Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

download Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

of 193

Transcript of Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    1/193

    Most Common Errors in

    Service Entrance and

    Load Side InstallationsPrior to Final DU Inspection

    Industrial and Commercial Buildings

    Primary Voltage / Overhead

    For RME Forum November 28, 2014IIEE Convention

    Presented by : Ray Anthony Rodriguez

    Team Leader- Meralco South CBG Technical Support

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    2/193

    Format of Presentation:

    1. Error Mentioned or Shown2. Relevant Standards or Codes

    3. Possible Corrections (-optional)

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    3/193

    Contents :1. What is Primary Metering?

    2. RME Responsibilities3. Errors

    b. Location of Lightning Arresters

    c. Using ABS instead of LBS

    d. Not Proper Coordinatione. Not Appropriate Transformer BIL

    and Connections

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    4/193

    References :

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    5/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    6/193

    BulacanBulacan

    Metro ManilaMetro Manila RizalRizal

    PampangaPampanga C

    C

    D C

    A C C

    B C C

    CB A ( A) C

    CB B&C (AC A) C

    C E C

    F () C

    . B

    A C

    B D C

    E C, C , C C

    A C

    CC C C

    F . E C

    E C C

    C

    C C

    B

    A B

    ( ) C

    C L C

    Major Load Growth CentersMajor Load Growth CentersMajor Load Growth CentersMajor Load Growth Centers

    CaviteCavite

    LagunaLaguna

    BatangasBatangas

    QuezonQuezon

    CaviteCavite

    LagunaLaguna

    QuezonQuezon

    B C

    F C E C

    C C

    D C

    F C C

    ( )

    F B

    C

    H E

    B B

    C (C )

    ( ) B

    F C C C

    C C

    L L C

    A

    L BA L

    E C

    A

    ( ) H . E (MEALAND) L

    L

    E L

    A G L

    C

    C

    C

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    7/193

    Generation - Transmission - Distribution

    Power Plants Transmission Lines

    7

    SubstationTransformers &

    Equipment

    DistributionLines &

    Transformers

    Customers

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    8/193

    C

    /B

    &

    C

    /+ /+ /+ /+

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    9/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    10/193

    M

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    11/193

    , O I,CO

    D = 5 30

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    12/193

    M

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    13/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    14/193

    Registered Master Electricians

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    15/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    16/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    17/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    18/193

    Most Common Errors in

    Service Entrance and

    Prior to Final DU Inspection

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    19/193

    Not Enough Clearance

    from other Conductors,Buildin s Structures and

    Trees

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    20/193

    Upper Level

    Conductors

    Open

    Secondary

    upto 750V

    Primary upto

    13.8 kV Y or

    Delta 34.5Y/20 kV 115 kVLower Level

    Conductors/ Nature of

    Surface

    mm (ft-in) mm (ft-in) mm (ft-in) mm (ft-in)

    Railroad Tracks

    7500 (24' 7") 8100 (26' 7'') 8100 (26' 7'') 8580 (28' 2")

    Vertical Clearance of Wires, conductors or cables above ground, etc,

    when it crosses over or overhang the surface

    D

    ,

    other areas subject to

    truck traffic

    5000 (16' 5") 5600 (18' 4") 5600 (18' 4") 6080 (19' 11")

    Driveways,parking lots

    and alleys

    5000 (16' 5") 5600 (18' 4") 5600 (18' 4") 6080 (19' 11")

    Spaces and ways

    subject to pedestrians

    or restricted traffic only

    3800 (12' 6") 4400 (14' 5") 4400 (14' 5") 4880 (16')

    13.8 kV Y or Delta470 (1' 7") 600 (2') 660 (2' 2") 1160 (3' 10")

    34.5Y/20 kV530 (1' 9") 660 (2' 2") 725 (2' 4") 1220 (4')

    115 kV 1030 (3' 5") 1160 (3' 10") 1220 (4') 1720 (5' 7")

    Vertical Clearance at Supports Between Line Conductors

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    21/193

    Distance from DUPrimary Metering

    Pole Is less than 5

    meters

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    22/193

    Too Near to DU Pole and Lines

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    23/193

    F6 G C B

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    24/193

    Not Enough Working ClearanceBetween Poles and Insulators

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    25/193

    Too Near to Buildings

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    26/193

    Too Near to DU Primary Lines

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    27/193

    Vertical Clearance Between Supply ConductorsSupported on the Same Structure

    For 34.5/ 20 kV lines = 725 mm or 2 4

    Clearances Between Wires Conductors or

    Cables Carried on Different SupportingStructures

    For 34.5/ 20 kV lines onlyHorizontal = 1500 mm

    Vertical = 600 mm

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    28/193

    Distance from DU

    Primary Metering

    Pole Is less than 5

    meters

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    29/193

    Working Clearance and distance from building

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    30/193

    Not Enough Working Clearance

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    31/193

    N E C

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    32/193

    E C

    & B

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    33/193

    Crisscrossing of DU

    and Customers Wiresalso clearances

    Sangley Point Navy & Air Force

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    34/193

    Not Enough Clearances

    from Buildings

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    35/193

    Not Enough Clearances

    from Buildings

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    36/193

    Upper Level

    Conductors

    Open

    Secondary

    upto 750V

    Primary upto

    13.8 kV Y or

    Delta 34.5Y/20 kV 115 kVLower Level

    Conductors/ Nature of

    Surface

    mm (ft-in) mm (ft-in) mm (ft-in) mm (ft-in)

    Railroad Tracks

    7500 (24' 7") 8100 (26' 7'') 8100 (26' 7'') 8580 (28' 2")

    Vertical Clearance of Wires, conductors or cables above ground, etc,

    when it crosses over or overhang the surface

    D

    ,

    other areas subject to

    truck traffic

    5000 (16' 5") 5600 (18' 4") 5600 (18' 4") 6080 (19' 11")

    Driveways,parking lots

    and alleys

    5000 (16' 5") 5600 (18' 4") 5600 (18' 4") 6080 (19' 11")

    Spaces and ways

    subject to pedestrians

    or restricted traffic only

    3800 (12' 6") 4400 (14' 5") 4400 (14' 5") 4880 (16')

    13.8 kV Y or Delta470 (1' 7") 600 (2') 660 (2' 2") 1160 (3' 10")

    34.5Y/20 kV530 (1' 9") 660 (2' 2") 725 (2' 4") 1220 (4')

    115 kV 1030 (3' 5") 1160 (3' 10") 1220 (4') 1720 (5' 7")

    Vertical Clearance at Supports Between Line Conductors

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    37/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    38/193

    :

    (..

    E

    ,

    , .).

    F ,

    (5)

    .

    D = M = 5

    3C3C

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    39/193

    3C3C

    DISTRIBUTORSDISTRIBUTORS

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    40/193

    OLD COSMOSOLD COSMOS SANSAN PEDROPEDRO

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    41/193

    OLD FORDOLD FORD

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    42/193

    SHIN HEUNGSHIN HEUNG

    SAMSUNGSAMSUNG

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    43/193

    SAMSUNGSAMSUNG

    CPIPCPIP

    CALTEXCALTEX

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    44/193

    CALTEXCALTEX

    BIANBIAN

    CPIP andCPIP and CarmelrayCarmelray 22

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    45/193

    CPIP andCPIP and CarmelrayCarmelray 22

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    46/193

    BOY SCOUTBOY SCOUT

    OF THE PHILS, LOS BAOSOF THE PHILS, LOS BAOS

    HV SWITCHGEAR BHV SWITCHGEAR B

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    47/193

    HV SWITCHGEAR BHV SWITCHGEAR B

    BESIDE METERING POLEBESIDE METERING POLE

    PNCC SLEXPNCC SLEX

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    48/193

    PEC Part 2 Table 3.4.6.3 (a) on 115 kV

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    49/193

    PEC Part 2 Table 3.4.6.3 (a) on 115 kV

    E l f 115 KV S b t ti

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    50/193

    Example of 115 KV Substations

    E ample of 115 KV S bstations

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    51/193

    Example of 115 KV Substations

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    52/193

    LindenLinden STA ROSA 115 KVSTA ROSA 115 KV

    YAZAKIYAZAKI

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    53/193

    TORRESTORRES

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    54/193

    ABI,ABI, CabuyaoCabuyao

    CPIPCPIP BatinoBatino

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    55/193

    CPIP,CPIP, BatinoBatino

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    56/193

    ALL ABO ABOE 600

    EC . 1 1 A 1.10.3.1 1. 10.3.6

    CHAE 1. AICLE 1.10 E I

    1.10.3 O 600 N 47

    1.10.3.2 M D F L 48

    1.10.3.5() M D C

    E E 52

    1.10.3.5() E L A 53

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    57/193

    ALL ABO ABOE 600

    EC . 1 1 A 2.25.1.14 2.25.1.26

    CHAE 2. AICLE 2.25 O B C F

    2.25.3 O 600 132 2.25.3.11 C , ,

    , , O L 135

    2.25.3.12 C B O 135

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    58/193

    ALL ABO ABOE 600

    EC . 1 1 A 3.0.2.1 3.0.2.12

    CHAE 3. AICLE 3.0 M

    . . ,

    3.0.2.20 M C 330

    EC . 1 1 A 4.90.2.4

    CHAE 4. AICLE 4.9 E O 600

    4.90.2.4 M 790 4.90.2.4 M C L 791

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    59/193

    - Distance from distribution lines Article 3.4.5.3 from PEC 2008part 2 pp.140-147 .

    - Height wrt to distribution poles Table 3.4.10.5 (b) (1)a p.194 fromPEC 2008 part 2.

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    60/193

    - Distance between conductors orpersonnel Article 3.4

    Clearance between wires,conductors or cables at

    supports,

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    61/193

    Table 3.4.6.2 (a) (2) a

    Horizontal clearance betweenline conductor smaller than

    sags.

    from PEC 2008 part 2 pp.162-164

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    62/193

    - Clearance from trees Article3.4.5.3 from PEC 2008 part 2

    pp.1471 PEC 2009 part1 vol.1

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    63/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    64/193

    Location of Lightning Arresters

    Should be located at the Highest Point

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    65/193

    Should be located at the Highest Point

    Due to Lightning Strikes

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    66/193

    A

    D

    Mall STAMall STA ROSAROSA

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    67/193

    Below the

    Load Break Switch

    Should be above orThe same level

    CalambaCalamba IndustrialIndustrial

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    68/193

    Below the

    Load Break Switch

    Should be above orThe same level

    Right Sample

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    69/193

    Lightning Arrester Above all

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    70/193

    Right Sample -Lightning Arrester

    Same Height of

    LBS

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    71/193

    A

    N

    () DL

    A :

    *

    MCOM C O

    MCO

    34.5 27 22 C II

    13.8 12 10 C II

    13.2 12 10 C II

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    72/193

    - Lightning arrester location Article 2090.3.11 p275-281 fromv .

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    73/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    74/193

    Using Air Break Switches

    Instead ofLoad Break Swithces

    A B

    .

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    75/193

    . A H

    .

    .

    .

    A B

    . . , ,

    . A A B L

    .

    A B

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    76/193

    Air Break Switch

    A

    .

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    77/193

    .

    D

    . A ,

    , .

    .

    A ( F6)

    .

    .

    L B

    Load Break Switch

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    78/193

    Load Break Switch

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    79/193

    Load Break Switch

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    80/193

    & :

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    81/193

    LOAD BEAK ICH

    , ,

    (C O)

    . :

    N

    F

    C

    C

    M

    (A)

    B

    II

    L

    H A (, .)

    13.2 14.4 60 40 95

    13.8 14.4 60 40 110

    34.5 34.5 60 30 110

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    82/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    83/193

    Not Proper Coordination

    Of Protective Devices

    : M C I

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    84/193

    Bank 1

    83 MVA

    Bank 2

    83 MVA

    Install 2 units of Synchro-check

    relay at CIP II Substation for CBs

    61SD4/62SD4 and 61SD8/62SD8

    : M C I

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    85/193

    SUBSTATION 1

    Tap115 kV Line

    Bk2

    83 MVA

    Bk1

    83 MVA

    SUBSTATION 3Bk350 MVA

    SUBSTATION 2

    Bank 1

    33 MVABank 2

    33 MVA

    62WW2463WW24Install 2 units of Synchro-check

    relay at FPIP Substation for CBs

    62WW24/63WW24

    61SD4

    61SD8

    62SD4

    62SD8

    63XE8

    63XE24

    Install 1 unit of Synchro-check

    relay at Canlubang Substation

    for 63XE8/24

    SUBSTATION 4

    Customers S/S

    M

    Customers Steam TurbineGenerators

    Construction of 4.6 km, 1-795 MCM ACSR

    conductor per phase from tapping point at FPIP-

    Los Baos 115 kV Line to MGPP Switchyard

    Install N.C. 115 kV LineDisconnect Switch and2 units LAs

    Bank 1

    33 MVA

    Bank 2

    115 kV-13.8 kV

    25 MVA

    Bank 1

    115 kV-13.8 kV

    25 MVA

    G2 G1

    SUBSTATION 5

    63WT4

    61WT4

    Install 2 units of Synchro-check

    relay at Los Baos Substation

    for 63WT4/61WT4

    64ZX4

    Install 1 unit of Synchro-

    check relay at Calauan

    Substation for 64ZX4

    Install 1 unit of 115 kV PT

    Install 2 units of 115 kV PTs

    Below 115 kV

    Legend:230 kV

    115 kV

    Proposed 115 kV

    for MGPP

    115 kV SCF & Metering

    : M B F D

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    86/193

    Protection Coordination

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    87/193

    Time,sec

    10

    100

    50

    5

    30E

    1,000A 2,000A

    1A

    34.5

    = 16.7A

    = 1,000A

    3 = 2,000A

    M =

    30E

    16.7 1.6 = 26.72 30E

    Current, amp

    0.01

    0.1

    0.5

    0.05

    10

    100

    1000

    10000

    10000 0

    50

    500

    5000

    5000 0

    Breaker Ground

    Delay Curve

    Breaker Ground

    Inst. Curve

    Breaker Phase

    Delay Curve

    Breaker Phase

    Inst. Curve

    MMT curve TCT curve

    C

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    88/193

    Using Maximum Rating

    Instead of proper coordinationWith DU rotection

    M F L

    O D

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    89/193

    O D

    M F L

    O D

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    90/193

    O D

    C F

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    91/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    92/193

    Power Fuse or

    Fuse Cutouts ?

    Power Fuses

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    93/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    94/193

    Fuse Cutouts

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    95/193

    F C

    F C I I B

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    96/193

    N

    F

    C

    C

    I

    C

    I

    B

    I

    I

    L

    H A . (, .)

    13.2 14.4 60 16 5 95

    13.8 14.4 60 16 5 110

    34.5 34.5 60 16 5 200

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    97/193

    Power Fuse or Fuse Cutouts ?

    C F

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    98/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    99/193

    Multiple Set of

    Power Fuses

    M F

    B F

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    100/193

    B F

    /C

    J O (1)

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    101/193

    J O (1) F

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    102/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    103/193

    Not Appropriate

    Transformer Specificationsand Connections

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    104/193

    C:

    ,

    .

    TRANSFORMER CONNECTON(Advantages and Disadvantages)

    Case I. Delta Grounded Wye

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    105/193

    Case I. Delta Grounded Wye(Recommended why?)

    Advantages:

    1. Complete symmetry and currents with respect to the three (3)lines to neutral.

    2. It provides two different values of secondary voltage instead of

    one; i.e -480/277v. (Less expensive in design compared todelta delta connections in terms of insulation).

    3. Stable neutral because of the delta, primary and good current

    balance; i.e., overall loading can be closely balanced.

    4. Most satisfactory connection due to a wide applications in LVdistribution systems, i.e., commercial buildings of power andlighting service.

    Disadvantages:

    1. It is also susceptible to ferroresonance *, especially during 1sequential switching when energized in series with cable

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    106/193

    sequential switching when energized in series with cablecapacitance to ground.

    2. The bank cannot be parallel with D-D or Y-Y banks because ofthe phase difference of 30 degrees between line voltages ofthe banks on the secondary side.

    * F

    .

    I

    ( ) ( ). I

    , .

    I ,

    .

    3

    (3) .

    ,

    ,

    A. Advantage to Distribution Utility

    1. Any unbalancing of load the secondary will just becontained at the primary System neutral current will not

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    107/193

    contained at the primary. System neutral current will notbe affected.

    B. Advantage to Wye Grounded Secondary to Customer

    1. Smaller fault current.

    2. Fault in any leg will be readily isolated. (In delta connectedsecondary, it is necessary to have two legs on before itcan be isolated. If only any one legs on faulty, it isnecessary to wait for a fault on another leg before it canbe isolated.

    3. Economy in insulation, since than delta connectedsecondary.

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    108/193

    Case IV. Grounded Wye Delta:

    Ad t

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    109/193

    Advantages:

    1. Drastically reduces the possibility of ferroresonance.

    2. In case of fuse blowing of one line on the primary, 3-phasepower is continued to be served the secondary. It operatesas an open type-open delta bank and a the wye connection

    continues to carry the load as much a 58% of a closed.

    3. All voltages are balanced and no roving neutrals arepresent.

    Disadvantages:

    1 Transformer bank acts as grounding transformer for fault

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    110/193

    1. Transformer bank acts as grounding transformer for faultexternal to itself.

    2. Unbalanced in load between phases cause current to flowin other wye-delta transformer banks connected to thesame line.

    3. If transformer normally carries 100% load, fuse blowing none line on the primary will cause the remaining twophases (open wye - open delta operation) overload by 73%.

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    111/193

    G di B k

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    112/193

    Grounding Bank

    Transformer

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    113/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    114/193

    BIL B I L. I

    , .

    BIL:

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    115/193

    , .

    BIL

    .

    , .

    .

    I ,

    .

    ,

    .

    > & C

    O E / D

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    116/193

    B

    B I I L(, M)

    D A . . .

    D 95 95 150

    , C

    95 110 150

    110 110 200

    D 110 110 200

    ANSI- IEEE and IEC on BIL

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    117/193

    ?

    A 34.5 :

    F ANI 100 BIL

    A 36 :

    F IEC 70 BIL

    ANSI- IEEE and IEC on BIL

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    118/193

    ?

    L E

    E (EE)

    IEC

    ANIIEEE

    C .

    D ? ( )

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    119/193

    . ( )

    .

    (400 , 200 , 110 , 66 , 33) 200MA.D .

    (11, 6.6 , 3.3 , 440, 230) 200 MA.

    A , . A

    , .

    . H,

    .

    .

    .

    I .

    .I , C D.( F

    L)

    I (H), C D (F

    L) B D , B G

    ( D ).

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    120/193

    4. Insulator KV rating Table 3.8.4.1.p.245 from PEC 2008 part 2 ora e . . . p. .

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    121/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    122/193

    LBS Handle

    Not Connected to

    roun ng a

    No Grounding Mat

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    123/193

    Operating handle not grounded

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    124/193

    LB H NO C

    G M O G

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    125/193

    G M C LB H

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    126/193

    L

    G M C LB H

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    127/193

    LB H

    G M

    G M C LB H

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    128/193

    G M E

    I

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    129/193

    G M E

    I

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    130/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    131/193

    - Grounding mat connection and

    material Article 2.90.3.20 -. . . . -

    2009 vol.

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    132/193

    Most Common Errors in

    Service Entrance InstallationsP i t Fi l DU I ti

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    133/193

    Prior to Final DU Inspection

    -End of Presentation-

    Industrial and Commercial Buildings

    Primary Voltage / OverheadFor RME Forum November 28, 2014

    IIEE Convention

    Presented by : Ray Anthony Rodriguez

    Team Leader- Meralco South CBG Technical Support

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    134/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    135/193

    Addendum 1

    y u

    Standard Clearances

    D C

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    136/193

    D C

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    137/193

    Vertical Line Configuration

    Horizontal Line Configuration

    Pole with Vertical Line andHorizontal Line Configuration

    Triangular Line Configuration

    The applicants primary distribution

    Customer-Owned Facilities

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    138/193

    pp p y

    facilities and substation shall comply withthe provisions of the latest edition of the

    Philippine Electrical Code regarding

    safety and clearance requirements.

    Vertical Clearance of Conductors Above

    Ground or Other Surfaces

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    139/193

    D C

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    140/193

    SAG = measured vertically from conductor (below itsend points) to the straight line joining its

    t/ ti l d f th id i t f

    Sag

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    141/193

    support/vertical drop of the mid-point of a span

    of conductor below its end supports.

    SPAN = horizontal distance between support points

    141

    Level Span

    Vertical Clearance Between Supply Conductors

    Supported on the Same Structure

    For 34 5/ 20 kV lines = 725 mm or 2 4

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    142/193

    For 34.5/ 20 kV lines = 725 mm or 2 4

    Clearances Between Wires Conductors or

    Cables Carried on Different Supporting

    Structures

    For 34.5/ 20 kV lines only

    Horizontal = 1500 mmVertical = 600 mm

    F

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    143/193

    F

    Horizontal and Vertical ClearanceBetween Conductors

    F

    C

    Clearances In Any Direction from Line

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    144/193

    Conductors to Supports and to Verticalor Lateral Conductors, Span or Guy

    Wires Attached to the Same Support

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    145/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    146/193

    Clearances of Wires, Conductors,

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    147/193

    Cables and Rigid Energized Parts fromBuildings, Signs, Chimneys, Radio and

    TV Antennas, Tanks and Other

    Installations Except bridges

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    148/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    149/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    150/193

    PEC Requirements

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    151/193

    151

    Outermost face of building

    D C

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    152/193

    3,000 mm clearance

    boundary

    (minimum)

    Property

    Plant strip/

    Side walk

    facilities

    / B C.

    CLEARANCES FROM BUILDINGS

    T LEGEND:

    V

    VH

    T T

    D C

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    153/193

    ARE PROHIBITEDCONDUCTORS

    REGIONS WHERE

    CLEARANCECONTROLLING

    V

    T

    H

    V

    H

    H

    VT T

    HH

    Vertical (Arc)

    Vertical

    T

    V

    HorizontalH

    / B C.

    T

    T TV

    T

    CLEARANCES FROM OTHER STRUCTURES

    D C

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    154/193

    VT H

    TV

    LEGEND:

    REGIONS WHERES I G N77H H

    V

    H

    T

    VT

    H

    H

    CONDUCTORS

    ARE PROHIBITED

    H H

    V

    H

    V T

    Vertical (Arc)

    H Horizontal

    Vertical

    T

    V

    CONTROLLINGCLEARANCE

    / B C.

    Minimum Clearance (in Millimeters) of Exposed/Non-insulatedWires, Conductors, Cables, and Unguarded Rigid Energized

    Parts Adjacent but Not Attached to Buildings and Other

    Installations Except Bridges

    D C

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    155/193

    Meralco System Voltage, kV

    6.24/3.6, 13.8/7.96, 34.5/20 115Clearance of

    Conductors Rigid Parts

    Conductors

    1. Buildings

    a. Horizontal(1) To walls, projections,and guarded windows

    2 300 2 000 2 750

    (2) To unguarded windows 2 300 2 000 2 750

    (3) To balconies and areas

    readily accessible topedestrians

    2 300 2 000 2 750

    b. Vertical(1) Over or under roofs orprojections not readilyaccessible to pedestrians

    3 800 3 600 4 250

    (2) Over or under balconiesand roofs readily accessible

    4 100 4 000 4 550

    D C

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    156/193

    and roofs readily accessible

    to pedestrians(3) Over roofs accessible tovehicles but not sub ect to

    4 100 4 000 4 550

    truck traffic(4) Over roofs accessible to

    truck traffic

    5 600 5 500 6 050

    2. Signs, chimneys,billboards, radio andtelevision antennas, tanks,and other installations notclassified as buildings orbridgesa. Horizontal 2 300 2 000 2 750b. Vertical (over or under) 2 450 2 300 2 900

    CH < (HB HM)/2

    :

    HB = Height of the building

    above ground

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    157/193

    above ground

    HM = Height of the topmost

    measured at the same

    level of reference as the

    building

    CH = Horizontal clearance

    between the outermost

    face of the building and

    the nearest part of

    Meralco facilities

    Horizontal ClearanceBetween Conductors Bounding

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    158/193

    the Climbing Space

    For 34.5/ 20 kV lines = 1000 mm

    C

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    159/193

    Approach Distance to Energized Parts

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    160/193

    For 34.5/ 20 kV lines only- -

    Phase-to-Phase = 770 mm

    For Outdoor Substation:

    Minimum Required Distance

    For 34.5/ 20 kV lines

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    161/193

    Vertical & HorizontalClearance from Buildings = 3048 mm

    Center-to-center phase spacing for buses = 915 mm

    Center-to-center phase spacing for switching = 1219 mmPhase-to-Ground = 610 mm

    Between lines of different voltages = 1067 mm

    Source: PEC 2009 Vol. 1 Part 1

    Article 1.10.3.1 to 1.10.3.6

    A D

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    162/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    163/193

    General Guidelines

    Measurement of Clearances and Spacings

    Unless otherwise specified, clearances shall be measured from

    D E C

    E A F

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    164/193

    surface to surface and spacings shall be measured center to

    .

    For clearance purposes, live metallic hardware electrically

    connected to line conductors shall be considered part of the line

    conductors shall be considered part of the line conductors.

    Metallic bases of surge arresters, cutouts and other similar

    devices shall be considered as part of the supporting structure.

    General Guidelines

    Covered Conductors

    Covered conductors (including tree wires) shall be considered as

    D E C

    E A F

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    165/193

    bare conductors for all clearance requirements

    General Guidelines

    Reduction in Clearance Requirements

    The clearances shown in this guideline may be reduced

    D E C

    E A F

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    166/193

    particularly in cases where the PEC specifically allows or where

    .

    All reductions in clearances shall conform to allowable limit set

    by PEC.

    Specific Guidelines

    Horizontal Clearance of Supporting Structure from other Objects

    Poles, support arms and equipment attached thereto, and braces

    D E C

    E A F

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    167/193

    shall have the following clearances from other objects. The

    objects concerned.

    Specific Guidelines

    Horizontal Clearance of Supporting Structure from other Objects

    Along streets, roads and highways

    D E C

    E A F

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    168/193

    Where there are no curbs, supporting structures should be

    ,

    right-of-way to avoid contact with ordinary vehicles.

    Location of overhead utility installations on highways with narrow

    right-of-way or on urban streets with closely abutting

    improvements are special cases which must be resolved in a

    manner consistent with prevailing limitations and conditions (PEC

    Part 2 2000, Sect. 3.4.2.1 [b][1]).

    Specific Guidelines

    Horizontal Clearance of Supporting Structure from other Objects

    From Railroad Tracks

    D E C

    E A F

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    169/193

    For overhead lines crossing or in parallel with railroad tracks, all

    , , ,

    and equipment attached thereto that are less than 6700 mm above

    track rail shall be located not less than 3600 mm from the said

    track rail. At industrial sidings (i.e., short railroad tracks

    connected to the main track), a clearance of not less than 2130

    mm is permitted (Fig. 3)

    Specific Guidelines

    Overhead Line Clearance

    Vertical Clearance of Conductors above Ground or other Surfaces

    D E C

    E A F

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    170/193

    The vertical clearances specified for conductors above ground

    . . . . . . .

    be applied at any point in the span. These clearances shall be

    maintained considering the maximum span and highest

    temperature that can be attained by the conductors during

    operation.

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    171/193

    Add d 2

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    172/193

    Addendum 2

    Case II. Grounded Wye Grounded Wye

    Provided Transformers are:A. Single-Phase Type )

    B. Three (3) Phase Shell Type ) Why?C. Three (3) Phase Five (5) legged Core-Type )

    Advantages:

    A 1 I id diff l f d l

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    173/193

    A. 1. It provides two different values of secondary voltagesinstead of one. (20 KV-139/278V or 34.5 KV-

    2. Availability of single phase (1) circuits with only oneconductor run (1 to N voltage)

    3. Economical in terms of insulation.4. Provides path for ground current, sufficient for protective

    devices to detect and operate.5. Suited to systems having high line voltages and relatively

    low currents.6. Best connection to minimize if not totally illuminate the

    occurrence of ferroresonance.

    Single phase sequential switching at the fuse disconnects does

    not produce a ferroresonant condition since transformer magnetizingreactance are not energized in series with the cable capacitance. Thecable capacitance is merely a load on one phase to neutral and is notin series with the transformer magnetizing reactance.

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    174/193

    7. It makes it possible to ground all three phases symmetrically

    phase source, making it almost fool proof.

    8. Low KV rating of LAs together with discharge spark overvoltage which is consonant with BIL requirement oftransformer as well as other associated equipment thuseconomy in design of the system is achieved.

    Additional four (4) oscillograph studies showed that with sinewave voltages between lines, the line to neutral voltages of the Y-Y

    banks about 60% third harmonic component.

    9. Three phase Shell Type & 5 legged Core Type

    I 3 t f f h ll t 5 l d t

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    175/193

    In a 3 transformer of shell-type or 5-legged core- type,react in the same manner as a (3) - 1 distribution-

    neutral connected to system neutral. The recommendedconnection is free from ferroresonant overvoltageconditions.

    10. Distribution Utility recommends 5-legged core type and not3-legged core type to avoid problems of tank heating due to

    unbalances loading condition, or secondary faults whichcause a primary fuse to open.

    Disadvantages:

    1. Necessitates tertiary windings to stabilize the neutralpotential in the primary wye and to suppress thirdharmonic currents.

    2. Severe induction voltages to telephone lines in case of line to

    gro nd fa lt

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    176/193

    ground fault.

    . ree- egge core type trans ormer exper ences tan eat ng,specially during unbalanced loading.

    Remedy: With the use of five-legged core type transformer,shell type transformers or to provide with a lowresistance lines installed in a 3-legged core type willact as a path for the magnetic flux.

    4. Deviation of voltage from the theoretical one duringunbalanced load condition.

    NOTES:

    a) If the primary neutral is not connected to the source

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    177/193

    a) If the primary neutral is not connected to the source,unbalanced load causes a roving neutral. (Roving neutral not stable neutral)

    b) If the neutral wire is connected from the source to the neutralof the primaries, each phase can work independently of theother; any unbalanced in current is then carried by theneutral.

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    178/193

    Case III. Delta Delta Connection

    Advantages:

    1. No third harmonic current will occur.

    2. Failure of one phase can still operate as an open delta.

    3 Sh i f l d di t th i d f h h

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    179/193

    3. Sharing of load according to the impedance of he phases.

    has a high impedance, therefore, it tends to take a smallershare of the load.

    4. Availability of balanced symmetrical voltage and currentswith load or at no load.

    5. Tank heating is minimized.

    Disadvantages:

    1. Higher KV rating of arrester needed thereby increase ininvestment of equipment is necessary.

    2. No path for sufficient ground current could be provided

    thus preventing protection devices to be applicable

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    180/193

    thus preventing protection devices to be applicable.

    . rov es on y a s ng e va ue o secon ary vo age noprovided with neutral)

    4. At least two conductors or ones could be made to supplysingle phase loads.

    5. Higher cost, more insulation required.

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    181/193

    Case V. Ungrounded Primary Wye and Grounded Wye Secondary

    with Delta Tertiary:

    1 This set-up eliminates the 3rd harmonic problems and

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    182/193

    1. This set-up eliminates the 3 harmonic problems and.

    2. The zero sequence reactance Xo, at the delta, provides the

    path for the zero sequence current, it has a very low Xoreactance in its grounded wye in a set-up.

    Advantages to Distribution Utility any unbalancing of load at thesecondary will just be contained at the primary systemneutral current will not be affected.

    Advantages to customer of Grounded Wye secondary:

    1. Smaller fault current.

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    183/193

    1. Smaller fault current.

    2. Fault in any leg of the secondary will be readily isolated.Does not need to wait for a fault on another leg as in delta

    connection.

    3. Less insulation than DELTA connected.

    Disadvantages:

    1. Susceptible to ferroresonance

    Advantages: Single Phase

    1. Same as wye grounded secondary advantages to

    customer

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    184/193

    customer.

    3. Tank heating eliminated

    4. Lower first cost

    Three Phase

    1. Must be shell type or 5 legged core type to eliminate tankheating.

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    185/193

    Addendum 3

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    186/193

    Addendum 3u

    Primary-Metered Service

    M

    I

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    187/193

    I

    (O)

    C F (CF)

    , I,CO

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    188/193

    , I,CO

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    189/193

    20 / 34.5

    I M

    I L L

    (3 .../3 C...)

    20 / 34.5

    I M

    I L L

    (3 .../3 C...)

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    190/193

    M

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    191/193

    M

    20 / 34.5

    I M

    I L L

    (3 .../3 C...)

    20 / 34.5

    I M

    I L L

    (3 .../3 C...)

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    192/193

  • 7/25/2019 Most Common Errors in Service Entrance and Load Side Installations Prior to Final DU Inspection

    193/193