Option 1 Pump Head Calculation

2
FOR CHILLED WATER PUMP Straight Pipe Length (One Way) = 426 Meter Straight Pipe Length (Two Way) = 852 Meter = 2794 Feet Considering Friction Loss of 2.5 Ft/100 Ft), Total Pressure Drop in straight pipes shall be Total Pressure Drop in Straight Pipes = 2794 X2.5/100 = 70 Feet ---------------------- ----- (A) Total pressure drop in pipe fittings = 70 X25/100 = 17.5 Feet -------------------------- (B) Pressure Drop Across the valve is calculated as follows Valve Size ( MM) Quantity Equivalent length (FT) Total Length (FT) GV 300 2 13 26 strainer 300 2 250 500 DRV 300 2 165 330 MV 300 1 13 13 GV 600 1 25 25 DRV 600 1 320 320 Total Equivalent length = 1334 Feet Pressure Drop across valves considering friction loss of 2.5 Fe et/100 Feet Pressure Drop Across vales = 33 Feet ----------------------------(C) Pressure Drop across Chiller Evaporator = 24.5 Feet ------------------------ (D) Pressure Drop across Last A/C unit & Valves = 4 Feet --------------------------- (E) Total Pressure Drop = 149 Feet Considering 15 % Safety = 164 Feet = 50 Meter = 5.0 Bar Hence Chilled Water Pump capacity shall be 3210 GPM @ 5.0 Bar Head.

Transcript of Option 1 Pump Head Calculation

Page 1: Option 1 Pump Head Calculation

7/25/2019 Option 1 Pump Head Calculation

http://slidepdf.com/reader/full/option-1-pump-head-calculation 1/2

FOR CHILLED WATER PUMP

Straight Pipe Length (One Way) = 426 Meter

Straight Pipe Length (Two Way) = 852 Meter = 2794 Feet

Considering Friction Loss of 2.5 Ft/100 Ft), Total Pressure Drop in straight pipes shall be

Total Pressure Drop in Straight Pipes = 2794 X2.5/100 = 70 Feet --------------------------- (A)

Total pressure drop in pipe fittings = 70 X25/100 = 17.5 Feet --------------------------

(B)

Pressure Drop Across the valve is calculated as follows

Valve Size ( MM) Quantity Equivalent length (FT) Total Length (FT)

GV 300 2 13 26

strainer 300 2 250 500

DRV 300 2 165 330

MV 300 1 13 13GV 600 1 25 25

DRV 600 1 320 320

Total Equivalent length = 1334 Feet

Pressure Drop across valves considering friction loss of 2.5 Feet/100 Feet

Pressure Drop Across vales = 33 Feet ----------------------------(C)

Pressure Drop across Chiller Evaporator = 24.5 Feet ------------------------ (D)

Pressure Drop across Last A/C unit & Valves = 4 Feet --------------------------- (E)

Total Pressure Drop = 149 Feet

Considering 15 % Safety = 164 Feet

= 50 Meter

= 5.0 Bar

Hence Chilled Water Pump capacity shall be 3210 GPM @ 5.0 Bar Head.

Page 2: Option 1 Pump Head Calculation

7/25/2019 Option 1 Pump Head Calculation

http://slidepdf.com/reader/full/option-1-pump-head-calculation 2/2

FOR CONDENSATE WATER PUMP

Straight Pipe Length (One Way) = 204 Meter

Straight Pipe Length (Two Way) = 408 Meter = 1340 Feet

Considering Friction Loss of 2.5 Ft/100 Ft), Total Pressure Drop in straight pipes shall be

Total Pressure Drop in Straight Pipes = 1340 X2.5/100 = 33.50 Feet ----------------------- (A)

Total pressure drop in pipe fittings = 33.50 X25/100 = 0.85 Feet ------------------------- (B)

Total pressure drop (Against Gravity) = 4 Meter = 13 Feet ---------------------------(C)

Pressure Drop Across the valve is calculated as follows

Valve Size ( MM) Quantity Equivalent length (FT) Total Length (FT)

GV 450 3 19 57

strainer 450 2 350 700

DRV 450 3 240 720

MV 450 2 19 38

GV 750 1 34 34

DRV 750 1 400 400

Total Equivalent length = 1949 Feet

Pressure Drop across valves considering friction loss of 2.5 Feet/100 Feet

Pressure Drop Across vales = 49 Feet --------------------------- (D)

Pressure Drop across Chiller Condenser = 21.9 Feet ------------------------ (E)

Pressure Drop across cooling tower = 16 Feet --------------------------- (F)

Total Pressure Drop = 134 Feet

Considering 15 % Safety = 154 Feet

= 47 Meter

= 4.7 Bar

Hence Condensate Water Pump capacity shall be 6420 GPM @ 4.7 Bar Head.