Metasys Integrator Cleaver-Brooks Application Note
Transcript of Metasys Integrator Cleaver-Brooks Application Note
Metasys Connectivity Technical Manual 629.5Metasys Integrator Section
Application NoteIssue Date 0900
© 2000 Johnson Controls, Inc. 1Code No. LIT-6295220 www.johnsoncontrols.com
lntroduction Page 3
• Application Details *3
• Component Requirements *8
• Vendor Contact Information 9
• Design Considerations *10
Cable Connections 11
• Cable Pinouts 11
• Connecting the Cable 12
Metasys Integrator Setup *13
Point Mapping Tables 15
• CB-Hawk Boiler Control Panel Points - CB-Hawk ASCII Interface 16
• CB-Hawk Boiler Control Panel Points - CB-GPI *17
• CB-Hawk Enhancer Boiler Points - for CB-Hawk ASCII Interface or CB-GPI 19
• CB-Hawk Enhancer General Points - CB-Hawk ASCII Interface or CB-GPI 20
• CB-780 Controller Points 21
• CB-783 Expanded Annunciator Points 22
Metasys Network Setup 23
• Mapping to a CS Object *23
Custom Integration *25
APPLICATION NOTE
Metasys Integrator® Cleaver-Brooks® Application
*Indicates those sections where changes have occurred since the last printing.
2 Metasys Integrator—Metasys Integrator Cleaver-Brooks Application
Metasys Integrator—Metasys Integrator Cleaver-Brooks Application 3
lntroduction
This document explains the Metasys Integrator Cleaver-Brooksapplication. Use this document with the Metasys Integrator technicalbulletins in the Metasys Connectivity Technical Manual (FAN 629.5)which provide information on installing and commissioning the MetasysIntegrator unit. For information on Cleaver-Brooks boiler control panels,see Cleaver-Brooks documentation (obtainable from a Cleaver-Brooksrepresentative).
Note: If you are using a Universal Packaging Module (UPM), you mustinstall the Metasys Integrator 300 Series in a two high enclosure(EN-EWC25-0) rather than a one high enclosure (EN-EWC13-0)as shown in the figures in this application note.
The Metasys Integrator unit allows Cleaver-Brooks equipment to becomean integral part of the Metasys and Metasys Companion Networks.Once either a CB-Hawk ASCII Interface or CB-General Purpose Interface(CB-GPI) and boiler control panels are connected to a Metasys orCompanion Network via the Metasys Integrator unit, their data is availableto the full complement of Metasys Building Automation System (BAS)features, including Change-of-State (COS) monitoring, alarm notification,trend, and totalization.
The CB-Hawk ASCII Interface allows information to be transmittedbetween CB-Hawk boiler control panels and non-Cleaver-Brooks devices(such as the Metasys Integrator unit). A six slot CB-Link is requiredbetween the CB-Hawk ASCII Interface and the boiler control panels.Optionally, you can connect a CB-Hawk Enhancer to Slot 6. However, ifyou use a CB-Hawk Enhancer, you must tie it into Slot 6, and you mustthen tie the CB-Hawk ASCII Interface into Slot 5 as shown in Figures 1and 2.
Each Metasys Integrator vendor port can connect to one CB-Hawk ASCIIInterface. Each CB-Link can connect to five CB-Hawk boiler controlpanels, or four CB-Hawk boiler control panels and one CB-HawkEnhancer.
Figure 1 shows a Metasys Network with the Metasys Integrator unitconnected to one CB-Hawk ASCII Interface. Four CB-Hawk boiler controlpanels connect to the CB-Hawk ASCII Interface through Slots 1 through 4on the CB-Link. A CB-Hawk Enhancer connects to Slot 6 on the CB-Link.Figure 2 shows a similar Cleaver-Brooks configuration integrated into aMetasys Companion Network.
ApplicationDetails
CB-Hawk ASCIIInterface
4 Metasys Integrator—Metasys Integrator Cleaver-Brooks Application
Note: For a single boiler, the CB-Hawk ASCII interface can connectdirectly to the CB-Hawk boiler control panel without a CB-Link.See your Cleaver-Brooks representative.
CB-HawkASCII
Interface
N2 Bus
Standard Network Control Unit (NCU)
Unitary (UNT) Controller
RS-232
MetasysIntegrator
Intcb1
CB-Link
1 2 3 4 5 6
CB-HawkEnhancer
N1 LAN
u m p
RS-485
CB-HawkBoiler
ControlPanel (1)
CB-HawkBoiler
ControlPanel (2)
CB-HawkBoiler
ControlPanel (3)
CB-HawkBoiler
ControlPanel (4)
Note: If you are using a UPM, you must install the Metasys Integrator 300 Series in atwo high enclosure (EN-EWC25-0) rather than a one high enclosure(EN-EWC13-0) as shown in the figures in this application note.
Figure 1: Cleaver-Brooks CB-Hawk Boiler Control Panelsand Metasys Integration (CB-Hawk ASCII Interface)
Metasys Integrator—Metasys Integrator Cleaver-Brooks Application 5
N2 Bus
UNT
MetasysIntegrator
Cbcomp
CB-HawkASCII
Interface
RS-232
CB-Link
1 2 3 4 5 6
CB-HawkEnhancer
RS-485
CB-HawkBoiler
ControlPanel (1)
CB-HawkBoiler
ControlPanel (2)
CB-HawkBoiler
ControlPanel (3)
CB-HawkBoiler
ControlPanel (4)
Panel Unit Workstation
Note: If you are using a UPM, you must install the Metasys Integrator 300 Series in atwo high enclosure (EN-EWC25-0) rather than a one high enclosure(EN-EWC13-0) as shown in the figures in this application note.
Figure 2: Cleaver-Brooks CB-Hawk Boiler Control Panel andMetasys Companion Integration (CB-Hawk ASCII Interface)
You can also integrate Cleaver-Brooks equipment with the Metasys andMetasys Companion Networks through the CB-GPI. This interface resideson an RS-485 bus. The CB-Link communicates with up to fiveCB-Hawk/CB-780 boiler controls and, optionally, a CB-Hawk Enhancer.
The RS-485 connects to a Johnson Controls RS-232 to RS-485 converter(MM-CVT101) which connects via an RS-232 cable to the MetasysIntegrator panel. The Metasys Integrator unit can receive data from, andsend data and commands to, Cleaver-Brooks equipment.
Each Metasys Integrator vendor port can connect to one RS-232 to RS-485converter which can connect by RS-485 bus to one CB-Link.
Install the CB-GPI in Slot 6 of the CB-Link, unless a CB-Hawk Enhanceris present. If a CB-Hawk Enhancer is present, you must install it in Slot 6,and you must install the CB-GPI card in Slot 5. The number of boilercontrollers that you may connect is then reduced to four.
CB-GPI
6 Metasys Integrator—Metasys Integrator Cleaver-Brooks Application
Figure 3 shows a CB-Link Communication Interface with burner/boilercontrol equipment integrated into the Metasys Network.
N2 Bus
Standard NCU
UNT
RS-232
N1 LAN
MetasysIntegrator
MM-CVT101Converter
intcbgpi
CB-780
RS-485
1 2 3 4 5 6*
CB-Link
CB-HawkBoiler
ControlPanel
*Slot 6 on the CB-Link CommunicationsInterface must contain a CB-GPI cardunless a CB-Hawk Enhancer optionis present.
Figure 3: Cleaver-Brooks Boiler Controland Metasys Integration (GPI Version)
Metasys Integrator—Metasys Integrator Cleaver-Brooks Application 7
Figure 4 shows a CB-Link with burner/boiler control equipment integratedinto the Metasys Companion Network.
N2 Bus
UNT
MetasysIntegrator
Cbgpcomp
RS-232
MM-CVT101Converter
RS-485
CB-Link
1 3 4 5 6*
CB-HawkBoiler
ControlPanel
*Slot 6 on the CB-LinkCommunications Interface mustcontain a CB-GPI card unless a CB-Hawk Enhancer option is present. CB-Hawk
Enhancer
WorkstationPanel Unit
**End-of-Line (EOL) Resistor Required
** **
Figure 4: Cleaver-Brooks CB-GPI andMetasys Companion Integration
8 Metasys Integrator—Metasys Integrator Cleaver-Brooks Application
The following lists describe the components that are needed to integrateCleaver-Brooks equipment through the CB-Hawk ASCII Interface orthrough the CB-GPI:
! Properly installed CB-Hawk ASCII Interface, CB-Link, andCB-Hawk boiler control panels
! RS-232 cable (for connecting the CB-Hawk ASCII Interface to theMetasys Integrator unit)
! Metasys Integrator unit
! N2 Bus (for connecting the Metasys Integrator unit to the Metasys orCompanion Network)
! Portable Personal Computer (PC) for downloading vendorcommunication tables (.VCT files) and network setup information intothe Metasys Integrator unit, and for running diagnostics
! Cable for connecting portable PC to the Metasys Integrator unit
! The correct vendor communication table (.VCT file) to download intothe Metasys Integrator unit (supplied on Metasys Integrator Tables andModels CD-ROM)
! Properly installed CB-Link with a CB-GPI card installed in Slot 6(unless you are using a CB-Hawk Enhancer option) andCleaver-Brooks equipment.(A Cleaver-Brooks representative isresponsible for installing all Cleaver-Brooks equipment.)
! If a CB-Hawk Enhancer is present, you must install it in the sixth slot,and you must install the CB-GPI card in the fifth slot.
! Johnson Controls RS-232 to RS-485 converter (MM-CVT101).
! RS-232 cable (for connecting the MM-CVT101 to the MetasysIntegrator unit).
! RS-485 cable (for connecting the MM-CVT101 to the CB-GPI).
! Metasys Integrator unit.
! N2 Bus (for connecting the Metasys Integrator unit to the Metasys orCompanion Network).
! Portable PC for downloading vendor communication tables(.VCT files) and network setup information into the Metasys Integratorunit, and for running diagnostics.
! Cable for connecting portable PC to the Metasys Integrator unit.
! The correct vendor communication table (.VCT file) to download intoMetasys Integrator (supplied on Metasys Integrator Tables and ModelsCD-ROM).
! CB-Hawk Enhancer Version 7.5 or higher.
ComponentRequirements
ASCII Interface
CB-GPI
Metasys Integrator—Metasys Integrator Cleaver-Brooks Application 9
This document describes the RS-232 cable and the vendor communicationtables. Cleaver-Brooks documentation describes their equipment. Theremaining components are described in the Metasys Integrator technicalbulletins.
To integrate Cleaver-Brooks equipment into the Metasys Network, youwill need:
! Metasys Operator Workstation (OWS) software Release 6.0 or higher
! Metasys Integrator software/firmware Release 7.0 or higher
To integrate Cleaver-Brooks equipment into the Metasys CompanionNetwork, you will need:
! Metasys Companion Release 5.0 or higher
! Metasys Integrator software/firmware Release 7.0 or higher
Integration between the Metasys Integrator unit and Cleaver-Brooks hasbeen tested with the CB-Hawk ASCII Interface Version 4.0 Rev. C.Integration of Cleaver-Brooks products not discussed in this documentwill require additional software development and testing by SystemsProducts. For information on integrating other products, refer to theCustom Integration section in this document.
Please contact the Service Group at your local Cleaver-Brooks office. CallCleaver-Brooks at (414) 359-0600 for assistance in determining how tocontact your local Cleaver-Brooks office.
Metasys ReleaseRequirements
MetasysCompanionReleaseRequirements
VendorComponentRequirements
Vendor ContactInformation
10 Metasys Integrator—Metasys Integrator Cleaver-Brooks Application
When integrating Cleaver-Brooks equipment, keep the followingconsiderations in mind:
• Make sure all Cleaver-Brooks equipment is set up and runningproperly before attempting to integrate with the Metasys orCompanion Network. (The Cleaver-Brooks representative isresponsible for operation of CB equipment.)
• RS-232 cable distance between the Metasys Integrator unit and theCB-Hawk ASCII Interface or the Johnson Controls MM-CVT101 is amaximum of 50 feet.
• Cable distance between the CB-GPI and MM-CVT101 can be amaximum of 1000 feet.
• The CB-780 Burner Control and the CB-783 Expanded Annunciatorfor a given burner must be commissioned to the same slot (they musthave the same vendor address).
• When using the CB-GPI with a CB-Hawk, configure the CB-Hawk as“Setback Capable = Yes.”
• When using the CB-GPI with an Enhancer, follow these instructions:
1. Disconnect the Metasys Integrator unit.
2. Connect the 9-pin female connector to a PC Commissioning portusing the RS-485 CVT-101 cable configured for a MetasysIntegrator unit.
3. Configure a terminal emulator for 9600 baud, 8 bit, 1 stop bit, noparity.
4. Enter this command in lower case to set the GPI to its defaultvalues:
sz zap
5. Enter this command in lower case to set the reply timeout to8 seconds:
st 8 15
Make sure you select the Enter key after each command.
DesignConsiderations
Metasys Integrator—Metasys Integrator Cleaver-Brooks Application 11
Cable Connections
Use the following cable pinouts (Figure 5) for the RS-232 connectionbetween the Metasys Integrator unit and the CB-Hawk ASCII Interface.(On standard NEMA 4 Version, make connections to terminal block insidepanel.)
DB-9 Female
Signal Pin
TD
RDGND
3
25
SignalPin
2
35
RS-232
Vendor Port A or Bof Integrator
CB-HawkASCII Interface
(50 ft maximum)
RD
TDGND
intcb2
DB-9 Female
Figure 5: Cable Pinouts for CB-Hawk ASCII Interface
Use the following cable pinouts (Figure 6) for the RS-232 connectionbetween the Metasys Integrator unit and the Johnson ControlsMM-CVT101 RS-232 to RS-485 converter for use with the CB-GPI.
DB-9 Female
Signal Pin
RD
TDGNDRTS
2
357
SignalPin
3
274
RS-232
Vendor Port A or Bon Integrator
RS-232 Connectoron MM-CVT101
(50 ft maximum)
RD
TDGNDRTSintcbgp1
DB-25 Male
Figure 6: Cable Pinouts to MM-CVT101 Converter for CB-GPI
Cable Pinouts
12 Metasys Integrator—Metasys Integrator Cleaver-Brooks Application
Use Figure 7 for the RS-485 bus wires connection between the RS-485side of the Johnson Controls MM-CVT101 RS-232 to RS-485 converterand the CB-GPI.
MM-CVT101 CB-GPI
N2+N2-REF
RS-485 +RS-485 -REF
a
bc
intcb485
RS-485
Figure 7: RS-485 Bus Wire Connection for CB-GPI
Connect the female end of the RS-232 cable to either Vendor Port A orVendor Port B on the Metasys Integrator unit. Connect the other end to theDB-9 on the CB-Hawk ASCII Interface. (Standard NEMA 4 Version has aterminal block instead of a connector.)
MetasysIntegrator
CB-HawkASCII
Interface
DB-9Vendor PortA or B
RS-232 Cable
intcb3
Figure 8: Port to Port Connection
Connecting theCable
Metasys Integrator—Metasys Integrator Cleaver-Brooks Application 13
Metasys Integrator Setup
To set up the Metasys Integrator unit, use a portable PC connected to theMetasys Integrator Terminal Port. The Metasys Integrator unit setupinvolves:
• downloading the correct vendor communication table (.VCT file)
• setting up the port
• setting up the network addressing
The following table provides information specific to the Cleaver-Brooksapplication. For detailed procedures, see the Metasys Integrator technicalbulletins.
If your system has a CB-Hawk Enhancer option, you need to downloadthe .VCT files required for the CB-Hawk Boiler points, CB-HawkEnhancer Boiler points, and the CB-Hawk Enhancer general points. If youare not using a CB-Hawk Enhancer, you need only the CB-Hawk points.
14 Metasys Integrator—Metasys Integrator Cleaver-Brooks Application
Table 1: Metasys Integrator Setup for Cleaver-BrooksVendor Communication Table (.VCT FILE)
CB-Hawk ASCIIInterface
CB-GPI
CB-Hawk Boiler Points CB_HAWK.VCT CB_HAWKG.VCT
CB-Hawk Enhancer Boiler Points
CB_NHBP.VCT CB_NHBPG.VCT
CB-Hawk Enhancer General Points
CB_NHGP.VCT CB_NHGPG.VCT
CB-780 Burner Controller Points
Not Available HW_RM78X.VCT
CB-783 Expanded AnnunciatorPoints
Not Available HW_S7830.VCT
Port Setup
Baud Rate 9600 9600
Word Length 8 8
Stop Bits 1 1
Parity Even None
Interface RS-232 RS-485
Network SetupVendor Address
For CB-Hawk Boiler Points:
For CB-Hawk Enhancer Boiler Points:
For CB-Hawk EnhancerGeneral Points:
CB-780
CB-783
1 to 5
1E to 5E
0
Not Available
Not Available
tgt, ss1
tgt, ss1, blr2
tgt, ss1
tgt, ss1
tgt, ss1
Timeout Value
With Enhancer
Without Enhancer
5000 ms
--
--
--
8100 ms
6000 ms
Poll Delay 55 ms 0 ms
Performance GuideApproximate Scan Time(For a single N2 address)
CB-Hawk Boiler Points
CB-Hawk EnhancerBoiler Points
CB-Hawk Enhancer GeneralPoints
CB-780 Series BurnerController Points
CB-783 Expanded AnnunciatorPoints
15 seconds
20 seconds
20 seconds
Not Available
Not Available
29 seconds
6 seconds
16 seconds
2 seconds
2 seconds
1 Where tgt = CB-GPI card address (default 0) and ss = CB-Link slot number (1-6)
2 Where tgt = CB-GPI card address (default 0), ss = CB-Link slot number (6) andblr = boiler number (1-4)
Metasys Integrator—Metasys Integrator Cleaver-Brooks Application 15
Point Mapping Tables
The following tables show the CB-Hawk boiler control points. The pointsavailable for mapping depend on the type of equipment you are using. Ifyou use only boiler control panels with an ASCII interface, use Table 2. Ifyou also have a CB-Hawk Enhancer, use the points shown in Tables 2, 4,and 5. The CB-Hawk Enhancer points have been split into two groups:CB-Hawk Enhancer Boiler Points (Table 4) and CB-Hawk EnhancerGeneral Points (Table 5).
16 Metasys Integrator—Metasys Integrator Cleaver-Brooks Application
Table 2: CB-Hawk Boiler Control Panel Points - CB-Hawk ASCIIInterface
NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
1
2
3
4
5
6
psi
DegF
psi
psi
DegF
%
Operating Pressure (Steam Boiler)
Operating Temperature (Hot Water Boiler)
Gas Pressure
Oil Pressure
Oil Temperature
Fire Rate
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
Fire Rate Mode 0-auto, 1-manual
Atomizing Air Proving Switch 0-off, 1-on
Assured Low-Fire Cutoff 0-off, 1-on
Demand Terminal 0-off, 1-on
Recycle Limits 0-off, 1-on
Pre-Ignition Interlock 0-off, 1-on
Lock Out Interlock 0-off, 1-on
Pilot Valve 0-off, 1-on
Gas Main Valve 0-off, 1-on
Oil Main Valve 0-off, 1-on
AO
AO
AO
AO
AO
AO
1
2
3
4
5
6
DegF
DegF
DegF
DegF
DegF
DegF
Operating Setpoint (psi) (0-750)
Operating Boiler Off Control Setpoint (psi) (0-750)
Operating Boiler On Control Setpoint (psi) (0-750)
Set Back Setpoint (psi) (0-750)
Set Back Boiler Off Control Setpoint (psi) (0-750)
Set Back Boiler On Control Setpoint (psi) (0-750)
BO 1 Set Back Mode 0-no, 1-yes
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
#
#
code
code
#
hour
code
code
code
#
hour
%
#
#
Fuel Selection (None, Gas, LtOil, HyOil, ChangOvr)
Boiler Medium (None, Steam, Hot Water)
Burner Status
Burner Status Extended
Total Cycles
Total Runtime
History - Burner Status
History - Burner Status Extended
History - Fault Code
History - Fault Cycle
History - Fault Hours
History - Fire Rate
History - Fuel Selection
History - Sequence Timer
1 Network Point Type
2 Network Point Address
CB-HawkBoiler ControlPanel Points -CB-Hawk ASCIIInterface
To get the hardwarereference formapping points to aControl System(CS) object (via thesoftware model),combine the NPT(Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor the GasPressure point isAI3.
The hardwarereference for thePilot Valve point isBI8.
The ADI points(internalparameters) cannotbe mapped tostandard objects.To monitor thesepoints, map them toCS object ADattributes (whichcan then bemapped to standardobjects).
Metasys Integrator—Metasys Integrator Cleaver-Brooks Application 17
Table 3: CB-Hawk Boiler Control Panel Points - CB-GPINPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
psi
DegF
psi
psi
DegF
%
hp
Volt
Operating Pressure (Steam Boiler Only)4
Operating Temperature (Hot Water Boiler Only)4
Gas Pressure (Gas Fuel Only)4
Oil Pressure (Oil Fuel Only)4
Oil Temperature (Oil Fuel Only)4
Fire Rate
Boiler Size
Flame Signal
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Gas Fuel Select 0-Off, 1-On
Light Oil Fuel Select 0-Off, 1-On
Heavy Oil Fuel Select 0-Off, 1-On
Pre-Ignition Interlock 0-Off, 1-On
Recycle Limits 0-Off, 1-On
Lock Our Interlock 0-Off, 1-On
Pilot Valve 0-Off, 1-On
Gas Main Valve 0-Off, 1-On
Oil Main Valve 0-Off, 1-On
Atomizing Air Proving Switch 0-Off, 1-On
Burner Switch (Demand) 0-Off, 1-On
Assured Low Fire Cutoff 0-Off, 1-On
Fire Rate Mode 0-Auto, 1-Manual
Keyboard Mode 0-Program, 1-Operate
AO
AO
AO
AO
AO
AO
1
2
3
4
5
6
DegF
DegF
DegF
DegF
DegF
DegF
Operating Setpoint (psi) (0-750)
Operating Boiler Off Control Setpoint (psi) (0-750)
Operating Boiler On Control Setpoint (psi) (0-750)
Set Back Setpoint (psi) (0-750)
Set Back Boiler Off Control Setpoint (psi) (0-750)
Set Back Boiler On Control Setpoint (psi) (0-750)
BO 1 Set Back Mode 0-No, 1-Yes
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
1
2
3
4
5
6
7
8
9
code
code
code
code
code
code
code
code
code
Boiler Medium (None, Steam, Hot Water)3
Boiler Type (None, Firetube, Watertube)3
Fuel Selection3
Fuel Series3
Flame Amplifier Part No. 833 - (2421, 2420, 2462)3
Rate Linearization3
Control Source (Auto, Manual, Remote)3
Set Back Capable (None, No, Yes)3
Program Identifier3
1 Network Point Type
2 Network Point Address
3 For more information, see Cleaver-Brooks documentation.
4 Only the points that are applicable to the boiler configuration will be reliable.
Continued on next page . . .
CB-HawkBoiler ControlPanel Points -CB-GPI
To get the hardwarereference formapping points to aCS object (via thesoftware model),combine the NPT(Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor the GasPressure point isAI3.
18 Metasys Integrator—Metasys Integrator Cleaver-Brooks Application
NPT1
(Cont.)NPA2 Unit Description
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
#
%
%
sec
sec
sec
code
code
#
hour
code
code
code
#
hour
code
%
code
sec
Response Factor
Low Fire Rate
Max Fire Rate
Prepurge Extend
Post purge Extend
Sequence Timer
Burner Status3
Burner Status Extended3
Total Cycles
Total Runtime
History - Burner Status3
History - Burner Status Extended3
History - Fault Code3
History - Fault Cycle
History - Fault Hours
History - Fault Message3
History - Fire Rate
History - Fuel Selection3
History - Sequence Timer
1 Network Point Type
2 Network Point Address
3 For more information, see Cleaver-Brooks documentation.
Metasys Integrator—Metasys Integrator Cleaver-Brooks Application 19
Table 4: CB-Hawk Enhancer Boiler Points - CB-Hawk ASCIIInterface or CB-GPINPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
DegF
%
%
%
%
MBTU
MBTU
$
Gal (or Therms)
%
%
See Note 3.
Stack Temperature4
Instant Efficiency4
Average Efficiency (1 hour)4
Average Efficiency (8 hour)4
Average Efficiency (24 hour)4
Total BTU Input4
Total BTU Output4
Average Cost of Output4
Total Fuel Used4
Oxygen5
Carbon Monoxide5
Opacity5
Fuel Flow5
Water/Steam Flow5
Nitrogen Oxides5
Auxiliary Input 15
Auxiliary Input 25
1 Network Point Type
2 Network Point Address
3 User-defined units. For more information, see Cleaver-Brooks documentation.
The following notes refer to optional features for CB-Hawk Enhancers. These pointsare valid only with a CB-Hawk Enhancer with the feature listed.
4 Efficiency
5 Auxiliary Input
CB-HawkEnhancerBoiler Points -forCB-Hawk ASCIIInterface orCB-GPI
To get the hardwarereference formapping points to aCS object (via thesoftware model),combine the NPT(Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor the Total FuelUsed point is AI9.
20 Metasys Integrator—Metasys Integrator Cleaver-Brooks Application
Table 5: CB-Hawk Enhancer General Points - CB-Hawk ASCIIInterface or CB-GPINPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
1
2
3
4
5
psi
DegF
DegF
DegF
DegF (or psi)
Header Pressure (Steam Boiler)3
Header Temperature (Hot Water Boiler)3
Ambient Temperature4
Outdoor Temperature5
Outdoor Reset Actual Setpoint (or psi)5
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
1
2
3
4
5
6
7
8
9
10
11
12
13
14
DegF (or psi)
DegF (or psi)
DegF (or psi)
DegF (or psi)
DegF (or psi)
DegF (or psi)
#
#
#
#
#
$
$
$
System Setpoint3 (psi) (0-750)
System On Point3 (psi) (0-750)
System Off Point3 (psi) (0-750)
Setback Setpoint3 (psi) (0-750)
Setback On Point3 (psi) (0-750)
Setback Off Point3 (psi) (0-750)
Lead Boiler # (0-5)3
1st Lag Boiler # (0-5)3
2nd Lag Boiler # (0-5)3
3rd Lag Boiler # (0-5)3
4th Lag Boiler # (0-5)3
Cost of Gas (0.0 - 9.99)4
Cost of Light Oil (0.0 - 9.99)4
Cost of Heavy Oil (0.0 - 9.99)4
BI 1 Set Back Status 0-No, 1-Yes5
BO 1 Reset Fuel Totals 0-Reset 1-Reset5
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
%
sec
%
sec
Lag On Trigger Point
Lag On Time Delay
Lag Off Trigger Point
Lag Off Time Delay
Reset Ratio
1 Network Point Type
2 Network Point Address
The following three notes refer to optional features for CB-Hawk Enhancers. Thesepoints are only valid with a CB-Hawk Enhancer with the feature described.
3 Lead Lag
4 Efficiency
5 Outdoor Reset
CB-HawkEnhancerGeneralPoints –CB-Hawk ASCIIInterface orCB-GPI
To get the hardwarereference formapping points to aCS object (via thesoftware model),combine the NPT(Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor the AmbientTemperature pointis AI3.
Metasys Integrator—Metasys Integrator Cleaver-Brooks Application 21
Table 6: CB-780 Controller PointsNPT1 NPA2 Unit DescriptionAI 1 Volt Flame Signal
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
11
12
Test/Run Switch 0-run, 1-test
Operating Control T6 0-off, 1-on
Interlock T7 0-off, 1-on
Pilot Valve T8 0-off, 1-on
Main Valve T9 0-off, 1-on
Ignition T10 0-off, 1-on
Pilot Valve Hold T16 0-off, 1-on
Manual Open Switch T17 0-off, 1-on
Low Fire Switch T18 0-off, 1-on
High Fire Switch T19 0-off, 1-on
Pre-Ignition Switch T20 0-off, 1-on
Valve 2/Start T21 0-off, 1-on
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
ADI
1
2
3
4
5
6
7
8
9
10
11
12
13
code
code
Sec
code
code
code
code
Sec
code
code
code
code
Sec
Sequence Status3
Sequence Extension3
Sequence Timer
Remote Command3
Burner Availability
Amplifier Type3
Flame Response3 0-0.8 sec, 1-3.0 sec
Purge Time
History -- Fault Code3
History -- Fault Message3
History -- Sequence Status3
History -- Sequence Extension3
History -- Sequence Timer
1 Network Point Type
2 Network Point Address
3 For more information, see Cleaver-Brooks documentation.
CB-780ControllerPoints
To get the hardwarereference formapping points toCS object attributes(via the softwaremodel), combine theNPT (Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor Test/Run Switchis BI1.
ADI points (internalparameters) cannotbe mapped tostandard objects.To monitor thesepoints, map them toCS object ADattributes (whichcan then bemapped to standardobjects).
22 Metasys Integrator—Metasys Integrator Cleaver-Brooks Application
Table 7: CB-783 Expanded Annunciator PointsNPT1 NPA2 Unit DescriptionBI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Valve Closure T4 0-off, 1-on
Burner Switch T5 0-off, 1-on
Operating Control T6 0-off, 1-on
Auxiliary Limit 1 T7 0-off, 1-on
Auxiliary Limit 2 T8 0-off, 1-on
Low Water Cut Out T9 0-off, 1-on
High Limit T10 0-off, 1-on
Auxiliary Limit 3 T11 0-off, 1-on
Oil Select T12 0-off, 1-on
Hi Oil Pressure T13 0-off, 1-on
Lo Oil Pressure T14 0-off, 1-on
Hi Oil Temperature T15 0-off, 1-on
Lo Oil Temperature T16 0-off, 1-on
Atomizing Switch T19 0-off, 1-on
Gas Select T17 0-off, 1-on
Hi Gas Pressure T18 0-off, 1-on
Lo Gas Pressure T19 0-off, 1-on
Airflow Switch T20 0-off, 1-on
Auxiliary Interlock 4 T21 0-off, 1-on
Auxiliary Interlock 5 T22 0-off, 1-on
ADI
ADI
ADI
1
2
3
code
code
code
Current Status3
Fault First Out3
Fault Valve Closure (unknown, off, on)3
1 Network Point Type
2 Network Point Address
3 For more information, see Cleaver-Brooks documentation.
CB-783ExpandedAnnunciatorPoints
To get the hardwarereference formapping points toCS object attributes(via the softwaremodel), combine theNPT (Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor Valve Closure isBI1.
ADI points (internalparameters) cannotbe mapped tostandard objects.To monitor thesepoints, map them toCS object ADattributes (whichcan then bemapped to standardobjects).
Metasys Integrator—Metasys Integrator Cleaver-Brooks Application 23
Metasys Network Setup
Metasys Network Setup is described in the Metasys Integrator technicalbulletins. This section contains details specific to Cleaver-Brooksapplications.
Table 8 lists the software model files and the recommended Display andNetwork Terminal (NT) Command Attributes.
Whether all the models shown in the table are needed depends on theequipment used. For example, if the system has only boiler control panels(and no CB-Hawk Enhancer), only the model file for boiler control pointsis needed. If the system has a CB-Hawk Enhancer and an ASCII interface,all the three ASCII model files are used.
The CB-Hawk Enhancer points are split into two groups:
• CB-Hawk Enhancer boiler points and
• CB-Hawk Enhancer general points
The point mapping tables show how the points are categorized.
Table 8: Software Model and CS Object DetailsApplication Software Model
(on Tables andModels CD-ROM)
DisplayAttribute(recommended)
NT CommandAttribute(recommended)
CB-Hawk BoilerControl Points -ASCII
CB_HAWK.DDL AI1 (steam) or
AI2 (hot water)1BO1
CB-Hawk EnhancerBoiler Points -ASCII or GPI
CB_NHBP.DDL AI1 AI1
CB-Hawk EnhancerGeneral Points -ASCII or CB-GPI
CB_NHGP.DDL AI1 (steam) or
AI2 (hot water)1BO1
CB-Hawk BoilerControl Points -GPI
CB_HAWKG.DDL AI1 (steam) or
AI2 (hot water)1BO1
CB-780 HW_RM78X.DDL AI1Flame Signal
AI12
CB-783 HW_S7830.DDL BI2Burner Switch
BI22
1 Whether you use the AI1 or AI2 point depends on whether your system has asteam boiler or a hot water boiler.
2 For the NT Command attribute, use the same attribute as the Display attribute.However, since the CB-780 and CB-783 points are not commandable, you will notbe able to command the attribute. (This must be defined, because the NTCommand attribute cannot be null.)
Mapping to aCS Object
24 Metasys Integrator—Metasys Integrator Cleaver-Brooks Application
Metasys Integrator—Metasys Integrator Cleaver-Brooks Application 25
Custom Integration
For information on integrating products which are not discussed in thisdocument, first refer to the Metasys Compatible Global Catalog, an onlinelist of released Connectivity products. If this list does not provide theinformation you require, consider using the System Integration ProjectData Sheet to request a custom contract from the System IntegrationTeam.
Both the Metasys Compatible Global Catalog and the System IntegrationProject Data Sheet are accessible from The Advisor by performing thefollowing steps:
1. Click on the Systems Products button located on the left side of TheAdvisor home page.
2. Click on the Product Literature link.
3. Click on the Manuals-FANS link.
4. Click on the 629.0 Metasys Connectivity Sales Resource Manual link.
5. Find the System Integration Project Data Sheet link in the table ofcontents. Click on this link to view an online copy of the SystemIntegration Project Data Sheet or click on the Metasys CompatibleGlobal Catalog link below the data sheet to view a list of releasedConnectivity products.
The System Integration Project Data Sheet (LIT-6290052) is found in theMetasys Connectivity Sales Resource Manual (FAN 629).
If you need further assistance, contact Johnson Controls Field SupportCenter.