OLC-K1 Technical manual

16
Lodam Optical Level Controlling Devices Technical manual Version 3.0 OLC-D1, OLC-K1

Transcript of OLC-K1 Technical manual

Page 1: OLC-K1 Technical manual

Lodam Optical Level Controlling Devices

Technical manualVersion 3.0

OLC-D1, OLC-K1

Page 2: OLC-K1 Technical manual

Page 2

Contents1. Read this first . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.1. Reading instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.2. User manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.3. Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

3. Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

4. Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4.1. Level monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4.2. Oil level monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4.3. Level monitoring in vessels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4.4. Red LED status light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

5. Examples of application use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

5.1. Oil level monitoring on a compressor – direct start . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

5.2. Oil level monitoring on a compressor – part-winding . . . . . . . . . . . . . . . . . . . . . . . . 8

5.3. Legend for the schematic diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

5.4. Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

6. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

7. Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

7.1. OLC-D1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

7.2. OLC-K1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

8. Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

8.1. The product is designed according to the following standards . . . . . . . . . . . 13

8.2. The product is tested according to the following standards . . . . . . . . . . . . . . 13

9. Troulbe shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

9.1. Check the LED on the OLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

10. Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

11. Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Page 3: OLC-K1 Technical manual

Technical manual OLC-D1, OLC-K1

Page 3

Page 4: OLC-K1 Technical manual

1. Read this firstThe contents of this manual are subject to change without

notice. Lodam electronics holds the copyright to this user’s

manual. The user shall follow any instructions given in this

user manual entirely and not only partly. Any non-follow-

ing of this user manual result in exclusion of all warranties,

guarantees, and liabilities. Copyright© 2014 by Lodam

electronics a/s. All Rights Reserved.

Disposing of the parts of the controller:

INFORMATION FOR USERS ON THE

CORRECT HANDLING OF WASTE ELECTRI-

CAL AND ELECTRONIC EQUIPMENT (WEEE)

In reference to European Union directive 2002/96/

EC issued on 27 January 2003 and the related national

legislation, please note that:

1. WEEE cannot be disposed of as municipal waste and

such waste must be collected and disposed of sepa-

rately;

2. The public or private waste collection systems defined

by local legislation must be used. In addition, the equip-

ment can be returned to the distributor at the end of its

working life when buying new

equipment;

3. The equipment may contain hazardous substances:

the improper use or incorrect disposal of such may

have negative effects on human health and on the

environment;

4. The symbol (crossed-out wheeled bin) shown on the

product or on the packaging and on the instruction

sheet indicates that the equipment has been intro-

duced onto the market after 13 August 2005 and that it

must be disposed of separately;

5. In the event of illegal disposal of electrical and elec-

tronic waste, the penalties are specified by local waste

disposal legislation.

1.1. Reading instructionsThe following symbols are used to draw the reader’s

attention to different warning levels.

Important information.

Danger!! General danger.

Danger of electrical current or voltage.

1.2. User manualBefore installation the user should be thoroughly

familiarized with this user manual, especially with

purposes, installation and operation.

Special care should be taken when installing and connect-

ing external equipment (high voltage etc.) and handling

the modules correctly according to protection against ESD.

Installation of the OLC-D1/OLC-K1 must be

performed by authorized personnel only. All valid

national legislations regarding electrical installa-

tions must be observed.

All warranties are excluded in case installation is per-

formed by unauthorized personnel or in case the OLC-D1/

OLC-K1 has not been correctly installed.

1.3. SafetyThe OLC-D1/OLC-K1 is a protection device and not

a safety component according to the Machinery

Directive and cannot be used in “medical” or “life

support” equipment.

Before plant commissioning the service technician shall

ensure that personal safety requirements are met in

conformity with the Machinery Directive on the basis of

safety estimations.

Electrical plant failures are to be immediately

solved, even though no immediate danger exists;

the OLC-D1/OLC-K1 must be without power.

Page 4

Page 5: OLC-K1 Technical manual

2. GeneralThe OLC-D1 and OLC-K1 are Optical Level Controlling de-

vices. The OLC-K1 is for monitoring oil level in compressors

while the OLD-D1 is for controlling levels in vessels.

The relay in OLC-K1 is used in the safety chain for the

compressor and will open and lock-out in case of a failure.

OLC-D1 is meant for keeping a specified level in a vessel by

turning the relay on and off.

3. Definitions

Product range

Definitions

ESD Electro Static Discharge

HW Hardware/electronics

OLC Optical Level Controller

NC Normally Closed (relay)

NO Normally Open (relay)

Technical manual OLC-D1, OLC-K1

Page 5

Page 6: OLC-K1 Technical manual

4. FunctionsThe OLC series consists of the two models, OLC-D1 and

OLC-K1. They have different monitoring functions which

are listed in the following.

4.1. Level monitoringThe OLC series consists of a screw-in prism unit and an

optical level detection device. The prism unit is installed in

the compressors oil chamber or in the vessel.

The level detection device can be replaced without open-

ing to the pressurized part of the compressor or vessel.

Detection of the level is via infrared light. There is a built-in

monitoring system for correct installation.

4.2. Oil level monitoringThe OLC-K1 is used for contactless oil level monitoring in

compressors in order to safeguard sufficient lubrication of

the internal mechanics.

As the refrigerant can be absorbed by oil, fluctuation of

the oil level in the compressor is common in refrigeration

systems and thereby oil levels need to be monitored.

OLC-K1 is for compressor use and locks out if oil level is

not sufficient after 90 seconds of compressor operation.

4.3. Level monitoring in vesselsThe OLC-D1 is meant for level monitoring in vessels and

does not have the operation recognition input needed for

compressor operation.

The OLC-D1 releases the relay if the level is too low and

activates the relay if the level is valid. There is a 5 seconds

time delay between switching the relay.

4.4. Red LED status lightAt start-up, the OLC will flash shortly with the LED. After

approx. 3 seconds the relay will be activated.

For OLC-D1 the level monitoring starts immediately; for

the OLC-K1 monitoring starts when the D1 signal is applied

and after the 90 seconds delay time the level is evaluated.

If the oil level is too low or there is a failure, the relay will be

opened and the LED will signal the failure.

• LED Off: Oil level good, no failures

• LED On: Oil level low

• LED flashing: OLC not correctly mounted, or Supply voltage too low, or Internal failure

Page 6

Page 7: OLC-K1 Technical manual

5. Examples of application use

5.1. Oil level monitoring on a compressor – direct start

1312

1110

98

76

54

32

1

L1 L2 L3 N PE

F11 0

Q1

F2 K1 10

F13

8

13

2

M1

M3

R1.

.3

F34A

01

S1

L

1 2

11B

1B

2

SE-B

1/SE

-B2

SE-B

3/S

E-B

4N

1214

OLC

-D1

/OLC

-K1

R7,

optio

n

4 3H

1

F13

3

C

NC

D1

NO

N

H2

K1 10

P>

F5 P<

F6 B1

K2T

12 K1 3/3/

3/11

12/1

3

F4

K1 10

K1 10

K2T

R8

F12

Ple

ase

see

deta

ilsre

gard

ing

conn

ectio

nin

side

the

term

inal

box

Gre

yV

iole

t

Blu

eOnlyOLC-K1

01

S2

Bro

wn

L

Pin

kO

rang

e

(Res

et)

4A

10

Technical manual OLC-D1, OLC-K1

Page 7

Page 8: OLC-K1 Technical manual

5.2. Oil level monitoring on a compressor – part-winding

1918

1716

1514

1312

1110

98

76

54

32

1

L1 L2 L3 N PE

F11 0

Q1

F2 K1 10

F13

10

1U1

1W1

1V1

M1

M3

R1.

.6

F34A

L

1 2

11B

1B

2

SE-B

1/S

E-B

2/

SE-B

3/S

E-B

4N

1214

R7,

optio

n

H1

K1 3/

3/3/

12/

15/1

6/18

/19

K1

10K

214

K1

10K

110

ϑB

2

Y2

Y3

K2T

R8

F12

4A

10

Ple

ase

see

deta

ilsre

gard

ing

conn

ectio

nin

side

the

term

inal

box

Option

K2 14

F14

10

2W1

2U1

2V1

K1T

5/5/

5/17

14m

ax0.

5se

c

01

S1 S2

(Res

et)

OLC

-D1

/OLC

-K1

H2

K1 10

Gre

yV

iole

t

Blu

e

Bro

wn

Pin

kO

rang

e

S3

(Res

et)

P>

F5

P<

F6

K2T

18

F13

3 F14

5

ϑB

1

K2

K1T

11

K1

10

Y1K

214

Option

Option

300

sec

15

D1

OnlyOLC-K1

F4

CL

NO

NC

N

Page 8

Page 9: OLC-K1 Technical manual

5.3. Legend for the schematic diagrams

5.4. Connections

Legend

B1 Control unit

B2 Control unit of capacity regulation (option)

F1 Main fuse

F2 Compressor fuse

F3 Control circuit fuse

F4 Oil level switch

F5 High pressure cut-out

F6 Low pressure cut-out

F12 Fuse of crank case heater

F13/F14 Thermal overload motor PW1 / PW2

H1 Signal light “Compressor over temperature fault”

H2 Signal light “Oil supply fault”

K1/K2 Motor contactors PW1 / PW2

K1T/K2T Time relays “part winding” / pause time

M1 Compressor

Q1 Main switch

R1..3/R1..R6 PTC sensors in motor windings

R7 PTC sensor in cylinder head/discharge gas tempera-ture sensor (option)

R8 Crank case heater (option)

S1/S2/S3 Control switch

Y1 Solenoid valve “start unloading” (option)

Y2 Solenoid valve “liquid line”

Y3 Solenoid valve “capacity regulation” (option)

View colour Function

Brown L; Phase

Blue N; Neutral

Grey C; Common signal

Orange NO; Normal open

Pink NC; Normal closed

Violet (only OLC-K1) D1; Compressor running

Technical manual OLC-D1, OLC-K1

Page 9

Page 10: OLC-K1 Technical manual

6. Technical dataDescription OLC-D1 OLC-K1

Supply voltage 115 VAC; ±10%, 50/60 Hz, 3VA / 230 VAC; ±10%, 50/60 Hz, 3VA / 24 VAC/VDC, ±10%, 50/60 Hz, 3VA

115 VAC; ±10%, 50/60 Hz, 3VA / 230 VAC; ±10%, 50/60 Hz, 3VA

Max media temperature +120°C +100°C

Lock-out Failure Failure Low oil level

Wires in cable 5 6

Compressor-start signal input No Yes; violet wire

Permitted ambient temperature Operation: -30°C – +60°C Storage: -30°C – +80°C

Relative humidity Max. 95%RH non-condensing. Circuit board is coated

Relay Switch voltage 240 VAC, min 24 VAC Continuous current max 2.5A, min 20mA Switching capacity 300 VA, C300 (pilot type use according to UL508)

Fuse required Max 4A, fast-blow

Enclosure class Housing IP54; cable outlet pointing downwards

Mounting of the detection circuit Screw mounted, M24 Max. tightening torque: 10 Nm by hand only

Reset of lock-out state Interrupt supply power for min. 5 seconds

Cable length 2050 ±50 mm 950 ±50 mm

Weight 252 g 152 g

Dimensions 55.5 mm (w) x 87.0 mm (d) x 57.5 mm (h)

UL file number E348183

Page 10

Page 11: OLC-K1 Technical manual

7. Drawings

7.1. OLC-D1

83,0 ±1,0 (6)

39,

0 ±1

,0 (4

)

83,0 to 87,0 (5)

57,

5 ±2

,0 (3

)

205

050

(2)

75,0 ±5,0 (1)

Ø29 Screw on CapM24x1 Internal thread(8)

55,5 1,0 (7)

LED

Technical manual OLC-D1, OLC-K1

Page 11

Page 12: OLC-K1 Technical manual

7.2. OLC-K1

83,0 ±1,0 (6)

39,

0 ±1

,0 (4

)

83,0 to 87,0 (5)

755 (1)

57,

5 ±2

,0 (3

)

950

50 (2

)

Ø29 Screw on CapM24x1 Internal thread(8)

55,5 1,0 (7)

LED

Page 12

Page 13: OLC-K1 Technical manual

8. Standards

8.1. The product is designed according to the following standards• 2002/95/EC RoHs compliance

• 2006/95/EC Low Voltage Directive (LVD)

• 2004/108/EC Electromagnetic Compatibility (EMC)

• 61010-1 Safety requirement for electrical equipment for measurement and control

• 61000-6-x Generic EMC

8.2. The product is tested accord-ing to the following standards• EN 61010-1 Safety requirement for electrical equipment

for measurement and control

• EN 61000-6-1 (EMC, Immunity for residential, commer-cial and light-industrial environments)

• EN 61000-6-3 (EMC, Emission standard for residential, commercial and light-industrial environments)

• UL 60730

• UL file number E348183

• CE marked

9. Troulbe shooting• Check if there is power to the unit according to specifica-

tion. If the power is ok,

• Turn off the power for 5 seconds and see if the relay is energized after power on again.

If not, turn off all the power to avoid risk of injury!

9.1. Check the LED on the OLC• ED Off: Oil level good, no failures

• LED On: Oil level low – there could be a leak or the oil is somewhere else in the cooling system and unavailable for the compressor

• LED is flashing: 1) OLC is not correctly mounted – check that the device is mounted correctly in the prism and the turn-ring is tightened properly. If the LED flashes during start-up there may be foreign light entering the prism from outside 2) The supply voltage might be too low. Check voltage levels 3) The device has an internal fault and needs replace-ment

Technical manual OLC-D1, OLC-K1

Page 13

Page 14: OLC-K1 Technical manual

10. IndexA

Application use 7

C

Connections 9

D

Definitions 5

Drawings 11

F

Functions 6

L

Legend 9

S

Safety 4

Standards 13

T

Technical data 10

Troulbe shooting 13

Page 14

Page 15: OLC-K1 Technical manual

11. Notes

Technical manual OLC-D1, OLC-K1

Page 15

Page 16: OLC-K1 Technical manual

Innovative and energy saving climate controlWhen it comes to climate control Lodam is one of the most experienced you can turn to. For more than four decades we have developed, produced and implemented electronic solutions dedicated to optimising applications like:

• Compressors• Condensing units• Heat pumps• Air conditioning• Refrigerated truck and trailer• Reefer containers

We know the importance of reliable, energy-efficient operation – and constantly push techno-logical boundaries to bring you the most innovative and forward-thinking solutions.

As part of the BITZER Group we are backed by one of the world’s leading players in the refrigeration and air conditioning industry. This alliance provides us with extensive network and application knowhow and allows us to stay at the forefront of climate control innovation. And to help ensure comfortable surroundings for humans and reliable protection of valuable goods anywhere in the world.

Lodam electronics a/sKærvej 776400 SønderborgDenmark

Tel. +45 7342 3737Fax +45 7342 [email protected]

For more information visit:

www.lodam.com

10-0

7-2

015

Co

nte

nts

are

su

bje

ct t

o c

ha

ng

e w

ith

ou

t n

oti

ce.