    Read this manual carefully, and ensure that it is accessible to operating and

    service personnel at all times.

    For safe and correct use of this product, it is essential to read this manual

    thoroughly before installation and maintenance.

    Additional information is provided for potential hazards which may arise from

    improper use. Special markings for DANGER, WARNING, and CAUTION are

    as follows.

    This recordable electronic watt-hour meter adopts an advanced programming function and

    the hourly metering (TOU) function which can calculate an hourly rate on-site or remotely

    and meter the amount of active power (kWh) and ground reactive power (Lagging, KVarh), a

    maximum demand (kW), a power factor, etc.

    DSC-DS40

    Dimensions & Connections diagram

    1. Introduction

    Safety markings are classified as three types: DANGER, WARNING, and CAUTION as

    below.

    DANGER Serious injury or death is likely to occur immediately if violatingthis marked instruction.

    WARNING Serious injury or death is likely to occur occasionally if violatingthis marked instruction.

    CAUTION Minor injury or product damage is likely to occur if violating thismarked instruction.

    Manual for Low-Voltage Multi-Function

    Electronic Watt-Hour Meter

    Communication

    120.0

    165.0

    75.0

    Input Output

  • 8/9/2019 Manual for Low-Voltage Electronic Watt-Hour Meter(DSC-DS40)_20130521

    2/5

    Type Static, Electronic single phase watt-hour meter

    StandardIEC 62052-11, IEC 62053-21, IEC60529, IEC60387, ISO 75-1,DIN 43857, IEC 6100-4-2, IEC6100-4-4

    Measuring scope Active energy

    Class index Class 1

    DisplayDisplay with 5 integer digits and 1 decimal digit, testing in absenceof voltage, with internal lithium battery

    Meter registration mode By-directional

    Network 1 phase 2 wire

    Reference voltage 120V, Limit of resistance of 250V

    Operating voltage range -20% to +15%

    Frequency 60 Hz

    Power consumptionVoltage circuitCurrent circuit

    Basic current 5A

    Maximum current 60A

    Meter constant Minimum, 1000 imp/kWh

    Constant of reading kWh x 1

    Indicators Forward energy indicated by red LED

    Operating temperature range -20to +70

    Limited temperature range ofoperation

    -40to +70

    Limited transportation range for

    storage-40to +70

    Degree of protection (IEC 60529) IP54 or IP53 with protective box that will allow for IP54

    Terminals connections Symmetric

    Terminal materialStainless steel (Ensure that will not oxidized during productlifetime)

    Connections DIN 43857

    Pulse output (IEC62053-31) Yes

    Material Meter case, base and terminal cover recyclable polycarbonate

    Terminal cover seals Long cover with drilling for wire

    Battery1,200 mAh, 3.6 V (non-rechargeable), days of outage

    compensation: 200 cumulative daysNumber of metering channels 2 channels (active power, ground reactive power)

    Rated voltage is the voltage applied to the voltage circuit, and it is a phase voltage in the 3-phase, 4-

    wire instrument.

    CAUTIONThis meter should be installed or tested in accordance with [Chapter 3.Installation Method].

    WARNINGALWAYS apply a rated current to the meter, and use within the ratedcurrent range. Out-ranged current use may cause burnout.

    1) Make sure that the power of the watt-hour meter is OFF, and then connect the wires as

    shown by the wiring diagram below (note that the identical wiring diagram is shownon each terminal cover).

    WARNING1. ONLY certified personnel may connect wires.

    2. Check the phase sequence when the 3-phase, 4-wire meter is wired.

    2) To supply DC power to the circuit unit, SMPS (Switching Mode Power Supply) is used.

    Working voltage is the rated voltage of 220 V, and the range of use should be -20% ~

    +15%.

    CAUTION

    1. Ensure terminal connections are correct, and the screw tightening torque

    of external wires is as follows.

    (1) 5A, 40A type: within 131.6 kgf.cm(2) 120 A type: within 10012 kgf.cm

    2. Short-circuit of power or current release may cause burnout or fire.

    3) Mount the meter approximately 1.8 m above from the floor so that the value on the LCD

    display can be read.

    CAUTION1. It may be difficult to read the value on the LCD display if installed

    below eye level.

    4) After installation is completed, install a 3.6 V battery, and then seal the cover of the set-

    up compartment.

    5) Install the connecting port of the on-site access device to avoid direct sunlight or light

    sources (flash, etc.).

    The setup unit of the meter can modify or change settings as below.

    1) Choose the item you want to change.

    - Choose the item you want to change while pressing the MENU button sequentially.

    4 Setup Unit

    3. Installation Method

    2. Rating and Specification

  • 8/9/2019 Manual for Low-Voltage Electronic Watt-Hour Meter(DSC-DS40)_20130521

    3/5

    Display and Description for each item are shown in the following table.

    Item Description Display Initial value Remark

    S1 Current date 07.11.20 00.01.01

    S2 Current time 13:10 00:00

    S3 Scheduled reading date 01 01

    S4 Metering type 1 2 1:1, 2:2

    S5 Sectional rate setup 2121 12001200, 2100, 1212, 2121

    sequential display

    S6 Start time of 1stsection 00:00 09:00

    S7 Start time of 2nd section 06:00 23:00

    S8 Start time of 3rd section 12:00 00:00

    S9 Start time of 4th section 18:00 00:00

    SA Additional signal function 01 01 See [External output]

    Sb Maximum demand interval 15 1515:15 min, 30:30 min, 60:60

    min

    SCInstrument identification number

    (upper)06141

    Designated by

    supplier (Unable

    to modify)

    Total 11-digit

    Supplier code (2) + Type (2) +Serial number (7)Sd

    Instrument identification number

    (lower)234567

    2) Move cursor left or right to modify.

    - Press MOVE button to move the cursor left. Place the cursor where you want to modify or

    change data.

    3) Change of data

    - If the INPUT button is pressed, the value where the cursor is currently located increases in

    increments of 1. Modify the value to what you want.

    4) Return to the normal display mode.

    - It will revert to the normal display mode after all settings are displayed.

    - Press and hold the MENU button for 2 seconds or longer to return to the normal display

    mode in the middle of value setting.

    CAUTION

    1. If the metering type (S4) is 1, the setup screens of the sectional rate setup (S5)

    and the start time of 1st~4thsections (S6~S9) do not appear.

    2. If the sectional Rate setup is 1200 or 2100, the setup screens of the start time of

    the 3rdand 4th(S8~S9) sections are not shown.

    3. Only if there is no continuity error of the sectional start time after S5~S9

    setting, the SA screen appears with the confirmed values of S5~S9. The values

    are not confirmed until the SA screen appears.

    LCD parts names and descriptions are listed in the following table.

    Name Function

    Display items

    1. Indicate the date, time, amount of power, maximum demand, automated meter

    reading date, etc.2. The amount of power is 6-digit, and displaying digits for each metering item are

    shown below.

    Type Classification Integer partFractional

    part

    Single instrument,

    single phase

    Active and reactive

    power5-digit 1-digit

    Maximum demand 4-digit 2-digit

    Single instrument, 3

    phase

    Active and reactive

    power6-digit 0-digit

    Maximum demand 4-digit 2-digit

    MOF (Metering

    Outfit)

    Active and reactive

    power4-digit 2-digit

    Maximum demand 3-digit 3-digit

    Number ofdisplay items

    Indicates the sequence of the displayed items as 2-digit.

    Battery/memoryerror indicator

    Indicates battery or memory malfunction with an Error indication. See [7.2 Displaymethod of event mode].

    Currently

    metering time

    indicator

    Class 1: Indicates A onlyClass 2: Indicates both A and B (blinking during the corresponding time)

    Communicationprocess

    indicatorIndicates whether the instrument is under communicating.

    Meteringindicator

    Indicates that the instrument is working correctly, and the indicator blinks under theload, but it is off without the load.

    Metering unit Shows a unit of currently metering value.

    Voltageindicator

    Checks whether the voltage is loaded, and the corresponding voltage is displayedunder the voltage load. If the applied voltage is lower than 80% of the requiredlevel of the rated voltage for 16 seconds or longer, the indicator blinks.

    5. LCD Parts Names and Functions

    Display items

    Currently metering time indicator

    Metering indicator

    Metering unit

    Number of display items

    Error indicator

    Voltage indicatorBattery/memoryerror indicator

    ommunication process indicator

  • 8/9/2019 Manual for Low-Voltage Electronic Watt-Hour Meter(DSC-DS40)_20130521

    4/5

    1. The instrument sequentially displays each display item for 6 seconds by the designated

    metering type (Class 1 or Class 2).

    2. Items and sequence on the LCD display are as follows.

    Number Class 1 Class 2

    1 Current date Current date

    2 Current time Current time

    3 Current cumulative active power (kWh) Current cumulative active power (kWh)-A

    4Current cumulative reactive power

    (kVarh)Current cumulative active power (kWh)-B

    5Previous month cumulative active power

    (kWh)Current cumulative reactive power (kVarh)-A

    6Previous month cumulative reactive

    power (kVarh)Previous month cumulative active power (kWh)-

    A

    7 Previous month cumulative maximumdemand (kW)

    Previous month cumulative active power (kWh)-

    B

    8 Previous month average power factor (%)Previous month cumulative reactive power

    (kVarh)-A

    9 Scheduled meter-reading date Previous month cumulative maximum demand(kW)-A

    10Previous month cumulative maximum demand

    (kW)- entire

    11 Previous month average power factor (%)

    12 Scheduled meter-reading date

    CAUTION 1. External operation button (set-up unit) can switch the metering class(Class 1, Class 2) of the meter.

    Example of display

    < Description of display >

    Shows the 5th

    Indicates that the normal voltage is applied tothe R-phase

    display item of the designatedprogram

    Indicates that the current meter is undercommunication communicating

    The operation indicator blinks when the meter

    is working under the load

    Displays a 6-digit value of the 5th

    Shows the kWh unit of the displayed item

    display item

    Display method of even mode

    1. If the Error indicator blinks regardless of whether the other indicators are working, the

    current event mode is displayed (it does not appear for normal conditions).

    Cause Display

    Memory error Error indicator at the bottom left and MEM indicator blink.

    Battery error Error indicator at the bottom left and BAT indicator blink.Reverse metering

    Error indicator at bottom left blinks and the last item of sequential displayshows 000002.

    Current open phase

    (when CT isdisconnected)

    Error indicator at bottom left blinks and the last item of sequential displayshows 000003.

    Err 000003 is displayed if the CT in the meter is disconnected.

    The timekeeping unit of this meter consists of RTC (Real Time Clock) and a 3.6 V battery.

    Even if power outage occurs, there is no problem to maintain the current time since an

    auxiliary battery supplies power to RTC automatically. The period of outage compensation

    is more than 200 days.

    CAUTION

    1. Use the genuine battery of the manufacturer when the external 3.6 V

    battery is replaced.

    2. When the battery is replaced due to lower battery voltage, RTC time

    (the meters time) is maintained if the meter is powered, otherwise, the

    time is initialized as 2000.01.01.

    8. Timekeeping Unit

    7. How to Read the Display6. Chart for Display Items

  • 8/9/2019 Manual for Low-Voltage Electronic Watt-Hour Meter(DSC-DS40)_20130521

    5/5

    The meter can export one of the metering pulsed active power and reactive power, the gate

    signal of remote load and time switch through an auxiliary terminal. Through an auxiliary

    terminal, the meter can export alternatingly one of four; the metered pulse of the amount of

    active power and (the metered pulse of the amount of) reactive power, the gate signal of

    remote load and (the gate signal of) time switch.

    The signal type can be chosen either on the setup unit in the field or remotely with aremote-metering unit.

    CAUTION

    1. Use an electronic relay (SSR) rather than a mechanical type when the

    gate signal of the time switch is used.

    2. Make sure that the allowable voltage (DC 24 V or less) and the

    allowable current (12 mA or less) are used when connecting with other

    systems.

    3. Refer to below for the output

    circuit diagram at the standard output terminal.

    4. Confirm the polarity (C1, C2) of the pulse output terminal on the

    meter.

    Selectable

    Input Number Output Signal

    01 Metering pulsed activepower

    02 Metering pulsed reactivepower

    03 Gate signal of remote load

    04 Gate signal of time switch

    C1

    C2

    - +

    DC

    (+12~24V)

    - ~

    SSR

    + ~MS

    3 220V

    ~

    R S T

    U V W

    AC220V

    C1

    C2

    - +

    DC

    (+12~24V)

    - ~

    SSR

    + ~MS

    3 220V

    ~

    R S T

    U V W

    AC220V

    The watt-hour meter adopts a communication interface that can transfer the metered and

    recorded data to PC via a dedicated modem and on-site access unit.

    CAUTION

    1. A designated communication board compatible with the modem port of

    the meter for communication MUST be used.

    2. Otherwise, communication may fail and cause severe damage to the

    meter.

    The meter is equipped with a temporary read function under the zero voltage condition.

    Even in the case of a power outage, the metering value can be displayed on LCD if an

    auxiliary 9 V battery is installed into a 3-PIN connector under the zero voltage condition

    after opening the cover of the setup compartment at the upper part of the meter.

    For no 3-PIN connector, the metering value can be sequentially displayed on the LCD with

    the MOVE button.

    DANGER

    Installation or disassembly with the power ON may cause electric

    shock or fire.

    Contact with PLC terminal to a live wire may cause an electric shock

    when the cover of the setup unit is opened when the power is ON.

    11. Temporary Read with Zero Voltage

    10. Communication Unit

    9. External Export

    Power supply

    < Schematic Diagram of Pulse Output>

    Interface of other systems

    Meter C1,

    pulse output terminal

    Meter C2,

    pulse output terminal

    Meter C1,

    pulse output terminal

    Meter C2,

    pulse output terminal

    AC 3-phase

    Unit for midnight power

    Midnight power- +

    DC powersupply (+12 ~ 24V)