Features and Benefits● 250A, 400A, 630A & 800A panelboard

versions available.

● 3 to 18 outgoing ways.

● Outgoing MCCBs up to 400A.

● KEMA certified.

● IP3X construction.

● Form 3B segregation (with terminal shields fitted).

● Tin - plated busbar systems throughout the range.

● Transient voltage surge (TVSS ) protection.

● Metering options.

● Reliable & safe operation assured throughKEMA testing & certification.

● Optional side extension modules provideimproved access for larger cables.

● Versatile solution, accommodating differentsize outgoing MCCBs to best matchapplication needs.

● Enhanced safety through fully shroudedincoming devices, to protect against contactwith live parts.

● Blanking plates finger protect unusedoutgoing ways.

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:23 Page 3

Page 3: MCCB Panelboard Distribution System

1

Contents Page

Panelboard Selection 2

Factory Built Assemblies 3

Panelboards up to 400A 4

Panelboards 400A to 630A 6

Panelboards 800A 8

TVSS 10

Dimensions 11

Circuit Breaker Technical Data 12

1 Lift off hinged door.

2 Form 3B segregation (with terminal shields fitted).

3 Removable top and bottom gland plates.

4 RAL 7004 epoxy polyester finish.

5 Neutral and earth arrangements:● Split neutral & earth.● Additional terminal capacity provided

for multiple single pole MCCB outgoers.

1

23

5

4

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:24 Page 4

Page 4: MCCB Panelboard Distribution System

2

● Incoming device;125A horizontallymounted

● Outgoing devices;3 x 16 – 125A TP or9 SP MCCBs

See page 4

● Incoming device; 250A – 400A

● Direct connection Lugs● Outgoing devices; up

to 2 x 63A – 250A TPMCCBs + up to 16 x 16A - 125ATP or 54 SP MCCBs

See page 6

Panelboard SelectionType 1 Panelboard – 125A Busbar

● Incoming device; 160A – 250A

● Outgoing devices;up to 12 x 16A –125A TP or 36 SP MCCBs

See page 4

Type 2 Panelboard – 250A Busbar

● Incoming device;

250A – 400A● Direct connection

lugs● Outgoing devices;

up to 12 x 16A –

125A TP or

36 SP MCCBs

See page 4

Type 3 Panelboard – 400A Busbar

Type 4 Panelboard – 400A Busbar

● Incoming device; 400A – 630A

● Direct connection Lugs● Outgoing devices;

up to 4 x 63A – 250A TP MCCBs+ up to 14 x 16A - 125A TP or 42 SP MCCBs

See page 6

Type 5 Panelboard – 630A Busbar

● Incoming device; 800A● Direct connection lugs● Outgoing devices; up

to 2 x 250A – 400A

TP MCCBs

+up to 4 x 63A – 250A

TP MCCBs + up to 6 x

16A – 125A TP or 18

SP MCCBs

See page 8

Type 6 Panelboard – 800A Busbar

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:26 Page 5

Page 5: MCCB Panelboard Distribution System

3

Options and Accessories

Choice of MCCB, circuit breaker switch or directconnection incomer.

Analogue and digital meter packs.

Side cable boxes and top / bottom cable extension boxes.

Door locking option.

Factory Built Assemblies

Complete factory built assemblies can be specified for individual projects, on which the factory will bepleased to advise.

Simple derivatives include:-

● The fitment of side extension boxes, dual

incomers and metering options etc.

Through a modular Panelboard system, more customsolutions can be accommodated to include:-

● 4 pole switching options.

● Fused combination switches for both incomers and outgoing ways.

● Form 4 type 2 solutions.

For more details on these services please contact ourcustomer support team on 08700 545 333.

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:28 Page 6

Page 6: MCCB Panelboard Distribution System

● IEC60439 – 1● Tin-plated busbars● Outgoing devices; 16A – 125A TP & SP● IP3X construction (Type 2 & 3)

Type 1, 2 & 3 Panelboard Selection - 125A & 250A Busbar

● Busbar system KEMA certified PBEG325 – 25kA Icc

PBEG625/825/1222 – 40kA Icc

PBEG640/1240 – 30kA Icw for 1s

4

1 - Panelboard

Description No of Ways List No Associated Incoming DeviceType 1 – 125A 3 PBEG325 GE - Frame Type 2 – 250A 6 PBEG625

8 PBEG825 GJ - Frame 12 PBEG1225

Type 3 – 400A 6 PBEG64012 PBEG1240 GL - Frame

2 - Incoming DeviceMCCBDescription GE - Frame GJ - Frame GL - Frame

List No List No List No

100A 18kA GEB3100FFG125A 18kA GEB3125FFG125A 25kA GEE3125FFG160A 40kA GJS3160AAG200A 40kA GJS3200AAG250A 40kA GJS3250AAG250A 50kA GLS3250AAM320A 50kA GLS3320AAM400A 50kA GLS3400AAM

Circuit Breaker Switch Incomer

Description GE - Frame GJ - Frame GL - Frame List No List No List No

100A 25kA GEK3100KSG125A 25kA GEK3125KSG160A 40kA GJK3160KSG200A 40kA GJK3200KSG250A 40kA GJK3250KSG250A 50kA GLK3250KSM320A 50kA GLK3320KSM400A 50kA GLK3400KSM

3 - Incomer Connection Kits

Description Incomer Connection Kit List No

Type 1 GE - Frame Not required Incoming device must be usedType 2 GJ - Frame Not required Incoming device must be used

GJ - Frame PBEGJG25M Metering version - includes CT‘s*Type 3 GL - Frame PBEGLG40

GL - Frame PBEGLG40M Metering version - includes CT‘s*Direct connection lugs kit PBEGL40Direct connection lugs kit PBEGL40M Metering version - includes CT‘s*

* Meter pack must be ordered seperately.

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:30 Page 7

Page 7: MCCB Panelboard Distribution System

5

5 - Accessories

Description List No

SP blanking module GE - Frame (1 pole per pack) PBEGB3Panel door lock with key PBDLK2MCCB accessory termination block for PBTB1

connection of shunt trips, UVR's, etc.

Extension Boxes

Side Cable Boxes

Description List NoTo fit Panelboard PBEG625 PBEGSX900To fit Panelboard PBEG640 & PBEG825 PBEGSX1050To fit Panelboard PBEG1225 PBEGSX1150To fit Panelboard PBEG1240 PBEGSX1300

Top / Bottom Cable Extension Boxes

Description List No250mm high PBEGEX250

Corner Filler Box

For use where top/ bottom / meter boxes are fitted in conjunction with PBEGSX250side cable boxes

Meter PacksIncoming connection kit: Metering version required

Description

Analogue Meter Packs 250A 400A Analogue voltmeter & selector switch.Analogue ammeter & selector switch.Phase indication lamps

List No List No6, 8, 12 way GJ - Frame incomer PBEGMPA256, 12 way GL - Frame incomer PBEGMPA40

Digital Meter PackskW/hr, phase Amps, phase Volts, line Volts, per phase PF, per phase kW, 3 phase PF, 3 phase kW, frequency, import kWh (ie; pulsed output)GJ/GL - Frame incomer PBEGMPD PBEGMPD

4 - Outgoing Devices GE - Frame MCCBs

Frame size 18kA 25kACurrent rating, (A) TP SP TP SP

List No List No List No List No16A GEB3016FFG GEB1016FFG GEE3016FFG GEE1016FFG20A GEB3020FFG GEB1020FFG GEE3020FFG GEE1020FFG32A GEB3032FFG GEB1032FFG GEE3032FFG GEE1032FFG40A GEB3040FFG GEB1040FFG GEE3040FFG GEE1040FFG50A GEB3050FFG GEB1050FFG GEE3050FFG GEE1050FFG63A GEB3063FFG GEB1063FFG GEE3063FFG GEE1063FFG80A GEB3080FFG GEB1080FFG GEE3080FFG GEE1080FFG100A GEB3100FFG GEB1100FFG GEE3100FFG GEE1100FFG125A GEB3125FFG GEB1125FFG GEE3125FFG GEE1125FFG

Meter packs include the meter and housing, cable loom and fuses. Where a meter pack is used with a GL incomer a cable extension box ; PBEGEX250,will also be required to provide additional space for incoming cables. This will need to be ordered separately.

PBEGB3

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:31 Page 8

Page 8: MCCB Panelboard Distribution System

6

● IEC 60439 – 1● Tin-plated busbars● Outgoing devices; these panelboards utilise two

frame sizes of MCCB: 63A – 250A TP and 16A –125A TP & SP

Type 4 & 5 Panelboard Selection - 400A & 630A Busbar● IP3X construction● Busbar system KEMA certified

Type 4 – 35kA Icw for 1sType 5 – 50kA Icw for 1s

1 - Panelboard

Description No of Ways List NoType 4 – 400A 6 (2 x 250A + 4 x 125A) PBJG640

12 (2 x 250A + 10 x 125A) PBJG124018 (2 x 250A + 16 x 125A) PBJG1840

Type 5 – 630A 8 (4 x 250A + 4 x 125A) PBJG86312 (4 x 250A + 8 x 125A) PBJG126318 (4 x 250A + 14 x 125A) PBJG1863

2 - Incoming Device - Connection kit requiredMCCB

Description Type 4 List No Type 5 List No

250A 40kA GJS3250AAG250A 50kA GLS3250AAM GLS3250AAM320A 50kA GLS3320AAM GLS3320AAM400A 50kA GLS3400AAM GLS3400AAM400A 70kA GLH3400AAM GLH3400AAM630A 50kA GLS3630AAM630A 70kA GLH3630AAM630A electronic LSI GLH363032GM

Circuit Breaker Switch Incomer

Description Type 4 List No Type 5 List No

250A 40kA GJK3250KSG250A 50kA GLK3250KSM GLK3250KSM320A 50kA GLK3320KSM GLK3320KSM400A 50kA GLK3400KSM GLK3400KSM630A 50kA GLK3630KSM

3 - Incomer Connection Kits

Description Incomer List NoType 4 GJ Frame 250A PBJGJG25

GJ Frame 250A PBJGJG25M Metering version - includes CT‘s*GL Frame 400A PBJGLG40GL Frame 400A PBJGLG40M Metering version - includes CT‘s*Lugs Connection 400A PBJGL40Lugs Connection 400A PBJGL40M Metering version - includes CT‘s*

Type 5 GL Frame 630A PBJGLG63GL Frame 630A PBJGLG63M Metering version - includes CT‘s*Lugs Connection 630A PBJGL63Lugs Connection 630A PBJGL63M Metering version - includes CT‘s*

* Meter pack must be ordered separately

4 - Outgoing Devices GJ - Frame MCCBsUp to 2 for size 4 Panelboards, up to 4 for size 5 Panelboards

Frame size 40kACurrent rating, (A) TP

List No63A GJS3063AAG80A GJS3080AAG100A GJS3100AAG125A GJS3125AAG160A GJS3160AAG200A GJS3200AAG250A GJS3250AAG

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:32 Page 9

Page 9: MCCB Panelboard Distribution System

7

Outgoing Devices GE - Frame MCCBs

Frame size 18kA 25kACurrent rating, (A) TP SP TP SP

List No List No List No List No16A GEB3016FFG GEB1016FFG GEE3016FFG GEE1016FFG20A GEB3020FFG GEB1020FFG GEE3020FFG GEE1020FFG32A GEB3032FFG GEB1032FFG GEE3032FFG GEE1032FFG40A GEB3040FFG GEB1040FFG GEE3040FFG GEE1040FFG50A GEB3050FFG GEB1050FFG GEE3050FFG GEE1050FFG63A GEB3063FFG GEB1063FFG GEE3063FFG GEE1063FFG80A GEB3080FFG GEB1080FFG GEE3080FFG GEE1080FFG100A GEB3100FFG GEB1100FFG GEE3100FFG GEE1100FFG125A GEB3125FFG GEB1125FFG GEE3125FFG GEE1125FFG

5 - Accessories

Description List No

SP blanking module GE - Frame (1 pole per pack) PBEGB3TP blanking module GJ - Frame PBJGB3Panel door lock with key PBDLK2MCCB accessory termination block for PBTB1connection of shunt trips, UVR's, etc.

Extension Boxes

Side Cable Boxes

Description List No

To fit panelboard PBJG640 & PBJG863 PBJGSX1400To fit panelboard PBJG1240 & PBJG1263 PBSX1600To fit panelboard PBJG1840 & PBJG1863 PBSX1800

Top / Bottom Cable Extension Boxes

Description List No

250mm high PBEX250

Corner Filler Box

For use where top / bottom / meterboxes are fitted in conjunctionwith side cable boxes

Meter PacksIncoming connection kit: Metering version required

Description

Analogue Meter Packs 250A 400A 630A Analogue voltmeter & selector switch.Analogue ammeter & selector switch.Phase indication lamps

List No List No List NoType 4 PBJGMPA25 PBJGMPA40Type 5 PBJGMPA63

Digital Meter PackskW/hr, phase Amps, phase Volts, line Volts, per phase PF, per phase kW, 3 phase PF, 3 phase kW, frequency, import kWh (ie; pulsed output)Type 4/5 PBJGMPD PBJGMPD PBJGMPD

Meter packs include the meter and housing, cable loom and fuses. Where a meter pack is used with a GL incomer a cable extensionbox; PBEX250, will also be required to provide additional space for incoming cables.

PBJGB3

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:32 Page 10

Page 10: MCCB Panelboard Distribution System

8

● IEC 60439 – 1● Tin-plated busbars● Outgoing devices; these panelboards utilise three

frame sizes of MCCB: 250A – 400A TP, 63A – 250ATP, 16A – 125A TP & SP

Type 6 Panelboard Selection - 800A Busbar

● IP3X construction● Busbar system KEMA certified;

50kA Icw for 1s

1 - Panelboard

Description No of Ways List NoType 6 – 800A 8 (2 x 400A + 2 x 250A + 4 x 125A) PBLG880

12 (2 x 400A + 4 x 250A + 6 x 125A) PBLG1280

2 - Incoming Device - Connection kit required

MCCB / Circuit Breaker Switch

Description List No800A 50kA MCCB GLW380032W800A 50kA CBS GLK3800KSW

3 - Incomer Connection Kits

Description Incomer List NoType 6 800A MCCB or CBS PBLGLW80

Direct connection lugs kit PBJGL63800A MCCB or CBS PBLGLW80M Metering version - includes CT‘s800A Direct connection lugs kit PBJGL63M Metering version - includes CT‘s

4 - Outgoing Devices GL - Frame MCCBsUp to 2 per panelboardSide cable box (es) required when fitting GL MCCB (s).

630A Frame size 50kACurrent rating, (A) TP

List No250A GLS3250AAG320A GLS3320AAG400A GLS3400AAG

Outgoing Devices GJ - Frame MCCBsUp to 2 for PBLG880, up to 4 for PBLG1280

250A Frame size 40kACurrent rating, (A) TP

List No63A GJS3063AAG80A GJS3080AAG100A GJS3100AAG125A GJS3125AAG160A GJS3160AAG200A GJS3200AAG250A GJS3250AAG

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:33 Page 11

Page 11: MCCB Panelboard Distribution System

9

Outgoing Devices GE - Frame MCCBs

125A Frame size 18kA 25kACurrent rating, (A) TP SP TP SP

List No List No List No List No16A GEB3016FFG GEB1016FFG GEE3016FFG GEE1016FFG20A GEB3020FFG GEB1020FFG GEE3020FFG GEE1020FFG32A GEB3032FFG GEB1032FFG GEE3032FFG GEE1032FFG40A GEB3040FFG GEB1040FFG GEE3040FFG GEE1040FFG50A GEB3050FFG GEB1050FFG GEE3050FFG GEE1050FFG63A GEB3063FFG GEB1063FFG GEE3063FFG GEE1063FFG80A GEB3080FFG GEB1080FFG GEE3080FFG GEE1080FFG100A GEB3100FFG GEB1100FFG GEE3100FFG GEE1100FFG125A GEB3125FFG GEB1125FFG GEE3125FFG GEE1125FFG

5 - Accessories

Description List No

SP blanking module GE - Frame PBEGB3(1 pole per pack)TP blanking module GJ - Frame PBJGB3TP blanking module GL - Frame PBLGB3Panel door lock with key PBDLK2MCCB accessory termination block for PBTB1connection of shunt trips, UVR's, etc.

Extension Boxes

Side Cable Boxes

Description List No800A (2 + 2 + 4 way) PBSX1600800A (2 + 4 + 6 way) PBSX1800

Top / Bottom Extension Boxes

Description List No250mm high PBEX250

Corner Filler Box

For use where top / bottom / meter boxes are fitted in PBSX250conjunction with side cable boxes

Meter Packs

DescriptionAnalogue Meter Packs 800A busbarAnalogue voltmeter & selector switch.Analogue ammeter & selector switch.Phase indication lamps

List NoPBLGMPA80

Digital Meter PackskW/hr, phase Amps, phase Volts, line Volts, per phase PF, per phase kW, 3 phase PF, 3 phase kW, frequency, import kWh (ie; pulsed output)

List NoPBLGMPD

Meter packs include the meter and housing, cable loom and fuses. Where a meter pack is used, a cable extension box; PBEX250, willalso be required to provide additional space for incoming cables.

PBLGB3

Meter PacksIncoming connection kit: Metering version required

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:33 Page 12

Page 12: MCCB Panelboard Distribution System

10

TVSS Kits for MCCB Panelboards

A Surge Protective Device has been developedspecifically for application with MCCB panelboardsensuring outstanding product performance for allsensitive, mission critical and general purpose loads.The UL1449 Second Edition and UL1283 listeddevices provide high peak surge current ratings andexceptionally low real-world measured limiting (let-through) voltage values, together with outstandingdurability, assuring a lifetime of effective,maintenance free protection for all electrical andelectronic systems.

Protection:Active Response Network (ARN) provides optimumsuppression of internal switching generatedtransients.

Threshold Response Network (TRN) providesmaximum suppression of high energy impulsegenerated transients.

This assures excellent protection of sensitiveelectronic, electro-mechanical and micro-processorbased equipment.

LED status indication is provided.

Volt free relay allows remote status indication.

Mechanical Specifications:

TVSS Enclosure: IP23 rated steel enclosure.

Mounting: Conduit fitting and multi-point mounting feet.

Connection: Standard products include approx. 450mm factory fitted stranded cable #10 AWG (≈ 6mm2). Flush mounting plateavailable, order list number ZPLATE-4

Shipping weight: 2.2kg.

TVSS MODULESEach TVSS module is supplied complete with the following:

● TVSS unit as detailed above● 32A TP MCCB● Fittings to attach TVSS unit to panelboard● Full instructions

Description LIST No.

TVSS Module Kit M2SSK3EG

For full details of TVSS products refer to the Transient Voltage Surge Suppression catalogue available on request.

General Specifications:

Description: Parallel configured, hard wire connected, 80kA per phase peak surge current Transient Voltage Surge Suppressor.

Application: Location Categories B and A, medium and low exposure level. General purpose, sensitive, and mission criticalloads. Small AC power service entrances (≤ 630amps), MCCB panelboards.

Warranty: 10-Year Free Replacement.

Unit listings: UL1449 Second Edition, UL1283 Filter.

Quality: ISO 9001: 1994 Quality System Certification BSI FM 30833.

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:33 Page 13

Page 13: MCCB Panelboard Distribution System

11

Panelboard Dimensions

Panelboard Cable Space

PANELBOARD 250A FRAME SIZE INCOMER 630A/800A FRAME SIZE INCOMER LUG INCOMER

TYPES 1 & 2

TYPES 3, 4 & 5

TYPE 6

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:34 Page 14

Page 14: MCCB Panelboard Distribution System

12

The First True Global CircuitBreaker FamilyEaton Series G Moulded Case Circuit Breakers (MCCBs)

provide unmatched performance in a dramatically more

compact package than standard circuit breakers or

comparable fusible devices. Eaton MCCBs can be

configured in cascade rated systems, allowing the use of

lower interruption circuit breakers downstream, which leads

to lower system cost. While meeting IEC 60947-2 service and

interrupting ratings, these breakers provide unmatched

flexibility by employing a wide variety of trip units including

fixed thermal-magnetic, adjustable-thermal adjustable-

magnetic, and electronic options.

Eaton MCCBs are available in five frame sizes in ratings from 16

to 2500 amperes and in interrupting capacities up to 100 kA at

415V AC. Standard calibration is at 40°C with optional 50°C

factory calibration available for applications where higher

ambient temperatures are encountered. Eaton MCCBs use

patented contact conductor designs featuring high-speed

“blow-open” action that results in superior performance when

high level fault currents produce extraordinary

electromechanical forces.

Current Limiting CharacteristicsIn accordance with BSEN60947-2 / IEC 60947-2, Eaton MCCBs

current limiting design is achieved with a high repulsion contact

configuration and advanced arc extinguishing technology.

Operating MechanismsIn standard configuration, Eaton use a toggle handle operating

mechanism which also serves as a switching position indicator.

The toggle handle indicates ON, OFF and TRIPPED positions.

World Class BreakersAdvanced design, superior manufacturing and unmatched

ruggedness combine to set the standard in world-class moulded

case circuit breakers.

Assured Reliability Through In-plant TestingThe quality, dependability, and reliability of every Eaton MCCB is

assured by a thorough program of in-plant testing. A minimum of

two calibration tests are conducted on every pole of every circuit

breaker to verify the trip mechanism, operating mechanism,

continuity, and accuracy.

High Service LevelsThe Eaton business has strategically located manufacturing plants

world-wide that assemble moulded case circuit breakers. These

plants employ a flexible manufacturing strategy that allows for

rapid and efficient order fulfillment.

Global CertificationEaton MCCBs are also available listed in accordance with UL 489

and CSA C22.2 No. 5.1. These are independent third party testing

houses who assure compliance with North American standards.

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:34 Page 15

Page 15: MCCB Panelboard Distribution System

13

Trip UnitsThe Eaton family of electronic Digitrip trip units offers unparalleled

protection and monitoring features. Digitrip RMS units provide

long delay, short delay, instantaneous, and ground fault

protection. Curve shaping, zone selective interlocking, system

diagnostics, and system monitoring and communications are all

features available by selecting the appropriate Digitrip RMS for

the specific requirement.

Eaton also offers electromechanical trip units that provide short

circuit protection and overload protection. Conventional moulded

case circuit breakers are available with either a fixed or adjustable

electromechanical trip unit, depending on frame size.

Temperature and CalibrationThe operating ambient temperature range for most Eaton

electromechanical or electronic trip units is between -20°C to

+70°C. Should the internal temperature rise to an unsafe level,

temperature protective circuits in the electronic designs initiate a

tripping operation and provide self-protection.

Standard calibration is 40°C. For applications in high ambient

temperature conditions, 50°C factory calibration is available.

Earth Leakage ModuleFeatures

• Field installable

• Self powered

• Adjustable earth leakage pick-up

• Adjustable time delay

• Adjustment seal

• Status indicator – led flashes to indicate proper operation

• Earth fault trip alarm contact

• Earth fault pre-trip alarm contact

• Push-to-test & push-to-trip

AccessoriesThe Eaton MCCB range offers a wide choice of internal andexternal accessories that complement moulded case circuitbreakers. Plug-in internal accessories are common for GE – GL– Frames — 16 - 630 amperes and are suitable for fieldinstallation. The available plug-in accessories include:

• Alarm switch

• Auxiliary switch

• Shunt trip

• Low energy shunt trip

• Undervoltage release mechanism.

Also offered is an extensive line of handle operatingaccessories. These accessories provide indirect electrical ormanual circuit breaker handle operations. They include:

• Electrical (solenoid) operator

• Motor driven electrical operator

• Rotary handle

• Vari-depth handle mechanism

• Flex shaft handle mechanism.

Two basic types of termination accessories are provided;terminal connection devices and termination protection devices:

• Line and load terminals

• End cap keeper nut

• Rear connected studs

• Terminal end covers

• Terminal shields

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:34 Page 16

Page 16: MCCB Panelboard Distribution System

14

Moulded Case Circuit Breaker Range 16A to 160A, GE-Frame

• GE-Frame MCCBs available in four breaking capacity ranges; 18kA, 25kA, 40kA & 70kA.

• Current ratings 16A to160A.

• User fitted, front fitting accessories.

• New design around space-saving footprint.

•Current limiting action provides for low values of let-through energy.

MCCB Description 18kA Range 25kA Range 40kA Range 70kA Range

1-pole 2-pole 3-pole 1-pole 3-pole 4-pole (TPSN) 3-pole 4-pole (TPSN) 3-pole 4-pole (TPSN)

Utilisation Category A A A A A A A A A A

Impulse Withstand Voltage 6kV 6kV 6kV 6kV 6kV 6kV 6kV 6kV 6kV 6kV

Thermal Trip Fixed Fixed Fixed Fixed Fixed Fixed Adjustable Adjustable Adjustable Adjustable

0.8 to 1 x In 0.8 to 1 x In 0.8 to 1 x In 0.8 to 1 x In

Magnetic Trip 16A to 40A fixed 16A to 40A fixed 16A to 40A fixed 16A to 40A fixed 16A to 40A fixed 16A to 40A fixed 16A to 40A fixed 16A to 40A fixed 16A to 40A fixed 16A to 40A fixed

at 500A at 500A at 500A at 500A at 500A at 500A at 500A at 500A at 500A at 500A

Others fixed at Others fixed at Others fixed at Others fixed at Others fixed at Others fixed at Others fixed at Others fixed at Others fixed at Others fixed at

10 x In 10 x In 10 x In 10 x In 10 x In 10 x In 10 x In 10 x In 10 x In 10 x In

BREAKING CAPACITY IEC60947-2/BSEN60947-2 (AC 50/60HZ)

380-415V AC lcu (kA) 18 18 18 25 25 25 40 40 70 70

Ics (kA) 14 14 14 13 13 13 40 40 35 35

220-240V AC lcu (kA) 25 25 25 35 35 35 85 85 100 100

Ics (kA) 13 13 13 18 18 18 43 43 50 50

25OV DC lcu (kA) 15 15 25 25 35 35 42 42

Ics (kA) 8 8 13 13 35 35 42 42

MCCBs List Number

Current Rating (A) Box Clamp Type Terminals

16A GEB1016FFG GEB2016FFG GEB3016FFG GEE1016FFG GEE3016FFG GEE4016FFG

20A GEB1020FFG GEB2020FFG GEB3020FFG GEE1020FFG GEE3020FFG GEE4020FFG GES3020AFG GES4020AFG GEH3020AFG GEH4020AFG

32A GEB1032FFG GEB2032FFG GEB3032FFG GEE1032FFG GEE3032FFG GEE4032FFG GES3032AFG GES4032AFG GEH3032AFG GEH4032AFG

40A GEB1040FFG GEB2040FFG GEB3040FFG GEE1040FFG GEE3040FFG GEE4040FFG GES3040AFG GES4040AFG GEH3040AFG GEH4040AFG

50A GEB1050FFG GEB2050FFG GEB3050FFG GEE1050FFG GEE3050FFG GEE4050FFG GES3050AFG GES4050AFG GEH3050AFG GEH4050AFG

63A GEB1063FFG GEB2063FFG GEB3063FFG GEE1063FFG GEE3063FFG GEE4063FFG GES3063AFG GES4063AFG GEH3063AFG GEH4063AFG

80A GEB1080FFG GEB2080FFG GEB3080FFG GEE1080FFG GEE3080FFG GEE4080FFG GES3080AFG GES4080AFG GEH3080AFG GEH4080AFG

100A GEB1100FFG GEB2100FFG GEB3100FFG GEE1100FFG GEE3100FFG GEE4100FFG GES3100AFG GES4100AFG GEH3100AFG GEH4100AFG

125A GEB1125FFG GEB2125FFG GEB3125FFG GEE1125FFG GEE3125FFG GEE4125FFG GES3125AFG GES4125AFG GEH3125AFG GEH4125AFG

160A GES3160AFG GES4160AFG

Circuit Breaker Switches (with high magnetic trip, will trip above 1700A)

Current Rating (A) 3-pole 4-pole (TPSN)

100A GEK3100KSG GEK4100KSG

125A GEK3125KSG GEK4125KSG

160A GEK3160KSG GEK4160KSG

Terminal Capacities 70mm2 70mm2 70mm2* 70mm2 70mm2* 70mm2* 70mm2* 70mm2* 70mm2* 70mm2*

(max)

Dimensions (mm)

A 25.4 50.8 76.2 25.4 76.2 101.6 76.2 101.6 76.2 101.6

B 140 140 140 140 140 140 140 140 140 140

C 70.4 70.4 70.4 70.4 70.4 70.4 70.4 70.4 70.4 70.4

D 92.0 92 92 92 92 92 92 92 92 92

Weight (kg) 0.5 0.9 1.4 0.5 1.4 1.8 1.4 1.8 1.4 1.8

All GE-Frame MCCBs can be supplied with 50˚C ambient calibration. To order, insert

V at the end of the list number eq. GEB1125FFGV or GEH4125AFGV

*120mm2 capacity extension terminals available :

List No 3TA160EFK (3 terminals with terminal shield)

List No 4TA160EFK (4 terminals with terminal shield)

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:34 Page 17

Page 17: MCCB Panelboard Distribution System

15

16A to 160A GE-Frame Auxiliaries and AccessoriesACCESSORY / AUXILIARY DESCRIPTION

List Number1 Pole 2 Pole 3 Pole 4 Pole

Terminal Shield (load end) EFTS1KA EFTS2K EFTS3K EFTS4KTerminal Shield (line end) EFTS1KB EFTS2K EFTS3K EFTS4KInterpole Barriers (2 per pack) EFIPBK EFIPBK EFIPBK EFIPBKTerminal End Cover (Gas Barrier) EEC3K EEC4K

Rotary Drive (Direct) Black Handle - - EHMCCB EHMCCBRotary Drive (Direct) Black Handle with interlock EHMCCBI EHMCCBIRotary Drive (Direct) Red Handle - - EHMCCR EHMCCRVari-depth rotary drive 152mm Black Handle - - EHMVD06B EHMVD06BVari-depth rotary drive 152mm R/Y Handle - - EHMVD06R EHMVD06RVari-depth rotary drive 305mm Black Handle - - EHMVD12B EHMVD12BVari-depth rotary drive 305mm R/Y Handle - - EHMVD12R EHMVD12R

Handle Lock Plastic EFPHB EFPHB EFPHB EFPHBHandle Lock Metal - - EFPHL EFPHLHandle Lock Padlock PD50 PD50 PD50 PD50Front mounted sliding bar interlock - - EFSBI

End Cap Set Metric - Line Side EF3RTWK EF4RTWKControl wire terminal kit (12 pack) EFCWTK EFCWTK EFCWTK EFCWTK

Earth Leakage Module (125A max.) - - ELESE3125W ELESE4125W

Motor Operator 120 Vac - - EOPEF240C EOPEF240CMotor Operator 240 Vac EOPEF240C EOPEF240CMotor Operator 24 Vdc EOPEF24D EOPEF24DMotor Operator 48 Vdc - - EOPEF48D EOPEF48DMotor Operator 125 Vdc - - EOPEF240C EOPEF240C

Plug in Block (incl power conns & safety trip) - - PAD3E PAD4E

Shunt TripsShunt Trip 24-48Vdc - - SNT060CPK SNT060CPKShunt Trip 120-240Vac - - SNT120CPK SNT120CPKShunt Trip 380-600Vac - - SNT480APK SNT480APK

Undervoltage ReleasesUVR 12Vac/dc - - UVR012CPK UVR012CPKUVR 24Vac/dc - - UVR024CPK UVR024CPKUVR 48Vac - - UVR048APK UVR048APKUVR 48Vdc - - UVR048DPK UVR048DPKUVR 120Vac - - UVR120APK UVR120APKUVR 120Vdc - - UVR125DPK UVR125DPKUVR 208-240Vac - - UVR240APK UVR240APKUVR 220-250Vdc - - UVR250DPK UVR250DPKUVR 308-500Vac - - UVR480APK UVR480APKUVR 525-600Vdc - - UVR600APK UVR600APK

Other AuxiliariesAuxiliary Switch 1NO/NC - - AUX1A1BPK AUX1A1BPKAuxiliary Switch 2NO/NC - - AUX2A2BPK AUX2A2BPKAuxiliary/Alarm Switch 1NO/NC - - AUXALRMEPK AUXALRMEPKAlarm Switch 1NO/NC - - ALM1M1BEPK ALM1M1BEPKAlarm Switch 2NO/NC - - ALM2M2BEPK ALM2M2BEPK

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:34 Page 18

Page 18: MCCB Panelboard Distribution System

16

Moulded Case Circuit Breaker Range 50A to 250A, GJ-Frame

• GJ-Frame MCCBs available in two breaking capacity ranges; 40kA & 70kA.

• Choice of thermal/magnetic or electronic trip units.

• User fitted, front fitting accessories.

• New design around space-saving footprint.

•Current limiting action provides for low values of let-through energy.

Thermal Magnetic Trip Unit Range Electronic Trip Unit (Digitrip RMS 310 LSI) Range

MCCB Description 40kA Range 70kA Range 40kA Range 70kA Range

3-pole 4-pole (TPSN) 3-pole 4-pole (TPSN) 3-pole 4-pole (TPSN) 3-pole 4-pole (TPSN)

Utilisation Category A A A A A A A A

Impulse Withst - 8kV 8kV 8kV 8kV 8kV 8kV 8kV 8kVand Voltage

Thermal Trip Adjustable 0.8 to 1 x In Adjustable 0.8 to 1 x In Adjustable 0.8 to 1 x In Adjustable 0.8 to 1 x In Adjustable 0.5 to 1 x In Adjustable 0.5 to 1 x In Adjustable 0.5 to 1 x In Adjustable 0.5 to 1 x In

Magnetic Trip Adjustable 5 to 10 x In Adjustable 5 to 10 x In Adjustable 5 to 10 x In Adjustable 5 to 10 x In Adjustable 2 to 14 x In Adjustable 2 to 14 x In Adjustable 2 to 14 x In Adjustable 2 to 14 x In

BREAKING CAPACITY IEC60947-2/BSEN60947-2 (AC 50/60HZ)

660-690V AC lcu (kA) 12 12 14 14 12 12 14 14

Ics (kA) 6 6 7 7 6 6 7 7

380-415V AC lcu (kA) 40 40 70 70 40 40 70 70

Ics (kA) 40 40 70 70 40 40 70 70

220-240V AC lcu (kA) 85 85 100 100 85 85 100 100

Ics (kA) 85 85 100 100 85 85 100 100

25OV DC lcu (kA) 35 35 42 42

Ics (kA) 35 35 42 42

MCCBs List Number

Current Rating (A) Box Clamp Type Terminals

50A GJS305032G GJS405032G GJH305032G GJH405032G

80A GJS3080AAG GJS4080AAG GJH3080AAG GJH4080AAG

100A GJS3100AAG GJS4100AAG GJH3100AAG GJH4100AAG GJS310032G GJS410032G GJH310032G GJH410032G

125A GJS3125AAG GJS4125AAG GJH3125AAG GJH4125AAG

160A GJS3160AAG GJS4160AAG GJH3160AAG GJH4160AAG GJS316032G GJS416032G GJH316032G GJH416032G

200A GJS3200AAG GJS4200AAG GJH3200AAG GJH4200AAG

250A GJS3250AAG GJS4250AAG GJH3250AAG GJH4250AAG GJS325032G GJS425032G GJH325032G GJH425032G

Current Rating (A) Bolt Type Terminals

50A GJS305032M GJS405032M GJH305032M GJH405032M

80A GJS3080AAM GJS4080AAM GJH3080AAM GJH4080AAM

100A GJS3100AAM GJS4100AAM GJH3100AAM GJH4100AAM GJS310032M GJS410032M GJH310032M GJH410032M

125A GJS3125AAM GJS4125AAM GJH3125AAM GJH4125AAM

160A GJS3160AAM GJS4160AAM GJH3160AAM GJH4160AAM GJS316032M GJS416032M GJH316032M GJH416032M

200A GJS3200AAM GJS4200AAM GJH3200AAM GJH4200AAM

250A GJS3250AAM GJS4250AAM GJH3250AAM GJH4250AAM GJS325032M GJS425032M GJH325032M GJH425032M

Circuit Breaker Switches (with high magnetic trip, will trip above 2500A)

Current Rating (A) Box Clamp Type Terminals

160A GJK3160KSG GJK4160KSG

200A GJK3200KSG GJK4200KSG

250A GJK3250KSG GJK4250KSG

Current Rating (A) Bolt Type Terminals

160A GJK3160KSG GJK4160KSG

200A GJK3200KSG GJK4200KSG

250A GJK3250KSG GJK4250KSG

Terminal Capacities

Box Clamp Terminal

Capacity (max) 150mm2 150mm2 150mm2 150mm2 150mm2 150mm2 150mm2 150mm2

Bolt Type M8 M8 M8 M8 M8 M8 M8 M8

Terminal Size

Dimensions (mm)

A 105 135.6 105 135.6 105 135.6 105 135.6

B 177.8 177.8 177.8 177.8 177.8 177.8 177.8 177.8

C 87.4 87.4 87.4 87.4 87.4 87.4 87.4 87.4

D 118 118 118 118 118 118 118 118

Weight (kg) 5.2 7 5.2 7 5.2 7 5.2 7

All thermal magnetic J-Frame MCCBs can be supplied with 50˚C ambient calibration. To order, insert V at the end of the list number eq. GJS3250AAGV or GJH4250AAMV

Electronic trip J Frame MCCBs are suitable for 40˚C or 50˚C applications

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:34 Page 19

Page 19: MCCB Panelboard Distribution System

17

50A to 250A GJ-Frame Auxiliaries and AccessoriesACCESSORY / AUXILIARY DESCRIPTION

List Number3 Pole 4 Pole

Terminal Shield (1 per pack) FJTS3K FJTS4KInterpole Barriers (2 per pack) FJIPBK FJIPBK4

Rotary Drive (Direct) Black Handle JHMCCB JHMCCBRotary Drive (Direct) Black Handle with interlock JHMCCBI JHMCCBIRotary Drive (Direct) Red Handle JHMCCR JHMCCRVari-depth rotary drive 152mm Black Handle FJHMVD06B FJHMVD06BVari-depth rotary drive 152mm R/Y Handle FJHMVD06R FJHMVD06RVari-depth rotary drive 305mm Black Handle FJHMVD12B FJHMVD12BVari-depth rotary drive 305mm R/Y Handle FJHMVD12R FJHMVD12R

Handle Lock Plastic FJPHB FJPHBHandle Lock Metal padlockable FJPHL FJPHLHandle Lock Padlock PD50 PD50Front mounted sliding bar interlock FJSBIWalking beam interlock FJWBIKey Interlock Kit (provision only) KYKFJ KYKFJ

End Cap Set Metric FJ3RTWK FJ4RTWKControl wire terminal kit (14 pack) FJCWTK FJCWTK

Earth Leakage Module (160A max.) ELJBE3160W ELJBE4160WEarth Leakage Module (250A max.) ELJBE3250W ELJBE4250W

Motor Operator 120 Vac EOPFJ240C EOPFJ240CMotor Operator 240 Vac EOPFJ240C EOPFJ240CMotor Operator 24 Vdc EOPFJ24D EOPFJ24DMotor Operator 48 Vdc EOPFJ48D EOPFJ48DMotor Operator 125 Vdc EOPFJ240C EOPFJ240C

Plug in Block (incl power conns & safety trip) PAD3J PAD4J

Digitrip Test Set (230V) MTST 230V MTST 230V

Shunt TripsShunt Trip 24-48Vdc SNT060CPK SNT060CPKShunt Trip 120-240Vac SNT120CPK SNT120CPKShunt Trip 380-600Vac SNT480APK SNT480APK

Undervoltage ReleasesUVR 12Vac/dc UVR012CPK UVR012CPKUVR 24Vac/dc UVR024CPK UVR024CPKUVR 48Vac UVR048APK UVR048APKUVR 48Vdc UVR048DPK UVR048DPKUVR 120Vac UVR120APK UVR120APKUVR 120Vdc UVR125DPK UVR125DPKUVR 208-240Vac UVR240APK UVR240APKUVR 220-250Vdc UVR250DPK UVR250DPKUVR 308-500Vac UVR480APK UVR480APKUVR 525-600Vdc UVR600APK UVR600APK

Other AuxiliariesAuxiliary Switch 1NO/NC AUX1A1BPK AUX1A1BPKAuxiliary Switch 2NO/NC AUX2A2BPK AUX2A2BPKAuxiliary/Alarm Switch 1NO/NC AUXALRMJPK AUXALRMJPKAlarm Switch 1NO/NC ALM1M1BJPK ALM1M1BJPKAlarm Switch 2NO/NC ALM2M2BJPK ALM2M2BJPK

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:34 Page 20

Page 20: MCCB Panelboard Distribution System

18

Moulded Case Circuit Breaker Range 250A to 630A, GL-Frame

• GL-Frame MCCBs Available in two breaking capacity ranges; 50kA & 70kA.

• Choice of thermal/magnetic or electronic trip units.

• User fitted, front fitting accessories.

• New design around space-saving footprint.

•Current limiting action provides for low values of let-through energy.

Thermal Magnetic Trip Unit Range Electronic Trip Unit (Digitrip RMS 310 LSI) Range

MCCB Description 50kA Range 70kA Range 50kA Range 70kA Range

3-pole 4-pole (TPSN) 3-pole 4-pole (TPSN) 3-pole 4-pole (TPSN) 3-pole 4-pole (TPSN)

Utilisation Category A A A A A A A A

Impulse Withstand Voltage 8kV 8kV 8kV 8kV 8kV 8kV 8kV 8kV

Thermal Trip Adjustable 0.8 to 1 x In Adjustable 0.8 to 1 x In Adjustable 0.8 to 1 x In Adjustable 0.8 to 1 x In Adjustable 0.5 to 1 x In Adjustable 0.5 to 1 x In Adjustable 0.5 to 1 x In Adjustable 0.5 to 1 x In

Magnetic Trip Adjustable 5 to 10 x In Adjustable 5 to 10 x In Adjustable 5 to 10 x In Adjustable 5 to 10 x In Adjustable 2 to 8 x In Adjustable 2 to 8 x In Adjustable 2 to 8 x In Adjustable 2 to 8 x In

BREAKING CAPACITY IEC60947-2/BSEN60947-2 (AC 50/60HZ)

660-690V AC lcu (kA) 20 20 25 25 20 20 25 25

Ics (kA) 10 10 13 13 10 10 13 13

380-415V AC lcu (kA) 50 50 70 70 50 50 70 70

Ics (kA) 50 50 70 70 50 50 70 70

220-240V AC lcu (kA) 85 85 100 100 85 85 100 100

Ics (kA) 85 85 100 100 85 85 100 100

25OV DC lcu (kA) 22 22 42 42

Ics (kA) 22 22 42 42

MCCBs List Number

Current Rating (A) Box Clamp Type Terminals

250A GLS3250AAG GLS4250AAG GLH3250AAG GLH4250AAG

320A GLS3320AAG GLS4320AAG GLH3320AAG GLH4320AAG

400A GLS3400AAG GLS4400AAG GLH3400AAG GLH4400AAG

500A GLS3500AAG GLS4500AAG GLH3500AAG GLH4500AAG

630A GLS3630AAG GLS4630AAG GLH3630AAG GLH4630AAG GLS363032G GLS463032G GLH363032G GLH463032G

Current Rating (A) Bolt Type Terminals

250A GLS3250AAM GLS4250AAM GLH3250AAM GLH4250AAM

320A GLS3320AAM GLS4320AAM GLH3320AAM GLH4320AAM

400A GLS3400AAM GLS4400AAM GLH3400AAM GLH4400AAM

500A GLS3500AAM GLS4500AAM GLH3500AAM GLH4500AAM

630A GLS3630AAM GLS4630AAM GLH3630AAM GLH4630AAM GLS363032M GLS463032M GLH363032M GLH463032M

Circuit Breaker Switches (with high magnetic trip)

Current Rating (A) Box Clamp Type Terminals

400A (will trip above 4000A) GLK3400KSG GLK4400KSG

630A (will trip above 6300A) GLK3630KSG GLK4630KSG

Current Rating (A) Bolt Type Terminals

400A (will trip above 4000A) GLK3400KSM GLK4400KSM

630A (will trip above 6300A) GLK3630KSM GLK4630KSM

Terminal Capacities

Box Clamp Terminal

Capacity (max) 240 mm2 240 mm2 240 mm2 240 mm2 240 mm2 240 mm22 240 mm2 240 mm2

Bolt Type Terminal Size M10 M10 M10 M10 M10 M10 M10 M10

Dimensions (mm)

A 140 183 140 183 140 183 140 183

B 257.3 257.3 257.3 257.3 257.3 257.3 257.3 257.3

C 139.7 139.7 139.7 139.7 139.7 139.7 139.7 139.7

D 140 140 140 140 140 140 140 140

Weight (kg) 7.3 9.1 7.3 9.1 7.3 9.1 7.3 9.1

All thermal magnetic L-Frame MCCBs can be supplied with 50˚C ambient calibration. To order, insert V at the end of the list number eq. GLS3630AAGV or GLH4630AAMV

Electronic trip L Frame MCCBs are suitable for 40˚C or 50˚C applications

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:35 Page 21

Page 21: MCCB Panelboard Distribution System

19

250A to 630A GL-Frame Auxiliaries and AccessoriesACCESSORY / AUXILIARY DESCRIPTION

List Number3 Pole 4 Pole

Terminal Shield (1 per pack) LT3SK LT4SKInterpole Barriers (2 per pack) LHIPBK LHIPBK

Rotary Drive (Direct) Black Handle LHMCCB LHMCCBRotary Drive (Direct) Black Handle with interlock LHMCCBI LHMCCBIRotary Drive (Direct) Red Handle LHMCCR LHMCCR

Vari-depth rotary drive 152mm Black Handle KLHMVD06B KLHMVD06BVari-depth rotary drive 152mm R/Y Handle KLHMVD06R KLHMVD06RVari-depth rotary drive 305mm Black Handle KLHMVD12B KLHMVD12BVari-depth rotary drive 305mm R/Y Handle KLHMVD12R KLHMVD12R

Handle Lock LBHP LBHP Handle Block LPHL LPHLHandle Lock Padlock PD50 PD50Front mounted sliding bar interlock 3P-3P SBKL3Front mounted sliding bar interlock 4P-4P SBKL4Walking beam interlock 3P-3P WBLL3630Walking beam interlock 4P-4P WBLL4630Key Interlock Kit (provision only) KYKL KYKL

End Cap Set Metric L3RTWK L4RTWKTerminal extensions LGTEW3 LGTEW4Terminal spreaders LGTES3 LGTES4

Earth Leakage Module (400A max.) ELLBE3400W ELLBE4400WEarth Leakage Module (630A max.) ELLBE3630W ELLBE4630W

Motor Operator 120 Vac EOPLG240C EOPLG240CMotor Operator 240 Vac EOPLG240C EOPLG240CMotor Operator 24 Vdc EOPLG24D EOPLG24DMotor Operator 48 Vdc EOPLG48D EOPLG48DMotor Operator 125 Vdc EOPLG240C EOPLG240C

Plug in Block incl power conns & safety trip PAD3L PAD4L

Digitrip Test Set (230V) MTST230V MTST230V

Shunt TripsShunt Trip 24-48Vdc SNT060CPK SNT060CPKShunt Trip 120-240Vac SNT120CPK SNT120CPKShunt Trip 380-600Vac SNT480APK SNT480APK

Undervoltage ReleasesUVR 12Vac/dc UVR012CPK UVR012CPKUVR 24Vac/dc UVR024CPK UVR024CPKUVR 48Vac UVR048APK UVR048APKUVR 48Vdc UVR048DPK UVR048DPKUVR 120Vac UVR120APK UVR120APKUVR 120Vdc UVR125DPK UVR125DPKUVR 208-240Vac UVR240APK UVR240APKUVR 220-250Vdc UVR250DPK UVR250DPKUVR 308-500Vac UVR480APK UVR480APKUVR 525-600Vdc UVR600APK UVR600APK

Other AuxiliariesAuxiliary Switch 1NO/NC AUX1A1BPK AUX1A1BPKAuxiliary Switch 2NO/NC AUX2A2BPK AUX2A2BPKAuxiliary/Alarm Switch 1NO/NC AUXALRMJPK AUXALRMJPKAlarm Switch 1NO/NC ALM1M1BJPK ALM1M1BJPKAlarm Switch 2NO/NC ALM2M2BJPK ALM2M2BJPK

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:35 Page 22

Page 22: MCCB Panelboard Distribution System

20

Moulded Case Circuit Breaker Range 800A to 1600A, GN-Frame

• GN-Frame MCCBs available in two breaking capacity ranges; 50kA & 70kA.

• Electronic trip units.

• LSI or LSIG Protection.

•Current limiting action provides for low values of let-through energy.

Electronic Trip Unit (Digitrip RMS 310 LSI) Range

MCCB Description 50kA Range 70kA Range

3-pole 4-pole (TPSN) 3-pole 4-pole (TPSN)

Utilisation Category A A A A

Impulse Withstand Voltage 8kV 8kV 8kV 8kV

Thermal Trip Adjustable 0.5 to 1 x In Adjustable 0.5 to 1 x In Adjustable 0.5 to 1 x In Adjustable 0.5 to 1 x In

Magnetic Trip Adjustable 2 to 8 x In Adjustable 2 to 8 x In Adjustable 2 to 8 x In Adjustable 2 to 8 x In

BREAKING CAPACITY IEC60947-2/BSEN60947-2 (AC 50/60HZ)

660-690V AC lcu (kA) 20 20 25 25

Ics (kA) 10 10 13 13

380-415V AC lcu (kA) 50 50 70 70

Ics (kA) 50 50 50 50

220-240V AC lcu (kA) 85 85 100 100

Ics (kA) 85 85 100 100

MCCBs List Number

Current Rating (A)

800A GNS3800T32WP19 GNS4800T32WP19 GNH3800T32WP19 GNH4800T32WP19

1250A GNS3125T32WP09 GNS4125T32WP09 GNH3125T32WP09 GNH4125T32WP09

1600A GNS316T32WP35 GNS416T32WP35

Circuit Breaker Switches (with high magnetic trip, will trip above 12,500A)

Current Rating (A)

800A GNK3800KSW GNK4800KSW

1250A GNK3125KSW GNK4125KSW

Bolt Type Terminal Size M12 M12 M12 M12

Dimensions (mm)

A 140 183 140 183

B 257.3 257.3 257.3 257.3

C 139.7 139.7 139.7 139.7

D 188 188 188 188

Weight (kg) 21.3 28.3 21.3 28.3

N Frame MCCBs are suitable for 40˚ or 50˚C applications

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:35 Page 23

Page 23: MCCB Panelboard Distribution System

21

800A to 1600A GN-Frame Auxiliaries and AccessoriesACCESSORY / AUXILIARY DESCRIPTION

List Number3 Pole 4 Pole

Vari-depth rotary drive 305mm Black Handle HMVD5B HMVD5BHandle Lock LKD4 LKD4Handle Block PLK5 PLK5Handle Lock Padlock PD50 PD50Handle extension HEX5 HEX5Front mounted sliding bar interlock 3P-3P SBK5Front mounted sliding bar interlock 4P-4P - SBK5Walking beam interlock 3P-3P WBL5Walking beam interlock 4P-4P WBL5Key Interlock Kit (provision only) KYK4 KYK4

Motor Operator 120 Vac EOP5T07 EOP5T07Motor Operator 240 Vac EOP5T11 EOP5T11Motor Operator 24 Vdc EOP5T21 EOP5T21Motor Operator 48 Vdc EOP5T22 EOP5T22Motor Operator 125 Vdc EOP5T26 EOP5T26

Digitrip Test Set STK2 STK2

Shunt TripsShunt Trip 24 Vdc SNT5LP03K SNT5LP03KShunt Trip 48Vdc SNT5LP23K SNT5LP23KShunt Trip 120-240Vac SNT5LP11K SNT5LP11KShunt Trip 220-250Vdc or 380-440Vac SNT5LP14K SNT5LP14KShunt Trip 480-600Vac SNT5LP18K SNT5LP18KLow Energy Flux Shunt Trip LST5LPK LST5LPK

Undervoltage ReleasesUVR 24Vac/dc UVH5LP21K UVH5LP21KUVR 48Vdc UVH5LP23K UVH5LP23KUVR 120Vac UVH5LP08K UVH5LP08KUVR 208-240Vac UVH5LP11K UVH5LP11K

Other AuxiliariesAuxiliary Switch 1NO/NC A1X5RPK A1X5RPKAuxiliary Switch 2NO/NC A2X5RPK A2X5RPKAuxiliary Switch 3NO/NC A3X5RPK A3X5RPKAuxiliary/Alarm Switch 1NO/NC AA115RPK AA115RPKAlarm Switch 1NO/NC A1L5RPK A1L5RPKAlarm Switch 2NO/NC A2L5RPK A2L5RPK

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:35 Page 24

Page 24: MCCB Panelboard Distribution System

Eaton Electric LimitedReddings LaneBirmingham B11 3EZTel: 0121 685 2100Fax: 0121 706 2012www.eatonelectrical.co.uk

Customer Support Services:All enquiries telephone: 08700 545 333

Commercial, Industrial & Automation Products:Fax: 08700 540 333E-mail: [email protected]

Residential / Consumer Products:Fax: 08700 507 333E-mail: [email protected]

Low / Medium Voltage Systems Support:Fax: 08700 507 520E-mail: [email protected]

Crane Control:Fax: 08700 507 530E-mail: [email protected]

© 2004 Eaton Corporation

Partial or complete reproduction isgranted with written permission ofEaton Electrical.

Company Information

Eaton’s Electrical business is a global leader in electrical control, power distribution, and industrial automation

products and services. Through advanced product development, world-class manufacturing methods, and global

engineering services and support, Eaton’s Electrical business provides customer-driven solutions under brand names

such as Cutler-Hammer®, Durant®, Heinemann®, Holec® and MEM®, which globally serve the changing needs of the

industrial, utility, light commercial, residential, and OEM markets. For more information, visit www.EatonElectrical.com.

Eaton Corporation is a diversified industrial manufacturer with 2003 sales of $8.1 billion. Eaton is a global leader in fluid

power systems and services for industrial, mobile and aircraft equipment; electrical systems and components for

power quality, distribution and control; automotive engine air management systems and powertrain controls for fuel

economy; and intelligent drivetrain systems for fuel economy and safety in trucks. Eaton has 54,000 employees and

sells products to customers in more than 100 countries. For more information, visit www.eaton.com.

CAT 958/06/04

33657 MEM-Eaton 24pp 958/06/04 5/7/04 15:23 Page 1