TABLE OF CONTENTS

1 Statement of problem 2 Objective 3 Hardware Components Update4 Specifications of The Components 5 NeuTron Operating Voltage Update6 Proposal7 The cost

Page 3: Operating Voltage Update for Haris System

Statement of Problem

Haris system is currently operating on 12 VDC. According to Aramco standards SAES-J-902 and SAES-J-505, all DC instruments should be operating at 24VDC

Page 4: Operating Voltage Update for Haris System

Objective

To make Haris system operate at 24VDC. This includes the power delivery devices such as the Solar panel, Solar regulator, battery and voltage regulator and all instrumentation. The total cost of the system should not increase significantly.

Page 5: Operating Voltage Update for Haris System

Hardware Components Update

Page 6: Operating Voltage Update for Haris System

Alternative components

RAWABI HOLDING

I. Master(controller)

Estimated cost (SR) Quantity Changed to

Currently cost (SR) Currently No.

500 1 Recom

RACM100-24S 500Power Supply

DNR120 1

446.25 1

105-350W Solar boost charge

controller 450Solar Controller SS-

10L-12V 2

3250 1LED Screen

OFU084E 3335.5 LED Screen 12V 3

1400 1 Alarm Bar 24V 1400 Alarm Bar 12V 4

570 2 Strobes 24V 570 Strobes 12V 5

6166.25 Total 6255.5 Total

Page 7: Operating Voltage Update for Haris System

II. Perimeter

RAWABI HOLDING

Estimated cost (SR) Quantity Changed to

Currently cost (SR) Currently No.

446.25 1210W Solar boost charge controller 450

Solar Controller SS-10L-12V 1

1400 1 Alarm Bar 24V 1400 Alarm Bar 12V 2

570 2 Strobes 24V 570 Strobes 12V 3

2416.25 Total 2420 Total

Page 8: Operating Voltage Update for Haris System

III. Repeater

PAGE # DATE PRESENTATION TITLE RAWABI HOLDING

Estimated cost (SR) Quantity Changed to

Currently cost (SR) Currently No.

446.25 1210W Solar boost charge controller 450

Solar Controller SS-10L-12V 1

446.25 Total 450 Total

Page 9: Operating Voltage Update for Haris System

• Input Voltage: 85-264 VAC • Output Voltage: 24V

• Output current: 4.17 A

• Typical Efficiency: 92 %

• Operating Temperature: -25°C ~ 85°C

• Power (Watt): 100

• Manufacturer: RECOM

•Size / Dimension: (91.4mm x 62.0mm x 39.2mm)

Image

Specifications of The New Components :

Power Supply  Recom RACM100-24S

PAGE # DATE PRESENTATION TITLE RAWABI HOLDING

Page 10: Operating Voltage Update for Haris System

• Rated Panel (Input) Current: 8A

• Minimum Panel Voltage for Charging: 5V

• Minimum Battery Voltage for Operation: 9.5V • Nominal Battery Voltage: 24V

• Maximum recommended Panel OpenCircuit Voltage: 51V

• Absolute Maximum Panel Open-Circuit Voltage : 63V

• Maximum Recommended Panel Vmp: 26V

• Absorption Voltage: 28.4

• Absorption Time: 2 Hours

• Dimensions:  14x6.5x3.1cm • Battery Temperature Compensation: -56mV/°C

• Manufacturer : GENASUN

Image

210W Solar boost charge controller

PAGE # DATE PRESENTATION TITLE RAWABI HOLDING

Page 11: Operating Voltage Update for Haris System

• Voltage: 24VDC , 50/60HZ • Operating Current: 0.25 Amps at 24VDC

• Operating Temperature: -31°F to 150°F

• Lamp Life: 7,000 Hours

• Dimensions: 5"H x 3"Diameter

• Warranty: 1 Year • Manufacturer: Detcon inc

Image

Alarm Bar 24V AV2-N4X

PAGE # DATE PRESENTATION TITLE RAWABI HOLDING

Page 12: Operating Voltage Update for Haris System

• Panel Type: 8.4” TFT Active Matrix Panel • Max. Resolution: 800 x 600

• Pixel Pitch: 0.213 (H) × 0.213 (V) [mm]

• Brightness: 1000 cd/m2

• Operation Temperature: -30° ~ 85° C •Storage Temperature: -30° ~ 85° C

• Dimension: 258 x 160 x 44 [mm] • Power Consumption: 5.08W

• Power Supply: 12VDC, 24VDC power options

• Weight: 2.95 lbs; 1.34 Kgs

• Manufacturer: Accuview

Image

LED Screen OFU084E

PAGE # DATE PRESENTATION TITLE RAWABI HOLDING

Page 13: Operating Voltage Update for Haris System

NeuTron Operating Voltage Update

Page 14: Operating Voltage Update for Haris System

Requirement

To make the input voltage range of NeuTron 10 VDC- 30 VDC without sacrificing the performance or the

cost.

Page 15: Operating Voltage Update for Haris System
Page 16: Operating Voltage Update for Haris System

Currently voltage regulators

Cost ($)Output current

(A)Output voltage

(v)Input voltage

(v) Model No.

10.5 1 3.3 4.75 - 28 V7803-1000 1

10.5 2 3.3 4.75 - 18 V7803-2000 2

0.62 0.75 3.3 4.7 - 15 TLV1117-33 3

0.62 0.75 5 6.4 - 15 TLV1117-50 4

0.5 0.2 8 10 - 30 L78L08ABUTR 5

22.74 Total

Page 17: Operating Voltage Update for Haris System

Proposal •Quad 40V/1A Step-Down Switching Regulator (LT3504)

Page 18: Operating Voltage Update for Haris System
Page 19: Operating Voltage Update for Haris System

2 A Non-isolated Buck Converter Module (MPM80)

Page 20: Operating Voltage Update for Haris System
Page 21: Operating Voltage Update for Haris System

Currently cost

Cost ($) Quantity Items No,0.62 1 TLV1117-33 10.62 1 TLV1117-50 210.5 1 V7803-2000 310.5 1 V7803-1000 40.5 1 L78L08ABUTR 50.5 ---------- External components 5

23.24 Total Cost

Total Cost for Proposal

Cost ($) Quantity Items No.

5 1 LT3504 1

5.6 1 MPM80 2

2.078 ----- External component 3

12.678 Total

Page 22: Operating Voltage Update for Haris System