MSA AUER Data Sheet MDA Module: Data Acquisition Unit ...

1
SUPREMA MSA AUER Data Sheet MDA Module: Data Acquisition Unit Order No.: 10080011 Function Technical Data Operating voltage feed (3 x 24 VDC): 14 ... 32 VDC Operating current: 40 mA Temperature range: 5 °C ... 55 °C Humidity: 0 ... 90% relative humidity Plug connector: 96-channel VG terminal strip Dimensions: 100 x 160 mm Weight: 87 g Measurement values from the preceding MAI modules are read via the SPI bus. Automatic presetting of the bridge current, zero point and sensitivity in passive sensors with MPI module through the SPI-Bus (possible only in connection with MDA20) Measurement signals are processed in 100-ms cycles; the mean value is calculated over a period of 1 sec. Data is transmitted to the MCP module over the CAN bus. All supply voltages are monitored (EXT, INT and BAT) and sent to the MCP for evaluation. System Failure relay is activated when a processor error occurs. Euro card with a 96-way connector. Description This module accepts the measurement values generated by the preceding Analog Input modules (MAI modules), of which there can be a maximum of 8. This provides the signal processing and calculation for a maximum of 64 sensors and the results are passed to the MCP module via the CAN bus.

Transcript of MSA AUER Data Sheet MDA Module: Data Acquisition Unit ...

Page 1: MSA AUER Data Sheet MDA Module: Data Acquisition Unit ...

MSA AUER Data Sheet

MDA Module: Data Acquisition Unit

Order No.: 10080011

Function

Technical Data

Operating voltage feed (3 x 24 VDC): 14 ... 32 VDC

Operating current: 40 mA

Temperature range: 5 °C ... 55 °C

Humidity: 0 ... 90% relative humidity

Plug connector: 96-channel VG terminal strip

Dimensions: 100 x 160 mm

Weight: 87 g

• Measurement values from the preceding MAI modules are read via the SPI bus.

• Automatic presetting of the bridge current, zero point and sensitivity in passive sensors with

MPI module through the SPI-Bus (possible only in connection with MDA20)

• Measurement signals are processed in 100-ms cycles; the mean value is calculated over a

period of 1 sec.

• Data is transmitted to the MCP module over the CAN bus.

• All supply voltages are monitored (EXT, INT and BAT) and sent to the MCP for evaluation.

• System Failure relay is activated when a processor error occurs.

• Euro card with a 96-way connector.

Description

This module accepts the measurement values generated by the preceding Analog Input modules

(MAI modules), of which there can be a maximum of 8. This provides the signal processing and

calculation for a maximum of 64 sensors and the results are passed to the MCP module via the

CAN bus.

SUPREMA