thakor Bhikhiben
Ganeshji-27 years
old
FH O/S 6.11.12 Deodar-1 Radhanpur A Fatal electrical accident occurred to victim,while victim came with contact of broken LT line
conductor,which conductor found broken and follown on ground and got electric shock.C.E.I report is awaited Maintenance work carried out No
Sr
no.Circle
Location of
accident
Details of
victim/owner
Type of
Accident
FH/NFH /FA
Dept
/outsiderDate S.Dn. Divn. Detailed Reason of Accident Finding of CEI/EI/ AEI
Remedies suggested by CEI /
EI/ AEI in various cases
Whether the
remedy
suggested is
complied
Action taken to avoid
recurrence of such Accident.Compensation Paid
1 2 9 3 4 5 7 8 11
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12TO MARCH-13)
Performa-SoP002:-Action taken report for safety measures complied for the accidents occurred
157 PLN Maktupur
Makwana Dipak
kumar
Parshottambhai-42
years old
NFH O/S 2.11.12 Unjha-Rural Sidhpur
A Non Fatal electrical accident occurred to outsider,while victim Repairing of Street light in
sardarnagar society at that time he was came with contact of LT line Phase wire conductor and fall
down on ground and got electric shock.
C.E.I report is awaited
Consumers were educated to
avoid direct or indirect contact
with the elecric line
No
158 PLN Radhanpur
Shivabhai
Ramsingbhai
Nirashrit-16 years
old
FH O/S 17.11.12 Radhanpur Radhanpur
Victim was climbed on the village water tank and was going to pull water through bucket and rope
from village water tank. Neutral conductor among the single phase two wire LT line passing over said
water tank was snapped. The victim came in contact with the snapped conductor and got
electrocuted.
C.E.I report is awaited Maintenance work carried out No
159 PLN Yavarpura
Owner -Shri
Harijan Bheraji
Kavaji
FA(Buffalo) 5.12.12 Dhanera-1 Deesa-2A Fatal accident occurred to Buffalo due to Snnapping of 11 kv Jadiyali feeder conductor on buffalo &
she came with contact of broken conductor and got electric shock.C.E.I report is awaited Maintenance work carried out No
160 PLN Manka
SHRIMALI
DIPAKKUMAR
RAMCHANDBHAI-
Helper s/dn gang
NFH Dept 2.01.13 Jalotara Palanpur-2
victim while climbed on T/Cstructure for getting the details of existing transformer by reading name
plate,which is fixed on the x'mer body. Mean while he touched with T/C's HT side bushing's stud &
got shocked & met with non fatal accident.
C.E.I report is awaited
Issue warning memo to
supervisor & victim due to not
follow of safety measure vide
letter no-
UGVCL/Jalotra/accident/est/9
68 & 970 dt-25-3-2013.
No
161 PLN Village-Dantiwada
owner of Buffalow :
Rabari Hamirbhai
Zalabhai
FA(Buffalo) 7.02.13 Dantiwada PALANPUR-1
A buffallow of Rabari Hamirbhai Zalabhai of Vill-Dantiwada came in to Contact with loose Stay wire of
AB Swich(Loc No-86/10) of 11 KV Dantiwada JGY Feeder whose stay insulator broken & Stay wire
touch to live Jumper of said AB Switch, So 11 KV Line current passed through Stay wire to Buffallow
& electrocuted and met with Fatal Electrical Accident.
C.E.I report is awaited Maintenance work carried out 5000
162 PLN Lakhani
Kanbi Ambabhai
Ramabhai-38 years
old
FH O/S
20.08.12
(reporting date
22.03.13)
Lakhani Deesa-2
On dated 28-8-2012 at 1.00 PM victim got electrical accident due to tough his finger on the top of fuse
at the time of fitting the fuse on fuse board in his own premises(Ag connection electric room) & got
died on the spot at accident location.
C.E.I report is awaitedConsumer was educated to
install ELCB in his premises.No
163 SBT ChankhedaManish Muljibhai
Jadav, Age:25 YrsFH O/S 14.10.12 Chankheda Gandhinagar
A boradband cable(GTPL) was passing over the HT line (11 KV IOC feeder) but the distance between
high tension line and boradband cable was very less (it was just hanging over high tension line). So
when the boradband cable came in contact with HT line and at the time 11 KV supply was passed
through the broadband cable to the consumer premises.At that time victim came in contact with the
computer and got shocked.
C.E.I report is awaited
Instruction given to all line
staff to use safety tools and
tackles and disconnect power
supply before attend complain
to avoid accident
No
164 SBT Akru
Mr.Pravinbhai
Valabhai Katara,
Helper (v/s)
FH Dept 24.10.12 Dhandhuka Bavla
The victim was working on LT pole to rectify Lighting complain of Mr.Laljibhai Bhojabhai Mundhva and
while working, came in to the contact of live LT Line conductor and got electric shock & he fell down
on the ground from the pole and met with fatal accident
C.E.I report is awaitedNew stay and earthing
providedNo
165 SBT KERALA
owner -
Govindbhai
Dhunabhai
Bharvad
FA(Buffalo)
11.09.12 AT
10:00 AM
(Late reporting)
Bavla(ind) Bopal
Due to deteriorated and melted insulation of twin core service wire of single phase connection of shri
c.d.patel at nursery of forest deptt., phase-neutral wire get short ckted so leakage current passed
through neutral wire to earthing wire of t/c. A buffalo passing nearby t/c came in contact with leakage
current and got electrocuted.C.E.I report is awaited Maintenance work carried out No
166 SBT Uvarsad
FH to Shankarbhai
Prabhabhai
Marvadi Apprx,
Age:20 Yrs, Nfh to
Kishanbhai
Chatrabhai
Marvadi , Apprx,
Age:18 Yrs
FH & NFH O/S 23.11.12 Adalaj Gandhinagar
At the time of preparation of decorative gate at Karnavati Dental colledge, the victim , Kishanbhai C.
Marvadi touch with live conductor of 11 KV Preksha feeder and got electric shock and his right hand
burns and hospitalised. And other victim Shri Shankarbhai P. Marvadi standing for support of iron pole
also got electrucution and died. Distance from 11 kv line to ground is 17.9 mtr.
C.E.I report is awaited90% channel cable wire
removedNo
167 SBT Nana ChilodaAnil Sogaji Thakor
Age:-18yearsFH O/S 24.12.12 Chiloda-1 Gandhinagar
Truck (dumpher) which is fully filled up with send, driver park his dumper to unload the send exectaly
under the 11 kv aeronetic feeder live line, and also at the location 66 kv line is crossing over 11kv
aeronetic feeder. While victim try to stand up on the fully send filled dumper, he come in contact with
live 11kv aeronetic feeder wire and due to this electrical accident occured.
C.E.I report is awaited
Consumers were educated to
avoid direct or indirect contact
with the elecric line
No
168 SBT Giramtha
Owner -Buffalo of
Kokilaben B
Parmar
F A(Buffalo) 26.12.12 Bareja SabarmatiNeutral wire of single phase two wire LT line broken (due to deteritoted condition) in front of house of
Rajuhai and Kokilaben parmar and buffalo came in contact with live wire and got electrocuted.C.E.I report is awaited
periocally service wire at
consumer premises &
replaced it if required
No
169 SBT HarsoliBaldevbhai
Bhikhabhai rabariNFH O/S 15.01.13 , Dehgam-R Gandhinagar
On dt 15.01.13, late evening, victim was standing on terrace for flying kite .The 22 KV Vasna Rathod
JGY feeder is passing nearbt it.Victim came in contact with live conductor by operating some means
of object & got shocked
C.E.I report is awaited
Consumers were educated to
avoid direct or indirect contact
with the elecric line
No
170 SBT Kalol(East)
Shri
Mukundchandra
Tulsidas Rathod,
Helper VS
FH Dept 19.01.13 Kalol-1 Kalol
While climbing upon the pole for Disconnection of lighting connection ,he came in contact with iron
wire surround with TV channel,cable wire passing through this pole.on investigation it was found that
the return current came from faulty internal wiring of lighting connection of shri V.M. Chauhan & got
shocked.
C.E.I report is awaited
All the channel cable wires
are removed from UGVCL
network under Kalol
D.O.juridiction
No
171 SBT Moti Bhoyan
Shri Ajitsinh
Jasubhai
Darbar(Helper of K-
1 S/D)35 year
NFH Dept 31.01.13 Santej Kalol
The victim was working on the 11 kv Arvind Ind.feeder of Santej S/dn during mass maintenance
program.During this work victim came in contact with leakage current & met with NFH accident. The
leakege current passing through transformer of temporory connection of M/S Arvind LTD due to faulty
change over switch of D G Set of this connection.
C.E.I report is awaited
Approval of DG Set is carried
out as per letter
no.UGVCL/KLD/TECH/Acc/2
388dated 1.3.2013
No
172 SBT Thuleta
(1) Kanchanben
Prabhubhai K Patel
age 30 years (2)
Babo Prahubhai K
Patel age 3years
NFH O/S 5.2.13 Vgm-R SBTDue to Snapping of conductor(AB Cable) at village T/C Thuleta on victicms passing on road and get in
contact with live wireC.E.I report is awaited
LT AB CABLE work is
providedNo
173 SBT Vasna RathodLilaben
Lalsangbhai DamorFH O/S 22.2.13 Dehgam-R Gandhinagar
In the morning @9 to 9-30,the victim went on roof of kacha house to call her husband ,who was
working in the field of Prajapati Kodarbhai Jethabhai,The 22 kv line of Vatva feeder was passing from
the angle of the the rooftop,the victim came into contact with 22 kv conductor and
electrocuted.Victims got burns on left hand and body parts.
C.E.I report is awaited
party has applied for line
shifting & estimate paid &
work is also completed to
avoid the accident
No
174 SBT PansarShri Babubhai
Punjabhai RavarNFH O/S 12.03.13 Kalol-2 Kalol
Victim self climbed on village t/c structure & touched live conductor of D.o. unit & got electrocuted &
fell down ,met with nonfatal accident. C.E.I report is awaited
Consumers were educated to
avoid direct or indirect contact
with the elecric line
No
175 SBT Bhimtalav
Owner -Chauhan
Jerambhai
Talsibhai
FA(Buffalo) 20.03.13 Dhandhuka Bavla
Suddenly buffallo run and passed between DP centre so touched with stay wire. Due to snatching,
corrosive stay came out with neutral earth wire of T/C came out from ground which touched to
buffallo ,got electrocuted and died.
C.E.I report is awaitedMaintenance carried and
deteriorated LT wire replacedNo
176 SBT Dhendhu
Owner -Shri
Thakor Ranchhodji
Khodaji
FA ( Calf) 12.03.13 Nardipur KalolDue to unknown reason, hay stock lying under 11 KV line, got fired,due to heat & flame of said fire,A
calf tied near there,died. C.E.I report is awaited LT Cable provided No
Within 50% of
stipulated time
Within stipulated
time
Upto double the
stipulated time
More than double
the stipulated time
1 2 3 4 5 6 7 8 9 10
A(i) 85 179665 179750 96799 81128 201 1600 179728 22
A(ii) 1 32823 32824 18857 13808 133 26 32824 0
A(iii) 13 12789 12802 7732 4787 4 277 12800 2
B(i) 5 5587 5592 4212 1308 2 70 5592 0
B(ii) 2 4922 4924 2341 2574 0 9 4924 0
C(i) 0 14980 14980 9419 5545 8 8 14980 0
C(ii) 1 6367 6368 3933 2383 0 51 6367 1
D(i) 0 10753 10753 6785 3952 0 16 10753 0
D(ii) 0 2405 2405 1468 932 0 5 2405 0
E(i) 14 6745 6759 3183 3299 9 263 6754 5
E(ii) 0 3358 3358 2191 1096 0 68 3355 3
F(i) 0 1668 1668 993 667 0 8 1668 0
F(ii) 2 1668 1670 995 667 0 8 1670 0
F(iii) 1 2757 2758 2095 660 0 3 2758 0
F(iv) 0 7996 7996 4405 3582 0 9 7996 0
G 0 1660 1660 1037 612 0 11 1660 0
H 6 19320 19326 8362 10645 9 302 19318 8
Total 130 315463 315593 174807 137645 366 2734 315552 41
Complaints
received during
the Year
Total complaints
YEAR 2012-13 ( APRIL-12 TO MARCH-13)
Balance
complaints to be
redressed (4) - (9)
Uttar Gujarat Vij Company Ltd
Performa SoP 003 B:
APPENDIX - B
REGISTER FOR COMPILING THE COMPLAINTS CLASSIFICATIONWISE
In stipulated time Beyond stipulated time
No.of complaints redressed during the month
Total (5) to
(8)
Classification
Pending
complaintof
previous
Month
Sr. No.Actons or steps carried out by distribution licensee towards
public awareness in the quarter
Likely number of
consumers
influenced
Details about media
1 2 3
1 Display board of SOP at circle, Division & S/Dn 345898 Notice Board
2 Display board of Name of information officers under RTI Act 2005 at
Circle,Division,Sub- division offices. 199766 Notice Board
3Consumer care centers
334883Verbal & Notice Board
at CCC
4 Advertisement through Daily News papers 1801100 Daily News papers
5Pamphlets distributed among public
261399 Pamphlets
6Advertisement through slide in TV / Banners
92391 T V Channels
7 On Uttar Gujarat Vij Company Ltd Web site 210636 Internet
8 Through Regular Energy Bill 6646895 Energy Bill
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12 TO MARCH-13)
Performa SoP 004
Sr. No. MonthDate of meeting
conducted
No. of complaints
registered at the meeting
No. of complaints
pending at the end of
the meeting
10.04.2012 17 7
13.04.2012 9 2
17.04.2012 7 1
21.04.2012 8 4
15.05.2012 13 13
16.05.2012 9 9
29.05.2012 8 8
30.05.2012 8 8
14.06.2012 5 0
16.06.2012 13 4
28.06.2012 6 1
30.06.2012 4 1
10.07.2012 5 1
13.07.2012 2 0
24.07.2012 6 2
26.07.2012 2 0
09.08.2012 6 0
16.08.2012 13 2
23.08.2012 11 1
31.08.2012 7 1
11.09.2012 5 1
18.09.2012 9 0
25.09.2012 4 0
29.09.2012 4 0
10.10.2012 2 1
12.10.2012 2 0
03.11.2012 3 0
12.11.2012 2 0
22.11.2012 4 0
05.12.2012 3 1
11.12.2012 5 0
18.12.2012 4 1
31.12.2012 7 0
17.01.2013 3 0
24.01.2013 4 2
30.01.2013 6 2
16.02.2013 5 2
21.02.2013 4 1
26.02.2013 5 0
08.03.2013 9 2
22.03.2013 3 0
26.03.2013 8 3
NB.: Total Sittings in a Year - 42 Nos.
Uttar Gujarat Vij Company Ltd
YEAR 2012-13( APRIL-12 TO MARCH-13)
Performa SoP 005 B: Action taken report by the Redressal Committee
March'13
1 Apr-12
2 May'12
3 June'12
12
9
10
11
November'12
December'12
January'13
February'13
4
5
6
7
8
August'12
September'12
October'12
July'12
Sr.
No.Class
No. of existing Distribution
transformer at the start of the
quarter / year
01.04.2012
No.of Distribution
transformers added
during the quarter / year
(April-12 to March-13)
Tota number of
Distribution
transformers As on
30.03.2013
Total number of
Distribution
tranformer failed
(Three months)
% failure rate of
Distribution
transformer
A B C=A+B D H= (D) * 100/C
1 11KV 131983 16796 148779 10083 6.78
2 22KV 532 -141 391 130 33.25
143301 16655 149170 10213 6.85
Uttar Gujarat Vij Company Ltd
Performa SOP 006 : Failure of Distribution Transformer.
YEAR 2012-13( APRIL-12 TO MARCH-13)
Total
-1 -2 -3 -4 -5 -6
Sample Size % age compliance
(Numbers) (6) = (5)*100/(3)
LT consumers 2%
1 Domestic 757706 2% 10923 1.44
2 Commercial 83435 2% 374 0.45
3 Industrial 14609 2% 65 0.44
4 Agricultural 138717 2% 2492 1.80
5 Public water works 4501 2% 28 0.62
HT consumers
6 HT Industrial 504 2% 1 0.20
Uttar Gujarat Vij Company Ltd
YEAR 2012-13( APRIL-12 TO MARCH-13)
Performa SoP 008: Sample Test result for Neutral Voltage
Compliance Sample Test Report for Neutral Voltage
Sr. No Category of consumersStandard specified
in regulation
Deviation of results from
the sample test (Numbers)
1 2 3 4 5
% age compliance
% age compliance
(5) = (4)*100/(2)
Low Voltage 718073 +6% to -6% 2457 0.34
High Voltage 782 +6% to -9% 3 0.38
Extra High Voltage 9 +10% to -10% 0 0
Uttar Gujarat Vij Company Ltd
YEAR 2012-13( APRIL-12 TO MARCH-13)
Performa 09: Compliance Sample Test Report for voltage variations
Voltage LevelSample Size
(numbers)
Limit or
prescribed
standard
Deviation of results
from the sample test
(Numbers)
-1 -2 -3 -4 -5 -6
Limit or
standard
prescribed
Deviation
of results
from the
%age
compliance
(6) =
(5)*100/(3)
1 LT consumers 22542 3.50% 310 1.38
2 HT consumers 148 3.00% 3 2.03
3 EHT consumers 7 3.00% 0 0
Uttar Gujarat Vij Company Limted
Performa SoP 010: Sample Test result for Harmonics
Compliance Sample Test Report for Harmonics
Sr. NoCategory of
consumers
Sample
size
(Numbers)
YEAR 2012-13 ( APRIL-12 TO MARCH-13)
Sr.
NoMonth
Ni - Number of
Customers for each
sustained
interruptions (in
numbers)
NT - Total No of
customers served
(in Numbers)
CI = ∑ NiSAIFI = ∑Ni/Nt
(Monthly SAIFI)
1 2 3 4 5 6= 5 / 4
1 Apr-12 217540 352707 745134 2.11
2 May-12 232421 355907 784509 2.20
3 Jun-12 284242 354833 1772779 5.00
4 Jul-12 298263 360644 1763039 4.89
5 Aug-12 297879 363015 1651669 4.55
6 Sep-12 298072 363554 1633383 4.49
7 Oct-12 258438 363554 1097596 3.02
8 Nov-12 272976 363669 1099093 3.02
9 Dec-12 244862 366363 1008605 2.75
10 Jan-13 260722 366794 1037755 2.83
11 Feb-13 276197 368458 1069875 2.90
12 Mar-13 269415 369221 958278 2.60
Sr.
NoMonth
Ri =
Restoration Time for
each sustained
interruption event
(in hours)
Ni - Number of
interrupted
Customers for each
sustained
interruption event
(in numbers)
Ri* Ni -
Total customer
interrution Duration
NT - Total No of
customers served
(in Numbers)
Customer Intt.
Duration CMI =
∑Ri*Ni
SAIDI =
∑Ri*Ni/Nt
(Monthly
SAIDI)
1 2 3 4 5 = 3 * 4 6 7 8= 7 / 6
1 Apr-12 8332:10 217540 352707 1490225:54 4:13
2 May-12 8081:44 232421 355907 1487178:11 4:10
3 Jun-12 14285:12 284242 354833 2863150:57 8:04
4 Jul-12 16394:15 298263 360644 3258903:50 9:02
5 Aug-12 13966:55 297879 363015 2832593:17 7:48
6 Sep-12 14028:32 298072 363554 2498967:20 6:52
7 Oct-12 9443:07 258438 363554 1837560:39 5:03
8 Nov-12 9521:13 272976 363669 1876359:08 5:09
9 Dec-12 10718:53 244862 366363 2369787:09 6:28
10 Jan-13 9246:17 260722 366794 1938151:40 5:17
11 Feb-13 10642:54 276197 368458 2105518:59 5:42
12 Mar-13 12070:37 269415 369221 2209809:45 5:59
Sr.
NoMonth
IMi =
Number of
Momentary
interruptions for the
month
(in numbers)
Nmi =
Total no of
customers for each
momentary
interruptions
(in numbers)
Imi =Nmi
Number of customer
Mementary
interruptions
(in numbers)
Nt -
Total no of customers
served
(in numbers)
Customer Intt.
∑Imi*Nmi
MAIFI=
∑Imi*Nmi/
Nt
1 2 3 4 5 6 = 3 * 4 7 8= 7 / 6
1 Apr-12 7907 308548 352707 1328916 3.77
2 May-12 7481 300023 355907 1168681 3.28
3 Jun-12 10440 275132 354833 1733456 4.89
4 Jul-12 12059 327131 360644 2118454 5.87
5 Aug-12 12997 333478 363015 2122334 5.85
6 Sep-12 13017 338279 363554 2183824 6.01
7 Oct-12 9846 334852 363554 1587325 4.37
8 Nov-12 8150 333504 363669 1773439 4.88
9 Dec-12 7950 306888 366363 1422617 3.88
10 Jan-13 7412 321364 366794 1340693 3.66
11 Feb-13 7363 331658 368458 1380167 3.75
12 Mar-13 7711 339199 369221 1338108 3.62
Uttar Gujarat Vij Company Ltd YEAR 2012-13( APRIL-12 TO MARCH-13)
SoP 011 - A : System Average Interrruption Frequency Index (SAIFI) for AG. Dominant category
SoP 011 - B : System Average Interrruption Duration Index (SAIDI) for AG. Dominant category
SoP 011 - C : Momentary Average Interruption Frequency Index (MAIFI) for AG. Dominant category
Sr.
NoMonth
Ni - Number of
Customers for
each sustained
interruptions (in
numbers)
NT - Total No of
customers
served
(in Numbers)
CI = ∑ Ni
SAIFI =
∑Ni/Nt
(Monthly
SAIFI)
1 2 3 4 5 6= 5 / 4
1 Apr-12 1250303 1651263 3051239 1.85
2 May-12 1275762 1651155 2683933 1.63
3 Jun-12 1530394 1654296 7126866 4.31
4 Jul-12 1474263 1652334 7701226 4.66
5 Aug-12 1417874 1653528 5865305 3.55
6 Sep-12 1452872 1660899 6476368 3.90
7 Oct-12 1267508 1660899 3933156 2.37
8 Nov-12 1120129 1663951 3235577 1.94
9 Dec-12 1084425 1664564 2662340 1.60
10 Jan-13 1263962 1665235 6258057 3.76
11 Feb-13 1310246 1667422 3889687 2.33
12 Mar-13 1171242 1668144 4955938 2.97
Sr.
NoMonth
Ri =
Restoration Time
for each
sustained
interruption
event
(in hours)
Ni - Number of
interrupted
Customers for
each sustained
interruption
event
(in numbers)
Ri* Ni -
Total customer
interrution
Duration
NT - Total
No of
customers
served
(in
Numbers)
Customer Intt.
Duration CMI =
∑Ri*Ni
SAIDI =
∑Ri*Ni/Nt
(Monthly
SAIDI)
1 2 3 4 5 = 3 * 4 6 7 8= 7 / 6
1 Apr-12 2653:29 1250303 1651263 6669620:53 4:02
2 May-12 2066:03 1275762 1651155 3862046:39 2:20
3 Jun-12 3768:39 1530394 1654296 10116321:14 6:06
4 Jul-12 3604:03 1474263 1652334 9445183:41 5:42
5 Aug-12 4282:02 1417874 1653528 5399164:00 3:15
6 Sep-12 2673:44 1452872 1660899 6957669:29 4:11
7 Oct-12 2420:23 1267508 1660899 6053698:31 3:38
8 Nov-12 1727:37 1120129 1663951 4095261:06 2:27
9 Dec-12 1503:29 1084425 1664564 3346737:16 2:00
10 Jan-13 2395:45 1263962 1665235 8527953:54 5:07
11 Feb-13 2526:27 1310246 1667422 6173072:05 3:42
12 Mar-13 1741:14 1171242 1668144 7972718:47 4:46
Sr.
NoMonth
IMi =
Number of
Momentary
interruptions for
the month
(in numbers)
Nmi =
Total no of
customers for
each
momentary
interruptions
(in numbers)
Imi =Nmi
Number of
customer
Mementary
interruptions
(in numbers)
Nt -
Total no of
customers
served
(in
numbers)
Customer Intt.
∑Imi*Nmi
MAIFI=
∑Imi*Nmi/
Nt
1 2 3 4 5 6 = 3 * 4 7 8= 7 / 6
1 Apr-12 4764 1657207 1651263 13594535 8.23
2 May-12 4309 1616072 1651155 11499334 6.96
3 Jun-12 5519 1637028 1654296 14119115 8.53
4 Jul-12 5683 1635484 1652334 14553114 8.81
5 Aug-12 5487 1629703 1653528 14265783 8.63
6 Sep-12 5526 1646752 1660899 14728104 8.87
7 Oct-12 6214 1626925 1660899 11956102 7.20
8 Nov-12 3694 1625316 1663951 10852188 6.52
9 Dec-12 3690 1551209 1664564 9930602 5.97
10 Jan-13 3780 1605885 1665235 10384037 6.24
11 Feb-13 3611 1584400 1667422 9994886 5.99
12 Mar-13 3565 1608686 1668144 9631916 5.77
Uttar Gujarat Vij Company Ltd YEAR 2012-13( APRIL-12 TO MARCH-13)
SoP 011 - A : System Average Interrruption Frequency Index (SAIFI) for JGY category
SoP 011 - B : System Average Interrruption Duration Index (SAIDI) for JGY category
SoP 011 - C : Momentary Average Interruption Frequency Index (MAIFI) for JGY category
Sr.
NoMonth
Ni - Number of
Customers for each
sustained
interruptions (in
numbers)
NT - Total No of
customers served
(in Numbers)
CI = ∑ NiSAIFI = ∑Ni/Nt
(Monthly SAIFI)
1 2 3 4 5 6= 5 / 4
1 Apr-12 528168 720403 1497481 2.08
2 May-12 646169 722613 1828019 2.53
3 Jun-12 684794 722264 3106066 4.30
4 Jul-12 660008 724201 2941149 4.06
5 Aug-12 623299 767959 2432841 3.17
6 Sep-12 575319 769011 2588769 3.37
7 Oct-12 582954 769011 1722098 2.24
8 Nov-12 451821 769011 1377466 1.79
9 Dec-12 468523 770957 1272703 1.65
10 Jan-13 615667 569501 2071001 3.64
11 Feb-13 571040 799948 1878755 2.35
12 Mar-13 475158 811179 1649380 2.03
Sr.
NoMonth
Ri =
Restoration Time for
each sustained
interruption event
(in hours)
Ni - Number of
interrupted Customers
for each sustained
interruption event
(in numbers)
Ri* Ni -
Total customer
interrution
Duration
NT - Total No of
customers
served
(in Numbers)
Customer Intt.
Duration CMI =
∑Ri*Ni
SAIDI =
∑Ri*Ni/Nt
(Monthly
SAIDI)
1 2 3 4 5 = 3 * 4 6 7 8= 7 / 6
1 Apr-12 1461:54 528168 720403 1955934:20 2:42
2 May-12 2472:50 646169 722613 3503654:51 4:50
3 Jun-12 2652:07 684794 722264 3520167:44 4:52
4 Jul-12 2771:51 660008 724201 2420496:34 3:20
5 Aug-12 1566:35 623299 767959 1983908:46 2:35
6 Sep-12 2122:10 575319 769011 2193741:47 2:51
7 Oct-12 1952:17 582954 769011 2366889:20 3:04
8 Nov-12 1292:49 451821 769011 1554239:34 2:01
9 Dec-12 1195:48 468523 770957 1054347:51 1:22
10 Jan-13 2260:36 615667 569501 2800236:22 4:55
11 Feb-13 1910:55 571040 799948 2303157:45 2:52
12 Mar-13 1459:36 475158 811179 1726028:01 2:07
Sr.
NoMonth
IMi =
Number of Momentary
interruptions for the
month
(in numbers)
Nmi =
Total no of customers
for each momentary
interruptions
(in numbers)
Imi =Nmi
Number of
customer
Mementary
interruptions
(in numbers)
Nt -
Total no of
customers
served
(in numbers)
Customer Intt.
∑Imi*Nmi
MAIFI=
∑Imi*Nmi/
Nt
1 2 3 4 5 6 = 3 * 4 7 8= 7 / 6
1 Apr-12 1607 702458 720403 3509677 4.87
2 May-12 1410 710524 722613 3120062 4.32
3 Jun-12 1988 730883 722264 4210166 5.83
4 Jul-12 1762 698703 724201 3424372 4.73
5 Aug-12 1834 709168 767959 3141341 4.09
6 Sep-12 1892 684507 769011 3423996 4.45
7 Oct-12 1558 674398 769011 2972238 3.87
8 Nov-12 1335 669610 769011 2380603 3.10
9 Dec-12 1452 661950 770957 2970519 3.85
10 Jan-13 1577 691753 569501 2184817 3.84
11 Feb-13 1341 726677 799948 2806699 3.51
12 Mar-13 1327 694615 811179 2352300 2.90
JGY was repeated in component of MAIFI figure earlier.
Uttar Gujarat Vij Company Ltd
YEAR 2012-13 ( APRIL-12 TO MARCH-13)
SoP 011 - A : System Average Interrruption Frequency Index (SAIFI) for Other than AG & JGY
SoP 011 - B : System Average Interrruption Duration Index (SAIDI) forOther than AG & JGY category
SoP 011 - C : Momentary Average Interruption Frequency Index (MAIFI) for Other than AG & JGY
Sr.
NoMonth
Ni - Number of
Customers for
each sustained
interruptions (in
numbers)
NT - Total No of
customers
served
(in Numbers)
CI = ∑ Ni
SAIFI =
∑Ni/Nt
(Monthly
SAIFI)
1 2 3 4 5 6= 5 / 4
1 Apr-12 1996011 2765956 5293854 1.91
2 May-12 2154352 2771258 5296461 1.91
3 Jun-12 2499430 2772976 12005711 4.33
4 Jul-12 2432534 2778762 12405414 4.46
5 Aug-12 2239052 2784502 9949815 3.57
6 Sep-12 2326063 2793464 10698520 3.83
7 Oct-12 2108900 2793464 6752850 2.42
8 Nov-12 1844926 2796631 5712136 2.04
9 Dec-12 1797810 2801884 4943648 1.76
10 Jan-13 2140351 2832038 9366813 3.31
11 Feb-13 2157483 2835828 6838317 2.41
12 Mar-13 1915815 2847822 7563596 2.66
Sr.
NoMonth
Ri =
Restoration Time
for each
sustained
interruption
event
(in hours)
Ni - Number of
interrupted
Customers for
each sustained
interruption
event
(in numbers)
Ri* Ni -
Total customer
interrution Duration
NT - Total
No of
customers
served
(in
Numbers)
Customer Intt.
Duration CMI =
∑Ri*Ni
SAIDI =
∑Ri*Ni/Nt
(Monthly
SAIDI)
1 2 3 4 5 = 3 * 4 6 7 8= 7 / 6
1 Apr-12 12447:34 1996011 2765956 10115781:08 3:39
2 May-12 12620:38 2154352 2771258 8852879:42 3:11
3 Jun-12 20705:59 2499430 2772976 16499639:56 5:57
4 Jul-12 22770:10 2432534 2778762 15124584:06 5:26
5 Aug-12 19815:33 2239052 2784502 10215666:04 3:40
6 Sep-12 18824:27 2326063 2793464 11650378:37 4:10
7 Oct-12 13815:48 2108900 2793464 10258148:31 3:40
8 Nov-12 12541:39 1844926 2796631 7525859:48 2:41
9 Dec-12 13418:10 1797810 2801884 6770872:17 2:25
10 Jan-13 13902:39 2140351 2832038 13266341:56 4:41
11 Feb-13 15080:16 2157483 2835828 10581748:50 3:43
12 Mar-13 15271:28 1915815 2847822 11908556:34 4:10
Sr.
NoMonth
IMi =
Number of
Momentary
interruptions for
the month
(in numbers)
Nmi =
Total no of
customers for
each momentary
interruptions
(in numbers)
Imi =Nmi
Number of customer
Mementary
interruptions
(in numbers)
Nt -
Total no of
customers
served
(in
numbers)
Customer Intt.
∑Imi*Nmi
MAIFI=
∑Imi*Nmi/
Nt
1 2 3 4 5 6 = 3 * 4 7 8= 7 / 6
1 Apr-12 14278 2668213 2765956 18433128 6.662 May-12 13246 2626619 2771258 15788077 5.703 Jun-12 18024 2683329 2772976 20062737 7.244 Jul-12 19584 2661318 2778762 20095940 7.235 Aug-12 20343 2672349 2784502 19529458 7.016 Sep-12 20435 2669538 2793464 20335924 7.287 Oct-12 16067 2636175 2793464 16515665 5.918 Nov-12 13179 2628430 2796631 15006230 5.379 Dec-12 13092 2520047 2801884 14323738 5.11
10 Jan-13 12769 2619002 2832038 13909547 4.9111 Feb-13 12315 2642735 2835828 14181752 5.0012 Mar-13 12603 2642500 2847822 13322324 4.68
Uttar Gujarat Vij Company Ltd YEAR 2012-13( APRIL-12 TO MARCH-13)
SoP 011 - B : System Average Interrruption Duration Index (SAIDI) for UGVCL as a whole
SoP 011 - A : System Average Interrruption Frequency Index (SAIFI) for UGVCL as a whole
SoP 011 - C : Momentary Average Interruption Frequency Index (MAIFI) for UGVCL as a whole
1
iEnergy Delivered into EHT / 11 KV and LT Distribution
System from EHT / 11 KV SS (Mus)A 17863.21
ii Energy Sold (Billed) EHT direct sales (Mus) B 1199.16
iii Energy Sold (Billed) in the 11 KV LT system (Mus) C 14150.46
iv Total Sales (Mus) (B+C) 15349.62
v Losses (Mus) {(A) - (B+C)} 2513.59
vi % Losses {(A) - (B+C)} X 100 / (A) 14.07
Uttar Gujarat Vij Company Ltd ,Mehsana
QUARTER :-Yearly April-12 to March-13
YEAR :-2012-13
Performance SoP 012 - System Losses at EHT / 11 KV and below
SoP 012 - CALCULATION OF SYSTEM LOSSES AT EHT / 11 KV
Losses in 11 KV System and Connected Equipment
Consumer
Category
No. of faulty meters
at the start of the
quarter / year
No. of faulty
meters added
during the quarter
/ year
Total No. of
defective / faulty
meter
No. of faulty Meters
repaired and
replaced
No. of faulty meters
pending at the end
of the quarter/year
1 2 3=2+1 4 5=3-4
Single Phase 4739 58323 63062 62108 954
Three Phase 12 7314 7326 7293 33
H.T. 0 43 43 43 0
Uttar Gujarat Vij Company Ltd
Performa SOP 013 : Meter faults
YEAR 2012-13( APRIL-12 TO MARCH-13)
Qtr. MonthsUnits input
(Mus)
Units Billed
(Mus)
Billing
Efficiency
Revenue
Billed
(Rs. Crore)
Revenue
Collected (Rs.
Crore)**
Collection
Efficiency % *
Business
EfficiencyATC Loss %
A B C=(B/A)*100 D E F=(E/D)*100 G=(C*F)/100 H=100-G
April'12 1559 1222 78.396 481 506 100.00 78.40 21.60
May'12 1588 1235 77.730 454 421 92.65 72.02 27.98
June'12 1392 1259 90.504 527 566 100.00 90.50 9.50
Sub Total 4539 3716 81.875 1461 1492 100.00 81.87 18.13
July'12 1297 1053 81.245 453 446 98.60 80.11 19.89
Aug.'12 1217.55 1047 85.988 493 454 92.05 79.15 20.85
Sept.'12 1045.38 1019 97.454 450 545 100.00 97.45 2.55
Sub Total 3560 3119.17 87.627 1396 1445 100.00 87.63 12.37
Oct.'12 1628.415 1359.79 83.504 485 487 100.00 83.50 16.50
Nov.'12 1539.955 1388.32 90.153 417 486 100.00 90.15 9.85
Dec.'12 1693.835 1396.84 82.466 468 520 100.00 82.47 17.53
Sub Total 4862.205 4144.94 85.248 1370 1492 100.00 85.25 14.75
Jan'13 1662.038 1453.53 87.455 423 405 95.88 83.85 16.15
Feb'13 1511.995 1462.78 96.745 478 559 100.00 96.75 3.25
Mar.'13 1727.466 1453.20 84.123 486 549 100.00 84.12 15.88
Sub Total 4901.499 4369.51 89.146 1387 1513 100.00 89.15 10.85
V Grand Total 17861.91 15349.63 85.935 5614 5942 100.00 85.93 14.07
*
**
III
IV
The details are provisional. Revenue collection is as per window collection.
Uttar Gujarat Vij Company Ltd ,MehsanaQUARTER :-Yearly April-12 to March-13
YEAR :-2012-13
Performa SoP 014: Statement Showing the ATC losses, collection efficiency and Billing Efficiency
I
II
Collection efficiency above 100% is taken as 100%
Consumer Category
Total No. of
consumers
connected As on
March-13
Total New
application
received at the
end of the quarter
/ year
No. of release of
connections in the
quarter / year
No. of pending applications for
release of new connections in
the quarter / year Paid & Pending
Domestic 2298488 57535 51353 512
GLP 19209 8463 380 33
NGRP & LTMD 267930 7053 12399 221
Agriculture (Total) 245079 90874 5515 1363
Industrial HT 2511 228 275 33
Uttar Gujarat Vij Company Ltd ,Mehsana
Performa SOP 015 : Release of New connection : Status as on 31.03.13
YEAR 2012-13( APRIL-12 TO MARCH-13)
Sr. No. Event Compensation
No. of cases where
compensation was given
(in numbers)
Amt.of compensation paid
(in Rs.)
Duty to provide supply
a) New connection
b) Additional load
c) Temporary supply
d) Shifting service
connection
e) Transfer of service
connection
f) Change in tariff category
of consumer
2 Complaints in billing Rs.50 for non reply within
the period prescribed in
Regulations
3 Replacement of metersLT Rs.25 per day of delay
maximum Rs.2,500 and HT
Rs. 250 per day of delay
maximum of Rs. 5,000/-
4 Interruption of supply LT Rs.25 for every 6 hrs. of
delay maximum of Rs.500
and HT Rs. 50 for every 6
hrs. delay maximum Rs.
1000
5 Voltage fluctuations and
complaintsRs.50 for failure to visit or
convey findings wihin the
stipulated period
6 Responding to consumers
complaints
Rs. 25 for each day of delay
maximum Rs. 500
7 Grievance Handling Rs. 25 for failure in handling
grievance.
TOTAL :- …NIL… ……NIL…..
Rs.50 per day of delay from
the limit specified in the
performance regulations
1
Uttar Gujarat Vij Company Ltd ,Mehsana
Performa SoP 016 : Compensation details
COMPENSATION DETAILS
YEAR 2012-13( APRIL-12 TO MARCH-13)