Motor Protection
-
Upload
hadrien-faryala -
Category
Documents
-
view
28 -
download
3
description
Transcript of Motor Protection
Test-A-Relay
Take a seat where you feel comfortable
Help yourself to coffee or tea
Please fill in the attendance register.
WELCOME
Workshop will start at 8:30
Test-A-Relay
Administrative Details Workshop programStart.....08.30
Refreshment Break....10.00 to 10.20
Lunch....12.30 to 13.30 approximately
Refreshment Break...15.00 to 15.20
Close... 17.00
Test-A-Relay
Practical
Power Systems Protection
For the Electrical Industry
Test-A-Relay
The LecturerWho am I?I am Dave Duncan and I am employed by TEST-A-RELAY CONSULTING
What is my background?I have been in the protection business for 33 years, both industrial and powertransmission & distribution
Am I contactable after this workshop?Yes
Test-A-Relay
The WorkshopThis workshop is for you!Interaction with you is important.Ask any question - don’t be intimidated by your peers.
Test-A-Relay
The WorkshopRelate any relevant experiences you have to other attendees.Time is precious, please keep any unrelated questions/experience to the breaks.Above all enjoy yourself. A good joke is always welcome.
Beep.TRY THATQUESTION AGAIN.
Test-A-Relay
Topics for the Day Introduction
Need for ProtectionFault Types and their effectsCauses of unbalanceSystem Earthing & Faults
ApplicationProtection calculations
Test-A-Relay
IntroductionWorkhorse of industry
Electrical energy to rotational energy
Squirrel cage induction motors (TEFC) very popular
Expected lifetime of up to 40 years
Test-A-Relay
Motor ProtectionMain Functions
1. To safeguard the motor to ensure continuity of use.
2. To minimise damage and repair costs.
3. To ensure safety of personnel.
Test-A-Relay
Power System ProtectionBasic Requirements
1.Selectivity: to detect and isolate the faulty item only.
2.Stability: to leave all healthy circuits intact to ensure continuity of supply.
3.Speed: to operate as fast as possible when called upon to do so, thereby minimising damage, production downtime and promoting safety to personnel.
4.Sensitivity: to detect even the smallest value of fault current or system abnormalities and operate correctly at its setting.
Test-A-Relay
Types of Motor FailuresFAILURES OF MOTORS
%
a) OVERLOADSb) POLLUTION (corrosive atmosphere)c) PHASE FAILURE (EARTH FAULTS)d) BEARING FAILUREe) AGEING (ambient temp too high)f) ROTOR FAULTSg) MISCELLANEOUS
301914131059
FIGURE 1ACKNOWLEDGEMENT TO SCHNEIDER SA
Test-A-Relay
Main causes of damage
26%
30%
20%
5%
19% Long timeoverheatingInsulation failure
Rotor or bearingfaultFaulty Protection
Other causes
Test-A-Relay
Protective functions needed
26%
30%
20%
5%
19%
Thermal overload
Short circuit & Earthfault
Start-up supervision andthermal sensor unit
Continuous self testing ofprotection relay
Other protectionfunctions/undertectablefaults
Test-A-Relay
Motor Capability Curve
1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0MOTOR CURRENT IN PER UNIT OF FULL LOAD
FIGURE 2 - MOTOR CAPABILITY LIMITS
0.1
1.0
10.0
100
1000
NO
RM
AL O
PER
ATIN
G A
RE
A
MOTOR START CURVE
FAU
LT O
N C
ABLE
OR
IN T
ERM
. BO
X
ROTOR LIMITATION AREASTATOR
LIMITATIONAREA
Test-A-Relay
Protection PhilosophySelectivity - Stability - Speed - Sensitivity
Emphasis on Speed for the following reasons:To minimise damage and repair costs.To reduce production downtime.To prevent undue thermal and magnetic overstressing of healthy equipment on through fault.To keep voltage depressions as short as possible in the interests of plant stability.Above all, to ensure the safety of personnel.
Test-A-Relay
Power System ProtectionQualities
Test-A-Relay
DependabilityIt must trip when called upon to do so
SecurityIt must NOT trip when it is not supposed to trip.
Test-A-Relay
Time Constants
FIGURE No 3
100%
80%
60%
40%
20%
0%0 1 2 3 4 5
TIME IN TERMS OF t/Tau (Tau = TIME CONSTANT)
HEATING
COOLING
PER
CE
NTA
GE
OF
FIN
AL
TEM
P R
ISE
63%
36%
Test-A-Relay
Fused Protection
FIGURE No 4
FAULT CURRENT IN AMPS
0,1
1
10
10 100 1000 10000
100
1000
TIM
E IN
SEC
ON
DS
CONTACTORCURRENTBREAKING LIMIT
FUSETHERMAL
PROTECT
MOTORFULLLOAD
MOTOR START
Test-A-Relay
Effect of Motor Heating
FIGURE No 5
MULTIPLES OF MOTOR FULL LOAD CURRENT
0,1
1
10
0 1 2 3 4 5 6
100
1000
AB
C
D
A - MOTOR CAPABILITY COLD , Tau = 30minB - P&B GOLD COLD, SET TO 105%, 14minC - P&B GOLD HOT, SET TO 105%, 14minD - MOTOR CAPABILITY HOT, Tau=30min, 10% TIME LEFT
Test-A-Relay
Motor contribution to a Fault
CURRENT INFEED FROM AN INDUCTION MOTOR TO AN EXTERNAL FAULT
10
8
6
4
2
00 5 10 15 20 25TIME FROM BEGINNING OF EXTERNAL FAULT - mS
AM
PS
IN P
ER
UN
I T I
full
loa d
FIGURE No 6
Test-A-Relay
(A) Phase-to-Earth (E) Three Phase-To-Earth
(B) Phase-to-Phase (F) Phase-to-Pilot
(C) Phase-to-Phase-to-Earth (G) Pilot-to-Earth
(D) Three Phase
Test-A-Relay
Motor Unbalance Capability
2 4 6 8 10 12 14
VOLTAGE UNBALANCE (E2/E1 x 100%)
% O
F M
OTO
R F
ULL
LO
AD
FIGURE 7
20
40
60
80
100
Z1/Z2 = 4
Z1/Z2 = 6
Z1/Z2 = 8
REDUCTION OF MOTOR OUTPUT FORWITH UNBALANCED SUPPY VOLTAGES
Test-A-Relay
Typical Motor Start
Test-A-Relay
CausesHIGH ROTOR TEMPERATURERS
CAUSED BY
a) TOO LONG A START TIME
c) TOO MANY STARTS WITH
b) A LOCKED ROTOR FAULT WITH LOCKED ROTOR TIME BEING
EXCEEDED
INSUFFICIENT COOLING TIMEBETWEEN STARTS
Test-A-Relay
Effect Of Unbalance
FIGURE No 8
I1
I2
CORRECT ROTATION ANTI CLOCKWISE FOR I1
Test-A-Relay
Positive/Negative/Zero Components
120º 120º
120º
120º 120º
120º
RotationRotation
Vb2
Va0 Vb0 Vc0Vc2 Va2Va1Vc1
Vb1
The Positive, Negative and Zero ComponentsOpposite rotation
Test-A-Relay
120º 120º
120º
120º 120º
120º
RotationRotation
Vc2
Va0 Vb0 Vc0Vb2 Va2Va1Vc1
Vb1
The Positive, Negative and Zero ComponentsSame rotation
Test-A-Relay
Maximum Continuous Output vsVoltage unbalance
Test-A-Relay
Unbalance Measurement
FIGURE 10
TIME
SIGNAL AT POINT `A'
I ave `B'
I ripple `C'
RELAY MEASUREMENTI max - I minI ave
TYPICAL CIRCUIT FOR UNBALANCED 'RIPPLE'
Test-A-Relay
Ratio of Unbalance to I2
1.4
1.5
1.6
1.7
0 60 120 180 240 360
ANGLE OF I WITH REFERENCE TO I2 1
II 2
FIGURE 11
I = I - I MAX MIN
300
FOR
RATIO OF UNBALANCE TO I2
Test-A-Relay
Motor Torques
TOR
QU
E
S=0
S=1S=-1
1è-POS SEQ
1è-NEG SEQ
NORMALVOLTAGE
FIGURE No 12
Test-A-Relay
Unbalance Tripping
2 4 6 8 10 12 14
VOLTAGE UNBALANCE (E2/E1 x 100
% O
F M
OTO
R F
ULL
LO
AD
FIGURE 13b
20
40
60
80
100
RESPONSE OF RELAY FORI FROM AN NPS FILTER
Z1/Z2 = 6
RELAY RESPONSE(DOES NOT VARY WITH PHASE ANGLE OF I2 W.R.T. I1 )
2 4 6 8 10 12 14
VOLTAGE UNBALANCE (E2/E1 x 100%)
% O
F M
OTO
R F
ULL
LO
AD
FIGURE 13a
20
40
60
80
100
RESPONSE OF RELAY FOR Imax - I average
Z1/Z2 = 6
RELAY RESPONSE (VARIES WITH PHASE ANGLE OF I2 W.R.T. I1 )
I average2
Test-A-Relay
Winding Earth Fault
NEUTRAL IMPEDANCE - Z
X%
V fault =
If
Vpn * X/100
If ÷ V fault / Z= X/100 * Vpn / Z
FIGURE No 14
Test-A-Relay
Basic Circuit of High Impedance Current Balance Scheme
Test-A-Relay
Calculation of stability setting
9000 A300/1
300/1
Calculate setting of stabilising resistor for the above REF protection. The relay is a type CAG14, rated 1A with 10-40% setting range (burden = 1.0 va)
Test-A-Relay
Calculation of stability setting
3Ω (Rct)
1Ω (Rl) 1Ω
3Ω
300/1
30A
300/1
Secondary fault current = 9000 x 1/300 = 30 amps
Relay operating current : Choose 10% tap on CAG14 relay rated at 1 amp.
Relay operating voltage : VA (burden) = 1.0 = 10 volts
I (current) 0.1
Stabilising voltage V = I(Rct + Rl) = 30( 3+1) = 120 volts
Resistor = (120 – 10) / 0.10 = 110/0.10 = 1100 ohms
120 v10v
110v
CAG14
relay
Test-A-Relay
Method of Earth Fault Detection
FIGURE No 15
M
THERMAL ETC
E/FSTAB R
DOTTED LINES SHOW ALTERNATE CT FOR E/F (NO STAB R)
F
NOTE:- CORE BALANCE GIVESNO PROTECTION FOR FAULT F
Test-A-Relay
Ground Fault Protection
Test-A-Relay
Useful Data
FIGURE No 16
FRAME SIZE (shaft height in mm)
AVERAGE THERMAL TIME CONSTANTS Tau IN MINUTES
MOTORDESIGN 355 400 450 500 560 630 710 800 900 1000
ORU
20 25 28 30 35 40 50 60 65 70- - - 45 50 55 60 70 80 90
30 35 40 45 50 - - - - -
O - OPEN TYPER - ENCLOSED WITH FORCED COOLING (DIN IP54)U - COMPLETELY ENCLOSED WITH COOLING RIBS (DIN IP
BBC INDUCTION MOTORS - FRAME SIZE AND DESIGN
Test-A-Relay
Single Phasing
FIGURE No 8a
VR
VR1
VR2
VB1
VB2
VW1
VW2
VWVB
VW-BSINGLE PHASE VOLTAGE
NOTE:- MAGNITUDE V pos = MAGNITUDE V neg = 0.5 V ph-nFOR SINGLE PHASING (NO OTHER LOADS & STARTING)
Test-A-Relay
CausesHIGH ROTOR TEMPERATURERS
CAUSED BY
a) TOO LONG A START TIME
c) TOO MANY STARTS WITH
b) A LOCKED ROTOR FAULT WITH LOCKED ROTOR TIME BEING
EXCEEDED
INSUFFICIENT COOLING TIMEBETWEEN STARTS
Test-A-Relay
Protection with FusesFUSES
a) CANNOT PROVIDE CLOSE THERMAL
b) DO NOT OPERATE FOR SYSTEM UNBALANCE
c) MUST BE SIZED LARGER FOR MULTIPLE
PROTECTION
MAY BE CAUSE OF SINGLE PHASING
STARTS TO COVER TOTAL TIME
DISADVANTAGES FOR MOTOR PROTECTION
Test-A-Relay
Bimetallic StripsBI-METALLIC ELEMENTS
a) TIME CONSTANT NOT FIELD ADJUSTABLE
b) COOLING AND HEATING TIME CONSTANT
c) SINGLE SHAPE CURVE TO COVER THERMAL
EQUAL - NO PROTECTION FOR MULTIPLE
OVERLOAD AND STARTING
RESTARTS
DISADVANTAGES FOR MOTOR PROTECTION
Test-A-Relay
Starting
METHODS OF DETECTION
a) DEFINITE TIME LAG FOR START CURRENT
b) a) PLUS CUMULATIVE START TIME
c) a) PLUS MAXIMUM HOT/COLD STARTSPER HOUR
d) DEPENDENT TIME LAG FOR STARTINGCURRENT (COMBINED WITH MOTOR STATOR TEMPERATURE ie I + 6I )
2
1
2
2
MOTOR STARTING PROTECT
Test-A-Relay
Relay gives stall protection
Test-A-Relay
Relay does not give stall protection
Test-A-Relay
Negative Sequence / Unbalance
MOTOR PROTECTION
a) WEIGHTED COMBINED HEATING EFFECT
b) A DEPENDENT I TIME CHARACTERISTIC
c) AN INDEPENDENT TIME CHARACTERISTIC
d) AN INDEPENDENT TIME CHARACTERISTICBUT OPERATES FOR I - I TOOLARGE
NEGATIVE SEQUENCE
IN THERMAL MODEL (I + 6I )2
1 2
2
2
MAX AVE
Test-A-Relay
Under Voltage ProtectionSYSTEM UNDERVOLTAGE
MOTOR TORQUE IS PROPORTIONAL TO I2
MAX TORQUE @ FULL VOLTAGE USUALLY 200%
100% TORQUE AVAILABLE AT 70% VOLTAGE
UNDERVOLTAGE TRIPPING BELOW 70% VOLTA
POS SEQ. or 3x SINGLE PHASE RELAYS
TRIP BEFORE AN AUTO RECLOSE
BUSBAR VOLTAGE DETECTION SUITABLE FOR A GROUP OF MOTORS
Test-A-Relay
Motor Information
Modern Relays require extra information
Manufacturers cannot always supply the required information
Information is difficult to obtain for old existing motors
Empirical tables may need to be used
Test-A-Relay
Accuracy of Settings
CTs USUALLY HAVE A NEGATIVE ERROR
CLASS 10P10 - 3%
CLASS 5P10 - 1%
-3% ERROR COULD ALLOW 6% OVERLOAD
WHICH WILL REDUCE INSULATION LIFE
THERMAL REPLICA FORMULA
THE RELAY HAS DEFINED INACCURACY (2%)
t = Tau ln I
I - (kI )
where `k' VARIES FROM 1.0 TO 1.05
for different manufacturers
H
B
2
2 2
Test-A-Relay
Additional Options
i) STORAGE OF FAULT DATA
ii) COMMUNICATION PORTS TO ALLOW:-
a) INTERROGATION & SETTING OF RELAY
MICROPROCESSOR RELAYS CAN INCLUDE
b) CONTROL OF BREAKER/CONTACTOR
c) DUAL SETTINGS FOR
DIFFERENT SYSTEM CONDITIONS
iii) MULTIPLE, MATRIX SELECTED OUTPUTS
iv) STARTER FUNCTIONS USED FOR BZone
v) SELF SETTING ADAPTION WITHEXTERNAL TEMPERATURE SENSORS
Test-A-Relay
Motor Bearing Failure
i) FAILURE CANNOT BE DETECTED BY I CHANGING
ii) COMPLETE FAILURE IS VERY RAPID
iii) MOTOR PROTECTED BY STALL PROTECTION
SLEEVE BEARINGS ON LARGER MOTORS
ROLLER / BALL BEARINGS ON SMALL MOTORS
a) FAILURE MODE IS SLOWER THAN BALL
b) TEMPERATURE RISE OF BEARING CAN
BEARINGS
BE USED FOR PROTECTION
ON BEARING FAILURE
c) MOTOR PROTECTED BY STALL PROTECTION
ON BEARING FAILURE
Test-A-Relay
Insulation Classes
A E B F H
CLASS OFINSULATION
AC WINDINGS - >200kW to <5000kW
AC WINDINGS - 600W to ó200kW
PERMANENTLY SHORT CIRCUITED
ROTOR WINDINGS
6060
7575
8080
105 125105 125
TEMPERATURE RISE SHALL
NOT BE DETRIMENTAL TO
OTHER INSULATION
ALLOWABLE TEMPERATURE RISE OF WINDINGS(MEASURED BY RESISTANCE METHOD)
TABLE No 1
A E B F H
CLASS OFINSULATION
ADJUSTMENT DECREASE FACTOR 0.6 0.7 0.8 1.0 1.25ON 1% PER 100m FOR CLASS F
ADJUSTMENT OF TEMPERATURE RISE FOR CLASS F INSULATIONIS 1% FOR EVERY 100m ABOVE 1000m. ADJUSTMENT FIGURESFOR OTHER CLASSES IS GIVEN ABOVE.
Test-A-Relay
Effect of Height above Sea Level
TABLE No 2
CLASS OFINSULATION
ALTITUDE A E B F H35øC 40øC 35øC 35øC 35øC
10001500200025003000
35øC40øC 40øC 40øC 40øC
1,000,97
1,001,001,00 1,001,041,031,011.000.98
0,980,970,950,94
1,031.021,000,980,96
0,980,960,950,93
1.03 1,03 1.021,010,990,970,95
0,980,960,940,92
1,000,970,950,92
0,950,920,89
0,990.960,920,89
0,970,940,900,87
m
MOTOR DERATING FACTORS FOR ALTITUDE AND AMBIENT TEMPERATURE
Test-A-Relay
Thank You
We hope you benefitted from the workshop.
We don’t stop here...
...if you have any further queries or require
help we would be delighted to assist you.
Test-A-Relay
Remember...I can be contacted at any time(012) 665 0545(082) 578 2558
OR
E-mail me at [email protected] [email protected]