Motor Protection

31
Test-A-Relay Take a seat where you feel comfortable Help yourself to coffee or tea Please fill in the attendance register. WELCOME Workshop will start at 8:30 Test-A-Relay Administrative Details Workshop program Start.....08.30 Refreshment Break....10.00 to 10.20 Lunch....12.30 to 13.30 approximately Refreshment Break...15.00 to 15.20 Close... 17.00

description

Motor Protection

Transcript of Motor Protection

Test-A-Relay

Take a seat where you feel comfortable

Help yourself to coffee or tea

Please fill in the attendance register.

WELCOME

Workshop will start at 8:30

Test-A-Relay

Administrative Details Workshop programStart.....08.30

Refreshment Break....10.00 to 10.20

Lunch....12.30 to 13.30 approximately

Refreshment Break...15.00 to 15.20

Close... 17.00

Test-A-Relay

Practical

Power Systems Protection

For the Electrical Industry

Test-A-Relay

The LecturerWho am I?I am Dave Duncan and I am employed by TEST-A-RELAY CONSULTING

What is my background?I have been in the protection business for 33 years, both industrial and powertransmission & distribution

Am I contactable after this workshop?Yes

Test-A-Relay

The WorkshopThis workshop is for you!Interaction with you is important.Ask any question - don’t be intimidated by your peers.

Test-A-Relay

The WorkshopRelate any relevant experiences you have to other attendees.Time is precious, please keep any unrelated questions/experience to the breaks.Above all enjoy yourself. A good joke is always welcome.

Beep.TRY THATQUESTION AGAIN.

Test-A-Relay

Topics for the Day Introduction

Need for ProtectionFault Types and their effectsCauses of unbalanceSystem Earthing & Faults

ApplicationProtection calculations

Test-A-Relay

IntroductionWorkhorse of industry

Electrical energy to rotational energy

Squirrel cage induction motors (TEFC) very popular

Expected lifetime of up to 40 years

Test-A-Relay

Motor ProtectionMain Functions

1. To safeguard the motor to ensure continuity of use.

2. To minimise damage and repair costs.

3. To ensure safety of personnel.

Test-A-Relay

Power System ProtectionBasic Requirements

1.Selectivity: to detect and isolate the faulty item only.

2.Stability: to leave all healthy circuits intact to ensure continuity of supply.

3.Speed: to operate as fast as possible when called upon to do so, thereby minimising damage, production downtime and promoting safety to personnel.

4.Sensitivity: to detect even the smallest value of fault current or system abnormalities and operate correctly at its setting.

Test-A-Relay

Types of Motor FailuresFAILURES OF MOTORS

%

a) OVERLOADSb) POLLUTION (corrosive atmosphere)c) PHASE FAILURE (EARTH FAULTS)d) BEARING FAILUREe) AGEING (ambient temp too high)f) ROTOR FAULTSg) MISCELLANEOUS

301914131059

FIGURE 1ACKNOWLEDGEMENT TO SCHNEIDER SA

Test-A-Relay

Main causes of damage

26%

30%

20%

5%

19% Long timeoverheatingInsulation failure

Rotor or bearingfaultFaulty Protection

Other causes

Test-A-Relay

Protective functions needed

26%

30%

20%

5%

19%

Thermal overload

Short circuit & Earthfault

Start-up supervision andthermal sensor unit

Continuous self testing ofprotection relay

Other protectionfunctions/undertectablefaults

Test-A-Relay

Motor Capability Curve

1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0MOTOR CURRENT IN PER UNIT OF FULL LOAD

FIGURE 2 - MOTOR CAPABILITY LIMITS

0.1

1.0

10.0

100

1000

NO

RM

AL O

PER

ATIN

G A

RE

A

MOTOR START CURVE

FAU

LT O

N C

ABLE

OR

IN T

ERM

. BO

X

ROTOR LIMITATION AREASTATOR

LIMITATIONAREA

Test-A-Relay

Temperature rise versus time

Test-A-Relay

Equivalent Circuit of Squirrel cage

Test-A-Relay

Protection PhilosophySelectivity - Stability - Speed - Sensitivity

Emphasis on Speed for the following reasons:To minimise damage and repair costs.To reduce production downtime.To prevent undue thermal and magnetic overstressing of healthy equipment on through fault.To keep voltage depressions as short as possible in the interests of plant stability.Above all, to ensure the safety of personnel.

Test-A-Relay

Power System ProtectionQualities

Test-A-Relay

DependabilityIt must trip when called upon to do so

SecurityIt must NOT trip when it is not supposed to trip.

Test-A-Relay

Time Constants

FIGURE No 3

100%

80%

60%

40%

20%

0%0 1 2 3 4 5

TIME IN TERMS OF t/Tau (Tau = TIME CONSTANT)

HEATING

COOLING

PER

CE

NTA

GE

OF

FIN

AL

TEM

P R

ISE

63%

36%

Test-A-Relay

Fused Protection

FIGURE No 4

FAULT CURRENT IN AMPS

0,1

1

10

10 100 1000 10000

100

1000

TIM

E IN

SEC

ON

DS

CONTACTORCURRENTBREAKING LIMIT

FUSETHERMAL

PROTECT

MOTORFULLLOAD

MOTOR START

Test-A-Relay

Effect of Motor Heating

FIGURE No 5

MULTIPLES OF MOTOR FULL LOAD CURRENT

0,1

1

10

0 1 2 3 4 5 6

100

1000

AB

C

D

A - MOTOR CAPABILITY COLD , Tau = 30minB - P&B GOLD COLD, SET TO 105%, 14minC - P&B GOLD HOT, SET TO 105%, 14minD - MOTOR CAPABILITY HOT, Tau=30min, 10% TIME LEFT

Test-A-Relay

Motor contribution to a Fault

CURRENT INFEED FROM AN INDUCTION MOTOR TO AN EXTERNAL FAULT

10

8

6

4

2

00 5 10 15 20 25TIME FROM BEGINNING OF EXTERNAL FAULT - mS

AM

PS

IN P

ER

UN

I T I

full

loa d

FIGURE No 6

Test-A-Relay

(A) Phase-to-Earth (E) Three Phase-To-Earth

(B) Phase-to-Phase (F) Phase-to-Pilot

(C) Phase-to-Phase-to-Earth (G) Pilot-to-Earth

(D) Three Phase

Test-A-Relay

Motor Unbalance Capability

2 4 6 8 10 12 14

VOLTAGE UNBALANCE (E2/E1 x 100%)

% O

F M

OTO

R F

ULL

LO

AD

FIGURE 7

20

40

60

80

100

Z1/Z2 = 4

Z1/Z2 = 6

Z1/Z2 = 8

REDUCTION OF MOTOR OUTPUT FORWITH UNBALANCED SUPPY VOLTAGES

Test-A-Relay

Typical Motor Start

Test-A-Relay

Motor Current during start

Test-A-Relay

Blocked Rotor Condition

Test-A-Relay

CausesHIGH ROTOR TEMPERATURERS

CAUSED BY

a) TOO LONG A START TIME

c) TOO MANY STARTS WITH

b) A LOCKED ROTOR FAULT WITH LOCKED ROTOR TIME BEING

EXCEEDED

INSUFFICIENT COOLING TIMEBETWEEN STARTS

Test-A-Relay

Effect Of Unbalance

FIGURE No 8

I1

I2

CORRECT ROTATION ANTI CLOCKWISE FOR I1

Test-A-Relay

Positive/Negative/Zero Components

120º 120º

120º

120º 120º

120º

RotationRotation

Vb2

Va0 Vb0 Vc0Vc2 Va2Va1Vc1

Vb1

The Positive, Negative and Zero ComponentsOpposite rotation

Test-A-Relay

120º 120º

120º

120º 120º

120º

RotationRotation

Vc2

Va0 Vb0 Vc0Vb2 Va2Va1Vc1

Vb1

The Positive, Negative and Zero ComponentsSame rotation

Test-A-Relay

Maximum Continuous Output vsVoltage unbalance

Test-A-Relay

Unbalance Measurement

FIGURE 10

TIME

SIGNAL AT POINT `A'

I ave `B'

I ripple `C'

RELAY MEASUREMENTI max - I minI ave

TYPICAL CIRCUIT FOR UNBALANCED 'RIPPLE'

Test-A-Relay

Ratio of Unbalance to I2

1.4

1.5

1.6

1.7

0 60 120 180 240 360

ANGLE OF I WITH REFERENCE TO I2 1

II 2

FIGURE 11

I = I - I MAX MIN

300

FOR

RATIO OF UNBALANCE TO I2

Test-A-Relay

Motor Torques

TOR

QU

E

S=0

S=1S=-1

1è-POS SEQ

1è-NEG SEQ

NORMALVOLTAGE

FIGURE No 12

Test-A-Relay

Unbalance Tripping

2 4 6 8 10 12 14

VOLTAGE UNBALANCE (E2/E1 x 100

% O

F M

OTO

R F

ULL

LO

AD

FIGURE 13b

20

40

60

80

100

RESPONSE OF RELAY FORI FROM AN NPS FILTER

Z1/Z2 = 6

RELAY RESPONSE(DOES NOT VARY WITH PHASE ANGLE OF I2 W.R.T. I1 )

2 4 6 8 10 12 14

VOLTAGE UNBALANCE (E2/E1 x 100%)

% O

F M

OTO

R F

ULL

LO

AD

FIGURE 13a

20

40

60

80

100

RESPONSE OF RELAY FOR Imax - I average

Z1/Z2 = 6

RELAY RESPONSE (VARIES WITH PHASE ANGLE OF I2 W.R.T. I1 )

I average2

Test-A-Relay

Winding Earth Fault

NEUTRAL IMPEDANCE - Z

X%

V fault =

If

Vpn * X/100

If ÷ V fault / Z= X/100 * Vpn / Z

FIGURE No 14

Test-A-Relay

Basic Circuit of High Impedance Current Balance Scheme

Test-A-Relay

Calculation of stability setting

9000 A300/1

300/1

Calculate setting of stabilising resistor for the above REF protection. The relay is a type CAG14, rated 1A with 10-40% setting range (burden = 1.0 va)

Test-A-Relay

Calculation of stability setting

3Ω (Rct)

1Ω (Rl) 1Ω

300/1

30A

300/1

Secondary fault current = 9000 x 1/300 = 30 amps

Relay operating current : Choose 10% tap on CAG14 relay rated at 1 amp.

Relay operating voltage : VA (burden) = 1.0 = 10 volts

I (current) 0.1

Stabilising voltage V = I(Rct + Rl) = 30( 3+1) = 120 volts

Resistor = (120 – 10) / 0.10 = 110/0.10 = 1100 ohms

120 v10v

110v

CAG14

relay

Test-A-Relay

Method of Earth Fault Detection

FIGURE No 15

M

THERMAL ETC

E/FSTAB R

DOTTED LINES SHOW ALTERNATE CT FOR E/F (NO STAB R)

F

NOTE:- CORE BALANCE GIVESNO PROTECTION FOR FAULT F

Test-A-Relay

Ground Fault Protection

Test-A-Relay

Useful Data

FIGURE No 16

FRAME SIZE (shaft height in mm)

AVERAGE THERMAL TIME CONSTANTS Tau IN MINUTES

MOTORDESIGN 355 400 450 500 560 630 710 800 900 1000

ORU

20 25 28 30 35 40 50 60 65 70- - - 45 50 55 60 70 80 90

30 35 40 45 50 - - - - -

O - OPEN TYPER - ENCLOSED WITH FORCED COOLING (DIN IP54)U - COMPLETELY ENCLOSED WITH COOLING RIBS (DIN IP

BBC INDUCTION MOTORS - FRAME SIZE AND DESIGN

Test-A-Relay

Single Phasing

FIGURE No 8a

VR

VR1

VR2

VB1

VB2

VW1

VW2

VWVB

VW-BSINGLE PHASE VOLTAGE

NOTE:- MAGNITUDE V pos = MAGNITUDE V neg = 0.5 V ph-nFOR SINGLE PHASING (NO OTHER LOADS & STARTING)

Test-A-Relay

CausesHIGH ROTOR TEMPERATURERS

CAUSED BY

a) TOO LONG A START TIME

c) TOO MANY STARTS WITH

b) A LOCKED ROTOR FAULT WITH LOCKED ROTOR TIME BEING

EXCEEDED

INSUFFICIENT COOLING TIMEBETWEEN STARTS

Test-A-Relay

Protection with FusesFUSES

a) CANNOT PROVIDE CLOSE THERMAL

b) DO NOT OPERATE FOR SYSTEM UNBALANCE

c) MUST BE SIZED LARGER FOR MULTIPLE

PROTECTION

MAY BE CAUSE OF SINGLE PHASING

STARTS TO COVER TOTAL TIME

DISADVANTAGES FOR MOTOR PROTECTION

Test-A-Relay

Bimetallic StripsBI-METALLIC ELEMENTS

a) TIME CONSTANT NOT FIELD ADJUSTABLE

b) COOLING AND HEATING TIME CONSTANT

c) SINGLE SHAPE CURVE TO COVER THERMAL

EQUAL - NO PROTECTION FOR MULTIPLE

OVERLOAD AND STARTING

RESTARTS

DISADVANTAGES FOR MOTOR PROTECTION

Test-A-Relay

Starting

METHODS OF DETECTION

a) DEFINITE TIME LAG FOR START CURRENT

b) a) PLUS CUMULATIVE START TIME

c) a) PLUS MAXIMUM HOT/COLD STARTSPER HOUR

d) DEPENDENT TIME LAG FOR STARTINGCURRENT (COMBINED WITH MOTOR STATOR TEMPERATURE ie I + 6I )

2

1

2

2

MOTOR STARTING PROTECT

Test-A-Relay

Relay gives stall protection

Test-A-Relay

Relay does not give stall protection

Test-A-Relay

Negative Sequence / Unbalance

MOTOR PROTECTION

a) WEIGHTED COMBINED HEATING EFFECT

b) A DEPENDENT I TIME CHARACTERISTIC

c) AN INDEPENDENT TIME CHARACTERISTIC

d) AN INDEPENDENT TIME CHARACTERISTICBUT OPERATES FOR I - I TOOLARGE

NEGATIVE SEQUENCE

IN THERMAL MODEL (I + 6I )2

1 2

2

2

MAX AVE

Test-A-Relay

Under Voltage ProtectionSYSTEM UNDERVOLTAGE

MOTOR TORQUE IS PROPORTIONAL TO I2

MAX TORQUE @ FULL VOLTAGE USUALLY 200%

100% TORQUE AVAILABLE AT 70% VOLTAGE

UNDERVOLTAGE TRIPPING BELOW 70% VOLTA

POS SEQ. or 3x SINGLE PHASE RELAYS

TRIP BEFORE AN AUTO RECLOSE

BUSBAR VOLTAGE DETECTION SUITABLE FOR A GROUP OF MOTORS

Test-A-Relay

Motor Information

Modern Relays require extra information

Manufacturers cannot always supply the required information

Information is difficult to obtain for old existing motors

Empirical tables may need to be used

Test-A-Relay

Accuracy of Settings

CTs USUALLY HAVE A NEGATIVE ERROR

CLASS 10P10 - 3%

CLASS 5P10 - 1%

-3% ERROR COULD ALLOW 6% OVERLOAD

WHICH WILL REDUCE INSULATION LIFE

THERMAL REPLICA FORMULA

THE RELAY HAS DEFINED INACCURACY (2%)

t = Tau ln I

I - (kI )

where `k' VARIES FROM 1.0 TO 1.05

for different manufacturers

H

B

2

2 2

Test-A-Relay

Additional Options

i) STORAGE OF FAULT DATA

ii) COMMUNICATION PORTS TO ALLOW:-

a) INTERROGATION & SETTING OF RELAY

MICROPROCESSOR RELAYS CAN INCLUDE

b) CONTROL OF BREAKER/CONTACTOR

c) DUAL SETTINGS FOR

DIFFERENT SYSTEM CONDITIONS

iii) MULTIPLE, MATRIX SELECTED OUTPUTS

iv) STARTER FUNCTIONS USED FOR BZone

v) SELF SETTING ADAPTION WITHEXTERNAL TEMPERATURE SENSORS

Test-A-Relay

Motor Bearing Failure

i) FAILURE CANNOT BE DETECTED BY I CHANGING

ii) COMPLETE FAILURE IS VERY RAPID

iii) MOTOR PROTECTED BY STALL PROTECTION

SLEEVE BEARINGS ON LARGER MOTORS

ROLLER / BALL BEARINGS ON SMALL MOTORS

a) FAILURE MODE IS SLOWER THAN BALL

b) TEMPERATURE RISE OF BEARING CAN

BEARINGS

BE USED FOR PROTECTION

ON BEARING FAILURE

c) MOTOR PROTECTED BY STALL PROTECTION

ON BEARING FAILURE

Test-A-Relay

Insulation Classes

A E B F H

CLASS OFINSULATION

AC WINDINGS - >200kW to <5000kW

AC WINDINGS - 600W to ó200kW

PERMANENTLY SHORT CIRCUITED

ROTOR WINDINGS

6060

7575

8080

105 125105 125

TEMPERATURE RISE SHALL

NOT BE DETRIMENTAL TO

OTHER INSULATION

ALLOWABLE TEMPERATURE RISE OF WINDINGS(MEASURED BY RESISTANCE METHOD)

TABLE No 1

A E B F H

CLASS OFINSULATION

ADJUSTMENT DECREASE FACTOR 0.6 0.7 0.8 1.0 1.25ON 1% PER 100m FOR CLASS F

ADJUSTMENT OF TEMPERATURE RISE FOR CLASS F INSULATIONIS 1% FOR EVERY 100m ABOVE 1000m. ADJUSTMENT FIGURESFOR OTHER CLASSES IS GIVEN ABOVE.

Test-A-Relay

Effect of Height above Sea Level

TABLE No 2

CLASS OFINSULATION

ALTITUDE A E B F H35øC 40øC 35øC 35øC 35øC

10001500200025003000

35øC40øC 40øC 40øC 40øC

1,000,97

1,001,001,00 1,001,041,031,011.000.98

0,980,970,950,94

1,031.021,000,980,96

0,980,960,950,93

1.03 1,03 1.021,010,990,970,95

0,980,960,940,92

1,000,970,950,92

0,950,920,89

0,990.960,920,89

0,970,940,900,87

m

MOTOR DERATING FACTORS FOR ALTITUDE AND AMBIENT TEMPERATURE

Test-A-Relay

Thank You

We hope you benefitted from the workshop.

We don’t stop here...

...if you have any further queries or require

help we would be delighted to assist you.

Test-A-Relay

Remember...I can be contacted at any time(012) 665 0545(082) 578 2558

OR

E-mail me at [email protected] [email protected]