MPU2IN-02

51
MPU – 2 APPLICATION GUIDE 2 29-02-2012 REV. DATE Verification and Approval R.T.

description

SMS Microsistemi lift controller board

Transcript of MPU2IN-02

Page 1: MPU2IN-02

MPU – 2

APPLICATION GUIDE

2 29-02-2012

REV. DATE Verification and Approval R.T.

Page 2: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 2

INDEX

1 INTRODUCTION .............................................................................. Page 3

2 SYSTEM DESCRIPTION.................................................................. Page 3

3 GENERAL SPECIFICATIONS .......................................................... Page 3

4 TECHNICAL SPECIFICATIONS OF THE CARDS WHICH MAKE UP THE MPU-2 SYSTEM....................................................................... Page 4 4.1 MICROPROCESSOR CARD (QCPU) ......................................................Page 4 4.2 BASE INTERFACE CARD (QINB) ................................................... Page 4 4.3 CAR POSITION INTERFACE CARD (QPOS).................................... Page 6 4.4 EXPANSION CARD (QEXP)........................................................... Page 7

5 INPUT/OUTPUT SIGNAL ................................................................. Page 10

6 FUNCTION OF THE INPUTS/OUTPUTS R0÷R15 WITH COLLECTIVE OPERATION .................................................... Page 15

7 OPERATION .................................................................................... Page 17 7.1 ELECTRONIC SELECTOR .....................................................................Page 17 7.2 NORMAL SERVICE..................................................................... Page 18 7.3 INSPECTION OPERATION .......................................................... Page 19 7.4 ADJUSTMENT SERVICE ............................................................. Page 19 7.5 EMERGENCY OPERATION ......................................................... Page 20 7.6 V.I.P. CALL................................................................................. Page 20 7.7 FIREFIGHTER OPERATION ACCORDING TO EN81-72 ED EN81-73......................................... Page 20

8 MPU-2 CONFIGURATION THROUGH MPU CONSOLE ................... Page 22

9 ALARM CODES ............................................................................... Page 29

10 EXAMPLES OF DIAGRAMS............................................................. Page 32 10.1 EXAMPLE OF DIAGRAM FOR A.P.B. OPERATION CONTROLLER – 2 SPEEDS.................................................................................. Page 33 10.3 EXAMPLE OF DIAGRAM FOR A.P.B. OPERATION CONTROLLER – HYDRAULIC.............................................................................................Page 37 10.1 EXAMPLE OF DIAGRAM FOR A.P.B. OPERATION CONTROLLER – HYDRAULIC WITH HYDROVERT..........................................................Page 41 10.2 EXAMPLE OF DIAGRAM FOR SIMPLEX OPER. CONTROLLER – WITH TAKEDO-3VF NXP........................................................................Page 44

11 DIMENSIONS AND FIXING .............................................................. Page 49

DECLARATION OF CONFORMITY .................................................. Page 51

Page 3: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 3

1 – INTRODUCTION MPU – 2 is a microprocessor system designed and built by SMS for the operation of lifts. Compact and versatile, for the type of functions integrated in the card, it allows to reduce to the minimum the external components on the controller. It is suitable both for hydraulic and rope systems, with different types of driving and doors (see Chapter 3 – GENERAL SPECIFICS).

In the basic configuration, it is suitable for the following types of operation:

− AUTOMATIC PUSH BUTTON (A.P.B.) OPERATION up to 16 stops

− SIMPLEX DOWN OPERATION up to 9 stops

− SIMPLEX FULL OPERATION up to 6 stops

With the addition of one or more expansion cards, use may be extended to:

− SIMPLEX OPERATION (down or full), DUPLEX, TRIPLEX up to 28 stops.

2 – SYSTEM DESCRIPTION In the BASE configuration, the MPU-2 system is made up of 2 cards: one small card (QCPU – see Chapter 4.1)), which contains the microprocessor and relative accessories, mounted through connectors on a basic card (QINB - see Chapter 4.2), which provides the interface with the power, shaft and car circuits.

To signal the car position, it is necessary to connect one or more additional cards (QPOS – see Chapter 4.3)

As described in the previous paragraph, the type of application may require the addition of one or more expansion cards (QEXP - see Chapter 4.4).

3 – GENERAL SPECIFICATIONS

Installation of the cards which make up the MPU-2 system must be carried out inside controllers for lifts. The operating temperature must be between 0 and +50 °C.

The MPU-2 system manages the following functions:

► DRIVES

- ROPE LIFT - AC 1 speed - AC 2 speed - VVVF (OPEN/CLOSED loop)

- HYDRAULIC LIFT - Direct Start up - Soft Starter start-up - HYDROVERT

NOTE: for hydraulic drive, the MPU-2 card does not manage the re-leveling operation directly, it must be carried out with external circuits (see example of diagram at Chapter 10.2).

► DOOR TYPES

- MANUAL - SEMI-AUTOMATIC - AUTOMATIC

- PARKING OPEN OR CLOSED - SINGLE OR DOUBLE ENTRANCE - SIMULTANEOUS OR SELECTIVE OPENING (the latter is only managed for A.P.B. operation)

► OPERATIONS

- INSPECTION OPERATION (see Chapter 7.3) - EMERGENCY OPERATION (see Chapter 7.5) - FIREFIGHTER OPERATION according to EN81-72 – EN81-73 (see Chapter 7.7) - V.I.P. CALL (see Chapter 7.6) - AUTOMATIC RESET TO THE TOP OR BOTTOM FLOOR UPON SYSTEM START-UP (see Chapter 7.1) - AUTOMATIC RETURN TO A SELECTED FLOOR

Page 4: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 4

► CAR POSITION CONTROL SYSTEM

- MONOSTABLE OR BISTABLE MAGNETIC SWITCHES

► CONTROLS AND PROTECTIONS

- MOTOR THERMAL PROTECTION THROUGH THERMISTORS - PHASE FAILURE / INVERSION - MAXIMUM TRAVEL TIME (separated by HIGH/LOW speed) - CAR LIGHT SHUT DOWN / TIMED FAN - LAW 13 – D.M. 236 (controls and signals)

► STANDARDS AND DIRECTIVES

- LIFT DIRECTIVE 95/16/EC - EUROPEAN STANDARDS EN 81-1 EN 81-2

- EMC DIRECTIVE 2004/108/EC - EUROPEAN STANDARDS EN 12015 EN 12016

(See DECLARATION OF CONFORMITY Page 51)

4 – TECHNICAL SPECIFICATIONS OF THE CARDS WHICH MA KE UP THE MPU-2 SYSTEM

4.1 – MICROPROCESSOR CARD (QCPU)

The QCPU card includes the following key components: • 16 bit Microprocessor , with incorporated program memory • E2PROM Memory , containing the programmable functions of the system (ex. number of stops, types of

doors, etc.) and eventual alarm codes. The data contained in E2PROM are stored also in case of power voltage failure. The modification to the functions and/or reading of alarm codes is possible through the MPU CONSOLE terminal.

The QCPU card is powered by the QINB card and does not require any other connection.

The jumpers on the J4 connector must never be removed or moved to other connectors, otherwise the good operation would be affected.

4.2 – BASE INTERFACE CARD (QINB)

POWER SUPPLY

The QINB card must be powered to the 18-18 terminals (M9) with 18Vac +/- 10%. 24VDC voltage for the interface circuits and 5 VDC for the microprocessor are generated inside the card itself. IMPORTANT Do not power the card with different voltage from the one prescribed, also the 24VDC

voltage negative (terminals 0 on M1-M5-M9-M12) MUST NOT be connected to the GROUND.

To enable the Phase Failure/Inversion Control of the three-phase power voltage, 2 phases of this voltage must necessarily be connected to the S-T terminals of terminal board M9. In particular, R - S - T being the three phases, connect phases S and T to the corresponding terminals, while the 18Vac voltage must be derived from a transformer whose primary must be connected to the R and S phases.

INPUTS

No. 5 Optoisolated inputs to check status of safety circuits series Terminal boards M7 – M8. Allowed voltage: 24 ÷ 110V ac/dc. These inputs are made in conformity to the EN81 EUROPEAN STANDARDS. The status of each of these inputs is shown by the corresponding Green Rectangular LED.

No. 44 24Vdc inputs for the signals coming from car and landing call push buttons, slowing and stop switches, maintenance push button board, door limit switches, photocells, etc. (see detailed list in Chapter 5). The status of each input is monitored by the corresponding Red LED. All the input circuits are protected against noises and overvoltage.

Page 5: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 5

No. 1 Thermistors Input, for motor thermal protection. Motor thermistors must be connected directly to the card, to the THM1 - THM2 terminals of Terminal board M3. When the protection is not active, the corresponding Red LED is ON.

OUTPUTS

No. 11 Relay output for the following controls (see detailed list on Chapter 5): - motor contactors (4 relays) - door motor contactors ( 1 or 2 car entrances) (2+2 relays) - retiring cam contactor - "OCCUPIED” signal - power supply enable (FAULT relay) In the terminal board, “voltage free” contacts of these relays are available, whose features are: Nominal voltage: 250Vac Nominal load AC15: 400VA Breaking capacity DC1: 110V 0.3A Since the controls of the motor contactors may be connected downstream of safety circuits, the insulation distance is compliant to what is required by Appendix H of EN81 EUROPEAN STANDARD.

No. 16 Transistor Outputs for signals COMING or REGISTERED M5 – M6 Terminals. Maximum current supplied by each output = 250mA. The output transistors are protected by short circuit through PTC. The COMING or REGISTERED signal must be connected to the same terminals provided for the call push buttons, as illustrated in Figure 1 (only one wire for the push button/lamp connection to the board):

Fig. 1

No. 5 BINARY code outputs for the car position sign al (Terminals B0, B1, B2, B3, B4 - Terminal board M1) These outputs cannot power lamps or displays directly, it is necessary to connect them to one or more QPOS interface cards (see Chapter 4.3).

No. 8 Transistor Outputs for optional controls such as Gong, Overload, Next Car Leaving Direction, etc (Terminal board M12), Emergency, Law 13 (EMO, FLA – M1 Terminal board) - See detailed list in Chapter 5. The outputs connected to M12 and M1 terminal board are “open collector” type and are NOT protected against short circuit. For this reason external relays with 24VDC coil, maximum current 50mA must be necessarily provided. The coils of the external relays must be connected between the relative terminal and 24, as indicated in the example in Fig.2 for the GONG signal. Always connect one fly-wheel diode parallel to the coil, as indicated in Fig.2.

Fig. 2

WARNING: A faulty connection may damage the circuit s on the QINB card, and also the microprocessor on the QCPU card.

24

GONG

Relay coil 24VDC – 50mA

(PUSH BUTTONS COMMON) 24 0 (SIGNALS COMMON) Rn

Push button floor no.N

Signal floor no.N

Page 6: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 6

SWITCHES - PUSH BUTTONS - DISPLAY

No.1 Switch (BEX) and 2 Push buttons (UP, DOWN) to control the movement of the car from the control board. This control excludes calls and allows to move the car between two or more floors as choice of the operator (see Chapter 5).

No.1 2 digit display to view the car position.

No.1 Switch (DGN) for the commutation of the function of the Display from “Car Position” to “Alarm Codes”. At any time (preferably with the car still at the floor), by turning the DGN switch to ON then using the UP or DOWN push button, the previously occurred alarms are displayed, in sequence (starting from the one with the lowest code, NOT in the sequence in which they occurred in time). In case of an alarm which causes the lift to be OUT OF SERVICE, the display automatically switches to the alarm code view, which flashes until normal operation is restored.

CONNECTORS

No.1 9 POLE connector (CN4), for the connection of the MPU CONSOLE terminal, to use for programming and diagnostics functions.

WARNING Read Chapter 8.1 MPU CONSOLE CONNECTION carefully for the relative instructions.

No.1 6 POLE TELEPHONE CONNECTOR (CN6), for serial connection with an eventual QEXP expansion card (if a second expansion card exists, it must be connected to the appropriate connector provided on the first one).

No.1 6 POLE TELEPHONE connector (CN7), for serial connection with other MPU – 2 systems, combined for DUPLEX or TRIPLEX operation.

SETTINGS

A JUMPER and some SOLDER POINTS allow to simply and directly vary certain operational features.

JP1 = Always in position 1 SP2 = Always in position 2 SP1 – SP3 = AU-AD relay coil connection � see Fig. 10 and Fig. 11 of Chapter 7.1 SP4 – SP5 = NUS-NDS Output types � see Fig. 7 and Fig. 8 of Chapter 5 – M12 Terminal board SP6 = Always open SP7 = Always in position 1

4.3 – CAR POSITION INTERFACE CARD (QPOS) The QPOS card is used to decode (from the binary to the decimal one) the signals on the B0÷B4 outputs of the QINB card, to control 16 car position signals . This means that up to 16 stops, only one card is needed, for a greater number of stops 2 cards are needed.

Maximum current supplied by each output = 250mA. The output transistors are protected by short circuit through PTC.

CONNECTIONS

M1 Terminal board: Terminals 0-24 24VDC Power supply, connect to 0-VD+ of M1 of the QINB5 card. Terminals B0÷B4 Connect to the corresponding M1 terminals of QINB5 card.

M2 Terminal board: CS terminal Signals Common (+24V). Terminals S0÷S7 Connect to the position lamps or to the display: for floors 0÷7, with jumper J1 in position 0÷15, for floors 16÷23, with jumper J1 in position 16÷31,

M3 Terminal board: CS terminal Signals Common (+24V). Terminals S8÷S15 Connect to the position lamps or to the display: for floors 8÷15, with jumper J1 in position 0÷15, for floors 24÷27, with jumper J1 in position 16÷31

IMPORTANT For connection to the QPOS card, it is necessary to provide a DISPLAY with 24VDC power supply voltage and POSITIVE COMMON.

Page 7: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 7

4.4 – EXPANSION CARD (QEXP)

TABLE 1 illustrates when it is necessary to provide the QEXP expansion cards and how many, depending on the type of operation and the number of stops.

OPERATION STOPS No. QEXP CARDS

AUTOMATIC PUSH BUTTON (A.P.B.)

Up to 16 ---

SIMPLEX DOWN Up to 9 ---

SIMPLEX DOWN From 10 to 16 1

SIMPLEX DOWN From 17 to 28 2

SIMPLEX FULL Up to 6 ---

SIMPLEX FULL From 7 to 16 1

SIMPLEX FULL From 17 to 28 2

DUPLEX From 2 to 16 1

DUPLEX From 17 to 28 3 (*)

TRIPLEX From 2 to 16 1

TRIPLEX From 17 to 28 4 (*)

Table 1

POWER SUPPLY

The QEXP card must be powered on terminals 24V-0V (M1 terminal board) with 24Vdc from the appropriately provided output on card QINB5, meaning terminals 24EXP and 0EXP of Terminal board M13.

INPUTS

No. 36 24Vdc Inputs for the signals coming from car and landing call push buttons Terminal boards M2 – M02 – M3 – M03 – M4 (see detailed list in Chapter 6). The state of each of these inputs is monitored by the corresponding red LED. All the input circuits are protected against distur bances and overvoltage.

OUTPUTS

No. 36 Transistor outputs for signals REGISTERED Terminal boards M2 – M02 – M3 – M03 – M4 (see detailed list in Chapter 6). Maximum current supplied by each output = 250mA. The output transistors are protected against short circuit through PTC. The REGISTERED signal must be connected to the same terminals provided for the call push buttons, as illustrated in Figure 3 (only one wire for the push button/light connection to the board):

Fig. 3

CONNECTORS

No.1 6 POLE TELEPHONE Connector (M5), for serial connection with the QINB basic card.

No.1 6 POLE TELEPHONE connector (M6), for serial connection with the eventual second expansion card QEXP.

(*) 1 expansion card + 1 expansion card for each car of the unit

(PUSH BUTTONS COMMON) 24V

0V (SIGNALS COMMON)

Registered push button floor no.N

Registered signal floor no.N

Page 8: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 8

SETTINGS

The QEXP card is set to assume different configurations, depending on the setting of the S1 Dip-Switch.

The Dip-Switch S1 is made up of 8 switches, the three most significant (6-7-8) are not used, therefore the following will only be an indication of the configuration of switches 1-2-3-4-5.

SW 1

SW 2

SW 3

SW 4

SW 5

MEANING

A 0 0 0 0 0 Expansion for simplex – number of stops ≤ 16: collects the up and down calls; the car calls are connected to the QINB card.

B 0 0 0 1 0 Expansion for simplex – number of stops > 16: collects the up and down calls from floors 0÷15, SW4=1 indicates that there is an additional expansion for the upper floors.

C 0 0 0 0 1 Expansion for simplex – number of stops > 16: collects the up and down calls and the car calls from for floors beyond 15.

D 1 0 0 0 0 Expansion for duplex – number of stops ≤ 16: collects the up and down calls; the car calls are connected to the QINB card.

E 0 1 0 0 0 Expansion for triplex – number of stops ≤ 16: collects the up and down calls; the car calls are connected to the QINB card.

F 1 1 0 0 0 Expansion for quadruplex – number of stops ≤ 16: collects the up and down calls; the car calls are connected to the QINB card.

G 1 0 0 1 0 Exapansion for duplex – number of stops > 16 : collects the up and down calls from floors 0÷15, SW4=1 indicates that there is an additional expansion for the upper floors.

H 0 1 0 1 0 Exapansion for triplex – number of stops > 16 : collects the up and down calls from floors 0÷15, SW4=1 indicates that there is an additional expansion for the upper floors.

I 1 1 0 1 0 Exapansion for quadruplex – number of stops > 16 : collects the up and down calls from floors 0÷15, SW4=1 indicates that there is an additional expansion for the upper floors.

J 0 0 0 0 1 Expansion for multiplex with number of stops > 16 : collects the car calls from floors beyond 15, for car 1.

K 1 0 0 0 1 Expansion for multiplex with number of stops > 16 : collects the car calls from floors beyond 15, for car 2.

L 0 1 0 0 1 Expansion for multiplex with number of stops > 16 : collects the car calls from floors beyond 15, for car 3.

M 1 1 0 0 1 Expansion for multiplex with number of stops > 16 : collects the car calls from floors beyond 15, for car 4.

Table 2

Page 9: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 9

INSTRUCTIONS FOR CONNECTION OF THE EXPANSION CARDS FOR SIMPLEX, DUPLEX, TRIPLEX OPERATION

In case of SIMPLEX, DUPLEX, TRIPLEX operation.. up to 16 stops, the landing calls must be connected to the single EXPANSION card (terminals U0 ÷ C5), according to the 1st Table on page 16 (QEXP No.1), while the car calls must be connected to the relative MPU-2 card (terminals R0 ÷ R15).

The QEXP cards which the landing calls are connected to, must be powered when even only one MPU-2 system is powered, therefore the 0V-24V terminals of these QEXP cards must be connected to the 0EXP-24EXP terminals of all existing MPU-2 cards.

The QEXP cards which only car calls are connected to, must be powered by the MPU-2 system which manages the relative car, therefore the 0V-24V terminals of these QEXP cards must be connected to the 0EXP-24EXP terminals of the corresponding MPU-2 card.

Fig. 4 Fig. 5

In case of SIMPLEX, DUPLEX, TRIPLEX operation.. from 17 to 28 stops, the landing calls from floors beyond 15 must be connected to a second QEXP expansion card (terminals U0 ÷ D11), according to the 2nd Table on page 16.

This same QEXP card will have connected the car calls beyond floor 15 of the simplex car or of the 1st car of the group. The car calls beyond floor 15 of each other car of the group must be connected to an other QEXP card (one for each car), to terminals C0 ÷ C11, according to the 2nd Table on page 16.

EXAMPLE OF CONNECTION FOR 28 STOP TRIPLEX

Fig. 6

QEXP 1 CARD → Dip-Switch S1 → 01010 QEXP 3 CARD → Dip-Switch S1 → 10001

QEXP 2 CARD → Dip-Switch S1 → 00001 QEXP 4 CARD → Dip-Switch S1 → 01001

EXAMPLE OF CONNECTION FOR 16 STOP SIMPLEX:

EXAMPLE OF CONNECTION FOR 16 STOP DUPLEX:

LANDING CALLS (0÷15)

CAR 2 CALLS (0÷15)

M5 M6 CN6 CN7

QE

XP

CAR 1 CALLS (0÷15)

MP

U-2

C

AR

2

MP

U-2

C

AR

1

CN6 CN7

24

EX

P

0E

XP

24V 0V

24

EX

P

0E

XP

M13 M13

LANDING CALLS (0÷15)

M5 M6

QE

XP

CAR CALLS (0÷15)

MP

U-2

CN6 CN7

24

EX

P

0E

XP

24V 0V M13

LANDING CALLS (16÷27)

LANDING CALLS (0÷15)

CAR 1 CALLS (16÷27)

CAR 2 CALLS (0÷15)

M5 M6 M5 M6 M5 M6 M5 M6 CN6 CN7

CAR 3 CALLS (16÷27)

CAR 2 CALLS (16÷27)

QE

XP

1

CAR 3 CALLS (0÷15)

CAR 1 CALLS (0÷15)

QE

XP

3

QE

XP

4

QE

XP

2

MP

U-2

C

AR

2

MP

U-2

C

AR

3

MP

U-2

C

AR

1

CN6 CN7 CN6 CN7

24

EP

0

EX

P

24

EP

0

EX

P 24V

0V 24V 0V

24V 0V

24

EP

0

EX

P 24V

0V

Dip-Switch S1 10000

Page 10: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 10

5 – INPUT / OUTPUT SIGNALS (QINB CARD TERMINAL BOAR DS)

TERMINAL BOARD M6 (INPUTS / OUTPUTS) TERMINAL

CODE TERMINAL NUMBER

DESCRIPTION

24 M6 - 1 POWER SUPPLY 24VDC (+): inputs common R0 M6 - 2 CALL / SIGNAL FLOOR 0 R1 M6 - 3 CALL / SIGNAL FLOOR 1 R2 M6 - 4 CALL / SIGNAL FLOOR 2 R3 M6 - 5 CALL / SIGNAL FLOOR 3 R4 M6 - 6 CALL / SIGNAL FLOOR 4 R5 M6 - 7 CALL / SIGNAL FLOOR 5 R6 M6 - 8 CALL / SIGNAL FLOOR 6 R7 M6 - 9 CALL / SIGNAL FLOOR 7

NOTE: The R0÷R7 terminals have the configuration described above in case of A.P.B. OPERATION; for any type of COLLECTIVE OPERATION see Chapter 6.

TERMINAL BOARD M5 (INPUTS / OUTPUTS) TERMINAL

CODE TERMINAL NUMBER

DESCRIPTION

0 M5 - 1 POWER SUPPLY 24VDC (−): signals common R8 M5 - 2 CALL / SIGNAL FLOOR 8 R9 M5 - 3 CALL / SIGNAL FLOOR 9

R10 M5 - 4 CALL / SIGNAL FLOOR 10 R11 M5 - 5 CALL / SIGNAL FLOOR 11 R12 M5 - 6 CALL / SIGNAL FLOOR 12 R13 M5 - 7 CALL / SIGNAL FLOOR 13 R14 M5 - 8 CALL / SIGNAL FLOOR 14 R15 M5 - 9 CALL / SIGNAL FLOOR 15

NOTES: The R8÷R15 terminals have the configuration described above in case of A.P.B. OPERATION; for any type of COLLECTIVE OPERATION see Chapter 6.

If the card is configured for A.P.B. OPERATION for a number of stops ≤ 8 and no double entrance is provided with selective opening, a CAR POSITION sig nal in decimal code will be present on the outputs corresponding to terminals R8 ÷R15, one output per floor, (R8 corresponds to the signal of floor 0 and so on, until R15, which corresponds to the signal of floor 7). Therefore in this condition the QPOS card is not necessary: the position signals are powered with 24VDC (Max load = 250mA, with protection from short circuit) and in case of a display, it MUST be the NEGATIVE COMMON type (common cathode).

TERMINAL BOARD M4 (INPUTS) TERMINAL

CODE TERMINAL NUMBER

DESCRIPTION

24 M4 - 1 POWER SUPPLY 24VDC (+): inputs common DOL1 M4 - 2 DOOR OPENING LIMIT SWITCH SIDE 1 DCL1 M4 - 3 DOOR CLOSING LIMIT SWITCH SIDE 1 URI M4 - 4 INSPECTION UP PUSH-BUTTON DRI M4 - 5 INSPECTION DOWN PUSH-BUTTON ULS M4 - 6 TOP FLOOR LIMIT SWITCH DLS M4 - 7 BOTTOM FLOOR LIMIT SWITCH USS M4 - 8 UP STOP SWITCH (DOWN SLOW DOWN) DSS M4 - 9 DOWN STOP SWITCH (UP SLOW DOWN)

NOTE: For the detailed operation of inputs ULS, DLS, USS, DSS see Chapter 7.1 - ELECTRONIC SELECTOR.

Page 11: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 11

TERMINAL BOARD M3 (INPUTS) TERMINAL

CODE TERMINAL NUMBER

DESCRIPTION

ODI M3 - 1 DOOR OPENING PUSH-BUTTON IN INSPECTION (N.O.) EC M3 - 2 CAR OCCUPIED (load ≥ 1 person) PE1 M3 - 3 PHOTOCELL SIDE 1 ODB M3 - 4 DOOR OPENING PUSH-BUTTON (N.C. - connect to 24V if not used) CDB M3 - 5 QUICK DOOR CLOSING PUSH-BUTTON TDC M3 - 6 CONTACTOR DROP DELAY See NOTES below EHC M3 - 7 See NOTES below

THM1 M3 - 8 THM2 M3 - 9

THERMISTORS

NOTES: TDC: Input active only for VVVF drive; connect, if existing, to the VVVF output dedicated to the contactor

control. If not connected, the contactor drop will be commanded after the stop command, with the delay set in parameter F17.

EHC: Input used for management of FIREFIGHTING OPERATION according to EN81-72/73 (with UNI R00 software and following) - See operation description in Chapter 7.7. Connect to 0V if not used.

TERMINAL BOARD M2 (INPUTS) TERMINAL

CODE TERMINAL NUMBER

DESCRIPTION

DOL2 M2 - 1 DOOR OPENING LIMIT SWITCH SIDE 2 DCL2 M2 - 2 DOOR CLOSING LIMIT SWITCH SIDE 2

FC M2 - 3 COMPLETE CAR (load > 80% capacity) OCI M2 - 4 OVERLOADED CAR (load > 110% capacity) ROP M2 - 5 EMERGENCY VIC M2 - 6 V.I.P. CALL See NOTES below ALL M2 -7 ALARM PUSH-BUTTON N.O. CONTACT See NOTES below RES M2 - 8 ALARM RESET See NOTES below ID1 M2 - 9 See NOTES below PE2 M2 - 10 PHOTOCELL SIDE 2 EA1 M2 - 11 EXTERNAL ALARM 1 See NOTES below EA2 M2 - 12 EXTERNAL ALARM 2 See NOTES below

NOTES: VIC: V.I.P. CALL - See operation description at Chapter 7.6. ALL: Input which activates the alarm flashing signal at floors (FLA - Terminal board M1) requested by

Law 13 (this Italian Law has now been overruled by European Standard EN81-28) RES: Input which causes the shut down of the flashing alarm at floors (FLA output) (Law 13). ID1: Input used for management of FIREFIGHTING OPERATION according to EN81-72/73 (with UNI R00

software and following) - See operation description of this operation in Chapter 7.7. EA1: The opening of this input causes the OUT OF SERVICE status with immediate car stop. For example

it can be connected to the VVVF alarm contact. When the input is restored closed, the lift returns to normal service, with a start-up operation. Connect to 24V if not used.

EA2: The opening of this input does not cause the system to go out of service, but only stops the car at the end of the ongoing run. For example it can be connected to the oil thermostat contact. Connect to 24V if not used.

TERMINAL BOARD M1 (OUTPUTS) TERMINAL

CODE TERMINAL NUMBER

DESCRIPTION

VD+ M1 - 1 0 M1 - 2

24VDC POWER SUPPLY FOR CAR POSITION DECODING CARD (QPOS)

B0 M1 - 3 BIT0 CAR POSITION DECODING B1 M1 - 4 BIT1 CAR POSITION DECODING B2 M1 - 5 BIT2 CAR POSITION DECODING B3 M1 - 6 BIT3 CAR POSITION DECODING B4 M1 - 7 BIT4 CAR POSITION DECODING

EMO M1 - 8 EMERGENCY SIGNAL See NOTES FLA M1 - 9 FLASHING ALARM SIGNAL AT FLOORS See NOTES ECL M1 - 10 “OCCUPIED” SIGNAL (0V common) See NOTES CRE M1 - 11 COMMON FOR LANDING PUSH-BUTTONS See NOTES BC M1 - 12 Not used

Page 12: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 12

NOTES: EMO: The output activates in response to the activation of the ROP input (M2 - emergency operation

activation) and remains active until the end of the operation itself. It can also be used to control an external signal.

FLA: The output activates in response to the ALL input activation (M2 - alarm push button activation), in flashing mode. It can be used to control the signal of flashing alarm at floors, as requested by Law 13.

ECL, CRE: terminals connected to a switching contact of the EC - OCCUPIED relay (NO contact on ECL and NC on CRE). See detailed diagram example at Chapter 10.1.

TERMINALS M7 AND M8 (INPUTS) TERMINAL

CODE TERMINAL NUMBER

DESCRIPTION

SC1 M7 - 1 OPTOISOLATED INPUT AT SAFETY CHAIN BEGINNING (downstream of the AUTOMATIC SWITCH)

SC1C M7 - 2 CONTROLLER GROUND

SEX M7 - 3 OPTOISOLATED INPUT 1ST SAFETY CHAIN TRACT (downstream of the OVERTRAVEL SWITCH, which must be the 1st in the safety chain)

SEXC M7 - 4 CONTROLLER GROUND

SC2 M7 - 5 OPTOISOLATED INPUT 2ND SAFETY CHAIN TRACT (downstream of the PIT STOP, SPEED GOVERNOR, SAFETY GEAR, ETC., and of the NORMAL / INSPECTION SWITCH) See NOTES below

SC2C M8 - 1 CONTROLLER GROUND

SC3 M8 - 2 OPTOISOLATED INPUT 3RD SAFETY CHAIN TRACT (downstream of the CAR STOP (eventual, for existings systems), MANUAL CAR DOOR CONTACT, LANDING DOOR CLOSE CONTACTS)

SC3C M8 - 3 CONTROLLER GROUND

SC4 M8 - 4 OPTOISOLATED INPUT 4TH SAFETY CHAIN TRACT (downstream of the AUTOMATIC CAR DOOR CONTACT and of the LANDING DOOR LOCKED CONTACTS)

SC4C M8 - 5 CONTROLLER GROUND

NOTE: The SC2 input must always remain open during the INSPECTION OPERATION.

TERMINAL BOARD M9 (INPUTS) TERMINAL

CODE TERMINAL NUMBER

DESCRIPTION

18 M9 - 1 18 M9 - 2

18VAC POWER SUPPLY FROM TRANSFORMER (primary connected to R – S phases)

24 M9 - 3 0 M9 - 4

24VDC POWER SUPPLY FOR INPUTS/OUTPUTS or EMERGENCY POWER SUPPLY FROM BATTERIES

RC M9 - 5 MOTOR CONTACTOR CHECK M9 - 6

S M9 - 7 S PHASE M9 - 8 (220 or 380V for phase inversion/failure check)

T M9 - 9 T PHASE

NOTES: RC: Input which controls the correct activation and deactivation of the motor contactors.

It must be connected to the auxiliary contacts of the contactors which control the motor, the "glueing" of which could cause a dangerous operation. It is possible to set if the input must be active HIGH (N.A. contacts in parallel) or active LOW (N.C. contacts in series)

Page 13: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 13

TERMINAL BOARD M10 (OUTPUTS) TERMINAL

CODE TERMINAL NUMBER

DESCRIPTION

CS M10 - 1 HIGH/LOW SPEED CONTROL COMMON HS M10 - 2 HIGH SPEED CONTROL (N.O. contact)

HSNC M10 - 3 HIGH SPEED CONTROL (N.C. contact) LS M10 - 4 LOW SPEED CONTROL

M10 - 5 AUP M10 - 6 ADP M10 - 7

UP/DOWN RELAY ACTIVATION PERMIT (AU, AD) FROM TOP/BOTTOM FLOOR LIMIT SWITCHES

HSU M10 - 8 HSD M10 - 9

HIGH SPEED RELAYS ACTIVATION PERMIT (HS) FROM TOP/BOTTOM FLOOR LIMIT SWITCHES

NOTES: AUP, ADP: To connect only for 1 SPEED systems – see diagram example on Page 19 – Fig.10 and 11. HSU, HSD: Do NOT connect for 1 SPEED systems – see diagram example on Page 19 – Fig.10 and 11.

TERMINAL BOARD M11 (OUTPUTS) TERMINAL

CODE TERMINAL NUMBER

DESCRIPTION

CA M11 - 1 UP/DOWN CONTROL COMMON AD M11 - 2 DOWN CONTROL AU M11 - 3 UP CONTROL

M11 - 4 CD M11 - 5 DOOR AND RETIRING CAM CONTROL COMMON

DO1 M11 - 6 DOOR OPENING CONTROL SIDE 1 DC1 M11 - 7 DOOR CLOSING CONTROL SIDE 1 DO2 M11 - 8 DOOR OPENING CONTROL SIDE 2 DC2 M11 - 9 DOOR CLOSING CONTROL SIDE 2

SIDE 2 CAM M11 - 10 RETIRING CAM CONTROL OS2 M11 - 11 OS1 M11 - 12

ALARM RELAY (OS) – N.O. VOLTAGE FREE CONTACT (to connect upstream of the safety chain)

TERMINAL BOARD M12 (OUTPUTS) TERMINAL

CODE TERMINAL NUMBER

DESCRIPTION

24 M12 - 1 0 M12 - 2

24VDC POWER SUPPLY FOR OPTIONAL EXTERNAL RELAYS

GONG M12 - 3 GONG SIGNAL CONTROL MS M12 - 4 MEDIUM SPEED CONTROL

OCO M12 - 5 OVERLOADED CAR WARNING SIGNAL CONTROL NUS M12 - 6 NEXT CAR LEAVING DIRECTION UP SIGNAL CONTROL NDS M12 - 7 NEXT CAR LEAVING DIRECTION DOWN SIGNAL CONTROL LC M12 - 8 CAR LIGHT / FAN CONTROL

M12 - 9

NOTES: NUS, NDS: The NUS and NDS outputs, in case of A.P.B. operation, can be used to control the eventual car run

direction signal.

EXAMPLES OF POSSIBLE CONNECTIONS

SP4 and SP5 IN POSITION 1

0

NUS

24V

NDS

NDS

24V

NUS

ULN

SP4 and SP5 IN POSITION 2

With solder points SP4 and SP5 in position1 , a max load of 250mA can be connected directly on each output with protection against short circuit. The common of the lamps or leds must be connected to 0 (NEGATIVE COMMON)

With solder points SP4 – SP5 in position 2, it is possible to connect the “open collector” type outputs with POSITIVE COMMON (identical to that of MPU-1 system). But in this case there is no protection against the short circuit, so it is necessary to connect an external relay as indicated in Figure 8. Fig.7 Fig.8

Page 14: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 14

TERMINAL BOARD M13 TERMINAL

CODE TERMINAL NUMBER

DESCRIPTION

24EXP M13 - 1 0EXP M13 - 2

24VDC POWER SUPPLY FOR EXPANSION CARD

Page 15: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 15

6 – FUNCTION OF R0 ÷ R15 INPUTS/OUTPUTS (TERMINAL BOARDS M5 /M6) FOR COLLECTIVE OPERATION

6.1- SIMPLEX DOWN OPERATION WITHOUT EXPANSION --- M AX NUMBER OF STOPS = 9 TERMINAL

CODE DESCRIPTION

R0 Car call input (car call registered output) BOTTOM floor R1 Landing call input (landing call registered output) floor 1 R2 Landing call input (landing call registered output) floor 2 R3 Landing call input (landing call registered output) floor 3 R4 Landing call input (landing call registered output) floor 4 R5 Landing call input (landing call registered output) floor 5 R6 Landing call input (landing call registered output) floor 6 R7 Landing call input (landing call registered output) floor 7 R8 Car call input (car call registered output) floor 1 R9 Car call input (car call registered output) floor 2

R10 Car call input (car call registered output) floor 3 R11 Car call input (car call registered output) floor 4 R12 Car call input (car call registered output) floor 5 R13 Car call input (car call registered output) floor 6 R14 Car call input (car call registered output) floor 7 R15 Car call input (car call registered output) TOP floor

To select the SIMPLEX DOWN OPERATION UP TO 9 STOPS, set F03 = "SIMPLEX DOWN"

If the stops are less than 9, the push buttons and signals relative to the top/bottom floors must still be connected to terminals R0 and R15, respectively.

6.2- SIMPLEX FULL OPERATION WITHOUT EXPANSION --- M AX NUMBER OF STOPS = 6 TERMINAL

CODE DESCRIPTION

R0 UP landing call input (landing call registered output) floor 0 R1 UP landing call input (landing call registered output) floor 1 R2 UP landing call input (landing call registered output) floor 2 R3 UP landing call input (landing call registered output) floor 3 R4 UP landing call input (landing call registered output) floor 4 R5 DOWN landing call input (landing call registered output) floor 1 R6 DOWN landing call input (landing call registered output) floor 2 R7 DOWN landing call input (landing call registered output) floor 3 R8 DOWN landing call input (landing call registered output) floor 4 R9 DOWN landing call input (landing call registered output) floor 5

R10 CAR call input (car call registered output) floor 0 R11 CAR call input (car call registered output) floor 1 R12 CAR call input (car call registered output) floor 2 R13 CAR call input (car call registered output) floor 3 R14 CAR call input (car call registered output) floor 4 R15 CAR call input (car call registered output) floor 5

6.3- SIMPLEX FULL OR DOWN OPERATION, WITH 1 OR 2 EX PANSIONS --- MAX NUMBER OF STOPS = 28 TERMINAL

CODE DESCRIPTION

R0 CAR call input (car call registered output) floor 0 R1 CAR call input (car call registered output) floor 1 R2 CAR call input (car call registered output) floor 2 R3 CAR call input (car call registered output) floor 3 R4 CAR call input (car call registered output) floor 4 R5 CAR call input (car call registered output) floor 5 R6 CAR call input (car call registered output) floor 6 R7 CAR call input (car call registered output) floor 7 R8 CAR call input (car call registered output) floor 8 R9 CAR call input (car call registered output) floor 9

R10 CAR call input (car call registered output) floor 10 R11 CAR call input (car call registered output) floor 11 R12 CAR call input (car call registered output) floor 12 R13 CAR call input (car call registered output) floor 13 R14 CAR call input (car call registered output) floor 14 R15 CAR call input (car call registered output) floor 15

Page 16: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 16

TERMINAL CODE QEXP CARD No.1

DESCRIPTION

U0 UP landing call input (landing call registered output) floor 0 U1 UP landing call input (landing call registered output) floor 1 U2 UP landing call input (landing call registered output) floor 2 U3 UP landing call input (landing call registered output) floor 3 U4 UP landing call input (landing call registered output) floor 4 U5 UP landing call input (landing call registered output) floor 4 U6 UP landing call input (landing call registered output) floor 6 U7 UP landing call input (landing call registered output) floor 7 U8 UP landing call input (landing call registered output) floor 8 U9 UP landing call input (landing call registered output) floor 9

U10 UP landing call input (landing call registered output) floor 10 U11 UP landing call input (landing call registered output) floor 11 D0 UP landing call input (landing call registered output) floor 12 D1 UP landing call input (landing call registered output) floor 13 D2 UP landing call input (landing call registered output) floor 14 D3 DOWN landing call input (landing call registered output) floor 1 D4 DOWN landing call input (landing call registered output) floor 2 D5 DOWN landing call input (landing call registered output) floor 3 D6 DOWN landing call input (landing call registered output) floor 4 D7 DOWN landing call input (landing call registered output) floor 5 D8 DOWN landing call input (landing call registered output) floor 6 D9 DOWN landing call input (landing call registered output) floor 7

D10 DOWN landing call input (landing call registered output) floor 8 D11 DOWN landing call input (landing call registered output) floor 9 C0 DOWN landing call input (landing call registered output) floor 10 C1 DOWN landing call input (landing call registered output) floor 11 C2 DOWN landing call input (landing call registered output) floor 12 C3 DOWN landing call input (landing call registered output) floor 13 C4 DOWN landing call input (landing call registered output) floor 14 C5 DOWN landing call input (landing call registered output) floor 15

TERMINAL CODE QEXP CARD No. 2

DESCRIPTION

U0 UP landing call input (landing call registered output) floor 15 U1 UP landing call input (landing call registered output) floor 16 U2 UP landing call input (landing call registered output) floor 17 U3 UP landing call input (landing call registered output) floor 18 U4 UP landing call input (landing call registered output) floor 19 U5 UP landing call input (landing call registered output) floor 20 U6 UP landing call input (landing call registered output) floor 21 U7 UP landing call input (landing call registered output) floor 22 U8 UP landing call input (landing call registered output) floor 23 U9 UP landing call input (landing call registered output) floor 24

U10 UP landing call input (landing call registered output) floor 25 U11 UP landing call input (landing call registered output) floor 26 D0 DOWN landing call input (landing call registered output) floor 16 D1 DOWN landing call input (landing call registered output) floor 17 D2 DOWN landing call input (landing call registered output) floor 18 D3 DOWN landing call input (landing call registered output) floor 19 D4 DOWN landing call input (landing call registered output) floor 20 D5 DOWN landing call input (landing call registered output) floor 21 D6 DOWN landing call input (landing call registered output) floor 22 D7 DOWN landing call input (landing call registered output) floor 23 D8 DOWN landing call input (landing call registered output) floor 24 D9 DOWN landing call input (landing call registered output) floor 25

D10 DOWN landing call input (landing call registered output) floor 26 D11 DOWN landing call input (landing call registered output) floor 27 C0 CAR call input (car call registered output) floor 16 C1 CAR call input (car call registered output) floor 17 C2 CAR call input (car call registered output) floor 18 C3 CAR call input (car call registered output) floor 19 C4 CAR call input (car call registered output) floor 20 C5 CAR call input (car call registered output) floor 21 C6 CAR call input (car call registered output) floor 22 C7 CAR call input (car call registered output) floor 23 C8 CAR call input (car call registered output) floor 24 C9 CAR call input (car call registered output) floor 25

C10 CAR call input (car call registered output) floor 26 C11 CAR call input (car call registered output) floor 27

Page 17: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 17

7 – OPERATION The MPU-2 system manages the electronic selector (7.1) and the OPERATION of the lift in the following different conditions: - normal operation (7.2) - inspection operation (7.3) - adjustment service (7.4) - emergency operation (7.5) - V.I.P. call (7.6) - firefighter operation according to EN81-72 and EN 81-73 (7.7)

7.1- ELECTRONIC SELECTOR The card uses the signal of two switches placed on the car as references for the position of the car itself, connected to the USS and DSS inputs.

The following Figure 9 shows the sequence of commutations of USS, DSS, ULS and DLS.

USS DSS ULS DLS N

= magnet

~2 cm Z2 2 X2 Z1 X1 Y1 1 Y2

~2 cm

0

X1 = UP slowing-down X2 = UP stop Fig. 9 Y1 = DOWN slowing-down Y2 = DOWN stop Z1 – Z2 = door zone

Page 18: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 18

The triggering of the selector, and consequently the eventual slowing-down, is controlled in UP direction by DSS and in DOWN direction by USS. If necessary, for example because of the speed of the system or the distance between floors, the magnets which control the slowing down may "cross" each other, meaning the magnet which controls the slowing down for the next floor can be placed soon after the magnets of the floor zone, at a distance of a few centimeters to allow the correct input reading (the distance depends on the nominal system speed). For most cases, 5 cm are enough, therefore the minimum distance between floors which the MPU-2 system can manage is equal to the slowing down space + the Z1/Z2 space + 5 cm .

The stop at the floor, if the car has slowed-down, is controlled in UP direction by USS and in DOWN direction by DSS (the stop occurs when both switches are engaged). The selector is updated each time the car reaches an extreme floor: two switches are provided, a top limit switch (ULS) and a bottom limit switch (DLS), which directly control the slowing down and set the selector to the respective extreme floor.

The ULS and DLS limit switches must be of N.C. type, while for slowing down and stopping (USS and DSS) it is possible to set the N.O. type (normally open, which closes when activated by the magnet) through the MPU CONSOLE, or N.C., as long as it is the same for both. SMS supplies cards previously set for the N.C. type.

The selector carries out its start-up bringing the car to an extreme floor each time there is a power supply failure, or returning to normal operation after certain types of alarms have occurred, like for example a maximum travel time intervention or a motor thermal protection intervention, faulty phase sequence, etc. During start-up, the car position is not definite for the card, therefore the display shows the symbol - - : it will be appropriately updated when the car will stop at the extreme floor and open the doors. The start-up is carried out differently in function of the position of the car and the type of drive provided:

• Car outside of the slowing zone of the bottom floor: starts in down direction in high speed and stops when the DLS switch opens (1 speed system), or slows down when DLS opens and stops at the opening of USS and DSS (in all other types of drive).

• Car in the slowing zone of the bottom floor but not at the floor's level:

− 1 or 2 speed system: starts in up direction in high speed and stops when the ULS switch opens (1 speed system), or slows down when ULS opens and stops with the opening of USS and DSS (2 speed system).

− Hydraulic system or with VVVF drive: starts in down direction in low speed and stops at the bottom floor when the USS and DSS switches are opened.

7.2- NORMAL OPERATION It provides full control of the lift's operating logic, which may be of A.P.B., simplex down, simplex full, duplex or triplex type. The starting is prepared activating the CAM output when the doors are closed, thern, 200 milliseconds after the closing of the SC4 input (landing door locked), the actual starting is activated and, except for particular cases, it always occurs in high speed, with the activation of the AU output (up) or AD (down) and simultaneously HS (high speed).

Slowing down is carried out by opening HS and activating the LS output (low speed).

The stop at the floor occurs by opening LS. The opening of AU / AD can be simultaneous to LS (for 2 speed or hydraulic systems without VVVF), or it can be appropriately delayed for systems with VVVF drive. The delay can be programmed through an appropriate internal timer (see Chapter 8.5 - Function F 17), or, if the contactor control contact, which is eventually in the VVVF drive, can be used: connect this contact (which must close during the run and open with delay at stop at floor) to the TDC input: this way the AU / AD relay opening (and consequently the opening of the motor contactors) will be controlled by the VVVF at the appropriate time.

To still guarantee stop at the extreme floors, even in case of microprocessor fault, the switches of the extreme floors (ULS and DLS) act as input signals for the microprocessor, but also directly on the HS output relay (high speed) for the 2 speed systems, with VVVF or hydraulic, or directly on the AU (up) or AD (down) output relays for the 1 speed systems. The AUP, ADP, HSU, HSD terminals are provided for this purpose on the QINB card, along with the SP1 and SP3 solder points. The following Figure 10 and 11 show the connections which must be wired in the above two cases. .

Page 19: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 19

Fig.10: AUP, ADP terminal connection, HSU, HSD and SP1-SP3 solder points for 1 speed systems

Fig.11 : AUP, ADP terminal connection, HSU, HSD and SP1-SP3 solder points for 2 speed , hydraulic or VVVF systems.

7.3- INSPECTION OPERATION During INSPECTION operation, the maintenance technician operates the elevator on the car roof (dead man). The microprocessor monitors the inspection board control state via the SC2 input (SC2 = 0 → inspection in progress) and controls the car movement when inputs URI (UP) or DRI (DOWN) are activated via an auxiliary contact of the maintenance control buttons. There is also the ODI input for opening the automatic doors (dead man).

The run in inspection can be carried out in high or low speed (programmable via the MPU CONSOLE). If high speed mode is required, the low speed control is actuated for 3 seconds any way , after which the system switches to high speed: this is to allow the operator to approach a specific point with low speed precision if necessary.

During the run in inspection, the car position is "cancelled", therefore the "- -" symbol will appear on the display. At the return in normal service, the start-up is carried out with subsequent update of the car position.

7.4- ADJUSTMENT SERVICE In adjustment service, the maintenance operator may control the car movement via the controller, while normal calls to the elevator are excluded. For this purpose a (BEX) switch and two push buttons (UP, DOWN) are provided on the QINB card.

By switching the BEX switch to ON, the ADJUSTMENT service is activated and normal service is excluded.

If the BEX switch is closed during run, the adjustment service is enabled only after the car has stopped at floor and the doors have opened. The UP and DOWN push buttons control car movement; the car moves in high speed while the button is held down. When the button is released, high speed continues until the car encounters a slowing-down zone, at which point it slows down and stops at the next floor.

AU AD HS

ULS DLS AUP ADP 24 HSU HSD

QINB CARD

ULS DLS

SP1 and SP3 IN POSITION 2

ULS DLS

ULS DLS AUP ADP 24 HSU HSD

QINB CARD

D U

SP1 and SP3 IN POSITION 1

AU AD HS

Page 20: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 20

If the button opposite to the running direction in progress is pressed (e.g. DOWN while the lift is going UP), the system stops immediately.

7.5- EMERGENCY OPERATION The emergency operation, to bring the car to the floor when the mains power has failed, is enabled by closing the ROP input.

When ROP is ON, phase control is immediately disabled, then the operating mode is different for hydraulic lifts and rope lifts. a) Hydraulic lifts After 5 seconds from ROP activation, the car carries out a run in down direction to

the bottom floor. Once reaching the floor, the eventual automatic doors open. At the end of the opening, any other function is disabled until the ROP input returns to OFF, after which the system returns to normal service carrying out a start-up.

b) Electric lifts After 5 seconds from ROP activation, the card commands the car to start in down direction: you cannot know which direction the car will take, because it depends on the load, but the speed will certainly be decreased because controlled by an emergency inverter (PWM). The lift stops (without slowing down) at the first stopping zone it encounters, i.e. when USS and DSS are both engaged), the eventual automatic doors open. At the end of the opening, any other function is disabled until the ROP input returns to OFF, after which the system will return to service carrying out a start-up.

7.6- V.I.P. CALL At the floor of the V.I.P. call, there is a key switch (VIC input).

When the key is put on (VIC=ON), the existing calls are cancelled, and it is no longer possible to register other calls.

The car reaches the floor of the V.I.P. call (set in F 15 through the MPU CONSOLE - see Chapter 8.5) as quickly as possible, meaning:

a) if the car is still, it immediately leaves towards the floor of the V.I.P. call.

b) if the car is running in the direction compliant to that requested by the V.I.P. call, it continues the run until it reaches the floor of the V.I.P. call.

c) if the car is running in a direction that is not compliant to that requested by the V.I.P. call, it slows down and stops at the first floor it encounters, it does not open the doors, and after 2 seconds it leaves again in the opposite direction to serve the V.I.P. call.

At the arrival of the car at the desired floor, the VIC key is removed and the system returns to the normal operation conditions.

In case of AUTOMATIC PUSH BUTTON operation (A.P.B.) the "V.I.P." user still has priority for a few seconds, to carry out its call. In case of COLLECTIVE operation, it is appropriate to provide a second switch key in the car to simulate the "full car” status (FC input): this way the "V.I.P." user can reach the desired floor without the car stopping to serve other eventual external calls.

7.7- FIREFIGHTER OPERATION ACCORDING TO EN81-72 AND EN81-73 The firefighter operation is possible in 2 modes:

1) Behavior in case of fire (EN81-73)

2) Fire prevention lift operation by firefighters (EN81-72) Both operations provide a first phase, indicated in the Standards as PHASE1, in which the activation of the operation brings the car to a programmable floor, with subsequent opening of the doors. In particular: a) if the car is still, it immediately leaves towards the firefighter floor.

b) if the car is running in the direction compliant to that requested by the firefighter operation, it continues the run until it reaches the firefighter floor.

c) if the car is running in a direction that is not compliant to that requested by the firefighter operation, it slows down and stops at the first floor it encounters, it does not open the doors, and it leaves again in the opposite direction towards the firefighter floor.

If the lift is built-up in compliance to EN81-72 Standards, there is a second phase, called PHASE2, in which the firefighters may move the car under their own exclusive control. For more detailed information, reading the referential Standards is advised.

For FIREFIGHTER OPERATION management you must use the existing inputs in the QINB card which are no longer used for other functions (EHC, ID1), the ALL and RES inputs as well as VIC and ODB.

Page 21: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 21

Also, there are 4 programmable functions via the MPU CONSOLE device, as indicated in Chapter 8.5: they are F 44, F 45, F 46, F 47, reported here for clarity and explained as follows:

F FUNCTION ALLOWED VALUES DEFAULT F 44 FIREFIGHTER OPERATION - NONE

- EN81 – 72 - EN81 – 73

NONE

F 45 FIREFIGHTER FLOOR 1 0 ÷ Fmax 0

F 46 FIREFIGHTER FLOOR 2 0 ÷ Fmax 0

F 47 DOOR CLOSING PHASE 1 - NO - YES

NO

The F 44 Function determines the functionality of the FIREFIGHTER OPERATION. If the function is set as "NONE", the EHC and ID1 inputs are not considered and the ALL and RES inputs are normally used for the "Law 13" function. If the function is programmed as “EN81-73” or “EN81-72”, the lift must be built in order to satisfy the referential Standards, moreover, according to EN81-72, the ALL and RES inputs are no longer available by Law 13. EHC Input KEY SWITCH AT FLOOR, used as request for FIREFIGHTER OPERATION, with arrival of

the car at the floor defined by Function F 45 FIREFIGHTERS FLOOR 1. The status of the input must be ON with firefighter operation. NOT ACTIVE (N.C. contact).

ID1 Input KEY SWITCH AT FLOOR, used as request for FIREFIGHTER OPERATION, with arrival of the car at the floor defined by Function F 46 FIREFIGHTERS FLOOR 2. The status of the input must be ON with firefighter operation. NOT ACTIVE (N.C. contact).

ALL Input KEY SWITCH EXTERNAL TO THE CAR, for activation of PHASE2 of firefighter operation type EN81-72, to allow firefighters to move the car towards a desired floor. As defined in point 5.8.8 g) of the Standards, if the key is removed when the car is at a different floor than the designated one, it closes the doors and goes to the designated floor. The status of the input must be OFF with PHASE 2 not active (N.O. contact).

RES Input KEY SWITCH IN THE CAR, for activation of PHASE2 of firefighter operation type EN81-72, to allow firefighters to move the car towards a desired floor. As defined in points 5.8.8 g) and h) of the Standards, it has priority compared to the external switch, and if the key is removed when the car is at a different floor than the designated one, it closes the doors and remains still. The status of the input must be OFF with PHASE 2 not active (N.O. contact).

Also:

VIC Input ADDITIONAL EXTERNAL CONTROL used to bring the lift to the designated floor (1 or 2 according to the EHC or ID1 activation input) by the firefighters, with lift compliant to EN81-72, after the designated floor has first been reached, then left for a operation controlled by a firefighter in the car. This option is described at point 5.8.2 of the Standards. The status of the input must be OFF with non active operation (N.O. contact).

ODB Input The DOOR OPENING PUSH BUTTON operates in PHASE1 and in PHASE 2 of the EN81-72 operation for opening of the car doors, as indicated in points 5.8.7 b) and 5.8.8 e) of the Standards. Also it can be activated at the end of PHASE1 of the EN81-73 operation as door opening push button, in the countries where car parking with doors open is not permitted, as indicated in point 5.3.5 of the Standards. In fact, by programming Function F 47 ‘DOOR CLOSING PHASE 1’ to 'YES', after 20 seconds from arrival of the car to the designated floor, the doors close automatically and may be re-opened by pressing the ODB push button. If the operation is type EN81-72 or if the F 47 value is set to 'NO', this function is not active and at the end of PHASE 1 the doors remain open. The status of the input must be ON in case of non activated push button, as for the normal operation (N.C. contact).

In case of return of the activation inputs to normal conditions, the system can return to normal operation only if it has been brought back to the firefighter floor from which the operation started (Point 5.8.8 m ) of the Standards).

Fmax = TOP FLOOR

Page 22: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 22

NOTE relative to Functions 45 and F 46

Function F 45 is the designated firefighters floor no.1, activated by the EHC input, prior compared to ID1, which is instead relative to the F 46 function, designated firefighters floor no.2.

The programmable value in F 45 and F 46 goes from 0 to the top floor, but 0 defines the "not leaving" of the car during PHASE1, meaning the opening of the doors directly at the floor in which the lift is stopped. This means that if you want to bring the lift to floor 0, actually you need to set for example F 45 = 1.

More generally, when the lift needs to be brought to a specific floor, the value of F45 and F46 must be set at the floor number plus 1.

8 – MPU-2 CONFIGURATION THROUGH MPU CONSOLE The configuration of the MPU-2 system, setting the system characteristics and the customization of data like timers or other operating options, is carried out through the MPU-CONSOLE device, which also allows access to the diagnostics of alarms occurred during use, stored on the control board (see Chapter 9).

MPU CONSOLE is equipped with a customizable access code, without which it is impossible to access any function of the programmer.

8.1- MPU CONSOLE CONNECTION - Ensure that the lift is still at floor with the empty car and that it is

not accessible by any user; disconnect the power supply from the MPU-2 system and open the operation valve.

- Check that Solder Point SP2 on the QINB card is in position 1, then insert the cable (supplied with the male DB9 connector) in the CN4 connector on the QINB card.

- Power the MPU-2 system and proceed to programming as illustrated in Chapter 8.4.

- Once programming is finished, disconnect the power supply, disconnect MPU CONSOLE and power the card and the operation again: the system will carry out a start-up, then will be ready for normal operation.

8.2- DESCRIPTION OF KEYBOARD AND DISPLAY MPU CONSOLE is made up of a liquid crystals display screen with 9 keys and 3 leds. The description of keys and leds is reported in the following Tables 1 and 2.

KEY FUNCTION

ARROW UP Skips to next function or increase the value of the selected function

ARROW DOWN Skips to the previous function or decrease the value of the selected function.

LEFT ARROW Cancels a modification done before pressing ENTER , moves the cursor to the left on the desired digit for a modification.

RIGHT ARROW Starts a function modification, moves the cursor on the desired digit for a modification.

ENTER Confirms the value of the function just modified.

RESET Allows to reset alarms and counters.

SELECT Allows passage between types of parameters (functions, alarms, counters, access)

START Pressed along with ARROW UP, increases the number of the function to work on by 10. Pressed along with ARROW DOWN, decreases the number of the function to work on by 10.

STOP NOT USED

Table 3

LED FUNCTION

READY ON when the correct access code has been entered

RUN NOT USED

FAULT ON during alarm display, if any.

Table 4

F04

Drive Type

2 Speed

read run fault

REA

Page 23: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 23

8.3- DEVICE OPERATION

The data accessible with MPU CONSOLE are divided in 4 menus , which can be selected with key SELECT and identified by the first letter at top left of the display. This letter means : A : Access menu Allows to modify the access code and language of the display.

F : Functions menu Allows the modification of configuration of the MPU-2 card (lift data).

E : Alarms menu Allows the display and reset of the alarms (see Chapter 9).

C : Counters menu Allows the display of statistical data about lift system operation (see Chapter 8.6).

8.3.1 – ACCESS WITH CODE When starting up, the text A 01 appears on the top left of the display, in the centre row the “Access code 1 ” description and in the lower row the flashing 8 digit code is shown: “00000000”. The modification of the card configuration is only allowed by entering the correct numerical access code, made up of 8 decimal digits, each of which may assume a numeric value from 0 to 9. SMS supplies the MPU-2 cards programmed with Access code = 00000000 , and it is up to the user to change it as desired after first access. To enter the code, use the arrow keys as described in Table 1. If the code is not correct, after having confirmed with ENTER, the display continues to flash with the written value until the correct code is entered. If the code is correct, F01 will appear on the display, it will then be possible to modify the card configuration and lift operation is forbidden until MPU CONSOLE is disconnected.

8.3.2 – CHOOSING THE LANGUAGE

MPU CONSOLE provides the choice between the Italian and English language, which may be set in A02.

8.4- CHANGE AND DISPLAY OF SYSTEM CONFIGURATION The characteristic features of the lift system and the various operating options are indicated on the display with the letter “F” (FUNCTION) followed by two digits that go from 01 to 50 and are illustrated in Chapter 8.5.

You can select the functions by pressing the ARROW UP (increasing the function number) or ARROW DOWN (decreasing the number) keys. It is also possible to increase the number of the function 10 by 10 with the START + ARROW UP key or decrease it 10 by 10 with the START + ARROW DOWN key.

The modification of the selected function occurs as follows: - From the Fxx display, by pressing RIGHT ARROW the current value of the function flashes on the lower

row of the display. - With the ARROW DOWN and ARROW UP keys, you decrease or increase the value of the function. - With the LEFT ARROW and RIGHT ARROW keys you select the following or previous digit of the

function, if it is a numeric type function. - When the function is set to the desired value, it is stored by pressing ENTER, while by pressing LEFT

ARROW you exit without memorizing the change.

Page 24: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 24

8.5- FUNCTION LIST FOR SYSTEM CONFIGURATION

F FUNCTION ALLOWED VALUES AND MEANING DEFAULT

F 01 TOP FLOOR 1 ÷ Fmax Fmax = 15 for A.P.B. OPERATION = 8 for SIMPLEX DOWN OPERATION without QEXP = 5 for SIMPLEX FULL OPERATION without QEXP = 27 for SIMPLEX or MULTIPLEX OPERATION with QEXP

5

F 02 MAIN FLOOR 0 ÷ Fmax It is used to correctly manage the calls from the floors in case of SIMPLEX DOWN operation up to 9 Stops, without QEXP EXPANSION card, if the main floor does not coincide with the bottom floor.

0

F 03 LIFT OPERATION - A.P.B. - SIMPLEX FULL - MULTIPLEX - SIMPLEX DOWN (up to 9 Stops, without QEXP EXPANSION card)

A.P.B.

F 04 DRIVE TYPE - 1 SPEED - 2 SPEEDS - ACVV for SMS MONOTAKEDO and ECOTAKEDO devices, now obsolete - VVVF - HYDRAULIC

2 SPEEDS

F 05 DOOR TYPE - MANUAL both in the car and at floors - SEMIAUTOMATIC this means automatic in the car and manual at floors - AUTOMATIC both in the car and at floors

AUTOMAT.

F 06 DOOR AT FLOOR - OPEN DOORS - CLOSED DOORS

CLOSED DOORS

F 07 CAR ENTRANCES - 1 - 2

1

F 08.00

F 08.01

F 08.01 . . . . . F 08.xx

DOOR OPENING F0

DOOR OPENING F1

DOOR OPENING F2 . . . . . DOOR OPENING Fmax

- SIDE 1 only opens side 1 door - SIDE 2 only opens side 2 door - SIMULTANEOUS both doors side 1 and 2 open simultaneously - SELECTIVE see Function F 08 – SELECTIVE OPENING at the bottom of this Table - NONE to use in case of entrance with manual doors

The Functions F 08.00÷F 08.xx only activate when F 07 = 2, and are shown for the number of floors set in F 01.

SIDE 1

F 09 INSPECTION SPEED - LOW - HIGH

LOW

F 10 FORCED DOOR CLOSING

- NO - YES the DOOR CLOSING control remains active during run

NO

F 11 LANDING CALL ERASE

- SELECTIVE when approaching a floor, only cancels the call compliant to the run direction of the car - SIMULTANEOUS when approaching a floor, always cancels both calls (up and down)

Only valid for SIMPLEX FULL / MULTIPLEX operation

SELECTIVE

F 12 THERMISTOR ALARM RESET

- MANUAL operation is prevented until manual reset through the BEX switch - AUTOMATIC operation resets automatically 10 minutes after thermistors return to normal status

MANUAL

F 13 AUTOMATIC RETURN - NO - YES Only valid for rope systems, since for hydraulic systems return to the bottom floor is always enabled.

NO

F 14 AUTOMATIC RETURN FLOOR

0 ÷ Fmax Only valid if the previous F 13 = YES

0

F 15 V.I.P. CALL FLOOR 0 ÷ Fmax Floor the car must reach in response to activation of the VIC input (see Chapter 7.6)

1

Page 25: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 25

F FUNCTION ALLOWED VALUES AND MEANING DEFAULT

F 16 STOP DELAY TIME 0.0 ÷ 2.0 sec. It is the delay time between the stop switch opening switch and actual car stop. By taking advantage of this delay, it is possible to always have the same stop distance, whichever is the type and speed of the system.

0

F 17 CONTACTOR OPENING DELAY

0.0 ÷ 2.0 sec. Only valid for VVVF drive, when TDC input is not used

2,0

F 18 EMERGENCY STOP DELAY

0.0 ÷ 2.0 sec. It is the equivalent of F 16 for the “emergency” operation

2,0

F 19 RETIRING CAM FALL DELAY

0.0 ÷ 2.0 sec. It is the delay time between opening of the contactors and opening of the relay which controls the retiring cam (CAM). For example it can be useful in one speed systems, to control retiring cam drop when the car has already stopped (at the end of braking).

0,3

F 20 DOOR OPENING DELAY

0.0 ÷ 2.0 sec. It is the delay time between opening of the contactors and door opening control. It can be useful for example in systems with automatic doors and retiring cam, to ensure that the doors begin to open when the retiring cam has already fallen.

0,5

F 21 EMERGENCY MAXIMUM TIME

1 ÷ 15 minutes If the emergency operation is not completed within this time, it is interrupted; to resume the normal operation it is necessary to deactivate the ROP input.

15

F 22 DOOR OPENING TIME 1 ÷ 60 sec. Protection of the door motor in opening; set a time which is a few seconds more than the normally necessary time to open the doors completely.

20

F 23 DOOR CLOSING TIME 1 ÷ 60 sec. Protection of the door motor in closing; set a time which is a few seconds more than the normally necessary time to close the doors completely.

20

F 24 HIGH SPEED TIME 1 ÷ 45 sec. It does not depend on the total travel of the lift system, because it starts again from 0 at every passage from a floor

45

F 25 LOW SPEED TIME

1 ÷ 45 sec. 45

F 26 START DELAY TIME 1 ÷ 60 sec. Only valid for SIMPLEX / MULTIPLEX operation: it is the car stop time at floor with open doors before the next leaving for an existing call.

2

F 27 OCCUPIED TIME 1 ÷ 60 sec. In the A.P.B. operation it is the classic delay which controls the "OCCUPIED" signals and disables the landing push-buttons. In the SIMPLEX / MULTIPLEX operation it is the car stop time at floor with open doors before reversing the run direction to serve calls in the opposite direction. It must be greater than the time set in F 26.

5

F 28 AUTOM. RETURN ACTIVATION DELAY

1 ÷ 15 minutes Valid both for rope and hydraulic systems.

15

F 29 GONG ACTIVE TIME 0.1 ÷ 3.0 sec. It is the time the command for the acoustic signal at the floor is active, from the beginning of the door opening, or from the stop in case of manual doors.

0,5

F 30 CAR LIGHT TIME 1 ÷ 255 sec. Controls the LC output and determines how long this output must remain active after “occupied” shut-off.

10

F 31 SELECTOR TYPE 0 NOT USED

0

F 32 IMPULSOR TYPE - NORMALLY OPEN N.O. contact - NORMALLY CLOSED N.C. contact

Refers to the count and stop magnetic switches USS and DSS, the limit switches ULS and DLS must always be NORMALLY CLOSED (N.C.)

NORMALLY CLOSED

Page 26: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 26

F FUNCTION ALLOWED VALUES AND MEANING DEFAULT

F 33 THERMISTOR STOP - END RUN - STOP AT ONCE Defines the car stop mode after a THERMISTOR Alarm, or at the end of the run in process, or stop at once.

STOP AT ONCE

F 34 PHASE DETECTOR - NO - YES

YES

F 35 NEXT CAR LEAVING DIRECTION SIGNAL

- OFF during RUN - ON during RUN Only valid for SIMPLEX / MULTIPLEX operation, in the first case the signal remains active from the stop at the floor until the next car leaving, in the second case it remains on also during the run, showing the run direction.

OFF IN RUN

F 36 EMERGENCY FLOOR 0 ÷ Fmax.

0

F 37 CONTACTOR INPUT (RC) TYPE

- ACTIVE HIGH connect to RC the contactor N.O. contacts, in parallel - ACTIVE LOW connect to RC the contactor N.C. contacts, in series

Choose the control logic of the contactor control input referring to the availability of the auxi liary contacts.

ACTIVE HIGH

F 38 CONTACTOR INPUT (RC) MODE

- UP & DOWN check is always carried out, both in UP and DOWN direction - ONLY UP check is only carried out in UP direction

The ONLY UP option is necessary for the hydraulic systems without down relay/contactor, when the down valve is controlled downstream the safety chain

UP & DOWN

F 39 TOTAL LIFTS - 1 LIFT - 2 LIFTS - 3 LIFTS - 4 LIFTS Only valid for SIMPLEX / MULTIPLEX operation, set in function of the total number of the combined cars.

1 LIFT

F 40 LIFT NUMBER - 0 ÷ 3 Valid only for MULTIPLEX operation. Identifies the car inside a group 0 = Car 1, 1 = Car 2, 2 = Car 3, 3 = Car 4

0

F 41 ZONE TIME-OUT 1 ÷ 5 minutes Valid only for MULTIPLEX operation. Indicates the maximum time one ZONE (one or more calls) may remain in waiting to be assigned to a car; once this time has elapsed, the zone becomes a priority.

5

F 42 EARLY DOOR OPENING

- NOT ACTIVE early opening is not enabled - ON SLOWING the opening control is given at the beginning of slowing down; an external safety circuit must provide the bypass of the door safety contacts in the consented floor zone, and activate the opening control at the proper time. - AT FLOOR the opening control is given when the car reaches the door unlocking zone (USS or DSS involved); an external safety circuit must provide the bypass of the door safety contacts in the consented floor zone.

NOT ACTIVE

F 43 MISSING FLOOR - NONE - LOWEST FLOOR - HIGHEST FLOOR - OTHER CAR LOW - OTHER CAR HIGH Valid in case of "LAME" DUPLEX operation, meaning in the particular case in which one or both cars can't reach an extreme floor, which is instead served by the other.

See explanation to Function F 43- “LAME DUPLEX” at the bottom of this Table.

NONE

Page 27: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 27

F FUNCTION ALLOWED VALUES AND MEANING DEFAULT

F 44 FIREMEN OPERATION - NONE - EN81 – 72 - EN81 – 73

NONE

F 45 FIREMEN FLOOR 1 0 ÷ Fmax. 0

F 46 FIREMEN FLOOR 2 0 ÷ Fmax. 0

F 47 DOOR CLOSE PHASE 1

- NO - YES

These functions, from F 44 to F 47, all refer to the FIREFIGHTER OPERATION.

For a detailed explanation of the OPERATION and the FUNCTION, see Chapter 7.7- FIREFIGHTER OPERATION ACCORDING TO EN81-72 AND EN81-73

NO

F 48 CAR LIGHT TIME - SECONDS - MINUTES Allows to change the measure unit of the time set in F 30 (1÷255 sec.), in order to slow the turning on and off of any neon lights in the car.

SECONDS

F 49 STANDBY TIME UNIT 1 ÷ 255 minutes Allows to manage the system standby. If the time is different from 0, when it expires in absence of calls, with the car still at floor and not in particular situations such as INSPECTION, EMERGENCY, FIREFIGHTERS OPERATION...the FLA output is deactivated. This output may be used to control a contactor which deactivates three-phase power supply for the entire control board and opens the SC1 input at the beginning of the safety chain, so that the position of the car is not lost. If any landing or car call push button is pressed, the FLA output is immediately re-activated, and returns the card to normal operating conditions.

0

F 50 RE-LEVELING TIME 0 ÷ 255 sec.

10

F 08 – SELECTIVE OPENING Selective opening is only available for the AUTOMAT IC PUSH BUTTON OPERATION (A.P.B.)

When selective opening is programmed for a floor, it means that it is possible to register two different call for that floor, one to open the side 1 doors and the other one to open the side 2 doors.

Selective opening may be programmed for a single floor or for more floors, up to a maximum of 8.

The push buttons calls corresponding to the side 1 opening have to be connected normally from R0 forward, just as the push-button calls of floors for which selective opening is not provided, while only the push buttons calls corresponding to the side 2 opening have to be connected from R15 backwards, connecting to R15 the lowest floor.

EXAMPLE:

Lift system with 6 stops, 2 car entrances, and SELECTIVE OPENING at floors 2 and 4.

SIDE 1 5 SIDE 2

4

3

2

1

0

The F 08.02 and F 08.04 Functions must be programmed "SELECTIVE"

The call push buttons must be connected as follows:

0 → R0 1 → R1 2 – side1 → R2 3 → R3 4 – side1 → R4 5 → R5 4 – side2 → R14 2 – side2 → R15

Page 28: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 28

F 43 – "LAME" DUPLEX

“LAME” DUPLEX is a duplex with a car with a missing stop: the missing floor can only be the bottom floor or the top one.

Function F 43 must be set for both cars, even for the one that has no missing floor, according to the following examples: 1) CASE of missing TOP FLOOR :

a) The F 01 - TOP FLOOR function must be set with the value of the highest existing floor for the car in subject.

b) If the car is the one with the missing floor, the F 43 function must be set as "HIGHEST FLOOR"

c) If the car is NOT the one with the missing floor, the F 43 function must be set as "OTHER CAR HIGH"

Assignment of the calls for the two cars occurs normally for the floors served by both cars, while the down call from the highest floor and the up call from the penultimate floor assignment is forced to the only car able to serve them.

2) CASE of missing BOTTOM FLOOR :

a) The F 02 - MAIN FLOOR function must be set to 1 (cannot be 0) If not set to 1, the software internally forces it to 1.

b) If the car IS the one with the missing floor, the F 43 function must be set as "LOWEST FLOOR"

c) If the car is NOT the one with the missing floor, the F 43 function must be set as "OTHER CAR LOW"

d) For the car with missing bottom floor, floor 1 is considered as bottom floor.

Assignment of the calls for the two cars occurs normally for the floors served by both cars, while the up call from floor 0 and the down call from floor 1 assignment is forced to the only car able to serve them.

8.6 – INFORMATION ON LIFT SYSTEM OPERATION There are 4 counters which give indications regarding lift system operation. To display the counters press SELECT until the “C” text appears, followed by a digit on the top left of the display. The viewable counters are:

C 01 Number of up runs C 02 Number of down runs C 03 Number of door openings C 04 Number of door closings

Table 5

For example, selecting C02, the number of down runs performed by the lift can be displayed.

The number is updated every 100 runs, so the minimu m value displayed different from zero is 100 .

To reset the counter press RESET.

Page 29: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 29

9 – ALARM CODES The lift system alarms are displayed on the MPU CONSOLE with the letter “E” (Errors) followed by two digits (from 01 to nn). They can only be displayed and reset.

To display the alarms press SELECT until the “E” text appears, followed by two digit on the top left of the display.

The first page of the alarms shows "E00" followed by the text “Total Alarms” and by the total number of the alarms. To see which kind of alarms are there, press the RIGHT ARROW key. If there are no alarms, the text "Total Alarms" appears, followed by "0".

If there is an alarm, the letter “E” appears followed by a number showing the alarm numeric code. The various alarm codes are listed in the following TABLE.

When the alarm numeric code is 4 digits, the first two after the "E" show the type of alarm, while the following ones indicate the floor where the alarm occurred.

Example: E0207 Car doors not closed or landing doors not locked, at floor 07 E06 Start-up aborted

♦ In the row at the bottom of the display, the number of times that the alarm has occurred appears.

♦ Pressing ARROW UP again, you move to the following alarm. If there is no following alarm, you return to the first alarm.

♦ To cancel all the alarms, press RESET.

The alarm codes may also be displayed in a simpler and more direct mode (without MPU CONSOLE) by using the DGN switch on the QINB card, which switches the Display function from “Car Position” to “Alarm Codes”.

At any time (preferably with the car still at the floor), by turning the DGN switch to ON then using the UP or DOWN push button, the previously occurred alarms are displayed, in sequence (starting from the one with the lowest code, NOT in the sequence in which they occurred in time).

If ZERO appears, it means <<NO ALARM>> In case of an alarm which causes the lift to be OUT OF SERVICE, the display automatically switches to the alarm code view, which flashes until normal operation is restored.

Page 30: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 30

ALARM CODE DESCRIPTION AFTERMATH

E 01 INCORRECT PHASE SEQUENCE OR PHASE LACKING

Can only be emitted if F 34 (PHASE DETECTOR) = YES

The power supply phase sequence is not correct, or a phase is lacking.

Since it is generally emitted upon power supply arrival, the car remains blocked and the start-up does not occur. The OS1-OS2 contact opens. Normal operation can start when correct power supply is restored.

E 02 CAR DOORS NOT CLOSED OR LANDING DOORS NOT LOCKED

At car leaving, with doors completely closed (active SC3 input and non active DCL1 and DCL2 inputs), the SC4 input does not activate within 2 seconds.

The E 02 code is completed with the number of the floor where the alarm occurred. Example: E0207 Car doors not closed or landing doors not locked at floor 7.

A.P.B. OPERATION The call is cancelled, the doors re-open and the car is waiting for a new call.

SIMPLEX OPERATION The car and landing calls are not cancelled and a total of 5 attempts to close are made: only if the problem persists, all the car and landing calls are cancelled and the car is waiting for new calls.

MULTIPLEX OPERATION The landing calls are not cancelled but are transferred to the other cars.

E 03 MOTOR CONTACTORS DO NOT ENERGIZE

At car leaving, with doors locked (SC4 input active), the RC input is not activated within 2 seconds.

The E 03 code is completed with the number of the floor where the alarm occurred. Example: E0306 Motor contactors do not energize at floor 6

A.P.B. OPERATION The call is cancelled, the doors re-open and the car is waiting for a new call.

SIMPLEX OPERATION The car and landing calls are not cancelled and a total of 5 attempts are made: only if the problem persists, all the car and landing calls are cancelled and the car is waiting for new calls.

MULTIPLEX OPERATION The landing calls are not cancelled but are transferred to the other cars.

E 04 NO TDC INPUT ACTIVATION

Can only be emitted for ACVV DRIVE (F 04).

At car leaving, the TDC input is not activated (there is no confirm that the ACVV regulator has received the starting command within 2 seconds from contactor activation.

A.P.B. OPERATION The call is cancelled, the doors re-open and the car is waiting for a new call.

SIMPLEX OPERATION The car and landing calls are not cancelled and a total of 5 attempts are made: only if the problem persists, all the car and landing calls are cancelled and the car is waiting for new calls.

MULTIPLEX OPERATION The landing calls are not cancelled but are transferred to the other cars.

E 05 CAR FAILED TO LEAVE At car leaving, after the contactor energization, the car does not leave the floor zone within a few seconds (5 for rope systems, 8 for hydraulic).

The E 05 code is completed with the number of the floor where the alarm occurred. Example: E0508 Car failed to leave at floor 8

A.P.B. OPERATION The call is cancelled, the doors re-open and the car is waiting for a new call.

SIMPLEX OPERATION The car and landing calls are not cancelled and a total of 5 leaving attempts are made: only if the problem persists, all the car and landing calls are cancelled and the car is waiting for new calls.

MULTIPLEX OPERATION The landing calls are not cancelled but are transferred to the other cars.

E 06 START-UP ABORTED The car cannot complete the start-up operation. (arrival at the bottom floor and eventual opening of doors).

The system remains out of service because it is not possible to set-up the car position.

Page 31: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 31

ALARM CODE DESCRIPTION AFTERMATH

E 07 CAR DOORS FAIL TO CLOSE

The doors do not complete closing within the time set in F 23.

A.P.B. OPERATION The call is cancelled, the doors re-open and the car is waiting for a new call.

SIMPLEX OPERATION The car and landing calls are not cancelled and a total of 5 attempts to close are made: only if the problem persists, all the car and landing calls are cancelled and the car is waiting for new calls.

MULTIPLEX OPERATION The landing calls are not cancelled but are transferred to the other cars.

If the closing failure occurs during PARKING at floor or START-UP, 5 closing attempts are carried out, after which the car remains still with open doors.

E 08 CAR DOORS FAIL TO OPEN

The doors do not complete opening within the time set in F 22.

The control for the door motor is deactivated and the lift remains normally in service.

E 09 MAXIMUM TRAVEL TIME IN HIGH SPEED

The car, in high speed run, has not reached the following floor within the time set in F 24.

The lift is placed OUT OF SERVICE. The normal operation can only be restored by a manual RESET, by means of the BEX switch: closing then re-opening BEX, a new start-up is carried out.

E 10 MAXIMUM TRAVEL TIME IN HIGH SPEED

The car, in low speed run, has not reached the floor within the time set in F 25.

The lift is placed OUT OF SERVICE. The normal operation can only be restored by a manual RESET, by means of the BEX switch: closing then re-opening BEX, a new start-up is carried out.

E 11 MAXIMUM TRAVEL TIME IN RE-LEVELING

Can only be emitted for HYDRAULIC DRIVE (F 04).

The car, in re-leveling, has not reached the floor within the time set in F 50.

The lift is placed OUT OF SERVICE. The OS1-OS2 contact opens. The normal operation can only be restored by a manual RESET, by means of the BEX switch: closing then re-opening BEX, a new start-up is carried out.

E 12 CONTACTOR DE-ENERGIZATION FAILURE

The RC input (run contactors) does not deactivate within 2 seconds from the contactor OFF command. (OFF of outputs AU / AD).

A next car leaving is prevented for the whole time that RC is active.

E 13 LIMIT SWITCH OR SELECTOR SWITCH OPERATION NOT CORRECT

The car position indicator shows an extreme floor, but no limit switch is involved.

A call is carried out for the opposite extreme floor, so that the floor selector is correctly updated.

E 14 OVERTRAVEL Opening of the overtravel switch (SEX input - 1st tract of the safety chain)

The lift is placed OUT OF SERVICE.

The normal operation can only be restored by a manual RESET, by means of the BEX switch: closing then re-opening BEX, a new start-up is carried out.

E 15 THERMISTOR MOTOR PROTECTION

The motor thermistors (connected to input TH1 - TH2) have detected an increase in motor temperature up to the protection threshold.

The car stops with the mode defined by F 33, then the elevator is placed OUT OF SERVICE. The OS1-OS2 contact opens. The normal operation can be restored AUTOMATICALLY or MANUALLY (in function of how F 12 is set), after a new start-up is carried out.

Page 32: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 32

ALARM CODE DESCRIPTION AFTERMATH

E 16 EXTERNAL ALARM 1 The contact connected to the EA1 input is open (for example the VVVF alarm contact).

The lift is placed OUT OF SERVICE. The OS1-OS2 contact opens. The normal operation is automatically restored when the contact closes again, after a new start-up is carried out.

E 17 EXTERNAL ALARM 2 The contact connected to the EA2 input is open (for example the oil thermostat contact).

The lift stops at the end of the run and a next car leaving is prevented. The normal operation is automatically restored when the contact closes again.

E 18 OPERATION VOLTAGE FAILURE

No voltage in the SC1 input (upstream of the safety chain)

The lift stops and a next car leaving is prevented.

The normal operation is automatically restored when the operation voltage is restored.

E 20 PHOTOCELL DARKENED FOR MORE THAN 20 SEC.

The contact connected to the PE1 input (or PE2 in case of double entrance) is open for over 20 sec.

A next car leaving is obviously prevented until the condition persists. The normal operation is automatically restored when the contact closes again.

IMPORTANT!

For HYDRAULIC lifts in alarm situations, even those that place the system out of service, the AUTOMATIC RETURN TO BOTTOM FLOOR within 15 minutes still always remains active.

10 – EXAMPLES OF DIAGRAMS This chapter reports some diagrams as an example:

10.1 - A.P.B. OPERATION CONTROLLER – 2 SPEEDS

10.2 - A.P.B. OPERATION CONTROLLER – HYDRAULIC

10.3 - A.P.B. OPERATION CONTROLLER – HYDRAULIC WIT H HYDROVERT

10.4 - SIMPLEX OPERATION CONTROLLER – WITH TAKEDO-3 VF NXP INVERTER

We have chosen to show a 3-phase type 125Vac 50Hz door motor, along with a 48Vdc operation voltage, but of course other solutions are also possible, as long as compatible with the SPECIFICS illustrated in Chapter 4 of this Manual.

Generally, it is recommended to ALWAYS connect, parallel to the relay coils, contactors, electromagnets, external to the card, a protection device against transitory overvoltage phenomena, meaning DIODES in presence of continuous or rectified voltage, or VARISTORS or RC FILTERS when drop speed is important or in the presence of alternate voltage.

Page 33: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 33

10.1 – EXAMPLE OF DIADRAM FOR A.P.B. OPERATION CONT ROLLER – 2 SPEEDS

Page 34: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 34

Page 35: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 35

Page 36: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 36

Page 37: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 37

10.2 - EXAMPLE OF DIADRAM FOR A.P.B. OPERATION CONT ROLLER – HYDRAULIC

Page 38: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 38

Page 39: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 39

Page 40: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 40

With regard to this example of controller for hydraulic lift system, note that relays RL1, RL2 and RL3, which perform the safety circuit for re-leveling operation, must be "forced guided" or "linked contact" safety relays, or minicontactors.

RL4, on the other hand, is only a control relay and can be a mini-relay on socket: it must always be excited, except when the safety circuit which allows the re-leveling operation is out of service. In this case, the MPU card detects the potential danger through opening of the RL4 contact connected to the EA2 input.

10.3.1 – SWITCHES FOR HYDRAULIC LIFT SYSTEM

Compared to the rope lift systems (see Fig.9), an extra switch is provided to control the re-leveling zone with safety circuit (RZS). The contact of this switch must be N.O. (closed at the floor). USS DSS ULS DLS RZS N

= magnet

~2 cm Z2 W1 2 X2 Z1 W2 X1 Y1 1 Y2

~2 cm

0

X1 = UP slowing-down X2 = UP stop Y1 = DOWN slowing-down Y2 = DOWN stop Z1 – Z2 = door zone W1 – W2 = re-leveling zone

Fig. 12

Page 41: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 41

10.3 - EXAMPLE OF DIADRAM FOR A.P.B. OPERATION CONT ROLLER – HYDRAULIC WITH HYDROVERT

Page 42: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 42

Page 43: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 43

Page 44: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 44

10.4 - EXAMPLE OF DRAWING FOR SIMPLEX OPERATION CON TROLLER – WITH TAKEDO-3VF NXP INVERTER

Page 45: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 45

Page 46: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 46

Page 47: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 47

Page 48: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 48

Page 49: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 49

11 – DIMENSIONS AND FIXING

For further information contact:

SMS SISTEMI e MICROSISTEMI s.r.l. (Gruppo SASSI HOLDING) Cap. Soc. 260.000€ i.v.

Via Guido Rossa, 46/48/50 40056 Crespellano (BO) Italy R.E.A 272354 CF - Reg. Imprese Bo 03190050371 P.IVA IT 00601981202

Tel. : +39 051 969037 Fax : +39 051 969303 Te chnical Service: +39 051 6720710 Website : www.sms.bo.it E-mail : [email protected]

Page 50: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 50

Page 51: MPU2IN-02

MPU – 2 APPLICATION GUIDE Version 2 - 29-02-2012 51

DECLARATION OF CONFORMITY

Manufacturer: SMS SISTEMI E MICROSISTEMI s.r.l.

Address: Via Guido Rossa, 46/48/50 – 40056 Crespellano (BO)

Product: MICROPROCESSOR BOARD FOR LIFT Model/Type: MPU - 2

The above mentioned products are in conformity to the requirements of the following European Directives:

� 95/16/CE ‘LIFTS’

� 2004/108/CE ‘ELECTROMAGNETIC COMPATIBILITY’

when installed following the instructions from the user guide.

To evaluate the conformity, the following STANDARDS have been taken into consideration:

� UNI EN 81.1: 2010

� UNI EN 81.2: 2010

� UNI EN 12015: 2005

� UNI EN 12016: 2008

DATE: 29-02-2012 SMS SISTEMI E MICROSISTEMI s.r.l. ____________________________

Dr. Eng. VITTORIO MAZZONI MANAGING DIRECTOR

SMS SISTEMI e MICROSISTEMI s.r.l. (Gruppo SASSI HOLDING) Cap. Soc. 260.000€ i.v.

Via Guido Rossa, 46/48/50 40056 Crespellano (BO) Italy R.E.A 272354 CF - Reg. Imprese Bo 03190050371 P.IVA IT 00601981202

Tel. : +39 051 969037 Fax : +39 051 969303 Te chnical Service : +39 051 6720710 Website : www.sms.bo.it E-mail : [email protected]