Mechanical specifications Design Modular MiCOM Px40 platform relay, P241 in 40TE case, P242 in 60TE case, P243 in 80TE case. Mounting is front of panel flush mounting or 19“ rack mounted (ordering options). Enclosure protection Per IEC 60529: 1992: IP 52 Protection (front panel) against dust and dripping water, IP 50 Protection for rear and sides of the case, against dust, IP 10 Protection Product safety protection for the rear due to live connections on the terminal block. Weight P241 (40TE): 7.3kg P242 (60TE): 9.2kg (with RTD, CLIO cards) P243 (80TE): 11.5kg (with RTD, CLIO cards) Terminals AC current and voltage measuring inputs Located on heavy duty (black) terminal block: Threaded M4 terminals, for ring lug connection. CT inputs have integral safety shorting, upon removal of the terminal block. General input/output terminals For power supply, opto inputs, output contacts and RP1 rear communications. Located on general purpose (grey) blocks: Threaded M4 terminals, for ring lug connection. Case protective earth connection Two rear stud connections, threaded M4. Must be earthed (grounded) for safety, minimum earth wire size 2.5 mm 2 . Front port serial PC interface EIA(RS)232 DCE, 9 pin D-type female connector Socket SK1. Courier protocol for interface to MiCOM S1 Studio or MiCOM S1 Agile software. Isolation to ELV (extra low voltage) level. Maximum cable length 15 m. Front download/monitor port EIA(RS)232, 25 pin D-type female connector Socket SK2. For firmware and menu text downloads. Isolation to ELV level. Rear communications port (RP1) EIA(RS)485 signal levels, two wire connections located on general purpose block, M4 screw. For screened twisted pair cable, multidrop, 1000 m max. For K-Bus, IEC-60870-5-103 or MODBUS Isolation to SELV (safety extra low voltage) level. Optional rear fiber connection for SCADA/DCS BFOC 2.5 -(ST®)-interface for glass fiber, as per IEC 874-10. 850 nm short-haul fibers, one Tx and one Rx. For Courier, IEC-60870-5-103 or MODBUS Optional second rear communications port (RP2) EIA(RS)232, 9 pin D-type female connector, socket SK4. Courier protocol: K-Bus, EIA(RS)232, or EIA(RS)485 connection. Isolation to SELV level. Optional rear IRIG-B interface modulated or un-modulated BNC plug Isolation to SELV level. 50 ohm coaxial cable. Optional rear Ethernet connection for IEC 61850 10BaseT/100BaseTX communications Interface in accordance with IEEE802.3 and IEC 61850 Isolation: 1.5 kV Connector type: RJ45 Cable type: Screened Twisted Pair (STP) 100 base FX interface Interface in accordance with IEEE802.3 and IEC 61850 Wavelength: 1300 nm Fiber: multi-mode 50/125 μm or 62.5/125 μm Connector style: BFOC 2.5 -(ST®) MiCOM Agile P24x Technical Data

Transcript of MiCOM Agile P24x Technical Data - CSE Uniserve MiCOM Agile P24x...Mechanical specifications Design...

Page 1: MiCOM Agile P24x Technical Data - CSE Uniserve MiCOM Agile P24x...Mechanical specifications Design Modular MiCOM Px40 platform relay, P241 in 40TE case, P242 in 60TE case, P243 in

Mechanical specifications

Design Modular MiCOM Px40 platform relay, P241 in 40TE case, P242 in 60TE case, P243 in 80TE case. Mounting is front of panel flush mounting or 19“ rack mounted (ordering options).

Enclosure protection Per IEC 60529: 1992: IP 52 Protection (front panel) against dust and dripping water, IP 50 Protection for rear and sides of the case, against dust, IP 10 Protection Product safety protection for the rear due to live connections on the terminal block.

Weight P241 (40TE): 7.3kg P242 (60TE): 9.2kg (with RTD, CLIO cards) P243 (80TE): 11.5kg (with RTD, CLIO cards) Terminals

AC current and voltage measuring inputs Located on heavy duty (black) terminal block: Threaded M4 terminals, for ring lug connection. CT inputs have integral safety shorting, upon removal of the terminal block.

General input/output terminals For power supply, opto inputs, output contacts and RP1 rear communications. Located on general purpose (grey) blocks: Threaded M4 terminals, for ring lug connection.

Case protective earth connection Two rear stud connections, threaded M4. Must be earthed (grounded) for safety, minimum earth wire size 2.5 mm2.

Front port serial PC interface EIA(RS)232 DCE, 9 pin D-type female connector Socket SK1. Courier protocol for interface to MiCOM S1 Studio or MiCOM S1 Agile software. Isolation to ELV (extra low voltage) level. Maximum cable length 15 m.

Front download/monitor port EIA(RS)232, 25 pin D-type female connector Socket SK2. For firmware and menu text downloads. Isolation to ELV level.

Rear communications port (RP1) EIA(RS)485 signal levels, two wire connections located on general purpose block, M4 screw. For screened twisted pair cable, multidrop, 1000 m max. For K-Bus, IEC-60870-5-103 or MODBUS Isolation to SELV (safety extra low voltage) level.

Optional rear fiber connection for SCADA/DCS BFOC 2.5 -(ST®)-interface for glass fiber, as per IEC 874-10. 850 nm short-haul fibers, one Tx and one Rx. For Courier, IEC-60870-5-103 or MODBUS

Optional second rear communications port (RP2) EIA(RS)232, 9 pin D-type female connector, socket SK4. Courier protocol: K-Bus, EIA(RS)232, or EIA(RS)485 connection. Isolation to SELV level. Optional rear IRIG-B interface modulated or un-modulated BNC plug Isolation to SELV level. 50 ohm coaxial cable. Optional rear Ethernet connection for IEC 61850

10BaseT/100BaseTX communications Interface in accordance with IEEE802.3 and IEC 61850 Isolation: 1.5 kV Connector type: RJ45 Cable type: Screened Twisted Pair (STP)

100 base FX interface Interface in accordance with IEEE802.3 and IEC 61850 Wavelength: 1300 nm Fiber: multi-mode 50/125 µm or 62.5/125 µm Connector style: BFOC 2.5 -(ST®)

MiCOM Agile P24x Technical Data

Page 2: MiCOM Agile P24x Technical Data - CSE Uniserve MiCOM Agile P24x...Mechanical specifications Design Modular MiCOM Px40 platform relay, P241 in 40TE case, P242 in 60TE case, P243 in

Optional rear redundant Ethernet connection for IEC 61850 (2 Fibre Optic or 2 RJ45 ports)

100 base FX interface Interface in accordance with IEEE802.3 and IEC 61850 Wavelength: 1300 nm Fiber: multi-mode 50/125 µm or 62.5/125 µm Connector style: BFOC 2.5 -(ST®) Transmitter optical characteristics 100 base FX interface

Parameter Sym Min Typ Max Unit Output Optical Power BOL 62.5/125 µm, NA = 0.275 Fiber EOL

PO -19 -20

-16.8 -14 dBm avg.

Output Optical Power BOL 50/125 µm, NA = 0.20 Fiber EOL

PO -22.5 -23.5

-20.3 -14 dBm avg.

Optical Extinction Ratio

10 -10

% dB

Output Optical Power at Logic “0” State

PO (“0”)

-45 dBm avg.

BOL - Beginning of life EOL - End of life

Receiver optical characteristics 100 base FX interface

Parameter Sym Min Typ Max Unit Input Optical Power Minimum at Window Edge

PIN Min. (W)

-33.5 -31 dBm avg.

Input Optical Power Minimum at Eye Center

PIN Min. (C)

-34.5 -31.8 Bm avg.

Input Optical Power Maximum

PIN Max. -14 -11.8 dBm

avg.

Fiber defect connector (watchdog relay) – redundant Ethernet board Connector (3 terminals): 2 NC contacts Rated voltage: 250 V Continuous current: 5 A Short-duration current: 30 A for 3 s

Breaking capacity: DC: 50 W resistive DC: 25 W inductive (L/R = 40 ms) AC: 1500 VA resistive (cos φ = unity) AC: 1500 VA inductive (cos φ = 0.5) Subject to maxima of 5 A and 250 V

10BaseT/100BaseTX Communications

The same as optional rear Ethernet connection for IEC 61850 Ratings

AC measuring inputs Nominal frequency: 50 and 60 Hz (settable) Operating range: 45 to 65 Hz

AC current Nominal current (In): 1 and 5 A dual rated. (1 A and 5 A inputs use different transformer tap connections, check correct terminals are wired). Nominal burden < 0.04 VA at In, <40 mΩ (0-30 In) In = 1 A < 0.01 VA at In, <8 mΩ (0-30 In) In = 5 A Thermal withstand: continuous 4 In for 10 s: 30 In for 1 s; 100 In Standard: linear to 64 In (non-offset AC current). Sensitive: linear to 2 In (non-offset AC current).

AC voltage Nominal voltage (Vn): 100 to 120 V phase- phase Nominal burden per phase: < 0.02 VA rms at 110/√3 V Thermal withstand: continuous 2 Vn for 10 s: 2.6 Vn Linear to 200 V. Power supply

Auxiliary voltage (Vx) Three ordering options: (i) Vx: 24 to 48 Vdc (ii) Vx: 48 to 110 Vdc, and 40 to 100 Vac (rms) (iii) Vx: 110 to 250 Vdc, and 100 to 240 Vac (rms)

Operating range (i) 19 to 65 V (dc only for this variant) (ii) 37 to 150 V (dc), 32 to 110 V (ac) (iii) 87 to 300 V (dc), 80 to 265 V (ac).

Page 3: MiCOM Agile P24x Technical Data - CSE Uniserve MiCOM Agile P24x...Mechanical specifications Design Modular MiCOM Px40 platform relay, P241 in 40TE case, P242 in 60TE case, P243 in

With a tolerable ac ripple of up to 12% for a dc supply, per IEC 60255-11: 1979.

Nominal burden Quiescent burden: 11 W. (Extra 1.25 W when fitted with second rear communications board). Additions for energized binary inputs/outputs: Per opto input: 0.09 W (24 to 54 V), 0.12 W (110/125 V), 0.19 W (220/250 V). Per energized output relay: 0.13 W

Power-up time Time to power up < 11 s.

Power supply interruption 3 power supply options: (i) Vx: 24 to 48 V dc (ii) Vx: 48 to 110 V dc, 40 to 100 V ac (rms) (iii) (i) Vx: 110 to 250 V dc, 100 to 240 V ac (rms) Per IEC 60255-11: 2008 The relay will withstand a 100% interruption in the DC supply without de-energizing as follows: (i) Vx: 24 to 48 V dc Quescent / half load 20 ms at 24 V 50 ms at 36 V 100 ms at 48 V maximum loading: 20 ms at 24 V 50 ms at 36V 100 ms at 48 V (ii) Vx: 48 to 110 V dc Quescent / half load 20 ms at 36 V 50 ms at 60 V 100 ms at 72 V 200 ms at 110 V maximum loading: 20 ms at 36 V 50 ms at 60 V 100 ms at 85 V 200 ms at 110 V (iii) (i) Vx: 110 to 250 V dc Quescent / half load 50 ms at 110 V 100 ms at 160 V 200 ms at 210 V maximum loading: 20 ms at 85 V 50 ms at 98V 100 ms at 135 V 200 ms at 174 V Per IEC 60255-11: 2008: The relay will withstand an interruption in the AC supply without de-energizing as follows: (ii) Vx = 40 to 100 V ac Quescent / half load 50 ms at 27 V for 100% voltage dip

maximum loading: 10 ms at 27 V for 100% voltage dip (iii) Vx = 100 to 240 V ac Quescent / half load 50 ms at 80 V for 100% voltage dip maximum loading: 50 ms at 80 V for 100% voltage dip Maximum loading = all digital inputs/outputs energized Quescent or 1/2 loading = 1/2 of all digital inputs/outputs energized

Battery backup Front panel mounted Type ½ AA, 3.6 V Lithium Thionyl Chloride Battery (SAFT advanced battery reference LS14250) Battery life (assuming relay energized for 90% time) >10 years

Field voltage output Regulated 48 Vdc Current limited at 112 mA maximum output Operating range 40 to 60 V with alarm at <35 V.

Digital (“Opto”) inputs Universal opto inputs with programmable voltage thresholds (24/27, 30/34, 48/54, 110/125, 220/250 V). May be energized from the 48 V field voltage, or the external battery supply. Rated nominal voltage: 24 to 250 Vdc Operating range: 19 to 265 Vdc Withstand: 300 Vdc, 300 Vrms. Peak current of opto input when energized is 3.5 mA (0-300 V) Nominal pick-up and reset thresholds: Nominal battery 24/27: 60 - 80% DO/PU (logic 0) <16.2 (logic 1) >19.2 Nominal battery 24/27: 50 - 70% DO/PU (logic 0) <12.0 (logic 1) >16.8 Nominal battery 30/34: 60 - 80% DO/PU (logic 0) <20.4 (logic 1) >24.0 Nominal battery 30/34: 50 - 70% DO/PU (logic 0) <15.0 (logic 1) >21.0 Nominal battery 48/54: 60 - 80% DO/PU (logic 0) <32.4 (logic 1) >38.4 Nominal battery 48/54: 50 - 70% DO/PU (logic 0) <24.0 (logic 1) >33.6 Nominal battery 110/125: 60 - 80% DO/PU (logic 0) <75.0 (logic 1) >88.0 Nominal battery 110/125: 50 - 70% DO/PU (logic 0) <55.0 (logic 1) >77.0 Nominal battery 220/250: 60 - 80% DO/PU (logic 0) <150.0 (logic 1) >176.0 Nominal battery 220/250: 50 - 70% DO/PU (logic 0) <110 (logic 1) >154 Recognition time: <2 ms with long filter removed, <12 ms with half cycle ac immunity filter on

Page 4: MiCOM Agile P24x Technical Data - CSE Uniserve MiCOM Agile P24x...Mechanical specifications Design Modular MiCOM Px40 platform relay, P241 in 40TE case, P242 in 60TE case, P243 in

Output contacts

Standard contacts General purpose relay outputs for signaling, tripping and alarming: Continuous Carry Ratings (Not Switched): Maximum continuous current: 10 A (UL: 8 A) Short duration withstand carry: 30 A for 3 s 250 A for 30 ms Rated voltage: 300 V Make & Break Capacity: DC: 50 W resistive DC: 62.5 W inductive (L/R = 50 ms) AC: 2500 VA resistive (cos φ = unity) AC: 2500 VA inductive (cos φ = 0.7) Make, Carry: 30 A for 3 secs, dc resistive, 10,000 operations (subject to the above limits of make / break capacity and rated voltage) Make, Carry & Break: 30 A for 200 ms, ac resistive, 2,000 operations (subject to the above limits of make / break capacity & rated voltage) 4 A for 1.5 secs, dc resistive, 10,000 operations (subject to the above limits of make / break capacity & rated voltage) 0.5 A for 1 sec, dc inductive, 10,000 operations (subject to the above limits of make / break capacity & rated voltage) 10 A for 1.5 secs, ac resistive / inductive, 10,000 operations (subject to the above limits of make / break capacity & rated voltage) Durability: Loaded contact: 10 000 operations minimum, Unloaded contact: 100 000 operations minimum. Operate Time Less than 5 ms Reset Time Less than 5 ms

Watchdog contacts Non-programmable contacts for relay healthy/relay fail indication: Breaking capacity: DC: 30 W resistive DC: 15 W inductive (L/R = 40 ms) AC: 375 VA inductive (cos φ = 0.7)

IRIG-B 12X Interface (modulated) External clock synchronization per IRIG standard 200-98, format B12x Input impedance 6 kΩ at 1000 Hz

Modulation ratio: 3:1 to 6:1 Input signal, peak-peak: 200 mV to 20 V

IRIG-B 00X Interface (Un-modulated) External clock synchronization per IRIG standard 200-98, format B00X. Input signal TTL level Input impedance at dc 10 kΩ

Environmental conditions

Ambient temperature range Per IEC 60255-6: 1988: Operating temperature range: -25°C to +55°C (or -13°F to +131°F) Storage and transit: -25°C to +70°C (or -13°F to +158°F) Per IEC 60068-2-1: 2007 -25°C storage (96 hours) -40°C operation (96 hours) Per IEC 60068-2-2: 2007 +85°C storage (96 hours) +85°C operation (96 hours)

Ambient humidity range Per IEC 60068-2-3: 1969: 56 days at 93% relative humidity and +40 °C Per IEC 60068-2-30: 1980 Damp heat cyclic, six (12 + 12) hour cycles, 93% RH, +25 to +55°C

Corrosive environments Per IEC 60068-2-60: 1995, Part 2, Test Ke, Method (class) 3 Industrial corrosive environment/poor environmental control, mixed gas flow test. 21 days at 75% relative humidity and +30oC exposure to elevated concentrations of H2S, NO2, Cl2 and SO2. Type tests

Insulation Per IEC 60255-27: 2005: Insulation resistance > 100 MΩ at 500 Vdc (Using only electronic/brushless insulation tester).

Creepage distances and clearances IEC 60255-27: 2005 Pollution degree 3, Overvoltage category III, Impulse test voltage 5 kV.

High voltage (dielectric) withstand (i) Per IEC 60255-27: 2005, 2 kV rms

Page 5: MiCOM Agile P24x Technical Data - CSE Uniserve MiCOM Agile P24x...Mechanical specifications Design Modular MiCOM Px40 platform relay, P241 in 40TE case, P242 in 60TE case, P243 in

AC, 1 minute: Between all independent circuits. Between independent circuits and protective (earth) conductor terminal. 1 kV rms AC for 1 minute, across open watchdog contacts. 1 kV rms AC for 1 minute, across open contacts of changeover output relays. 1 kV rms AC for 1 minute for all D-type EIA(RS)232/EIA(RS)485 ports between the communications port terminals and protective (earth) conductor terminal. (ii) Per ANSI/IEEE C37.90-1989 (reaffirmed 1994): 1.5 kV rms AC for 1 minute, across open contacts of normally open output relays. 1 kV rms AC for 1 minute, across open watchdog contacts. 1 kV rms AC for 1 minute, across open contacts of changeover output relays.

Impulse voltage withstand test Per IEC 60255-27: 2005: Front time: 1.2 µs, Time to half-value: 50 µs, Peak value: 5 kV, 0.5J Between all independent circuits. Between all independent circuits and protective (earth) conductor terminal. Between the terminals of independent circuits. EIA(RS)232 & EIA(RS)485 ports and normally open contacts of output relays excepted. Electromagnetic compatibility (EMC) 1 MHz burst high frequency disturbance test Per IEC 60255-22-1: 1988, Class III, Common-mode test voltage: 2.5 kV, Differential test voltage: 1.0 kV, Test duration: 2 s, Source impedance: 200 Ω (EIA(RS)232 ports excepted). Damped oscillatory test Per EN61000-4-18: 2007 + A1: 2010: Level 3 100 kHz and 1 MHz Common mode test voltage: 2.5 kV Power Supply, Relay contacts, CT, VT, Opto Input, Communications, IRIG-B Differential mode test voltage: 1 kV Power Supply, Relay contacts, CT, VT, Opto Input 3 MHz, 10 MHz and 30 MHz Common mode test voltage: 4 kV Power Supply, Relay contacts, CT, VT, Opto Input, Communications, IRIG-B

Immunity to electrostatic discharge Per IEC 60255-22-2: 1996, Class 4, 15 kV discharge in air to user interface, display, communication port and exposed metalwork. 8 kV point contact discharge to any part of the front of the product.

Electrical fast transient or burst requirements Per IEC 60255-22-4: 2002 and EN61000-4-4:2004. Test severity Class III and IV: Amplitude: 2 kV, burst frequency 5 kHz (Class III), Amplitude: 4 kV, burst frequency 2.5 kHz (Class IV). Applied directly to auxiliary supply, and applied to all other inputs. (EIA(RS)232 ports excepted). Amplitude: 4 kV, burst frequency 5 kHz (Class IV) applied directly to auxiliary.

Surge withstand capability Per IEEE/ANSI C37.90.1: 2002: 4 kV fast transient and 2.5 kV oscillatory

applied directly across each output contact, optically isolated input, and power supply circuit.

4 kV fast transient and 2.5 kV oscillatory applied common mode to communications, IRIG-B.

Surge immunity test (EIA(RS)232 ports excepted). Per IEC 61000-4-5: 2005 Level 4, Time to half-value: 1.2 / 50 µs, Amplitude: 4 kV between all groups and protective (earth) conductor terminal,

Amplitude: 2 kV between terminals of each group.

Conducted/radiated immunity For RTDs used for tripping applications the conducted and radiated immunity performance is guaranteed only when using totally shielded RTD cables (twisted leads).

Immunity to radiated electromagnetic energy Per IEC 60255-22-3: 2000, Class III: Test field strength, frequency band 80 to 1000 MHz: 10 V/m, Test using AM: 1 kHz / 80%, Spot tests at 80, 160, 450, 900 MHz Per IEEE/ANSI C37.90.2: 2004: 80 MHz to 1000 MHz, 1 kHz 80% am and am pulsed modulated. Field strength of 35 V/m.

Radiated immunity from digital communications Per EN61000-4-3: 2002, Level 4: Test field strength, frequency band 800 to 960 MHz, and 1.4 to 2.0 GHz: 30 V/m, Test using AM: 1 kHz/80%.

Page 6: MiCOM Agile P24x Technical Data - CSE Uniserve MiCOM Agile P24x...Mechanical specifications Design Modular MiCOM Px40 platform relay, P241 in 40TE case, P242 in 60TE case, P243 in

Radiated immunity from digital radio telephones Per IEC 61000-4-3: 2002: 10 V/m, 900 MHz and 1.89 GHz.

Immunity to conducted disturbances induced by radio frequency fields Per IEC 61000-4-6: 1996, Level 3, Disturbing test voltage: 10 V.

Power frequency magnetic field immunity Per IEC 61000-4-8: 1994, Level 5, 100 A/m applied continuously, 1000 A/m applied for 3s. Per IEC 61000-4-9: 1993, Level 5, 1000 A/m applied in all planes. Per IEC 61000-4-10: 1993, Level 5, 100 A/m applied in all planes at 100 kHz/1 MHz with a burst duration of 2 s.

Conducted emissions Per EN 55022: 1998 Class A: 0.15 - 0.5 MHz, 79 dBµV (quasi peak) 66 dBµV (average) 0.5 – 30 MHz, 73 dBµV (quasi peak) 60 dBµV (average).

Radiated emissions Per EN 55022: 1998 Class A: 30 – 230 MHz, 40 dBµV/m at 10 m measurement distance 230 – 1 GHz, 47 dBµV/m at 10 m measurement distance. EU directives

EMC compliance Per 2006/95/EC: Compliance to the European Commission Directive on EMC is claimed via the Technical Construction File route. Product Specific Standards were used to establish conformity: EN50263: 2000

Product safety Compliance to the European Commission Low Voltage Directive. (LVD) is demonstrated using a Technical File. A product specific standard was used to establish conformity. EN 60255-27: 2005

R&TTE compliance Radio and Telecommunications Terminal Equipment (R & TTE) directive 99/5/EC. Compliance demonstrated by compliance to both the EMC directive and Low voltage directive, down to zero volts. Applicable to rear communications ports.

ATEX compliance ATEX Potentially Explosive Atmospheres directive 94/9/EC, for equipment. The equipment is compliant with Article 1(2) of European directive 94/9/EC. It is approved for operation outside an ATEX hazardous area. It is however approved for connection to Increased Safety, “Ex e”, motors with rated ATEX protection, Equipment Category 2, to ensure their safe operation in gas Zones 1 and 2 hazardous areas. CAUTION - Equipment with this marking is not itself suitable for operation within a potentially explosive atmosphere. Compliance demonstrated by Notified Body certificates of compliance.

II (2) G

Note: Programmable IDMT curves shall not be used for ATEX applications. ATEX marked models are only approved for use with a fixed IDMT curve. Mechanical robustness

Vibration test Per IEC 60255-21-1: 1996: Response Class 2 Endurance Class 2

Shock and bump Per IEC 60255-21-2: 1996: Shock response Class 2 Shock withstand Class 1 Bump Class 1

Seismic test Per IEC 60255-21-3: 1995: Class 2

Transit Packaging Performance Product testing to simulate protection offered by primary packaging carton, to ISTA 1C specification

Vibration and Drop Release Tests:

Vibration tests in 3 orientations, vibratory

movement 7 Hz, amplitude 5.3 mm, acceleration 1.05g Drop tests - 10 drops from 61 cm height on multiple carton faces, edges and corners

Vibration tests in 3 orientations, vibratory

movement 7 Hz, amplitude 5.3 mm, acceleration 1.05g Drop tests - 10 drops from 61 cm height on multiple carton faces, edges and corners

Vibration tests in 3 orientations, vibratory movement 7 Hz, amplitude 5.3 mm, acceleration 1.05g Drop tests - 10 drops from 61 cm height on multiple carton faces, edges and corners