![Page 1: Models: PMNFP14A0 PMNFP14A1 PGNFP14A0gscs-b2c.lge.com/downloadFile?fileId=KROWM000179967.pdf · *Note: See the PI 485 manual for the internal setting. *Note: Because the RS485 communication](https://reader030.fdocuments.in/reader030/viewer/2022041303/5e13e9ca44f020744d02cf7c/html5/thumbnails/1.jpg)
ENG
LISHLGPI485 for Outdoor UnitINSTALLATION MANUAL
LG
IMPORTANT
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it thoroughly.
Visit us at : http://www.lgservice.com
Models: PMNFP14A0PMNFP14A1 PGNFP14A0
ITALIA
NO
ESPAÑ
OL
FRA
NÇ
AIS
DEU
TSCH
CH
INESE
![Page 2: Models: PMNFP14A0 PMNFP14A1 PGNFP14A0gscs-b2c.lge.com/downloadFile?fileId=KROWM000179967.pdf · *Note: See the PI 485 manual for the internal setting. *Note: Because the RS485 communication](https://reader030.fdocuments.in/reader030/viewer/2022041303/5e13e9ca44f020744d02cf7c/html5/thumbnails/2.jpg)
2 485 Gateway(M)
PI 485 INSTALLATION MANUAL
TABLE OF CONTENTS
� Safety Precautions.........................................................3~4
� Part Description .................................................................5
� Accessory Parts .................................................................6
� Installation Guide .........................................................7~11
� Installation Steps........................................................................................7
� DIP Switch Configuration...........................................................................8
� Simple Central Controller Connection Diagram........................................9
� PC / Deluxe Central Controller Connection Diagram ............................10
� How to connect the base station controller .............................................11
![Page 3: Models: PMNFP14A0 PMNFP14A1 PGNFP14A0gscs-b2c.lge.com/downloadFile?fileId=KROWM000179967.pdf · *Note: See the PI 485 manual for the internal setting. *Note: Because the RS485 communication](https://reader030.fdocuments.in/reader030/viewer/2022041303/5e13e9ca44f020744d02cf7c/html5/thumbnails/3.jpg)
ENG
LISHSafety Precautions
Installation Manual 3
Don't touch with thehands while the power ison
• There is risk of fire or electricshock.
Use standardparts(connector).
• Do not disassemble or repairthe product. There is risk of fireor electric shock.
For electrical work, contactthe dealer, seller, a qualifiedelectrician, or an AuthorizedService Center.
• Do not disassemble or repairthe product. There is risk of fireor electric shock.
� Installation
ON
L1 2 3 4
KSDO4H
ON
L1
2 3
4
KSD
O4H
ON
L1
2 3
4
KSD
O4H
Safety PrecautionsTo prevent injury to the user or other people and property damage, the following instructionsmust be followed.� Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
� Meanings of symbols used in this manual are as shown below.
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
Be sure not to do.
Be sure to follow the instruction.
WARNING
![Page 4: Models: PMNFP14A0 PMNFP14A1 PGNFP14A0gscs-b2c.lge.com/downloadFile?fileId=KROWM000179967.pdf · *Note: See the PI 485 manual for the internal setting. *Note: Because the RS485 communication](https://reader030.fdocuments.in/reader030/viewer/2022041303/5e13e9ca44f020744d02cf7c/html5/thumbnails/4.jpg)
Safety Precautions
4 485 Gateway(M)
When the product is soaked (flooded orsubmerged), contact an Authorized ServiceCenter.• There is risk of fire or electric shock.
Be cautious that water could not enter theproduct.
• There is risk of fire, electric shock, or productdamage.
ON
L1
2 3
4
KSD
O4H
ON
L1
2 3
4
KSD
O4H
� Operation
Use the correctly ratedbreaker or fuse.
• There is risk of fire or electricshock.
Do not install, remove, or re-install the unit by yourself(customer).
• There is risk of fire, electricshock, explosion, or injury.
For installation, alwayscontact the dealer or anAuthorized Service Center.
• There is risk of fire, electric
shock, explosion, or injury.
ON
L1
2 3
4
KSD
O4H
ON
L1
2 3
4
KSD
O4H
ON
L1
2 3
4
KSD
O4H
![Page 5: Models: PMNFP14A0 PMNFP14A1 PGNFP14A0gscs-b2c.lge.com/downloadFile?fileId=KROWM000179967.pdf · *Note: See the PI 485 manual for the internal setting. *Note: Because the RS485 communication](https://reader030.fdocuments.in/reader030/viewer/2022041303/5e13e9ca44f020744d02cf7c/html5/thumbnails/5.jpg)
ENG
LISHPart Description
Installation Manual 5
Part DescriptionPMNFP14A0 / PMNFP14A1 / PGNFP14A0
PI485 GATEWAY(M)
CN_PWR: AC 220V Connector
+10V: DC 10V Terminal
GND: Ground
BUS_A: *RS-485 (+) Terminal(Refer to note)
BUS_B: RS-485 (-) Terminal
CN_OUT: Outdoor Unit Connector
LED1:RS-485 Status LED
DIP Switch: Product Selection (Refer to the DIP Switch Configuration )
LED01G, 02G, 03G: Communication Status LED
Reset Switch: PI485(M) Reset
CN_DRY: DRY Contact
ON L1
2 3
4
KSDO
4H
1
23456
7891011
1
234
5
6
78910
11
✽ The location of parts might be different in case of PMNFP14A1.PMNFP14A0 : For connecting 1 ~ 16 Indoor UnitsPMNFP14A1 : For connecting 1 ~ 48 Indoor UnitsPGNFP14A0 : For connecting only base controller
* Note : RS-485 is one of the international interface standards for serial communication.
![Page 6: Models: PMNFP14A0 PMNFP14A1 PGNFP14A0gscs-b2c.lge.com/downloadFile?fileId=KROWM000179967.pdf · *Note: See the PI 485 manual for the internal setting. *Note: Because the RS485 communication](https://reader030.fdocuments.in/reader030/viewer/2022041303/5e13e9ca44f020744d02cf7c/html5/thumbnails/6.jpg)
Acceassory Parts
6 485 Gateway(M)
Acceassory Parts
ON L1
2 3
4
KSDO
4H
PI485 : PMNFP14A0(1EA) or PMNFP14A1(1EA) or PGNFP14A0(1EA)
BRACKET (1EA)
Multi-V
Multi-V MPS Multi
WIRE ASSY 1(1EA)
SCREW (4EA)
WIRE ASSY 2(1EA) WIRE ASSY 3(1EA)
Others : Tie Wrap (3 EA) - Cable TieClamp (1 EA)
![Page 7: Models: PMNFP14A0 PMNFP14A1 PGNFP14A0gscs-b2c.lge.com/downloadFile?fileId=KROWM000179967.pdf · *Note: See the PI 485 manual for the internal setting. *Note: Because the RS485 communication](https://reader030.fdocuments.in/reader030/viewer/2022041303/5e13e9ca44f020744d02cf7c/html5/thumbnails/7.jpg)
Installation Guide
Installation Manual 7
ENG
LISH
Installation Steps
1. Connect CN_OUT with Outdoor Unit by the cable (provided)
2. Connect RS-485 BUS_A(+) and BUS_(B)(-) with other network products (ex.Central Controller , I-Gateway.....)
3. In case of using Simple Central Controller, connect VCC(+10V) and GND. No need to connect otherwise.
4. Select DIP Switch Configuration(Refer page 8)
5. Connect CN_PWR with Outdoor PCB Power connector (Refer page 9, 10)
6. After Power is ON, check the Communication LED- LED1G(Red)
• Normal : LED blinks for 5 times and then gets OFFThis process is repeated after every 3 minutes
• Error : Check the Indoor Unit's address & wiring connections- LED2G(Yellow), LED3G(Orange)
• Normal : LED blinks continuously• Error : Check the DIP Switch setting & wiring connections
7. Check RS-485 Communication Status LED: • Normal : LED's blinks 2 times in every 10~30 seconds • Error : Check the wiring connections
8. Finally if all of the above steps are OK, then tie the cables by tie wraps & clamp
Installation Guide
6
8
1
7
9
4 5
2 3
* Example about Multi V plus
CAUTION: Install the PI485 on the Noise Filter in Multi V plus. Install the PI485 after checking the hole for screw.
![Page 8: Models: PMNFP14A0 PMNFP14A1 PGNFP14A0gscs-b2c.lge.com/downloadFile?fileId=KROWM000179967.pdf · *Note: See the PI 485 manual for the internal setting. *Note: Because the RS485 communication](https://reader030.fdocuments.in/reader030/viewer/2022041303/5e13e9ca44f020744d02cf7c/html5/thumbnails/8.jpg)
Installation Guide
8 485 Gateway(M)
ON L1
2 3
4
KSDO
4HON KSDO 4H
ON KSDO4H
ON KSDO4H
ON KSDO4H
ON KSDO4H
ON KSDO4H
DIP Switch Configuration
Select AirConditioner Type
Select NetworkType
* LGAP : LG Air conditioner Protocol
1 ON, All others OFF: Multi V products(Except CRUN products) orMulti(Non-Inverter) Product applied Common PCB(Refer toNOTE) or Multi(Inverter) Product + Central Controller(Alltypes) - Without LGAP
1 and 4 ON, All others OFF: Multi V products(Except CRUN products)or Multi(Non-Inverter) Product applied Common PCB orMulti(Inverter) Product + Central Controller(All types) - UsingLGAP
2 ON, All others OFF: Multi(Non-Inverter) Product + Centroller(All types) - Without LGAP
2 and 4 ON, All others OFF: Multi Non-Inverter Product + Central Controller(All Types) - Using LGAP
1,2,3,4 ON : Multi V CRUN Product + Central Controller(All types) - Using LGAP
Multi V & Multi(LGAP applied) products Configuration Methods
CAUTION: The wrong setting of air-conditioner switch could cause malfunctioning.Switch setting must be done carefully.Push the Reset button after changing the Dip switch.
NOTE: Multi(Non-Inverter) Product applied Common PCBPCB P/NO. : 6871A20917*P/NO. : 6871A20918*P/NO. : 6871A20910*
* Please refer the corresponding Central Controller installation manual if you want to know whetheryour Central Controller is compatible with LGAP or not.
![Page 9: Models: PMNFP14A0 PMNFP14A1 PGNFP14A0gscs-b2c.lge.com/downloadFile?fileId=KROWM000179967.pdf · *Note: See the PI 485 manual for the internal setting. *Note: Because the RS485 communication](https://reader030.fdocuments.in/reader030/viewer/2022041303/5e13e9ca44f020744d02cf7c/html5/thumbnails/9.jpg)
Installation Guide
Installation Manual 9
ENG
LISH
ON L1
2 3
4
KSDO
4H
PI485
CD
VCC
MAIN PCB
MAIN PCB
PI485
Control Box
GND
MAIN PCB
CN_CENTRAL
CN_CENTRAL
CN_OUT
Simple Central Controller - Connection Diagram
CAUTION: After product installation, tie the cables with Clamps & Tie-Wraps provided.Check the right connection of each BUS A and BUS B.
![Page 10: Models: PMNFP14A0 PMNFP14A1 PGNFP14A0gscs-b2c.lge.com/downloadFile?fileId=KROWM000179967.pdf · *Note: See the PI 485 manual for the internal setting. *Note: Because the RS485 communication](https://reader030.fdocuments.in/reader030/viewer/2022041303/5e13e9ca44f020744d02cf7c/html5/thumbnails/10.jpg)
Installation Guide
10 485 Gateway(M)
ON L1
2 3
4
KSDO
4H
CNU PCB
BUS_A
BUS_A
BUS_B
BUS_BLAN PORT
A B C D VCC GNDMULTI OUTDOOR TERMINAL BLOCK
CN_CENTRAL
Outdoor PCB
PC / Deluxe Central Controller
• In case of Multi V, either connect PI485 to Multi V terminal block or connect it directly to the CNU PCB as shown here.
PC/ Deluxe Central Controller - Connection Diagram
CAUTION: After product installation, tie the cables with Clamps & Tie-Wraps provided.Check the right connection of each BUS A and BUS B.
![Page 11: Models: PMNFP14A0 PMNFP14A1 PGNFP14A0gscs-b2c.lge.com/downloadFile?fileId=KROWM000179967.pdf · *Note: See the PI 485 manual for the internal setting. *Note: Because the RS485 communication](https://reader030.fdocuments.in/reader030/viewer/2022041303/5e13e9ca44f020744d02cf7c/html5/thumbnails/11.jpg)
Installation Guide
Installation Manual 11
ENG
LISH
[Steps to connect]
*Note: See the PI 485 manual for the internal setting.*Note: Because the RS485 communication line connecting to the PI 485 has polarity, check
A and B. PI485
How to connect the base station controller
• PGNFP14A0 (Only)
Connecting the PI 485 communication line
POWER
RUN/STOP RESETMODE
EREORRUN
Indoor unit #1 (Control address : 01)
Indoor unit #1 (Control address : 02)
Base station controller
A B
BUS_B
BUS_A
GND
10V
BUS_B
BUS_A
GND
10V
Aircon
![Page 12: Models: PMNFP14A0 PMNFP14A1 PGNFP14A0gscs-b2c.lge.com/downloadFile?fileId=KROWM000179967.pdf · *Note: See the PI 485 manual for the internal setting. *Note: Because the RS485 communication](https://reader030.fdocuments.in/reader030/viewer/2022041303/5e13e9ca44f020744d02cf7c/html5/thumbnails/12.jpg)
Memo
12 485 Gateway(M)
![Page 13: Models: PMNFP14A0 PMNFP14A1 PGNFP14A0gscs-b2c.lge.com/downloadFile?fileId=KROWM000179967.pdf · *Note: See the PI 485 manual for the internal setting. *Note: Because the RS485 communication](https://reader030.fdocuments.in/reader030/viewer/2022041303/5e13e9ca44f020744d02cf7c/html5/thumbnails/13.jpg)
P/No.: MFL37115809After reading this manual, keep it in a place easily accessible to the user for future reference.