MERO Access Floor Type 3 / Steeltempwebmiumusersrecovery.blob.core.windows.net/users/... · 2015....

4
MERO Access Floor Type 3 / Steel Innovative solution from one source Floor systems MERO-TSK International GmbH & Co. KG Development Consulting Planning Manufacturing Installation Access floor Hollow floor Floor covering and Installation Services

Transcript of MERO Access Floor Type 3 / Steeltempwebmiumusersrecovery.blob.core.windows.net/users/... · 2015....

  • MERO Access Floor Type 3 / SteelInnovative solution from one source

    Floor systems

    MERO-TSK International GmbH & Co. KG

    Development

    Consulting

    Planning

    Manufacturing

    Installation

    Accessfloor

    Hollowfloor

    Floorcoveringand

    Installation

    Services

  • 2

    Stability under loadThe strong access floor of steel

    In addition to high strength and fracture resistance of access floors, extremely robust material properties are required in production areas, clean rooms, data centers or measuring rooms.At the same time there are high demands for flexibility to meet the requirements of new technologies or the reconfiguration of rooms. Furthermore, it is necessary to accommodate different service lines da-mage-free and to adapt them to any mo-dification without great effort. The steel access floor of MERO-TSK has proven itself in many fields. The floor panels can be combined with a variety of different floor coverings.

    Application TheMEROaccessfloortype3/steelissuitablefor• productionareas,laboratories• cleanrooms,measuringrooms• datacenters• printshops• floorswithlaminarairflowventilation

    Advantages

    • highstrengthandfractureresistance• extremelyrobustmaterialproperties• highflexibility• easy installation of additional equip-

    ment• variable construction heights, more

    than1,000mmonrequest• hugeinstallationplenum• suitable for the application of various

    floorcoverings

    TheMEROaccessfloorsystemsare testedacc.toDINEN12825andcertifiedbyinde-pendentinstitutes.

    Construction principle

    Floor panel

    Thefloorpanel type3 /steelconsistsofasteel tubing frame provided with a high-gradesteel cover plate. The conductive powdercoatingprotectsagainstabrasionandcorro-sion.The same size matching of floor coveringand steel cover plate guaranteesmaximizeedgeaccuracy.

    MERO-TSK International GmbH & Co. KG

  • 3

    Construction principle

    Substructure

    Thesubstructurecanbeused for all paneltypes.Theprecisionsteelpedestalsareadjustableinheightandprotectedagainstcorrosionbygalvanizationandpassivation.Thepedestalbaseplatesaregluedtothesubfloorandcanbedowelledonrequest.Forinstallationthepedestalheadsarepro-videdwithsounddampeningandconductivegasketswhichfixthepanel.Ifhighfrequen-cyshieldingisrequiredgasketscanbesup-pliedwithmetalrivets.The use of galvanized stringers increasestheloadbearingcapacityaswellastheho-rizontalstabilityofthewholesystemsothattheaccessfloorisformingaself-supportingconstructionevenwithout being connectedto the wall. The stringers can also be in-stalledafterwards.The screwing of stringers on the pedestalhead avoids frequency interferences. Thestringers are available as U-type or M-typestringer for lateral stability and as C-typestringerforincreasedloadsandlateralsta-bility.

    Planning instructions

    FlexibilityToguaranteehighflexibilitypanelswithfac-toryappliedfloorcoveringsshouldbeused.Thuselementswithbuilt-inunitscaneasilybeexchangedagainststandardpanels.

    Floor coveringsThe system type 3 can be provided withmanydifferentfloorcoverings.Elasticfloor coverings suchasPVC, linole-umand rubber aswell as laminate canbeappliedatfactory.Textile floor coverings can be firmlyappliedorlooselylaid.Thesuitabilityoffirm-ly applied floor coverings must be tested.MERO-TSK has many years of experienceand can test the suitability of new floorcoveringsintheirownlaboratories.Perforatedsteelpanelsincombinationwithairpermeablecarpetscanalsobeusedforlaminarairflowventilation.

    Built-in unitsCutouts for built-in units as power supplyunits,airoutletsorsimilarcanbecarriedoutinthefactoryandonsite.

    Connections to the wallConnectionsof theaccessfloorsystemstothewallorascendingconstructionpartsarecarried out by special self-adhesive foamtapes which avoid impact sound trans-missionandsealstheconnectionjoints.

    MERO-TSK International GmbH & Co. KG

  • Technicaldata*:Access Floor Type 3 / Steel

    06/1

    1/Ty

    pe3

    -s

    teel

    Subj

    ectt

    ote

    chni

    calc

    hang

    esw

    ithou

    tprio

    rnot

    ice

    Panel

    Dimensions: 600x600mmPanelthickness:(withoutfloorcovering) 33-44mmSystemweight:(withoutfloorcovering,floorheight1000mm)

    47-67kg/m²

    Panelweight: 16-22kg/pc

    Panelmaterial: steelconstruction,powdercoated,screwedonrequest

    Substructure

    Module: 600x600mmPedestalmaterial: galvanizedsteelConstructionheight:(withoutfloorcovering) ~70-1800mm

    Recommendation: Stringersshouldgenerallybeusedataheightof>500mm,e.g.u-typestringers

    Load values

    Concentratedload:• acc.toDINEN12825• nominalload• ultimateload

    Class5-65.000-7.000N>10.000-14.000N

    Electrostatic

    (dependingonsystemandfloorcovering) >105Ohm

    Fire protection

    Buildingmaterialclassacc.toDIN4102T1: A1

    Thermal conductivity

    Basematerial: ~50W/mk

    1. Floorpanel2. Gasket3. Tube4. Baseplategluedtothesubfloor

    (dowelledonrequest)

    Accessories: (see brochure)CutoutsSpecialwallconnectionsPowersupplyunitsAiroutletsAirconditioningpanelsFasciasBridgingsExpansionjointsStairsandrampsAdditionalimpactsoundinsulationMERO-TSKfloorcoverings

    *For further technical dataplease ask for our product data sheets.

    1

    2

    3

    4

    Headoffice:

    MERO-TSKInternational GmbH & Co. KG

    Max-Mengeringhausen-Str.5

    97084Würzburg,Germany

    Postaladress:

    MERO-TSKInternational GmbH & Co. KG

    ProductDivisionFloorSystems

    LauberStraße7

    97357Prichsenstadt,Germany

    Phone.:+49(0)9383203-603

    Fax:+49(0)9383203-629

    E-mail:[email protected]