Model: TG300 - PenncatGenerator Controller Options Manufacturer EEMarathon NEMA MG1, IE , AND ANSI...

4
Standby: kW 300 kVA 375 Ratings Range — 60 Hertz Operation RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. STANDBY RATINGS: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. PRIME POWER RATINGS: Prime power ratings apply to installations where utility power in unavailable or unreliable. At varying load the number of generator set oper- ating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO-8528/1, overload power in accordance with ISO -3046/1, BS5514, AS2789, and DIN 6271. For limited running time and base load ratings consult the factory. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. GENERAL GUIDELINES FOR DERATION: Altitude: Derate 0.5% per 100m (328 ft.) elevation above 1000m (3279 ft.)Temperature: Derate 1.0% per 10°C (18°F) tem- perature above 40°C (104°F). Genset Model Number Alternator Voltage L-N / L-L Phase Hertz Natural Gas 130º Rise Standby Rating LP Gas 130º Rise Standby Rating kW / kVA Amps kW / kVA Amps TG300 433CSL6216 277/480 3 60 300/375 452 170/213 256 139/240 3 60 300/375 903 170/213 511 127/220 3 60 300/375 985 170/213 558 240/416 3 60 300/375 521 170/213 295 120/208 3 60 300/375 1042 170/213 590 120/240 3 60 300/375 903 170/213 511 220/380 3 60 300/375 570 170/213 323 Single source responsibility for the generator set and accessories. Prototype and production tested to insure one step load acceptance per NFPA 110. Two year limited warranty on generator sets and accessories. Extended warranties also available. Unit conforms to CSA, NEMA, EGSA, ANSI and other standards. Heavy duty 4 cycle industrial engine for reliability and fuel efficiency. Brushless rotating field generator with class H insulation. Heavy duty steel base with integral vibration isolators. EPA Certified Engine. Shown with optional features. Model: TG300 GEN SET RATINGS FEATURES

Transcript of Model: TG300 - PenncatGenerator Controller Options Manufacturer EEMarathon NEMA MG1, IE , AND ANSI...

Page 1: Model: TG300 - PenncatGenerator Controller Options Manufacturer EEMarathon NEMA MG1, IE , AND ANSI standards Type Ext. Voltage Regulated, Brushless compliance for temperature and motor

Standby: kW 300 kVA 375

Ratings Range — 60 Hertz Operation

RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. STANDBY RATINGS: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. PRIME POWER RATINGS: Prime power ratings apply to installations where utility power in unavailable or unreliable. At varying load the number of generator set oper-ating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO-8528/1, overload power in accordance with ISO-3046/1, BS5514, AS2789, and DIN 6271. For limited running time and base load ratings consult the factory. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. GENERAL GUIDELINES FOR DERATION: Altitude: Derate 0.5% per 100m (328 ft.) elevation above 1000m (3279 ft.)Temperature: Derate 1.0% per 10°C (18°F) tem-perature above 40°C (104°F).

Genset Model Number

Alternator Voltage L-N / L-L

Phase Hertz

Natural Gas 130º Rise

Standby Rating

LP Gas 130º Rise

Standby Rating

kW / kVA Amps kW / kVA Amps

TG300 433CSL6216 277/480 3 60 300/375 452 170/213 256

139/240 3 60 300/375 903 170/213 511

127/220 3 60 300/375 985 170/213 558

240/416 3 60 300/375 521 170/213 295

120/208 3 60 300/375 1042 170/213 590

120/240 3 60 300/375 903 170/213 511

220/380 3 60 300/375 570 170/213 323

Single source responsibility for the generator set and accessories.

Prototype and production tested to insure one step load acceptance per NFPA 110.

Two year limited warranty on generator sets and accessories. Extended warranties also available.

Unit conforms to CSA, NEMA, EGSA, ANSI and other standards.

Heavy duty 4 cycle industrial engine for reliability and fuel efficiency.

Brushless rotating field generator with class H insulation.

Heavy duty steel base with integral vibration isolators.

EPA Certified Engine.

Shown with optional features.

Model: TG300

GEN SET RATINGS

FEATURES

Page 2: Model: TG300 - PenncatGenerator Controller Options Manufacturer EEMarathon NEMA MG1, IE , AND ANSI standards Type Ext. Voltage Regulated, Brushless compliance for temperature and motor

Application and Engineering Data

Basic Technical Data Manufacturer Doosan Model D146L H.O. Number of cylinders 8

Cylinder arrangement Vertical in-line

Cycle 4 Induction system Turbocharged, Aftercooled

Compression ratio 10.5.:1

Bore 5.04 in (128 mm) Stroke 5.59 in (142 mm) Cubic capacity 892 cu in (14.6 L)

Piston speed 1677 ft/min (511 m/min)

Main bearings: qty and type 10, Precision Half-Shell Governor type Electronic Rated rpm 1800 Max power at rated rpm 459 HP (342 kW)

MEP (@ rated load on NG) 226.2 psi (15.6 bar)

Dry Weight Rad to Flywheel 4450 lb (2018 kg)

Frequency regulation, no-load to full-load

Isochronous

Frequency regulation, steady state

± 0.5%

Frequency Fixed

Air cleaner type Dry

Exhaust System

Exhaust manifold type Wet

Exhaust Flow at Rated Pow-er @ 1350 °F

2521 cfm (71.3 m³/min)

Exhaust Flow at Rated Pow-er

3172 lb/hr (1301 kg/hr)

Exhaust temperature at rat-ed kW

1382 ºF (750 ºC)

Maximum allowable back pressure

3.0 in (10.2 kPa)

Exhaust outlet size at engine hookup

N/A

Air Induction System

Combustion Air required 2993 lb/hr (1227 kg/hr) Combustion Air required 687 cfm (19 m³/min)

Cooling System Ambient temperature 147 ºF (64 ºC) Engine jacket water capacity 9.5 gal (43.2 L) Radiator system capacity, including engine

28 gal (127.3 L)

Engine jacket water flow 180 gpm (680 Lpm) Heat rejected to cooling water at rated

18456 Btu/min (77.52 kcal/sec)

Max restriction of cooling air, intake and discharge side of radiator

0.5 H2O (0.125 kPa)

Ambient temperature Oil 150 °F (66 °C)

Lubrication System

Type Full Pressure

Oil pan capacity 42.3 qt (40 L)

Oil pan capacity with filter 49.7 qt (47.1 L)

Oil filter: qty and type 2, Cartridge

Electrical System

Ignition system N/A

Battery charging alternator:

Ground negative

Volts 24

Ampere rating 45

Starter motor rated voltage 24

Battery, recommended cold cranking amps (CCA):

Qty rating for –18 ºC (0 ºF) Two, 1000

Battery voltage 12

Operation Requirements

Radiator-cooled cooling air, m³/min (scfm) ‡

30000 scfm (849 m³/min)

Combustion air 687 cfm (19 m³/min)

Heat rejected to ambient air:

Engine 3765 Btu/min (66 kW)

Alternator 1309 Btu/min (23 kW)

Fuel System

Fuel Type LP Gas, Natural Gas or Dual Fuel

Fuel Consumption

Natural Gas

100% Load 3172 cfh (72 ks/hr)

LP Gas 100% Load 926 cfh (49 ks/hr)

Page 3: Model: TG300 - PenncatGenerator Controller Options Manufacturer EEMarathon NEMA MG1, IE , AND ANSI standards Type Ext. Voltage Regulated, Brushless compliance for temperature and motor

Generator Controller Options

Manufacturer Marathon NEMA MG1, IEEE, AND ANSI standards compliance for temperature and motor starting. Type Ext. Voltage Regulated, Brushless

Gen Frame MAGNAPLUS Sustained short-circuit current of the rated current for up to 10 seconds. Insulation NEMA

Material Class H Sustained short-circuit current enabling downstream

circuit breakers to trip without collapsing the alternator Temperature Rise 130 ºC, Standby

Hertz 60 Self-ventilated and dripproof construction.

Phase 3 Superior voltage waveform from a two-thirds pitch stator and skewed rotor. RPM 1800

Exciter Rotating Linkboards

# Leads 12 Reconnectable Optimized Electrical Design

PF 0.8 Enhanced Ventilation

Ambient 40ºC Fully Guarded

Coupling Single Bearing Flexible Heavy Duty Bearings

Amortisseur Windings Full

Cooling Air Volume 880 CFM

Peak Motor Starting 30% Voltage Dip, 1424 skVA @ 480V

Voltage Regulation no-load and full-load

1 Phase Sensing 1% Optional 3 Phase Sensing 1/2%

Alternator Specifications

- Ethernet or Dial Up Connection

- Engine Status Indicators

- SAE J1939 ECU Communications

- Internet Connection & Web Browser

- Fuel Consumption

- Internet Bridge Module

- Fleet Scalability

- CAT 5e, RS232/485, RJ 45- Receive Emails or IM Text- Automatic Downloads, Report Writer- Site Overview & Statistic Settling- SNMP, PC SCADA- InteliMonitor Network Management- Remote Access & Control

- Remote Contacts Form C, RS 232/485- Ethernet Communications- CanBus, ModBus

- Metering, Data Trending, Alarms- Load Share Synch Features

- NFPA 110 - Dashboard Style LCD Panel

Page 4: Model: TG300 - PenncatGenerator Controller Options Manufacturer EEMarathon NEMA MG1, IE , AND ANSI standards Type Ext. Voltage Regulated, Brushless compliance for temperature and motor

OVERALL SIZE, L x W x H, in.: 120 in x 75 in x 75 in WEIGHT: 8251 lbs. Note: Dim and weights reflect standard open unit with no options

Note: This drawing is provided for reference only and should not be used for planning installation. Contact your local distributor for more detailed information.

Heavy Duty Steel Base

Vibration Isolators

Oil Drain Valve with Extension

Battery Rack

Battery Cables

High Ambient Unit Mounted Radiator

Battery Charging Alternator

Factory Paint

Factory Test Prior to Shipment

2 Year Warranty

Owners Manual

STANDARD FEATURES

AVAILABLE ACCESSORIES

WEIGHTS AND DIMENSIONS

DISTRIBUTED BY:

OPEN UNIT

⃞ Narrow Skid Base

⃞ Radiator Duct Flange

⃞ Ship Loose Flex Exhaust

⃞ Ship Loose Critical Silencer

ENCLOSED UNIT

⃞ Wide Skid Base

⃞ Standard Enclosure With Internal Silencer

⃞ Sound Attenuated Enclosure With Silencer

⃞ Load Center With Lights and GFI Receptacle

CONTROLLER

MISCELLANEOUS

⃞ Flexible Fuel Lines

⃞ Coolant Drain Kit

⃞ Water Jacket Heater

⃞ Oil Pan Heater

⃞ Generator Strip Heater

⃞ Battery

⃞ Battery Charger

⃞ Pad Type Battery Heater

⃞ Battery Heater Blanket with Thermostat

⃞ Line Circuit Breaker

⃞ Dual Fuel

WARRANTY

⃞ 3 Year Warranty

⃞ 5 Year Warranty

InteliLite Model IL-NT-MRS19

Ethernet Bridge

Remote Annunciator

NORTH WALES, PA 19454404 ELM AVEPENNCAT CORPORATION