Module 5 understaning disability access provisions
-
Upload
michael-farrugia -
Category
Education
-
view
103 -
download
0
description
Transcript of Module 5 understaning disability access provisions
National Construction Code Training Program
MODULE 5
Understanding theDisability Access Provisions
Content of Module 5
• Part 1 - Introduction to Module 5• Part 2 - Background to Access Provisions• Part 3 - Performance Requirements• Part 4 - Deemed-to-Satisfy Provisions • Part 5 - Administrative Matters
PART 1
Introduction to Module 5
Introduction to Module 5• This Module is one of a series produced by
the Australian Building Codes Board (ABCB); the organisation responsible for the development and maintenance of the Building Code of Australia (BCA)
• For the purposes of this presentation it is assumed that participants have a general understanding of how the BCA works
Part 1 - Introduction to Module 5
Module 1 - recap
• Module 1 was titled ‘An Introduction to the Building Code of Australia’
• The objective of Module 1 was to provide information on:– the background to the development of the BCA – the operation of the BCA, and – the application of the BCA
Part 1 - Introduction to Module 5
Module 1 - recap
• BCA applies to all new building work. This includes:• new buildings• renovations or upgrades to existing buildings
Part 1 - Introduction to Module 5
Module 1 - recap • The BCA establishes minimum acceptable
standards for new building work• The BCA:
• is referenced in State/Territory law • is amended annually• requirements are intended to be cost effective• is intended to eliminate poor practice • does not address best practice
Part 1 - Introduction to Module 5
Module 1 - recap
• Volume One contains requirements for the design and construction of commercial buildings, i.e. Class 2 to 9 buildings, plus some Class 10 building matters
• Volume Two contains requirements for the design and construction of domestic buildings, i.e. Class 1 and 10 buildings
Part 1 - Introduction to Module 5
Module 2 - recap
• Module 2 was titled ‘Understanding the BCA’s Performance Requirements’
• The objective of Module 2 was to provide information on how to comply with the BCA without using Deemed-to-Satisfy Provisions, i.e. by developing an Alternative Solution
Part 1 - Introduction to Module 5
Building Solutions
Performance Requirement
Functional Statement
Objective
Alternative SolutionsDTS Provisions
Guidance
Mandatory
Methods of achieving compliance
Documentary Evidence
Verification Methods
Expert Judgement
Comparative Analysis AssessmentMethods
Part 1 - Introduction to Module 5
MODULE 5 Understanding the Disability
Access Provisions
Objective of Module 5
• The objective of Module 5 is to provide basic information on BCA provisions for people with disability relating to Class 1b, Class 2 to 9 buildings, as well as Class 10 buildings
• Information is also available from the ABCB website: www.abcb.gov.au
Part 1 - Introduction to Module 5
People with disability
• Broad definition of disability includes people who-
– are blind or have low vision; – have learning or intellectual disabilities; – are deaf or hearing-impaired; – have a physical disability; – experience mental health or psychological difficulties;
and – people with an acquired brain injury.
Part 1 - Introduction to Module 5
Principle of access
• Provide safe, equitable and dignified access to buildings, and facilities and services within buildings
Part 1 - Introduction to Module 5
PART 2 Background to NCC Access Provisions
General background• Disability access requirements have been in
the BCA since 1990• Focus was on access to commercial and
public buildings (Classes 3, 5-9)
Part 2 - Background to Access Provisions
BCA access provisions• BCA has historically required access for
people with disability to be provided:– to a building– within a building (including lifts, signage and
hearing augmentation)– to certain carparking spaces– to suitable sanitary facilities
Part 2 - Background to Access Provisions
BCA scope• The BCA only addresses the physical fabric
and layout of a building, it does not:– address the fixtures and fittings such as furniture
or reception desks used in a building– address some wayfinding information such as
room numbers or general signs– address management policies or staff behavior
Part 2 - Background to Access Provisions
The challenge of inconsistent laws
• The Disability Discrimination Act (DDA) has applied to buildings since 1993
• Complaints could be made about the level and quality of access a building provided
• Buildings could comply with the BCA, but still be subject to a successful DDA complaint
• Uncertainty for building industry
Part 2 - Background to Access Provisions
Achieving consistency
• In 2001, Federal Gov’t asked ABCB to develop proposals to address inconsistency
• Resulted in the development of Premises Standards and BCA amendments to align the two
Part 2 - Background to Access Provisions
Development of Premises Standards
• Developed through stakeholder committees, specialist working groups and specialist consultants
• Proposals were refined through extensive industry and community consultation
• Draft provisions subjected to formal regulatory impact analysis process
Part 2 - Background to Access Provisions
Regulation Impact Statement (RIS)
• All proposals for new regulation, including the Premises Standards and changes to the BCA, are subjected to a rigorous regulation impact assessment process that includes cost benefit analysis
• The Premises Standards RIS is available from the ABCB website
Part 2 - Background to Access Provisions
Benefits for industry
• In addition to improving access, RIS process sought to ensure new requirements:– are cost-effective– can be reasonably achieved– provide the greatest certainty possible
Part 2 - Background to Access Provisions
Background to new requirements
• 1995: Building Access Policy Committee (BAPC), established by ABCB, begins its work on progressive changes to the BCA
• 2001: Gov’t asks ABCB to develop proposals for Premises Standards and changes to BCA
Part 2 - Background to Access Provisions
Background to new requirements
• 2005: Draft Premises Standards and a Regulation Impact Statement released for public comment
• 2006: ABCB develops revised proposals and a revised Regulation Impact Statement following consideration of public comment
Part 2 - Background to Access Provisions
Background to new requirements• 2008: Draft Disability (Access to Premises –
Buildings) Standards (Premises Standards) tabled in Parliament and referred to a House of Representatives Committee to conduct a public inquiry
• 2009: Parliamentary Committee makes recommendations in its report Access All Areas
Part 2 - Background to Access Provisions
Background to new requirements• February 2010: Government responds to
report and finalises Premises Standards
• 2010: ABCB aligns BCA to reflect content of Premises Standards
• 1 May 2011: Premises Standards and BCA 2011 adopted
Part 2 - Background to Access Provisions
Premises Standards structure• Premises Standards comprise:
– Parts 1 – 6 including trigger dates and objectives, scope, exceptions and concessions and review information
– Access Code for Buildings which provides the Performance Requirements and Deemed-to-Satisfy Provisions
Part 2 - Background to Access Provisions
Achieving consistency• Relevant provisions in Parts 1 – 6 are to be
reflected in State and Territory building control systems
• Access Code is reflected in BCA
• Compliance with the BCA will ensure compliance with the Access Code
Part 2 - Background to Access Provisions
Voluntary best practice• The Premises Standards and BCA contain the
minimum requirements for access
• Some project briefs may require a higher standard
• Best practice and innovation is still possible and encouraged
Part 2 - Background to Access Provisions
PART 3 Disability Access
Performance Requirements
Parts D3, E3, and F2 of Volume One
Key Performance Requirements
• Key Performance Requirements relating to access:– DP1 Access to a building– DP2 Access within a building– DP6 Travel path to an exit– DP8 Accessible carparking– DP9 Communication system for hearing impaired– EP3.4 Lifts– FP2.1 Sanitary facilities
Part 3 - Performance Requirements
Overall access objectives• To provide, as far as is reasonable, people
with safe, equitable and dignified access to:– a building; and– the services and facilities within a building
Part 3 - Performance Requirements
• Access must be provided to enable people to:– approach a building from the road boundary,
associated accessible building and associated accessible carparking space
– get into a building and to all areas normally used by occupants including toilets
– identify accessible facilities
DP1 - overview
Part 3 - Performance Requirements
DP2 - overview• People must be able to move safely to and within a building
• Special attention should be paid to:
– walking surfaces – doors
– ramps – stairways
– landings – handrails
Part 3 - Performance Requirements
DP6 - overview• People must be able to safely evacuate the
building
• Building use and the characteristics of the occupants, including their mobility, must be considered
Part 3 - Performance Requirements
DP8 - overview• Carparking spaces suitable for use by people
with disability must be provided
• Spaces must be marked and easy to find
Part 3 - Performance Requirements
DP9 - overview• An inbuilt communication system, such as a
lecture theatre PA system, must be suitable for people who are deaf or have a hearing impairment
Part 3 - Performance Requirements
EP3.4 - overview• When a passenger lift is provided in a building
required to be accessible, it must be suitable for use by people with disability.
Part 3 - Performance Requirements
FP2.1 - overview• Sanitary facilities suitable for use by people
with disability must be provided at convenient locations
Part 3 - Performance Requirements
PART 4 Disability Access
Deemed-to-Satisfy Provisions
Deemed-to-Satisfy Provisions• One method of meeting Performance
Requirements
• Compliance with Deemed-to-Satisfy Provisions of BCA ensures compliance with Deemed-to-Satisfy Provisions of Access Code
Part 4 - Deemed-to-Satisfy Provisions
Parts D3, E3, F2 and H2
• Part D3 covers general building access requirements
• Part E3 covers lifts• Part F2 covers accessible toilets and showers• Part H2 covers requirements for public
transport buildings
Part 4 - Deemed-to-Satisfy Provisions
D3.1 General access requirements
Part 4 - Deemed-to-Satisfy Provisions
D3.1 – General requirements
• Table D3.1 sets out which buildings and parts of buildings have to be accessible
• Different classes of buildings have different access requirements
Part 4 - Deemed-to-Satisfy Provisions
Some useful terms
• Accessible means having features to enable use by people with disability.
• Accessway means a continuous, accessible path of travel (as defined in AS 1428.1) to, into or within a building.
Part 4 - Deemed-to-Satisfy Provisions
References to Australian Standards
• AS 1428.1 contains technical information on the construction of accessways, for example:– dimensions and clearances at doorways– design of handrails– layout of accessible toilets
Part 4 - Deemed-to-Satisfy Provisions
Class 1b – small hostels, B&B• Specifies number of dwellings required to be
accessible
• Specifies number of bedrooms and sanitary facilities required to be accessible
• Specifies common areas required to be accessible in B&Bs, guest houses etc
Part 4 - Deemed-to-Satisfy Provisions
Class 2 – apartment blocks • Access required from a pedestrian entrance to the
front doors of sole-occupancy units (SOU) on at least one level
• Common areas required to be accessible including BBQ area, gym, pool
• If other levels are served by a lift or ramp, similar access must be provided on those levels
Part 4 - Deemed-to-Satisfy Provisions
Class 3 – hotels and motels• Access required from a pedestrian entrance to the
front doors of sole-occupancy units (SOU) on at least one level
• Specifies common areas required to be accessible including BBQ area, gym, pool
• If other levels are served by a lift or ramp, similar access must be provided on those levels
Part 4 - Deemed-to-Satisfy Provisions
Class 3 – hotels and motels• Specifies the number of accessible SOUs
required depending on size of hotel/motel
• Specifies location and groupings of accessible SOUs to ensure choice
Part 4 - Deemed-to-Satisfy Provisions
Classes 5, 6, 7, 8 and 9a • To and within:
– all areas normally used by the occupants
• Class 7a (carparking)– to and within any level containing accessible
carparking spaces
Part 4 - Deemed-to-Satisfy Provisions
Class 9b – educational/assembly• For schools, early childhood centres and
universities etc.– to all areas normally used by the occupants
• For assembly buildings such as cinemas or concert halls– to all areas normally used by the occupants, but not
every tier or level if no wheelchair seating spaces are provided on that level
Part 4 - Deemed-to-Satisfy Provisions
Class 9c – aged care• Requirements for aged care facilities are
essentially the same as for Class 3 buildings, including access to specified common areas and numbers of accessible SOUs
Part 4 - Deemed-to-Satisfy Provisions
Class 10a – toilet block/shelter• If located in an accessible area access is
required to and within an accessible toilet, change room or shelter
Part 4 - Deemed-to-Satisfy Provisions
Class 10c – swimming pool• Swimming pools, other than private pools,
with a perimeter greater than 40 m are required to provide some means of access into the pool
Part 4 - Deemed-to-Satisfy Provisions
D3.2 Access to buildings
Part 4 - Deemed-to-Satisfy Provisions
Access to buildings• D3.2 covers the requirements for access:
– to a building from the allotment boundary;
– between associated accessible buildings;
– to a building from accessible carparking spaces on the allotment
Part 4 - Deemed-to-Satisfy Provisions
Access to buildings• D3.2 also specifies:
– number of accessible entrances required– number of accessible doorways required when
there are multiple doorways at an entrance– where a required accessible doorway has multiple
leaves, one of the leaves must have a clear opening width of at least 850 mm
Part 4 - Deemed-to-Satisfy Provisions
D3.3 Parts of a building to be accessible
Part 4 - Deemed-to-Satisfy Provisions
Parts of buildings to be accessible
• D3.3 covers:– ramps and stairways– passenger lifts– passing and turning spaces on corridors– small building concession– carpet pile height
Part 4 - Deemed-to-Satisfy Provisions
D3.3 - Ramps
• Ramps are a way of providing a continuous accessible path of travel between levels
• Ramps must comply with AS 1428.1
• Concessions for fire-isolated ramps
Part 4 - Deemed-to-Satisfy Provisions
D3.3 - Stairways• Stairways cannot form part of a continuous
accessible path of travel but where provided, must meet certain requirements
• Stairways must comply with AS 1428.1
• Concessions for fire-isolated stairways
Part 4 - Deemed-to-Satisfy Provisions
D3.3 - Lifts• D3.3 requires every passenger lift to comply
with E3.6, which provides the detailed requirements for passenger lifts
Part 4 - Deemed-to-Satisfy Provisions
D3.3 - Passing and turning spaces• Passing spaces are required every 20 m
along an accessway where a clear line of sight is not possible
• Turning spaces are required every 20 m along an accessway and within 2m of a dead-end
• Specifications for passing and turning spaces are in AS 1428.1
Part 4 - Deemed-to-Satisfy Provisions
D3.3 - Small building concession• While generally access is required to all levels of
buildings, there is a concession for certain small buildings
• In some 2 and 3 storey buildings where the storeys, other than the entrance storeys, are each under 200 m2, an accessible ramp or lift does not have to be provided to those storeys
Part 4 - Deemed-to-Satisfy Provisions
D3.3 - Carpet pile height
• While the use of carpets on an accessway is allowed, if the carpet pile is too high it would make movement in a wheelchair difficult
• A combined pile carpet height and backing thickness of up to 15 mm is allowed
Part 4 - Deemed-to-Satisfy Provisions
Additional features• While D3.3 specifically refers to design
features such as ramps and stairways, the general requirement to comply with AS 1428.1 applies to other accessible features such as:– doors and doorways– switches and controls
Part 4 - Deemed-to-Satisfy Provisions
Doorways• for doorways, AS 1428.1 provides
specifications for:– clear opening dimensions– force for opening– circulation space around doorway– luminance contrast– door controls
Part 4 - Deemed-to-Satisfy Provisions
Door controls
1. Round knob 3. ‘D’ type2. ‘Lever’ type
Part 4 - Deemed-to-Satisfy Provisions
D3.4 Exemptions
Part 4 - Deemed-to-Satisfy Provisions
Exemptions
• D3.4 allows exemptions from general rule of access to all areas
• Exemptions need to be assessed on a case-by-case basis
• This is no different to other parts of the BCA where professional judgement is required
Part 4 - Deemed-to-Satisfy Provisions
Exemptions• Areas which pose a
health or safety risk or are otherwise inappropriate for people with disability (such as a foundry floor or rigging loft) are exempt
Part 4 - Deemed-to-Satisfy Provisions
D3.5 Accessible Carparking
Part 4 - Deemed-to-Satisfy Provisions
Carparking• If a carpark is provided in a building or in a
carparking area on the same allotment, accessible carparking spaces must be provided
• Accessible carparking spaces must be designated with signage if more than 5 spaces in total
Part 4 - Deemed-to-Satisfy Provisions
Carparking
• Proportion of accessible carparking spaces determined by Table D3.5
• Accessible carparking spaces must comply with AS/NZS 2890.6
Part 4 - Deemed-to-Satisfy Provisions
Carparking
5400
240024002400
Shared areas
Accessible space
Accessible space
Bollard
Parking aisle or roadway
2400
Part 4 - Deemed-to-Satisfy Provisions
D3.6 Signage
Part 4 - Deemed-to-Satisfy Provisions
Signage
• BCA contains requirements for certain signage related directly to building matters, including:– identification of all sanitary facilities – location and type of hearing augmentation – directional information in some situations
Part 4 - Deemed-to-Satisfy Provisions
Signage - toilets
• All toilets must be identified using tactile and braille signage in addition to male/female signage
• All accessible unisex toilets must incorporate the international symbol of access
• All accessible unisex toilets must identify if the toilet is left or right hand transfer
• If there is no accessible unisex toilet at a bank of toilets, directional signage must be provided indicating the closest accessible toilet
Part 4 - Deemed-to-Satisfy Provisions
Non-compliant signage
Part 4 - Deemed-to-Satisfy Provisions
Signage - hearing augmentation
• Identify a room with hearing augmentation using the international symbol for deafness
• Within the room, indicate:– type of system– area covered – if receivers are being used, where a receiver can be
obtained
• Braille and tactile signage requiredPart 4 - Deemed-to-Satisfy Provisions
Signage - entrances
• Directional information including the international symbol of access is required at an inaccessible entrance to identify the location of the nearest accessible entrance
Part 4 - Deemed-to-Satisfy Provisions
Specification D3.6 Braille and tactile signage
Part 4 - Deemed-to-Satisfy Provisions
Specification D3.6
• Provides details in relation to the:
– design;
– location; and
– luminance contrast
required for braille and tactile signs
Part 4 - Deemed-to-Satisfy Provisions
Braille and tactile sign location• Signs should be at an
accessible height - between 1200 mm and 1600 mm from the floor
Part 4 - Deemed-to-Satisfy Provisions
Braille and tactile sign location• A person reading braille
should not be at risk of injury from opening doors or pedestrian traffic
Part 4 - Deemed-to-Satisfy Provisions
D3.7 Hearing augmentation
Part 4 - Deemed-to-Satisfy Provisions
Hearing augmentation
• A hearing augmentation system is required:– in a room in a Class 9b building, eg cinema– in an auditorium, conference room, meeting room or
room used for judiciary purposes– at any ticket office, teller booth or reception area
where the public is screened from service provider
…. but only if the room has an in-built amplification system
Part 4 - Deemed-to-Satisfy Provisions
Hearing augmentation
• Area covered depends on system used– Induction loop - 80% of the floor area– Receiver based systems such as radio frequency
or infrared systems - 95% – Ratio of receivers set out in D3.7
• Emergency-only systems are exempt
• Scoreboard or screen announcements
Part 4 - Deemed-to-Satisfy Provisions
D3.8 Tactile indicators
Part 4 - Deemed-to-Satisfy Provisions
Tactile indicators
• To assist blind people and people with low vision, tactile ground surface indicators (TGSIs) are used to facilitate safe movement around buildings
• BCA only requires warning (hazard alert) TGSIs
• Technical details of TGSIs are in AS/NZS 1428.4.1
Part 4 - Deemed-to-Satisfy Provisions
Examples of warning TGSIs
Part 4 - Deemed-to-Satisfy Provisions
Tactile indicators
• Required at the top and bottom of stairs, escalators, moving walkways and ramps
• Also required where a person might encounter an overhead obstruction where no barrier exists
• Not required on fire-isolated stairs and fire-isolated ramps or those which lead to areas exempted under D3.4
Part 4 - Deemed-to-Satisfy Provisions
Example of when TGSIs might be required because of the danger of the overhead obstruction created by an open stairway
Part 4 - Deemed-to-Satisfy Provisions
D3.9 Wheelchair seating spaces in Class 9b assembly buildings
Part 4 - Deemed-to-Satisfy Provisions
Wheelchair seating spaces• If fixed seating is provided in a Class 9b
assembly building, such as a cinema or stadium, wheelchair seating spaces must also be provided
• Spaces must be available in single and grouped configurations
• Table D3.9 specifies number of spaces to be provided
Part 4 - Deemed-to-Satisfy Provisions
Wheelchair seating spaces• In small cinemas (up to 300 seats), wheelchair
seating spaces cannot be placed in the front row
• In larger cinemas (over 300 seats), 75% of wheelchair seating spaces must be in rows other than the front row
Part 4 - Deemed-to-Satisfy Provisions
D3.10 Swimming pools
Part 4 - Deemed-to-Satisfy Provisions
Swimming pools• A swimming pool required to be accessible by
Table D3.1, and with a perimeter of more than 40 m, must be provided with at least one means of access into the pool
• Latches on swimming pool gates are not required to be at an accessible height
Part 4 - Deemed-to-Satisfy Provisions
Accessible pool entry• Options include:
– fixed or movable ramp and aquatic wheelchair– zero depth entry and aquatic wheelchair– platform lift and aquatic wheelchair– Sling-style lift
Part 4 - Deemed-to-Satisfy Provisions
Specification D3.10
• Provides detailed specifications for the different forms of access into pools including:– dimensions– slip resistance– weight capacity– handrails
Part 4 - Deemed-to-Satisfy Provisions
D3.11 Ramps
Part 4 - Deemed-to-Satisfy Provisions
Ramp limitation
• A series of connected ramps must not have a combined vertical rise of more than 3.6 m
• A landing for a step ramp must not overlap a landing for another step ramp or ramp
Part 4 - Deemed-to-Satisfy Provisions
1:14 ramp
1200 landing
1200 landing
1200 landing
Step ram
p
1:14 ramp
1200 landing
1200 landing
1200 landing
Step ram
p
1200 landing
Part 4 - Deemed-to-Satisfy Provisions
D3.12 Glazing on an accessway
Part 4 - Deemed-to-Satisfy Provisions
Glazing on an accessway
• Visual indicators must be provided on frameless or fully glazed doors, sidelights and other glazing that might be mistaken for a door or opening if there is no chair rail, handrail or transom
Part 4 - Deemed-to-Satisfy Provisions
Glazing on an accessway
• If relying on marking the glass, must comply with AS 1428.1
Part 4 - Deemed-to-Satisfy Provisions
E3.6 Passenger lifts
Part 4 - Deemed-to-Satisfy Provisions
Passenger lifts• Passenger lifts must be suitable for use by
people with disability
• A variety of lift types can be used. However, Table E3.6a contains limitations on the use of some types of lifts
Part 4 - Deemed-to-Satisfy Provisions
Passenger lifts
• Table E3.6b describes the features required on lifts such as handrails, lighting, control buttons and dimensions
• If a lift car is fully enclosed, it must not rely on a constant pressure device to operate it
Part 4 - Deemed-to-Satisfy Provisions
Part 4 - Deemed-to-Satisfy Provisions
F2 Sanitary facilities
Part 4 - Deemed-to-Satisfy Provisions
F2.4 Accessible sanitary facilities
• Requires accessible unisex toilets be provided in accordance with Table F2.4(a)
• Requires accessible unisex showers be provided in accordance with Table F2.4(b)
• Specifies requirements for ‘ambulant accessible’ toilet cubicles
Part 4 - Deemed-to-Satisfy Provisions
F2.4 Accessible unisex toilets• Accessible unisex toilets must be provided:
– in buildings required to be accessible and containing toilets
– on every accessible storey where there are toilets
• However …
Part 4 - Deemed-to-Satisfy Provisions
Accessible unisex toilets• Where male and female banks are at separate
locations, an accessible unisex toilet is only required at one of the locations
• Where there is more than one bank of male and female toilets on a floor an accessible unisex toilet is only required at 50% of banks
Part 4 - Deemed-to-Satisfy Provisions
Accessible unisex toilets• Exceptions and exemptions:
– toilets on a floor not required to be accessible under the small building concession (D3.3(f)) are not required to have accessible toilets
– toilets in an area not required to be accessible under D3.4 Exemptions are not required to include accessible unisex toilets
Part 4 - Deemed-to-Satisfy Provisions
Accessible unisex toilets• Must comply with circulation space, fixture and
fittings requirements in AS 1428.1
• Must contain closet pan, washbasin, shelf or bench top, means of sanitary towel disposal
• Must not be accessed through an area reserved for one gender
Part 4 - Deemed-to-Satisfy Provisions
Part 4 - Deemed-to-Satisfy Provisions
Accessible unisex toilets
• Where multiple accessible unisex toilets are provided in a building, they should be provided for both left and right transfer in numbers as even as possible
Part 4 - Deemed-to-Satisfy Provisions
‘Ambulant accessible cubicles’
• A toilet cubicle suitable for people with an ambulant disability must be provided if there is a toilet cubicle in addition to an accessible unisex toilet at a bank
• Details for design and fit out are in AS 1428.1
Part 4 - Deemed-to-Satisfy Provisions
Accessible unisex showers
• Table F2.4(b) provides requirements for accessible unisex showers depending on the Class of building
• Design specifications for accessible unisex showers are found in AS 1428.1
Part 4 - Deemed-to-Satisfy Provisions
H2 Public transport buildings
Part 4 - Deemed-to-Satisfy Provisions
H2 Public transport buildings
• Passenger use areas of public transport buildings like airports or railway stations are generally Class 9b and Class 10
• These buildings are subject to sometimes different requirements because of the earlier Disability Standards for Accessible Public Transport 2002
Part 4 - Deemed-to-Satisfy Provisions
Part H2
• H2 takes precedence where different to other BCA requirements
• H2 refers to different editions of Australian Standards for elements such as accessways, ramps, stairways, signage, lifts and doorways – check which edition applies
Part 4 - Deemed-to-Satisfy Provisions
PART 5 State and Territory
Administrative Matters
State and Territory matters• BCA provides a model code, but State and
Territory building laws and regulations may include additional material
• Relevant provisions in Parts 1 – 6 of the Premises Standards are to be reflected in changes to State and Territory building law or systems
Part 5 - Administrative Matters
State and Territory matters
• Different application for new and existing buildings in some situations
• Triggers for ‘affected part’ upgrades
• Questions of possible ‘unjustifiable hardship’
Part 5 - Administrative Matters
Existing buildings
• Existing Class 1b and Class 2 buildings treated differently
• Existing lifts travelling more than 12 m floor space concession
• Existing accessible unisex toilets circulation space and fitout concession
Part 5 - Administrative Matters
Affected part
• Affected part is the path of travel from the principle pedestrian entrance to any new work in an existing building
• Access upgrades are required if the building approval applicant is the owner or the lessee if they occupy the whole building
Part 5 - Administrative Matters
Unjustifiable hardship
• Premises Standards allows for a defense of unjustifiable hardship in some situations
• Access Panels or similar• Check with your State or Territory building
control administration to find out how this is considered in your area
Part 5 - Administrative Matters
Any questions?