MV Dstribution Substation

download MV Dstribution Substation

of 20

Transcript of MV Dstribution Substation

  • 8/8/2019 MV Dstribution Substation

    1/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    18

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    INTRODUCTION

    The physical structure of most power systems consists of

    generation facilities feeding bulk power into a high-voltage bulk

    transmission network, that in turn serves any number of

    distribution substations. A typical distribution substation will

    serve from one to as many as ten feeder circuits. A typical

    feeder circuit may serve numerous loads of all types. A light to

    medium industrial customer may take service from the distribution

    feeder circuit primary, while a large industrial load complex may

    take service directly from the bulk transmission system. All

    other customers, including residential and commercial, are

    typically served from the secondary of distribution transformers

    that are in turn connected to a distribution feeder circuit.

    Figure 6.1 illustrates a representative portion of a typicalconfiguration.

    The Electric Power System is usually divided into three

    segments, which are generation, transmission, and distribution.

    In a broad definition, the distribution system is that part of

    the electric utility system between the bulk power source and the

    customers service switches.

  • 8/8/2019 MV Dstribution Substation

    2/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    19

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    A distribution system includes the following components

    Sub-transmission system;

    Distribution substations;

    Distribution primary feeders;

    Distribution transformers;

    Secondary circuits;

    Some distribution system engineers define the distribution

    system as that part of the electric utility system between the

    distribution substations and the consumers service entrance.

    3.1 PRIMARY SUBUSTATIONS

    Following diagram shows a Typical distribution substation

    arrangement

  • 8/8/2019 MV Dstribution Substation

    3/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    20

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    Nature of a typical substation

    The voltage of the high side bus can be anywhere from 34.5

    kV all the way to 345 kV and beyond.

    The average or preferred high side voltage level is

    approximately 115 to 138 kV.

    The average substation consists of twotransformers with an

    impedance of approximately 10 percent (0.1 p.u.).

    The low voltage bus in a multiple transformer substation isusually split (contains a normally open breaker or switch)

    to alleviate circulating currents as well as reduce the

    short circuit current seen by the system.

    Normally, Two or more feeders are connected to each bus

    through a feeder breaker.

    On smaller substations where short circuit levels are lower,

    a re-closeris sometimes used instead of abreaker.

    Short circuit levels at the terminals of the low voltage bus

    are generally kept at 12 000 amperes or less although there

    are many systems where much higher levels can be found.

    3.1.1 Main Equipmentsinatypical Substation

    Power transformers

    Circuit breakers

    Current transformer

    Capacitor voltage transformer (CVT)

    EarthingTransformers

    Protective Relays

  • 8/8/2019 MV Dstribution Substation

    4/20

  • 8/8/2019 MV Dstribution Substation

    5/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    22

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    BREATHER

    Breather is mounted on the top of the conservator tank

    & it is a small cylindrical unit containing silica gel to

    absorb moisture of air entering the conservator tank.

    RADIAT

    ORThese are fitted for cooling the transformer oil. The

    hot oil circulate through these unit where it becomes cool

    due to the air touching.

    WINDINGS

    Transformer windings are wound with rectangular, cable

    paper insulated copper wires. There are two windings HV side

    and LV side.

    ON LOAD TAPCHANGER

    Tap changer is used for on load changing of the voltageratio. It is a three-phase unit located in one container,

    which is placed in the transformer tank. Each phase

    regulating winding is located at the star point of HV side

    of transformer. Tap changer is controlled from a motor drive

    unit, fixed to the transformer tank. Transformer voltage may

    have to be constantly regulated and it is often very

    inconvenient to cut off the power supply each time. On load

    tap changer solve such problems, and are being used

    increasingly as a means of offering better power supply

    service as well as for general power receiving purposes.

    BUCHHOLZ RELAYThis relay is situated in the pipe connected between

    the transformer and the conservator. Relay is a gas actuated

    relay which is meant for the protection of oil immersed

    transformer from insulation failure, core heating or any

    type of internal fault which may cause the heating of coil

    beyond the specified temperature due to this faults either

    alarm circuit or the trip circuit operate.

    PRESSURE RELIEF VALVE

    If is the transformer oil vapor pressure increase in

    transformer tank a signal is came to relief valve and it is

    operated.

    TEMPERATUREMETERS

    Those meters measure oil temperature and winding

    temperature and meters are set to fixed temperature.

    ARCHING HORNS

    Arching horns are situated top of the transformer it is

    protected transformer by lightings.

  • 8/8/2019 MV Dstribution Substation

    6/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    23

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    Electrical Characteristic parameters of a transformer

    Ratedpower (Pn): the conventional apparent-power in kVA on

    which other design parameter values and the construction of the

    transformer are based. Manufacturing tests and guarantees are

    referred to this rating

    Frequency: for power distribution systems of the kinddiscussed in this guide, the frequency will be 50 Hz or 60 Hz

    Ratedprimaryandsecondary voltages: For a primary winding

    capable of operating at more than one voltage level, a kVA rating

    corresponding to each level must be given. The secondary rated

    voltage is its open circuit value

    Rated insulation levels are given by overvoltage-withstand

    test values at power frequency, and by high voltage impulse tests

    values which simulate lightning discharges. At the voltage levels

    discussed in this guide, over voltages caused by MV switching

    operations are generally less severe than those due to lightning,

    so that no separate tests for switching -surge withstand

    capability are madeOff-circuittap-selectorswitch generally allows a choice of

    up to 2.5% and 5% level about the rated voltage of the

    highest voltage winding. The transformer must be de -energized

    before this switch is operated

    Windingconfigurations are indicated in diagrammatic form by

    standard symbols for star, delta and inter-connected-star

    windings; (and combinations of these for special duty, e.g. six-

    or twelve-phase rectifier transformers, etc.) and in an IEC-

    recommended alphanumeric code. This code is read from left -to-

    right, the first letter refers to the highest voltage winding,

    the second letter to the next highest, and so on:

    Capital letters refer to the highest voltage windingD = delta

    Y = star

    Z = interconnected-star (or zigzag)

    N = neutral connection brought out to a terminal

    Lower-case letters are used for tertiary and secondary windingsd= delta

    y= star

    z = interconnected-star (or zigzag)

    n= neutral connection brought out to a terminal

    A number from 0 to 11, corresponding to those, on a clock dial

    (0 is used instead of 12) follows any pair of letters to

    indicate the phase change (if any) which occurs during thetransformation.

    A very common winding configuration used for distribution

    transformers is that of a Dyn 11 transformer, which has a delta

    MV winding with a star-connected secondary winding the neutral

    point of which is brought out to a terminal. The phase change

    through the transformer is +30 degrees, i.e. phase 1 secondary

    voltage is at 11 oclock when phase 1 of the primary voltage is

    at 12 oclock.

  • 8/8/2019 MV Dstribution Substation

    7/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    24

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    Circuit breakers

    A circuit breaker is defined as a mechanical switching

    device capable of making, carrying and breaking currents under

    normal circuit conditions and also making, carrying and breaking

    for a specified time, and breaking currents under specified

    abnormal circuit conditions such as a short circuit Circuit

    breakers are generally classified according to the interrupting

    medium used to cool and elongate the electrical arc permitting

    interruption. The types are:

    Oil circuit breaker

    Air blast circuit breaker

    Vacuum circuit breaker

    SF6 gas circuit breaker

    Oil circuit breakers have been widely used in the utility

    industry in the past but have been replaced by other breaker

    technologies for newer installations. Two designs exist bulk

    oil (dead tank designs) and oil minimum breaker technology (live

    tank design). Bulk oil circuit breakers were designed as single-

    tank or three-tank mechanisms; generally, at higher voltages,

    three-tank designs were dominant. Oil circuit breakers were large

    and required significant foundations to support the weight and

    impact loads occurring during operation. Environmental concerns

    forcing the necessity of oil retention systems, maintenance

    costs, and the development of the SF6 gas circuit breaker have

    led to the gradual replacement of the oil circuit breaker for new

    installations.

    Oil circuit breaker development has been relatively static for

    many years. The design of the interrupter employs the arc causedwhen the contacts are parted and the breaker starts to operate.

    The electrical arc generates hydrogen gas due to the

    decomposition of the insulating mineral oil. The interrupter is

    designed to use the gas as a cooling mechanism to cool the arc

    and to use the pressure to elongate the arc through a grid (arc

    chutes), allowing extinguishing of the arc when the current

    passes through zero.

  • 8/8/2019 MV Dstribution Substation

    8/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    25

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    Vacuum circuit breakers use an interrupter that is a small

    cylinder enclosing the moving contacts under a high vacuum. When

    the contacts part, an arc is formed from contact erosion. The arc

    products are immediately forced to and deposited on a metallic

    shield surrounding the contacts. Without anything to sustain thearc, it is quickly extinguished.

    Gas (SF6) circuit breakers generally employ SF6 (sulfur

    hexaflouride) as an interrupting and sometimes as an insulating

    medium. In single puffer mechanisms, the interrupter is

    designed to compress the gas during the opening stroke and usethe compressed gas as a transfer mechanism to cool the arc and to

    elongate the arc through a grid (arc chutes), allowing

    extinguishing of the arc when the current passes t hrough zero. In

    other designs, the arc heats the SF6 gas and the resulting

    pressure is used for elongating and interrupting the arc. Some

    older two-pressure SF6 breakers employed a pump to provide the

    high-pressure SF6 gas for arc interruption.

  • 8/8/2019 MV Dstribution Substation

    9/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    26

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    SF6 Gas circuit breakers

    typically operate at pressures

    between six and seven

    atmospheres. The dielectric

    strength of SF6 gas reducessignificantly at lower

    pressures, normally as a result

    of lower ambient temperatures.

    Monitoring of the density of

    the SF6 gas is critical and

    some designs will block

    operation of the circuit

    breaker in the event of low gas

    density.

    Currenttransformer

    A current transformer is a device for

    measuring a current flowing through a power system

    and inputting the measured current to a protective

    relay system. Electrical power distribution

    systems may require the use of a variety of

    circuit condition monitoring devices to facilitate

    the detection and location of system malfunctions.

    Current transformers and current sensors are well

    known in the field of electronic circuit breakers,providing the general function of powering the

    electronics within the circuit breaker trip unit

    and sensing the circuit current within the

    protected circuit. Ground fault circuit breakers

    for alternating current distribution circuits are

    commonly used to protect people against dangerous shocks due to

    line-to-ground current flow through someone's body. Ground fault

    circuit breakers must be able to detect current flow between line

    conductors and ground at current levels. Upon detection of such a

    ground fault current, the contacts of the circuit breaker are

    opened to de energize the circuit. Current transformers are an

    integral part of ground fault circuit breakers. Current

    transformer assemblies are often positioned between the line side

    of a trip unit of a circuit breaker and the load side in order to

    monitor the current there between. Current transformers in

    electrical substations measure the system currents at

    predetermined measuring points of the switchgear with a certain

    measurement inaccuracy. The measuring points are typically

    located at all incoming and outgoing lines and possibly also

  • 8/8/2019 MV Dstribution Substation

    10/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    27

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    within the system, e.g. for the busbar protection. The current

    measurement signals are used for protective functions, for

    monitoring the substation, for calculating performance data for

    operating purposes or for consumption billing and for the

    representation on a display. The output of the current

    transformer provides a representation of the current flowingthrough the assembly that is being monitored. Associated

    monitoring and control instrumentation in combination with the

    current transformer may provide critical system functions such as

    overload protection and power usage monitoring.

    Capacitor voltagetransformer (CVT)-

    A capacitor voltage transformer (CVT), or

    capacitance coupled voltage transformer (CCVT)

    is a transformer used in power systems to step

    down extra high voltage signals and provide a

    low voltage signal, for measurement or to

    operate a protective relay. In its most basic

    form the device consists of three parts: two

    capacitors across which the transmission line

    signal is split, an inductive element to tune

    the device to the line frequency, and a

    transformer to isolate and further step down the

    voltage for the instrumentation or protective

    relay. The device has at least four terminals: a

    terminal for connection to the high voltage signal, a groundterminal, and two secondary terminals which connect to the

    instrumentation or protective relay.

    CVTs are typically single-phase

    devices used for measuring

    voltages in excess of one hundred

    kilovolts where the use of

    voltage transformers would be

    uneconomical. In practice,

    capacitor C1is often constructed

    as a stack of smaller capacitors

    connected in series. This provides a large voltage drop across C1

    and a relatively small voltage drop across C 2.

    The CVT is also useful in communication systems. CVTs in

    combination with wave traps are used for filtering high frequency

    communication signals from power frequency. This f orms a carrier

    communication network throughout the transmission network.

  • 8/8/2019 MV Dstribution Substation

    11/20

    CHAPTER 03

    Mediu

    Volt

    e System Maintenane

    P a g

    28

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    Earthing Transformers

    In areas where earth point is not

    available, a neutral point is created

    using an earthing transformer. Earthingtransformer, having the zig-zag

    (interstar) winding is used to achieve

    the required zero phase impendence

    stage which provides the possibility of

    neutral earthing condition. In addition

    an auxiliary windings can also be

    provided to meet the requirement of an

    auxiliary power supply.

    Earthing transformers are usually oil immersed and may be

    installed outdoor. As for connection, the earthing can beconnected directly, through an arc -suppression reactor or through

    a neutral earthing reactor or resistor. In cases where a separate

    reactor is connected between the transformer neutral and earth,

    the reactor and the transformer can be incorporated into the same

    tank.

    Line Traps

    High voltage transmission lines are

    also used for transmitting carrier signals

    between 30 kHz and 500 kHz for remote

    control, voice communication, remote

    metering & protection, and so forth, and

    are often referred to as Power Line

    Carrier (PLC) systems.

    Line traps prevent

    transmission of these high

    frequency signals to unwanted

    directions without loss of energy

    at power frequency.

    Line traps are series-

    connected to the transmission

    lines, and are designed to

    withstand the rated power

    frequency current and the short-

    circuit current to which the lines

    are subjected.

  • 8/8/2019 MV Dstribution Substation

    12/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    29

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    3.1.2Different MVserviceconnectionsSingle-line service connection

    The substation is supplied by a

    single circuit tee-off from a MV

    distributor (cable or line).In general,

    the MV service is connected into a panel

    containing a load-break/ isolating

    switch-fuse combination and earthing

    switches, as shown in Figure B11.

    In some countries a pole-mounted

    transformer with no MV switchgear or

    fuses (at the pole) constitutes the

    substation. This type of MV service is

    very common in rural areas.

    Protection and switching devices are

    remote from the transformer, and

    generally control a main overhead line,

    from which a number of these elementary

    service lines are tapped.

    Ring-main service connection

    Ring-main units (RMU) are normally

    connected to form a MV ring main or

    interconnector-distributor(2), such that

    the RMU busbars carry the full ring-main

    or interconnector current (see Fig. B12).

    The RMU consists of three units,

    integrated to form a single assembly,

    2 incoming units, each containing a load break/isolating

    switch and a circuit earthing switch

    1 outgoing and general protection unit, containing a load -

    break switch and MV fuses, or a combined load-break/fuse

    switch, or a circuit-breaker and isolating switch, together

    with a circuit-earthing switch in each case.

    All load-break switches and earthing switches are fully

    rated for short-circuit currentmaking duty.This arrangement

    provides the user with a two-source supply, thereby reducing

    considerably any interruption of service due to system faults or

    operations by the supply authority, etc.

    The main application for RMUs is in utility supply MV

    underground-cable networks in urban areas.

  • 8/8/2019 MV Dstribution Substation

    13/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    30

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    Parallel feeders service connection

    Where a MV supply connection to two

    lines or cables originating from the samebusbar of a substation is possible, a

    similar MV switchboard to that of a RMU

    is commonly used (see Fig. B13).

    The main operational difference

    between this arrangement and that of a

    RMU is that the two incoming panels are

    mutually interlocked, such that one

    incoming switch only can be closed at a

    time, i.e. its closure prevents the

    closure of the other.On the loss of power

    supply, the closed incoming switch must be opened and the

    (formerly open) switch can then be closed. The sequence may be

    carried out manually or automatically.

    This type of switchboard is used particularly in networks of

    medium-load density and in rapidly-expanding urban areas supplied

    by MV underground cable systems.

    3.1.3Protection of transformer and circuitsGeneral protection

    The electrical equipment and circuits in a substation must

    be protected in order to avoid or to control damage due to

    abnormal currents and/or voltages. All equipment normally used in

    power system installations have standardized short-time withstand

    ratings for overcurrent and overvoltage. The role of protective

    scheme is to ensure that this withstand limits can never be

    exceeded. In general, this means that fault conditions must be

    cleared as fast as possible without missing to ensure

    coordination between protective devices upstream and downstream

    the equipement to be protected. This means, when there is a fault

    in a network, generally several protective devices see the faultat the same time but only one must act.

    These devices may be:

    Fuses which clear the faulty circuit directly or together

    with a mechanical tripping attachment, which opens an

    associated three-phase load-break switch

    Relays which act indirectly on the circuit -breaker coil

  • 8/8/2019 MV Dstribution Substation

    14/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    31

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    Transformer protection

    Stresses due to the supply network

    Some voltage surges can occur on the network such as:

    Atmospheric voltage surgesAtmospheric voltage surges are caused by a stroke of

    lightning falling on or near an overhead line.

    Operating voltage surges

    A sudden change in the established operating conditions

    in an electrical network causes transient phenomena to occur.

    This is generally a high frequency or damped oscillation

    voltage surge wave.

    For both voltage surges, the overvoltage protection device

    generally used is a varistor (Zinc Oxide).In most cases, voltagesurges protection has no action on switchgear.

    Stresses due to the load

    Overloading is frequently due to the coincidental demand of

    a number of small loads, or to an increase in the apparent power

    (kVA) demand of the installation, due to expansion in a factory,

    with consequent building extensions, and so on. Load increases

    raise the temperature of the wirings and of the insulation

    material. As a result, temperature increases involve a reduction

    of the equipment working life. Overload protection devices can belocated on primary or secondary side of the transformer.

    The protection against overloading of a transformer is now

    provided by a digital relay which acts to trip the circuit-

    breaker on the secondary side of the transformer. Such relay,

    generally called thermal overload relay, art ificially simulates

    the temperature, taking into account the time constant of the

    transformer. Some of them are able to take into account the

    effect of harmonic currents due to non linear loads (rectifiers,

    computer equipment, variable speed drives).This type of relay is

    also able to predict the time before overload tripping and the

    waiting time after tripping. So, this information is very helpful

    to control load shedding operation.

    In addition, larger oil-immersed transformers frequently

    have thermostats with two settings, one for alarm purposes and

    the other for tripping.

    Dry-type transformers use heat sensors embedded in the

    hottest part of the windings insulation for alarm and tripping.

  • 8/8/2019 MV Dstribution Substation

    15/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    32

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    Internal faults

    The protection of transformers by transformer-mounted

    devices, against the effects of internal faults, is provided on

    transformers which are fitted with air breathing conservatortanks by the classical Buchholz mechanical relay (see Fig. B15).

    These relays can detect a slow accumulation of gases which

    results from the arcing of incipient faults in the winding

    insulation or from the ingress of air due to an oil leak.

    This first level of detection generally gives an alarm, but if

    the condition deteriorates further, a second level of detection

    will trip the upstream circuit-breaker.

    An oil-surge detection feature of the Buchholz relay will

    trip the upstream circuit breaker instantaneously if a surge of

    oil occurs in the pipe connecting the main tank with the

    conservator tank.

    Such a surge can only occur due to the displacement of oil

    caused by a rapidly formed bubble of gas, generated by an arc of

    short-circuit current in the oil.

    By specially designing the cooling-oil radiator elements to

    perform a concerting action, totally filled types o f

    transformer as large as 10 MVA are now currently available.

    Expansion of the oil is accommodated without an excessive

    rise in pressure by the bellows effect of the radiator

    elements. A full description of these transformers is given in

    Sub-clause 4.4 (see Fig. B16).Evidently the Buchholz devices mentioned above cannot be

    applied to this design; a modern counterpart has been developed

    however, which measures:

    The accumulation of gas

    Overpressure

    Over temperature

    The first two conditions trip the upstream circuit-breaker,

    and the third condition trips the downstream circuit-breaker of

    the transformer.

    Internal phase-to-phase short-circuit

    Internal phase-to-phase short-circuits must be detected and

    cleared by:

    3 fuses on the primary side of the transformer or

    An over current relay that trips a circuit-breaker upstream

    of the transformer

  • 8/8/2019 MV Dstribution Substation

    16/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    33

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    Internal phase-to-earth short-circuit

    This is the most common type

    of internal fault. It must be

    detected by an earth fault relay.

    Earth fault current can becalculated with the sum of the 3

    primary phase currents (if 3

    current transformers are used) or

    by a specific core current

    transformer. If a great

    sensitivity is needed, specific

    core current transformer will be

    preferred. In such a case, a two

    current transformers set is sufficient (see Fig. B17).

    Discrimination between the protective devices upstream and

    downstream of the transformer

    The consumer-type substation with LV metering requires

    discriminative operation between the MV fuses or MV circuit-

    breaker and the LV circuit-breaker or fuses.

    The rating of the MV fuses will be chosen according to the

    characteristics of the transformer.

    The tripping characteristics of the LV circuit-breaker must

    be such that, for an overload or short-circuit condition

    downstream of its location, the breaker will trip sufficiently

    quickly to ensure that the MV fuses or the MV circuit -breaker

    will not be adversely affected by the passage of overcurrent

    through them.

    The tripping performance curves for MV fuses or MV circuit-

    breaker and LV circuit breakers are given by graphs of time-to-

    operate against current passing through them. Both curves have

    the general inverse-time/current form (with an abrupt

    discontinuity in the CB curve at the current value above which

    instantaneous tripping occurs).

    These curves are shown typically

    in Figure B18.

  • 8/8/2019 MV Dstribution Substation

    17/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    34

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    3.2.0 Distribution Line Protection Devices

    Overhead distribution lines are generally to faults due to

    high winds, lighting, falling tree, birds etc. Most faults are

    transient in nature and the system would be ready for operation

    again as soon as the fault has been interrupted by the system

    protection. The fault current might have been caused by a falling

    tree, which falls across the high voltage line .In many tree wil l

    fall off the line again after a circuit breaker has de-energized

    line. Alighting stroke will cause the same transient fault; a

    flash over will cause a short circuit current to flow, but as

    soon as this current is interrupted, the system is back to normal

    again.

    Usually majority of the faults recoded in an overhead line

    system is of a transient in nature. This is in contrast to a

    cable network distribution system where most faults are of a

    permanent nature.

    Drop Down Lift Off (DDLO)

    A non-current-limiting

    device interruption the

    current by the melting of a

    fuse element and an arc is

    drawn inside a gas evolving

    type. These may be recharged

    with limited cost.

    An expulsion fuses in

    a holder, arranged in such a

    way that the expulsion fuse

    tube drops out of the

    electrical circuit when the fuse has operated. These are commonly

    used in the CEB distribution network mainly for the protection of

    distribution transformers and some cases for sectionalizing spur

    MV lines.

  • 8/8/2019 MV Dstribution Substation

    18/20

    CHAPTER 03

    Medium Voltage System Maintenane

    P a g

    35

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    Air break Switch

    A switch device, which is

    normally, only used as a

    disconnection, i.e. only

    operated in a de energized

    system. However a very

    limiting making and breaking

    and breaking performance.

    Contact velocity at making is

    operator dependent; an arcing

    horn may give a high arcing contact velocities at oppugn

    sufficient for the interruption of load transformers.

    The switch can in most cases be equipped with a load current

    interrupting device. Still, the switch has only very limited

    making performance .In the CE, the A

    S were installed in area

    boundaries, interconnection points and on long spur line etc. to

    facilitate isolation of section for fault location, maintenance

    and repair works.

    Load Break Switch

    The so-called general purpose

    switch is according to standards

    defined as follows; mechanical

    switching device capable of making,

    carrying the breaking currents under

    normal. A circuit condition, which may

    include specified operating overload

    conditions, such as those of a short

    circuit .It may also be capable of as those of a short circuit.

    It may be capable to making but not breaking of short circuit

    current. The load break switch contains some special arts .One of

    the interrupter head. It reduces their formed When the switch is

    operate.

  • 8/8/2019 MV Dstribution Substation

    19/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    36

    NATIONAL DIPLOMA IN ENGINEERING SCIENCES

    Auto Recloser

    Auto reclosers are self contaminated devises that make and

    break the distribution system under normal at and fault

    conditions. A basic feature of a

    recloser is to reclose immediately

    once the circuit under which it

    served breaks due to temporary

    fault. Recloser will lock out its

    operation whenever it senses a

    permanent fault clears before lock

    out, recloser will reset for another

    cycle of operation.

    Before CEB has introduced auto

    reclosers to the distribution system, only

    DDLOs are provided as the protective

    devices.

    But this needs some one to operate the

    DDLO in order to isolate the line from the

    power supply. Therefore by introducing auto

    reclosers to distribution system, the speed

    of fault clearing has improved and hence

    which promotes the stability of the power

    system. Because of these reasons the concepts

    of auto reclosers entered as a time and money saving method [the

    interruption period becomes less].

    The minimum requirement for installing an auto recloser is

    100 km 1 MVA. The reclosers are sensitive for over current, and

    in modern types sensitive earth faults too.

    There are three types of auto reclosers

    available in medium voltage system in CEB.

    SF6 gas auto recloser

    Oil auto recloser

    Vacuum auto recloser

  • 8/8/2019 MV Dstribution Substation

    20/20

    CHAPTER 03

    Medium Voltage System Maintenance

    P a g

    37

    The following CT ratios are available in CEB 33KV CT ratio

    300/100/1, 11KV CT ratio 300/100/1.The main advantage of

    Programmable type Auto Recloser is;

    This type is programmable and therefore different settings

    can be given

    Availability of memory facility, data for later viewing can

    be stored. This will includes the no of tripping occurred,

    the no of occurred as over current and earth fault or

    sensitive earth fault and the percentage of these f ailures .

    The only thing is to maintain the pressure of the gas in

    side at specified region given in the name plate.

    The tripping period (dead time) for this type when

    connecting in the distribution system are selected as follows;

    1st tripping operation 0.25 sec.

    2nd

    tripping operation 0.50 sec

    3rd tripping operation 1.00 sec

    4th

    tripping operation trip /lockout