OFFSET-FLUTED FILM FILL - STAR Cooling Towers

2
OFFSET-FLUTED FILM FILL Features High thermal performance. Increased fouling resistance over cross-fluted fill designs. Bonded edge with dedicated bond points for added strength and durability. Material exceeds Cooling Technology Institute (CTI) Standard 136. Mechanically assembled and available with AccuShield technology. Brentwood’s Offset-Fluted Film Fill is designed for high thermal performance, low pressure drop, and reduces potential for fouling in counterflow towers. OF21MA

Transcript of OFFSET-FLUTED FILM FILL - STAR Cooling Towers

OFFSET-FLUTED FILM FILL

Features• High thermal performance.

• Increased fouling resistance over cross-fluted fill designs.

• Bonded edge with dedicated bond points for added strength and durability.

• Material exceeds Cooling Technology Institute (CTI) Standard 136.

• Mechanically assembled and available with AccuShield technology.

Brentwood’s Offset-Fluted Film Fill is designed for high thermal performance, low pressure drop, and reduces potential for fouling in counterflow towers.

OF21MA

ApplicationsOF21MAFor use in counterflow cooling towers (field-erected and factory assembled installations) in power, refining, chemical, steel, food processing, and HVAC applications where water contains a moderate level of total suspended solids.*

BRENTWOOD INDUSTRIES, INC.brentwoodindustries.com

[email protected]+1.610.236.1100

CT007-1_11-14_ENAll Rights Reserved. © 2015 Brentwood Industries, Inc.

Offset-Fluted Film Fill Product Details

PRODUCT SURFACEAREA

SHEETSPACING

FLUTEANGLE

MEDIA PACK SIZES: Depth (D), Width (W), Length (L) – Inches (mm)MINIMUM MAXIMUM STANDARD

OF21MA 45 ft2/ft3(147.8 m2/m3)

0.82”(20.8 mm)

0°/27°D: 11.8” (300)

W: 5” (127)L: 12” (305)

D: 23.6” (600)W: 18” (458)

L: 120” (3048)

D: 11.8” (300) or 23.6" (600)W: 18” (458)

L: 48” (1220), 72” (1829), 96” (2439), or 120” (3048)

OF21MA Detail

Offset-Fluted Film FillBrentwood’s AccuPac® Offset-Fluted Fill combines the low-fouling characteristics of vertical flow with the enhanced water distribution of cross-fluted designs. OF21MA’s design yields comparable thermal performance to CF1900 but with lower potential for fouling at a lower cost.

Rel

ativ

e P

erfo

rman

ce (

%)

Water Loading Gpm/ft2 (M3/hr/m2)

OF21MAVF19PLUS

HTP25

VF3800

TYPICALSPLASH GRID

Fill air velocity between500 and 600 ft/min (2.5 and 3.0 m/sec)

100

110

90

80

70

60

504 (10) 5 (12.5) 6 (15) 8 (20)7 (17.5)

CF1900 = 100

Relative Tower Performance with Brentwood Counterflow Fills (5’ Fill Depth)

* Reference Brentwood’s online Applications Manual to determine guidelines on water quality.

Benefits• Most versatile fill for use in varying water qualities while

maintaining high performance.

• Engineered to provide the performance of a cross-fluted product with the fouling resistance of vertical-fluted media.

• Ideal for existing vertical-fluted thermal upgrades.