Noise Analysis PPM Top Notch Wind Farm - Amazon S3 Analysis PPM Top Notch Wind Farm TO: Top Notch...
-
Upload
vuongtuyen -
Category
Documents
-
view
220 -
download
0
Transcript of Noise Analysis PPM Top Notch Wind Farm - Amazon S3 Analysis PPM Top Notch Wind Farm TO: Top Notch...
M E M O R A N D U M
Noise Analysis PPM Top Notch Wind Farm TO: Top Notch Project Team
FROM: Mark Bastasch/CH2M HILL
DATE: April 24, 2006
Summary This memorandum provides a baseline noise assessment for the proposed Top Notch Wind Power Facility (the Facility). Atlantic Wind, LLC proposes to construct a wind generation facility in Herkimer County, New York, with generating capacity of up to approximately 100 megawatts (MW). The facilities noise levels were compared to the local noise requirements and New York State noise guidelines.
The facilities noise levels are predicted to comply with the Town of Fairfield’s Wind Energy Facilities Ordinance limit of 50 dBA at non-participating land owners. In fact, the facility is predicted to comply with the 50 dBA limit at all residences, both participating and non-participating. The New York State Department of Environmental Conservation (NY DEC) published guidance “Assessing and Mitigating Noise Impacts” suggest that “new noise sources should probably not increase the noise level by more than 6 dBA”. The facilities noise level is predicted not to exceed the existing levels by 6 dBA under low wind speeds. Under wind speeds that result in full power generation, the facilities noise level is predicted to exceed existing levels by up to 8 dBA at 10 non-participating landowners, but maintains compliance with the Town of Fairfield’s Wind Energy Facilities Ordinance limit of 50 dBA.
Fundamentals of Acoustics It is useful to understand how noise is defined and measured. Noise is defined as unwanted sound. Airborne sound is a rapid fluctuation of air pressure above and below atmospheric pressure. There are several ways to measure noise, depending on the source of the noise, the receiver, and the reason for the noise measurement. Table 1 summarizes the technical noise terms used in this memo.
TABLE 1 Definitions of Acoustical Terms
Term Definitions
Ambient noise level The composite of noise from all sources near and far. The normal or existing level of environmental noise at a given location.
Decibel (dB) A unit describing the amplitude of sound, equal to 20 times the logarithm to the base 10 of the ratio of the measured pressure to the reference pressure, which is 20 micropascals.
A-weighted sound pressure level (dBA)
The sound pressure level in decibels as measured on a sound level meter using the A-weighted filter network. The A-weighted filter de-emphasizes the very low and very high frequency components of the sound in a manner similar to the frequency response of the human ear and correlates well with subjective reactions to noise. All sound levels in this report are A-weighted.
1
TABLE 1 Definitions of Acoustical Terms
Term Definitions
Equivalent Sound Level (Leq)
The Leq integrates fluctuating sound levels over a period of time to express them as a steady state sound level. As an example, if two sounds are measured and one sound has twice the energy but lasts half as long, the two sounds would be characterized as having the same equivalent sound level. Equivalent Sound Level is considered to be directly related to the effects of sound on people since it expresses the equivalent magnitude of the sound as a function of frequency of occurrence and time.
Day–Night Level (Ldn or DNL)
The Day-Night level (Ldn or DNL) is a 24 hour average Leq where 10 dBA is added to nighttime levels between 10 pm and 7 am. For a continuous source that emits the same noise level over a 24 hour period, the Ldn will be 6.4 dB greater than the Leq.
Statistical noise level (Ln)
The noise level exceeded during n percent of the measurement period, where n is a number between 0 and 100 (for example, L50 is the level exceeded 50 percent of the time)
Table 2 shows the relative A-weighted noise levels of common sounds measured in the environment and in industry for various sound levels.
TABLE 2 Typical Sound Levels Measured in the Environment and Industry
Noise Source At a Given Distance
A-Weighted Sound Level in Decibels
Qualitative Description
Carrier Deck Jet Operation 140
130 Pain threshold
Jet takeoff (200 feet) 120
Auto Horn (3 feet) 110 Maximum Vocal Effort
Jet takeoff (2000 feet) Shout (0.5 feet)
100
N.Y. Subway Station Heavy Truck (50 feet)
90 Very Annoying Hearing Damage (8 hr continuous exposure)
Pneumatic drill (50 feet) 80 Annoying
Freight Train (50 feet) Freeway Traffic (50 feet)
70 Intrusive Telephone Use Difficult
Air Conditioning Unit (20 feet) 60
Light auto traffic (50 feet) 50 Quiet
Living Room Bedroom
40
Library Soft whisper (5 feet)
30 Very Quiet
Broadcasting Studio 20 Recording studio
10 Just Audible
Adapted from Table E, “Assessing and Mitigating Noise Impacts”, NY DEC, February, 2001.
2
It is also useful to understand the difference between a sound pressure level (or noise level) and a sound power level. A sound power level (commonly abbreviated as PWL or Lw) is analogous to the wattage of a light bulb; it is a measure of the acoustical energy emitted by the source and is therefore independent of distance. A sound pressure level (commonly abbreviated as SPL or Lp) is analogous to the brightness or intensity of light experienced at a specific distance from a source and is measured directly with a sound level meter. Sound pressure levels should always be specified with a location or distance from the noise source.
Sound power level data is used in acoustic models to predict sound pressure levels. This is because sound power levels take into account the size of the acoustical source and account for the total acoustical energy emitted by the source. For example, the sound pressure level 15 feet from a small radio and a large orchestra may be the same, but the sound power level of the orchestra will be much larger because it emits sound over a much larger area. Similarly, a 2-hp and 2,000-hp pumps can both achieve 85 dBA at 3 feet (a common specification) but the 2,000-hp pump will have significantly larger sound power level. Consequently the noise from the 2,000-hp pump will travel farther. A sound power level can be determined from a sound pressure level if the distance from and dimensions of the source are known. Sound power levels will always be greater than sound pressure levels and sound power levels should never be compared to sound pressure levels such as those in Table 2. The sound power level of a wind turbine will typically vary between 100 and 110 dBA, this will result in a sound pressure level of about 55 to 65 dBA at 130 feet (similar in level to a normal conversation).
Existing Land Use All Facility components will be located on private land on which the Applicants have negotiated long-term wind energy leases with the landowners. The majority of the area consists of open crop fields (primarily hay and corn) and pastures, with forested areas generally confined to small woodlots and slopes that descend into adjacent valleys. A few areas of relatively large, contiguous forest tracks exist. In the area where the Facility will be located, scattered residences exist.
Significance Thresholds The New York State Department of Environmental Conservation (NY DEC) published guidance “Assessing and Mitigating Noise Impacts” (NY DEC, 2001) is the basis used to assess the Facilities potential for noise impacts. This guidance does not provide quantitative noise limits but its key recommendations are briefly summarized below:
• New noise sources should not increase noise level above 65 dBA in non-industrial areas.
• EPA found that 55 Ldn was sufficient to protect public health and welfare, and in most cases did not create an annoyance. (55 Ldn is equal to a continuous level of 49 dBA)
• New noise sources should probably not increase the noise level by more than 6 dBA. An increase of 6 dBA may result in complaints, although there may be occasions where increases of 6 dBA might be acceptable.
• In determining the potential for an adverse noise impact, consider not only ambient noise levels, but also the existing land use, and whether or not an increased noise level or the introduction of a discernable sound that is out of character with existing sounds will be considered annoying or obtrusive.
3
• Any unavoidable adverse effects must be weighed along with other social and economic consideration in deciding whether to approve or deny a permit.
In addition to the NY DEC guidelines, the Town of Fairfield’s Wind Energy Facilities Ordinance (January 23, 2006) states the following : “The Applicant shall provide documentation that the maximum noise level generated by wind power facilities shall not exceed 50 dBA, as measured at the closest residence owned by a non-participating landowner. A non-participating landowner can waive this requirement by a written recordable agreement with the applicant, which shall further require a resolution of the Town Planning Board consenting to such waiver.”
Table 3 summarizes the significance thresholds established for this analysis. Two types of thresholds are established, absolute and relative. Absolute limits are limits on project generated noise that should not be exceeded. Relative limits are limits on the increase in noise resulting from the project. Because a project participant becomes one willingly and derives benefit from the project, significance thresholds for participants allow higher noise levels.
TABLE 3 Summary of Significance Thresholds
Participating Landowner Non-Participating Landowner
Absolute Threshold (Leq) 55 dBA 50 dBA
Relative Threshold (Leq) None 6 dBA1
Notes: 1. Resulting noise level must exceed 35 dBA to be considered potentially significant increase.
For a conventional power plant or industrial facility, the increase in noise resulting from the projects would be evaluated under calm wind conditions when ambient noise levels are low. Because a wind turbine needs wind to operate, evaluating increases in noise under calm conditions, when noise levels are lowest, is inappropriate. The speed at which the wind turbine starts to operate and generate power is called the cut-in wind speed. The speed at which the wind turbine generates the maximum noise level can be referred to as the full power wind speed.
The NY DEC guidance document states that “For estimation purposes, ambient SPL’s (sound pressure levels) will vary from approximately 35 dBA in a wilderness area to approximately 87 dBA in a highly industrial setting. A quiet seeming serene setting such as rural farm land will be at the lower end of the scale at about 45 dBA”. Although the NY DEC guidance does not specify, the EPA reference cited states that these levels are in terms of Day-Night sound level (Ldn). The equivalent (Leq) average steady state noise level, what one would hear or measure with a sound level meter would be approximately 6 dB less than the Ldn. That is, a steady noise of 39 dBA would result in a Day-Night level (Ldn) of 45 dBA. Figures 1 and 2 provide examples of outdoor Day-Night sound levels (Ldn) provided in the EPA documents referenced by the NY DEC.
4
FIGURE 1 Examples of Outdoor Day-Night Sound Levels (Ldn dBA)
FIGURE 2 Additional Examples of Outdoor Day-Night Sound Levels (Ldn dBA)
5
For the purposes of this impact assessment, the existing average sound pressure level is assumed to be 35 dBA Leq at wind speeds corresponding to above cut-in conditions and 41 dBA Leq at wind speeds corresponding to full power. This results in relative significance thresholds of 41 dBA under cut-in conditions and 47 dBA under full power conditions at non-participating residences. As shown in Table 4, these relative thresholds are more restrictive than the 50 dBA limit established in the Town of Fairfield’s Wind Energy Ordinance.
TABLE 4 Thresholds of Potential Significance
Participating Landowner Non-Participating Landowner
Absolute Threshold (Leq) 55 dBA 50 dBA
Relative Threshold (Leq)
Low Windspeeds (above cut-in)
55 dBA 41 dBA
High Windspeeds (full power)
55 dBA 47 dBA
Facility Sound Levels Standard acoustical engineering methods were used in the noise analysis. The noise model, CADNA/A by DataKustik GmbH of Munich, Germany, is a sophisticated software program that facilitates noise modeling of complex projects. The sound propagation factors used in the model have been adopted from ISO 9613 (ISO, 1993) and VDI 2714 (VDI, 1988). Atmospheric absorption for conditions of 10°C and 70 percent relative humidity (conditions that favor propagation) was computed in accordance with ISO 9613-1, Calculation of the Absorption of Sound by the Atmosphere.
Each wind turbine was considered to be a point source of noise at the hub height with an overall sound power level of 100 dBA under cut-in conditions or 106 dBA under full power conditions. The full power conditions corresponds to the guaranteed maximum noise level generated by the turbines as measured in accordance with IEC61400-11 (the turbine noise level would be less at lower windspeeds). Transformers are expected to have a National Electrical Manufacturers Association (NEMA) sound rating of 87 dBA. The transmission line is 115-kilovolt (kV) therefore audible corona noise is anticipated to be negligible (corona noise is generally associated with voltages exceeding 345 kV).
All turbines and substations were assumed to be operating at the sound power levels shown in Table 5.
6
TABLE 5 Modeled Octave Band Sound Power Levels
Octave Band Center Frequency, Hz (A-weighted)
Overall (dBA) 63 125 250 500 1,000 2,000 4,000 8,000
GE 1.5-MW Turbine (Full Power – Hub height winds of 20 mph)
106 87 96 99 101 100 97 89 80
GE 1.5-MW Turbine (Hub height winds of 11 mph)
97 78 87 90 92 91 88 80 71
Substation Transformers 107 84 96 98 104 101 97 92 83
Figure 3 presents the predicted project levels under full power conditions. Because full power conditions represent the loudest project levels, Table 6 compares the predicted project noise levels to the absolute noise limits under these conditions. No residences are predicted to exceed the Town of Fairfield’s limit of 50 dBA, even at participating homes.
TABLE 6 Comparison of Predicted Project Noise Levels to Absolute Project Noise Limits
Map ID Participant Absolute Limit
(Leq dBA) Predicted Project Level
(Leq dBA) Exceed
Absolute Limit?
R164 Yes 50 48.8 No
R149 No 50 48.2 No
R147 No 50 48.1 No
R153 No 50 47.3 No
R138 No 50 47.1 No
R143 Yes 55 47.0 No
R150 Yes 55 46.8 No
R122 No 50 46.7 No
R142 No 50 46.6 No
R120 Yes 55 46.4 No
R184 No 50 46.3 No
R145 No 50 46.0 No
R183 No 50 46.0 No
R117 No 50 45.7 No
R105 Yes 55 45.6 No
R151 No 50 45.4 No
R154 No 50 45.3 No
R148 Yes 55 45.2 No
R155 No 50 45.2 No
R107 No 50 45.2 No
R169 Yes 55 45.2 No
R118 No 50 45.2 No
7
TABLE 6 Comparison of Predicted Project Noise Levels to Absolute Project Noise Limits
Map ID Participant Absolute Limit
(Leq dBA) Predicted Project Level
(Leq dBA) Exceed
Absolute Limit?
R125 Yes 55 45.0 No
R157 No 50 45.0 No
R185 No 50 44.7 No
Note: Refer to Figure 3 for predicted levels at more distant locations not included in this table. Noise levels are predicted to be less than 44.7 at locations not listed in this table.
Figure 4 presents the predicted project levels under low wind speeds. Table 7 evaluates increase over the existing level of 35 dBA when the hub height wind speed is approximately 11 mph. At all locations, the predicted existing plus project noise level is less than 41 dBA and the resulting increase is less than 6 dBA over the existing level of 35 dBA.
TABLE 7 Evaluation of Increase over Existing Noise Levels – Low Windspeeds
Map ID Participant Existing Level
(dBA) Predicted Project
Level (dBA) Existing plus Project (dBA)
Increase over Existing (dBA)
R164 Yes 35 39.1 40.5 5.5
R149 No 35 38.8 40.3 5.3
R147 No 35 38.8 40.3 5.3
R153 No 35 38.1 39.8 4.8
R138 No 35 38.1 39.8 4.8
R143 Yes 35 38 39.8 4.8
R150 Yes 35 37.8 39.6 4.6
R122 No 35 37.7 39.6 4.6
R142 No 35 37.6 39.5 4.5
R120 Yes 35 37.4 39.4 4.4
R184 No 35 37.2 39.2 4.2
R145 No 35 36.9 39.1 4.1
R183 No 35 36.9 39.1 4.1
R117 No 35 36.7 38.9 3.9
R105 Yes 35 36.6 38.9 3.9
R151 No 35 36.3 38.7 3.7
R154 No 35 36.2 38.7 3.7
R148 Yes 35 36.2 38.7 3.7
R155 No 35 36.2 38.7 3.7
R107 No 35 36.2 38.7 3.7
R169 Yes 35 36.2 38.7 3.7
R118 No 35 36.1 38.6 3.6
8
TABLE 7 Evaluation of Increase over Existing Noise Levels – Low Windspeeds
Map ID Participant Existing Level
(dBA) Predicted Project
Level (dBA) Existing plus Project (dBA)
Increase over Existing (dBA)
R125 Yes 35 36 38.5 3.5
R157 No 35 36 38.5 3.5
R185 No 35 35.7 38.4 3.4
Table 8 evaluates increase over the existing level of 41 dBA when the hub height wind speed is approximately 20 mph.
TABLE 8 Evaluation of Increase over Existing Noise Levels – High Windspeeds
Map ID Participant Existing Level
(dBA) Predicted Project
Level (dBA) Existing plus Project (dBA)
Increase over Existing (dBA)
R164 Yes 41 48.8 49.5 8.5 R149 No 41 48.2 49.0 8.0 R147 No 41 48.1 48.9 7.9 R153 No 41 47.3 48.2 7.2 R138 No 41 47.1 48.1 7.1 R143 Yes 41 47.0 48.0 7.0
R150 Yes 41 46.8 47.8 6.8
R122 No 41 46.7 47.7 6.7 R142 No 41 46.6 47.7 6.7 R120 Yes 41 46.4 47.5 6.5
R184 No 41 46.3 47.4 6.4 R145 No 41 46.0 47.2 6.2 R183 No 41 46.0 47.2 6.2 R117 No 41 45.7 47.0 6.0 R105 Yes 41 45.6 46.9 5.9
R151 No 41 45.4 46.7 5.7
R154 No 41 45.3 46.7 5.7
R148 Yes 41 45.2 46.6 5.6
R155 No 41 45.2 46.6 5.6
R107 No 41 45.2 46.6 5.6
R169 Yes 41 45.2 46.6 5.6
R118 No 41 45.2 46.6 5.6
R125 Yes 41 45.0 46.5 5.5
R157 No 41 45.0 46.5 5.5
R185 No 41 44.7 46.2 5.2
9
Construction Noise Impact Assessment The U.S. Environmental Protection Agency (EPA) Office of Noise Abatement and Control studied noise from individual pieces of construction equipment, as well as from construction sites for power plants and other types of facilities (see Table 9). Because specific information about types, quantities, and operating schedules of construction equipment is not known at this stage, data from the EPA document for industrial projects of similar size have been used. These data are conservative, because the evolution of construction equipment has generally been toward quieter design. Use of these data is reasonable for estimating noise levels, given that they are still widely used by acoustical professionals.
TABLE 9 Average Noise Levels from Common Construction at a Reference Distance of 50 feet (dBA)
Construction Equipment Typical Average Noise
Level at 50 ft, dBA
Air compressor 81
Backhoe 85
Concrete mixer 85
Concrete pump 82
Crane, mobile 83
Dozer 80
Generator 78
Grader 85
Loader 79
Paver 89
Pile driver 101
Pneumatic tool 85
Pump 76
Rock drill 98
Saw 78
Scraper 88
Shovel 82
Truck 91
Source: U.S. EPA, 1971.
Table 10 shows the total composite noise level at a reference distance of 50 feet, based on the pieces of equipment operating for each construction phase and the typical usage factor for each piece. The noise level at 1,500 feet is also shown. The calculated level at 1,500 feet is probably conservative, because the only attenuating mechanism considered was geometric spreading, which results in an attenuation rate of 6 dBA per doubling of distance; attenuation related to the presence of structures, trees or vegetation, ground effects, and terrain was not considered.
10
TABLE 10 Composite Construction Site Noise Levels
Construction Phase
Composite Equipment Noise Level at 50 feet, dBA
Composite Equipment Noise Level at 1,500 feet, dBA
Clearing 88 58
Excavation 90 60
Foundation 89 59
Erection 84 54
Finishing 89 59
Construction activities are anticipated to occur over a 8 month duration. The following Best Management Practices will be followed to reduce potential for annoyance from construction related activities:
• Establish a project telephone number that the public can use to report complaints.
• Ensure equipment is adequately maintained and equipped with manufacturers recommended muffler.
• Conduct noisiest activities during weekdays between the hours of 8 am and 5 pm. For unusually loud activities, such as blasting or pile driving, notify residence by mail or phone at least 1 week in advance.
• Locate stationary construction equipment (air compressors/generators) as far away from residences uses as feasible. When feasible, utilize equipment in acoustically designed enclosures and/or erect temporary barriers.
With the above mitigation measures, project construction activities will be minimized to the greatest extent reasonable. While they may still result in short term annoyance, they do not represent a significant adverse impact.
References Beranek, L.L. 1988. Acoustical Measurements. American Institute of Physics. Woodbury, New York.
CADNA/A Version 3.5. 2005. Datakustik, GmbH, Munich, Germany. August 2005. http://www.datakustik.de/frameset.php?lang=en
International Electrotechnical Commission (IEC) 61400-11. 2002. Wind Turbine Generator Systems—Part 11: Acoustic Noise Measurement Techniques. Geneva, Switzerland.
International Organization for Standardization (ISO). 1993. Acoustics—Sound Attenuation During Propagation Outdoors. Part 1: Calculation of the Absorption of Sound by the Atmosphere, 1993. Part 2: General Method of Calculation. ISO 9613. Switzerland.
U.S. Environmental Protection Agency (EPA). 1971. Noise from Construction Equipment and Operations, Building Equipment, and Home Appliances.
VDI. 1988. Outdoor Sound Propagation. VDI (Verein Deutscher Ingenieure) 2714, Verlag GmbH, Dussledorf, Beuth Verlag, Berlin, Koln, Germany.
11
45dBA
50dBA
35dBA
40dB
A
45dBA
50dB
A
35dB
A
40dBA
35dBA
40dBA
35dB
A
50dB
A
45dB
A
35dB
A
45dBA
45dB
A
40dB
A
50dB
A
50dBA
45dB
A
35dBA
50dB
A
45dB
A
35dB
A
50dBA
40dBA
40dB
A
40dB
A
R275
R257
R250
R265R260
R266
R259
R227
R002
R004
R261
R001
R273
R255
R274
R258
R239
R114R110
R008
R028
R015
R005R032
R026
R014
R251
R249
R228
R119
R010R016R013
R023R012
R246
R136
R242
R144
R019
R268R152
R240
R017
R029
R236
R220
R234R233
R264
R049
R231R232
R159
R022
R020
R230
R011
R018
R209
R226
R021
R156
R204
R165
R225R223
R222
R062
R070
R042
R167
R221
R201
R219
R199
R213
R202
R088
R181
R216
R200
R207R206
R203
R215
R256
R238
R131
R030
R121
R237
R034
R139
R135
R108
R036
R132
R196R194
R134
R041
R126
R113
R130
R043
R129
R243
R076
R235
R050
R133
R046
R128
R075
R127
R047
R191
R140
R056
R027
R074
R025
R253
R058
R269
R057
R061
R192
R064
R054R053
R063
R248R244
R189
R083
R066
R065
R052
R059
R067
R071
R031
R146
R080
R082
R081
R044
R178
R078
R077
R072
R124
R055
R084
R073
R180
R188
R195
R193
R051
R103
R089
R218
R039
R241
R115
R090
R160
R186
R168
R212
R229
R161
R187
R100
R190
R197
R112
R211
R085
R198
R101
R092
R141
R177
R170
R176R174
R106
R098
R104
R171R172
R254
R163
R097
R111
R252
R245
R166
R247
R175
R102
R173
R182R179
R162
R096
R093
R185
R157
R125
R118
R169
R107
R155
R154
R148
R151
R105
R117
R183
R145
R184
R120
R142
R122
R150
R153
R143
R138
R164
R147R149
29
170169
29
170
169
Military
Castle
Dairy Hill
Cole
Hard S
crabble
170a
Stahl
Davis
Platform
Parkhurst
Creek
Myers
Kelly
Snyder
Ryan
Teall
Burrell
Thompson
Beaver
Top Notch
Elm Tree
Sandy Lane
Reservoir
Satterlee
Peckville
Mexico
Mang
Comstock
Observatory
West End
Rath
Spruce
Rockwell
Bronner
Warren
Gould
Eatonville
No rway
Arnold
K ilts H
ill
New
port Gray
Yellow Church
Tucker
Cas ler
Frye
Delayton
Snyder
Burrell
Davis
CC ii tt yy BBrr oo oo kk
2,000 0 2,000 Feet
PPM EnergyTop Notch Wind Farm
Figure 3Full Power Conditions
Legend
Proposed Wind Turbine
Residence
Particpating Landowners
* 50 dBA - Town Limit for Non-Participating
File Path: \\rosa\proj\PPMEnergy\337822\GIS\mxds\Figure3_FullPower11x17.mxd, Date: April 25, 2006 10:15:02 AM
40dB
A
40dBA35dB
A
30dB
A
30dBA
30dB
A
30dB
A
30dBA
30dBA
35dB
A
40dBA
35dB
A
40dB
A
35dB
A
40dB
A
40dBA
35dBA
35dBA
35dB
A40
dBA
35dB
A
R275
R257
R250
R265R260
R266
R259
R227
R002
R004
R261
R001
R273
R255
R274
R258
R239
R114R110
R008
R028
R015
R005R032
R026
R014
R251
R249
R228
R119
R010R016R013
R023R012
R246
R136
R242
R144
R019
R268R152
R240
R017
R029
R236
R220
R234R233
R264
R049
R231R232
R159
R022
R020
R230
R011
R018
R209
R226
R021
R156
R204
R165
R225R223
R222
R062
R070
R042
R167
R221
R201
R219
R199
R213
R202
R088
R181
R216
R200
R207R206
R203
R215
R256
R238
R131
R030
R121
R237
R034
R139
R135
R108
R036
R132
R196R194
R134
R041
R126
R113
R130
R043
R129
R243
R076
R235
R050
R133
R046
R128
R075
R127
R047
R191
R140
R056
R027
R074
R025
R253
R058
R269
R057
R061
R192
R064
R054R053
R063
R248R244
R189
R083
R066
R065
R052
R059
R067
R071
R031
R146
R080
R082
R081
R044
R178
R078
R077
R072
R124
R055
R084
R073
R180
R188
R195
R193
R051
R103
R089
R218
R039
R241
R115
R090
R160
R186
R168
R212
R229
R161
R187
R100
R190
R197
R112
R211
R085
R198
R101
R092
R141
R177
R170
R176R174
R106
R098
R104
R171R172
R254
R163
R097
R111
R252
R245
R166
R247
R175
R102
R173
R182R179
R162
R096
R093
R185
R157
R125
R118
R169
R107
R155
R154
R148
R151
R105
R117
R183
R145
R184
R120
R142
R122
R150
R153
R143
R138
R164
R147R149
29
170169
29
170
169
Military
Castle
Dairy Hill
Cole
Hard S
crabble
170a
Stahl
Davis
Platform
Parkhurst
Creek
Myers
Kelly
Snyder
Ryan
Teall
Burrell
Thompson
Beaver
Top Notch
Elm Tree
Sandy Lane
Reservoir
Satterlee
Peckville
Mexico
Mang
Com
sto ck
Observatory
West End
Rath
Spruce
Rockwell
Bronner
Warren
Gould
Eatonville
No rway
Arnold
K ilts H
ill
New
port Gray
Yellow Church
Tucker
Cas ler
Frye
Delayton
Snyder
Burrell
Davis
CCii ttyy BBrr ooookk
2,000 0 2,000 Feet
PPM EnergyTop Notch Wind Farm
Figure 4Low Windspeed Conditions
Legend
Proposed Wind Turbine
Residence
Particpating Landowners
* 50 dBA - Town Limit for Non-Participating
File Path: \\rosa\proj\PPMEnergy\337822\GIS\mxds\Figure4_LowWind11x17.mxd, Date: April 25, 2006 10:48:05 AM