MANUAL for Inverter 3.5 KW LNC

download MANUAL for Inverter 3.5 KW LNC

of 78

Transcript of MANUAL for Inverter 3.5 KW LNC

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    1/78

    Chapter 1 Before using

    Thank you for choosing LNC high-performance A-SERIES. A-SERIES are manufactured by adopting

    high-quality components, material and incorporating the latest microprocessor technology available.

    Before using this inverter, this manual will be helpful in the installation, parameter setting,

    troubleshooting, and daily maintenance of the AC motor drives. To guarantee safe operation of the

    equipment, read the following safety guidelines before connecting power to the AC drives. Keep this

    operating manual handy and distribute to all users for reference

    DANGER !

    1. AC input power must be disconnected before any maintenance. Do not connect or disconnect

    wires and connectors while power is applied to the circuit.

    2. A charge may still remain in the DC-link capacitor with hazardous voltages even if the power has

    been turned off. To avoid personal injury, please ensure that power has turned off before operatingAC drive and wait ten minutes for capacitors to discharge to safe voltage levels.

    3. The AC drive may be destroyed beyond repair if incorrect cables are connected to the input/output

    terminals. Never connect the AC drive output terminals U/T1V/T2and W/T3 directly to the AC

    main circuit power supply.

    4. The A-SERIES is only for 3 phase induction motor, other application will not be suitable.

    5. Ground the A-SERIES using the ground terminal. The grounding method must comply with the

    laws of the country where the AC drive is to be installed. Refer to Basic Wiring Diagram. PE

    terminal must be ground correctly, 230V the 3

    rd

    way.

    WARNING !

    1. There are highly sensitive MOS components on the printed circuit boards. These components are

    especially sensitive to static electricity. To avoid damage to these components, do not touch these

    components or the circuit boards with metal objects or your bare hands.

    2. Do not test the A-SERIES with pressure.

    3. Even the motor is stop, the main circuit may still have dangerous high voltages inside.

    4. Maintenance must be performed by qualified technicians.

    WARNING !

    1. Please select safe area to install A-SERIES. Keep this A-SERIES from high temperature, direct

    sunlight, moisture and splashing of water droplets.

    2. When the cable between inverter and motor is too long, the layer insulation of motor may be

    damaged. Please change to use professional AC motor or install another resistor between inverter

    and motor to prevent burn down of motor.

    3. The rated voltage for power system can not be over than 240V, current can not be over than 5000A

    RMS.

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    2/78

    Index

    Chapter 1 BEFORE USING

    1.1 Receiving and inspection 1-1

    1.2 Product appearance 1-2

    1.3 Specifications 1-3

    1.4 Take out of front cover 1-5

    Chapter 2 STORAGE AND INSTALLATION

    2.1 Storage 2-1

    2.2 Installation environment 2-1

    2.3 Dimension 2-2

    2.4 Wiring 2-3

    2.4.1 Main circuit terminal explanations 2-32.4.2 Control terminal explanations 2-4

    Chapter 3 DESCRIPTIONS OF PARAMETER SETTINGS

    3.1 Parameter 0-System parameter 3-1

    3.2 Parameter 1-Basic parameter 3-5

    3.3 Parameter 2-Multi-step speed and procedural operation parameter 3-7

    3.4 Parameter 3-Digital/analog output/input function parameter 3-11

    3.5 Parameter 4-Motor Parameters 3-11

    Chapter 4 KEYPAD OPERATION4.1 KEYPAD function 4-1

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    3/78

    Chapter 1 BEFORE USING1-1. Receiving and inspection

    This A-SERIES drive has gone through rigorous quality control tests at the factory before

    shipment. After receiving the AC drive, please check for the following:

    If the model name of this AC drive is correct. (refer to below info)

    Inspect the unit to insure it was not damaged during shipment, if this AC drive was damaged,

    please do not connect with power.

    Nameplate Information

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    4/78

    1-2. Product appearance

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    5/78

    1-3. SpecificationsTake out of Keypad

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    6/78

    1-4. Take out of front cover

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    7/78

    Chapter 2 STORAGE AND INSTALLATION

    2.1 Storage

    For better ventilation, please follow below method to install AC drives.

    (a) Surrounding space (b) Air flow

    Mount the AC drive vertically with screws on a solid structure. Do not mount with up side down way,

    tilt-side, or horizontal side.

    2.2 Installation environment

    Improper installation of the A-SERIES will greatly reduce its life. Be sure to observe the following

    precautions when selecting a mounting location

    Ambient Temperature -10~50

    Do not install the AC drive in a place subjected to high temperature, high humidity, or directsunlight.

    Do not install the AC drive in a place subjected to corrosive gases or liquids, or airborne dust ormetallic particles.

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    8/78

    2.3 Dimension

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    9/78

    2.4 Wiring

    After taking out of upper cover, you will see terminal connection, check if all main circuit terminal

    labels with technical data sticker affixed to the AC drive are all correct and clear. Follow below steps

    to do installation.

    2.4.1 Main circuit terminal explanations

    Terminal Content

    R, S, T R/L1, S/L2, T/L3 Input terminals for business-used power supply (3 phase power)

    U, V, W U/T1, V/T2, W/T3 AC drive output-connect with 3 phase induction Motor

    BR+BR- BR+,BR- Connection with brake resistance>follow option sheet to choose

    PE Ground terminal, under 1 0 0

    When setting wiring, follow the cable width rule to select proper cables and regulations of the

    electrical wiring to do wiring. For better safety.

    The connection between the three-phase AC input power and the main circuit terminal R/L1, S/L2,

    T/L3 has to set up a none-fusing switch in between.

    Input power R/L1,S/L2,T/L3 has no order rule, random connection is available.

    Please have E grounded following the third-type grounding of 230V series (Resistor is under 100)

    When KEYPAD displays, please do not connect or tear any cables at that time.

    No braking resistor is installed within the A-SERIES inverter (selective purchasing item), therefore,

    be sure to purchase and install the braking resistor if to be used on occasions when the loading inertiais great or that it is of frequent start/stop.

    Be sure not to connect the AC power with the terminals U/T1, V/T2 and W/T3 on the power

    generating side of the inverter.

    When several inverters are grounded at the same time, be sure not to make it into a ground circuit.

    Please refer to the following diagram.

    YES YES NO

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    10/78

    2.4.2 Control terminal explanations

    Terminal

    Symbol

    Explanation on the Terminal Function Factory Setting SINKmode

    FWD FWD RUN-STOP command

    Between terminal FWD-DCM(ON)>CW

    (OFF)>STOP

    REV REV RUN-STOP commandBetween terminal REV-DCM(ON)>CCW

    (OFF)>STOP

    JOG JOG-STOP commandBetween terminal JOG-DCM(ON)>CW, JOG

    setting frequency running(OFF)>STOP

    MI1 Multi-function input selection 1

    MI2 Multi-function input selection 2

    MI3 Multi-function input selection 3

    MI4 Multi-function input selection 4

    MI5 Multi-function input selection 5

    MI6 Multi-function input selection 6

    Terminal MI1~MI6 function selection can refer to

    parameter of 03-23~ 03-26(multi-function)

    +24V Digital control signalthe common end (Source) +24V

    DCM Digital control signalthe common end (Sink) Multi-function input- the common end

    RA Multi-function relay output contact (NO a)

    RB Multi-function relay output contact (NC b)

    240VAC/5A.110VAC/7A.24V/7A

    MO1 Multi-function output terminal 1 (photo coupler)

    MO2 Multi-function output terminal 2 (photo coupler)

    MCM Multi-function output terminalthe common end

    +10V Auxiliary reference power

    AVI Analog voltage frequency command

    ACI Analog current frequency command

    AUI Analog voltage frequency command

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    11/78

    Chapter 3 DESCRIPTIONS OF PARAMETER SETTINGS

    3.1 Parameter 0-System parameter

    0 System Parameter = This parameter cannot be set during operation.

    0-00 Software Version Factory Setting

    Settings Read-only

    0-01 Identity Code Factory setting

    Settings Read-only

    0-02 Rated Current Display Factory setting

    Settings Read-only

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    12/78

    denitity Code examples:

    L = 200~240V, 3.7= 3.7kW

    H = 380~480V, 0.7= 0.75kW

    Users can use the following table to check if the rated current of the Drive is corresponds to the identity

    code

    200-240VClass kW(Hp)

    0.4[.5]

    0.75[1]

    1.5[2]

    2.2[3]

    3.7[5]

    5.5[7.5]

    7.5[10]

    11[15]

    15[20]

    18.5[25]

    22[30]

    30[40]

    37[50]

    45[60]

    55[75]

    75[100]

    Model Code 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32

    Rated outputcurrent 3.0 5 7.5 11 17 25 33 49 65 75 90 120 146 182 220 300

    Maximum CarrierFrequency

    16kHz 10kHz 5kHz

    380-460V ClasskW(Hp)

    0.4[.5]

    0.75[1]

    1.5[2]

    2.2[3]

    3.7[5]

    5.5[7.5]

    7.5[10]

    11[15]

    15[20]

    18.5[25]

    22[30]

    30[40]

    37[50]

    45[60]

    55

    [75]

    75[100]

    Model Code 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33

    Rated outputcurrent 1.6 3 4.2 6 8.5 13 18 24 32 38 45 60 73 91 110 150

    Maximum CarrierFrequency 16kHz 10kHz 5kHz

    Pr0-01 displays the drive model code.

    Pr0-02 displays rated output current of the drive. The following chart may be used to look up the

    identity code, current, and hp of your drive.

    Those parameters are read-only.

    0-03 Multi-Function Display 1 Factory Setting 1

    0-04 Multi-Function Display 2 Factory Setting 2

    0-05 Multi-Function Display 3 Factory Setting 3

    0-06 Multi-Function Display 4 Factory Setting 7

    0-07 Multi-Function Display 5 Factory Setting 9

    1 Motor speed (rpm) 2 DC-BUS voltage

    3 Vac Output 4 Vac command

    5 PID feedback 6 Auto Resart after Fault

    Settings

    7 Th1 8 Th2

    FWD

    FWD REV FAIL EXT LOC

    FWD

    FWD REV FAIL EXT LOC

    FWD

    FWD REV FAIL EXT L OC

    FWD

    FWD REV FAIL EXT L OC

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    13/78

    9 Power factor 1.000 10 Counter

    11 Muti step 12 Plc step

    13 Plc cycle 14 plcTimer

    15 Vdc at ERROR 16 Vac at ERROR

    17 H at ERROR 18 Th1 at ERROR

    19 Th2 at ERROR 20 I at ERROR

    21 Power on day 22 Power on minu

    23 Run day 24 Run minu

    25 avi 26 aci

    27 aui 28 Ani6

    29 AN7 30 Ani8

    31 aniflag 37 DI pin

    38 DO pin 41 OL timer

    42 OLI timer 43 OLI timer

    61 Phase lose level 95 Ani1

    96 Ani2 97 Ani3

    98 Ani4 99 Ani5

    100 Ani6 101 Ani7

    102 Ani8 111 Port0

    112 Port1 113 Port3

    114 Port4 115 Port5

    116 Port9 117 Port20

    This parameter defines the display content the User Defined setting. The User Defined setting

    may be displayed upon power up (Pr0-06) or by pressing the DISP key on the keypad and

    scrolling After A page.

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    14/78

    0-09 resolution of frequency dial on PU

    0=0.01 Hz Factory Setting 2

    1=0.10Hz

    2=1.00HzSettings

    3=10.00 Hz

    This setting provide user easy to adjust output frequency(F page) by rotary dial on PU.

    0-10 Power on Display Factory Setting 0

    0 F (Master frequency command)

    1 H (Output frequency)

    2 A (Output current)Settings

    3 U (multi-function display of Pr0-03~0-07)

    This parameter allows the start-up display to be customized. The display may still be changed,

    but during each power on, the display will default to the setting in this parameter.

    0-08 Most Recent Fault Record 116 Factory Setting 0setting 0~15

    0 no error 19 oH2 (brake overheat)

    1 oc (over-current) 20 Soft start (Inrush limit)

    2 sc (IGBT failure) 21ACI (ACI error)

    3 GF (ground fault) 22ASC (RS-485 error)

    4 ov (over-voltage) 23 PID (PID error)

    5 oL (drive overload) 24 PU (KEYPAD communication overtime)

    6 oL1 (electronic thermal relay) 25 Tune (Motor auto tuning failure)

    7 oL2 (electronic thermal relay) 26 brake (braking transistor failure)

    8 Ot1 (Over-Torque) 27 PHL (Phase loss)

    9 Ot1 (Over-Torque) 28 CPU

    10OCN (over-current during constant speed) 29 FAN (FAN failure)

    11 CC 30 ANI

    12 EP1 (EPROM error 1) 31 hour

    13 EP2 (EPROM error 2) 39 LV (Low Voltage)

    14 EF (external fault) 40 BB (External Base Block )

    15 CT1 (current sensor 1)

    16 CT2 (current sensor 2)

    17 HPF (protection circuit fault)

    Content

    display

    18 oH1 (IGBT overheat)

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    15/78

    0-11 Parameter Reset Factory Setting 0

    10 Parameter reset for

    1 LOCK

    2 2:not save to eeprom

    Settings

    5 reload as power on

    If users would like to reset the parameters to original factory-settings, simple set the

    parameters to 10

    0-12 Password unlock Factory Setting 0

    Settings 065535

    0-13 Password Setting Factory Setting 0

    Settings 065535

    Pr0-12: This parameter allows the user to input their password and disable the parameter lockout.,

    alerting the user the password is incorrect.

    Pr0-13: This parameter allows the user to input their password to lock out the parameters from

    further changes.

    To enter a password, the same password must be input twice within two minutes. To verify the

    password was entered correctly, display the content of Pr0-13. If the content is 1, the password

    is entered. If the content is 0, no password is entered.

    To permanently disable the password. Enter the password in Pr0-12, then enter 0 into Pr0-13

    twice within two minutes.

    To re-activate the password, either enters an incorrect password into Pr0-12 or power down and

    then reapply power to the inverter

    0-14 Source of the Frequency Command Factory setting 0

    0 The digital keypad

    1 The RS485 communication port input

    2 The external analog inputSettings

    3 The external up/down pins (multi-function input terminal)

    This parameter determines the drive master frequency command source.

    0-15 Source of the Operation Command Factory setting 0

    0 The RS485 communication port / digital Keypad

    1 The external terminal / digital Keypad operation

    Settings

    2 The digital keypad operation`

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    16/78

    3 The external terminal operation

    This parameter sets the drive operation command source, which may also be switched via

    the LOC/REM key on the digital keypad. When the LOC led on the keypad is illuminated the

    Keypad has control over the drive operation.

    0-16 2-Wire/3-Wire Operation Control Factory Setting 0

    0 2-Wire (1)

    1 2-Wire (2)Settings

    2 3-Wire (MI1)

    The drive offers three types of external operation control.

    For Line Start Lockout setting, please refer to Pr0-17

    When 3-wire operation control was selected, the stop signal(between MI1 and DCM) must

    be a normal close connection.

    Pr0-16 Control Circuits of the External Terminal

    0

    2-wire operation

    FWD/STOP

    REV/STOP

    1

    2-wire operation

    RUN/STOP

    FWD/REV

    2

    3-wire operation

    control

    0-17 Stop Methods Factory Setting b00000

    0 Ramp to stopBit0

    1 Coast to stop

    0 FWD/REV edge trig

    Settings

    Bit1 1 FWD/REV level trig

    FWD: ( "OPEN" : STOP ; "CLOSE" : FWD )

    DCMTOPVERT

    REV/STOP

    FWD/STOP

    REV: ( "OPEN" : STOP ; "CLOSE" : REV)

    STOP RUN

    FWD/REV

    FWD " CLOSE " : RUN

    MI1 " OPEN " : STOP

    FWD/REV " OPEN " : FWD " CLOSE" : REV

    DCM TOPVERT

    FWD/REV

    DCM TOPVERT

    RUN/STOP FWD: ( "OPEN" : STOP ; "CLOSE" : RUN)

    REV: ( "OPEN" : FWD ; "CLOSE" : REV)

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    17/78

    0 Power on DI cannot runBit2

    1 Power on DI can run

    Bit3 1 OL (125%)

    Bit4 1 Power on run

    bit 0:

    When a STOP command is received, the drive will follow the stop method programmed in this

    parameter.

    Ramp to stop: The drive will ramp down from operation frequency to startup

    frequency (Pr1-20) based on the deceleration time.

    Coast to stop: The drive will stop the output instantly upon a STOP command and the motor

    will coast to stop according to its inertia (time unknown).

    In applications where the motor must stop after the drive is stopped, please select Ramp to

    Stop. This is often a safety consideration.

    If the inertial load is large, it is recommended to set the drive for Coast to Stop to eliminate

    FWD

    FWD REV FAIL EXT LOC

    FWD

    FWD REV FAIL EXT LOC

    Frequency

    Output Frequency

    Motor RotationSpeed

    OperationCommand

    RUN STOP

    Stops according to

    deceleration timeTime

    Operation

    CommandSTOPRUN

    Free running

    to stop

    Ramp to Stop and Coast to Stop

    Bit 0 = 0 Bit 0 = 1

    Output Frequency

    Frequency

    Motor RotationSpeed

    Time

    BIT4 3 2 1 0

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    18/78

    nuisance Over Voltage faults.

    Bit 1 :

    Bit 1=0 FWD/REV edge trig ,power on or after error reset must re-triger again to run drive

    Bit 1=1 After the error of the drive is eliminated, The drive will restart after reset

    Line Start Lockout is disabled (also known as Auto-Start)

    Bit 2 :

    Bit 2=0: Line Start Lockout is enabled

    The drive will not start when powered up with a run command applied.

    The drive must see the run command transition from stop to run after power up.

    Bit 2=1 : Line Start Lockout is disabled (also known as Auto-Start)

    The drive will start when powered-up with run commands applied.This is a safety feature for applications where applying power does not determine a RUN

    command.

    BIT 1=1 mean BIT2 = 1,

    The Line Start Lockout feature does not guarantee the motor will never start under this condition. It

    is possible the motor may be set in motion by a malfunctioning switch.

    Bit 3 :

    When 0 is selected, the oL starting level is 100% of rated drive current.oL trip level is 150%

    60 Sec.When 1 is selected, the oL starting level is 125% of rated drive current.oL trip level is 150%

    60 Sec

    It will offer biger margin while working in constant torque mode,but it will offer less margin while

    working in variable torque mode

    Bit 4 :

    When Pr0-15=0,1,2. drive power on is operation by RS485 or keypad.

    If bit4=1 drive will auto-run after power on

    0-18 Stop timer Factory Setting 0.000

    Settings 0.000~60.000sec

    To setup the waiting time for restart.

    0-19 Reverse Operation Factory Setting b00000

    Bit0=0REV/FWD enabled

    Bit0=1REV disabledSettings

    Bit1=1PID can reversBIT 0 enables the drive ability to run in the Reverse Direction. It may be used toprevent a motor

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    19/78

    from running in a direction that would consequently injure humans or damage the equipment.

    BIT 1 = 0 ,when PID function operation. Frequency output same direction as command,

    Frequency output form 0~Maximum Operation Frequency (Pr1-00)

    BIT1 = 1 Frequency output form FWD/REVMaximum Operation Frequency

    0-20 Fan control mode Factory Setting b11010

    Bit 0=0when power is applied, the fan will turn on

    Bit 0=1When the run command is given, the fan will turn on

    Bit 1=1 : keypad F unneed (PROG)

    Bit 2=1 : pu fault led disable

    Bit3=1error page auto_return

    Settings

    Bit4=1JOG pid off

    This parameter determines the operation mode of cooling fan.

    Bit 0=1, reduce the fan noise when drive is stop, and also extension fans life.

    0-21 Auto Restart after Fault Factory Setting 0

    Settings 010

    This parameter determines the number of restarts after the following faults, OC, GFF and OV.

    The Auto Restart after Fault begins with the Maximum Output Frequency Speed Search

    method.

    If this parameter is set to 10 and 3 faults occur, the remaining number of faults for auto restart is 7.

    If there are no more faults within 10 minutes, the drive will reset this parameter to 10.

    0-22 Carrier Frequency Upper Bound Factory Setting 5

    00.7kHzSettings

    116kHz

    Carrier

    Frequency

    Acoustic

    Noise

    Electromagnetic

    Noise

    Leakage

    Current

    Heat

    Dissipation

    0.7kHz

    10kHz

    16kHz

    Signification

    Minimal

    Minimal

    Signification

    Minimal

    Signification

    Minimal

    Signification

    This parameter sets the carrier frequency of PWM output. The factory setting and setting

    range depend on the model type.

    The PWM carrier frequency has a direct effect on the electromagnetic noise of the motor and

    heat dissipation of the drive. Therefore, if the surrounding noise is higher than the electromagnetic

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    20/78

    noises of the motor, it is suggested to lower the carrier frequency, to decrease the temperature

    of the drive. Although a quiet operation may be achieved with a higher carrier frequency, it is

    necessary to take into consideration the relative wiring length between the motor and drive and the

    effect this high frequency may have on the motor windings

    0-23 Frequency Gain Factory Setting 1

    10~600.00HzSettings

    2 :0~1200.00Hz(all Hz parameters double

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    21/78

    3.2 Parameter 1-Basic parameter

    1 Basic Parameter

    1-00 Maximum Operation Frequency

    Settings 50.00600.00Hz Factory Setting 50.00

    This parameter determines the drive maximum output frequency.

    All master frequency commands set by the keypad or analog inputs are limited by this parameter.

    Analog input frequency command signal (AVI, ACI, AUI) are refer to this setting.

    1-01 User-Defined Coefficient Setting Factory Setting 0

    0:no use (Hz)

    1: rpm

    2: 100.0 %

    3:100.00%

    2 Settings

    4060000 (relative to Pr1-00)

    1-02 Number of the decimal places Factory Setting 0

    Settings 0~3(Pr1-01 :40~60000)

    Example: To display rpms for a 4-pole 60Hz motor with a base speed 1800rpm and no slip,

    Pr1-02 must be set to 0.The result of setting 1800 in Pr1-01 determines the value at 60Hz

    (Maximum Output Frequency).. In case of higher resolution need to set Pr1-01=18000 and

    Pr1-02=1, then get 1800.0rpm readout, 0.1rpm resolution.

    After this parameter is set, all functions relative to the frequency (except for the V/F Curve

    frequency parameters) will automatically be changed to an RPM scale. RPM, instead of Hz,

    will now be the unit for the keypad, and thus, if it is displayed as 60.00 before the setup,

    it will now display 1800 after the setup. Other parameters such as the multi-step speed and

    JOG will be automatically changed also.

    1-03 Motor1 Base Frequency

    Settings 0.00600.00 Hz Factory Setting 50.00

    This parameter sets the frequency, where the maximum output voltage (Pr1-02) will be reached.

    The output frequency may exceed this setting, but the output voltage doesnt increase beyond

    this point. This parameter should be set according to the rated frequency of the motor as indicated

    on the motor nameplate.

    If this parameter setting is smaller than the rated frequency of the motor, nuisance over current

    faults or damage to the drive may occur. If this parameter setting is greater than the rated

    frequency of the motor, the motor will encounter torque loss.

    This parameter must be set to the motors nameplate frequency rating.

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    22/78

    1-04 Motor1 base Voltage Setting resolution 0.1

    230V models Settings 0.0255.0V Factory Setting 220.0

    460V models Settings 0.0510.0V Factory Setting 380.0

    This parameter determines the Maximum Output Voltage of the Drive. This parameter setting

    should be set according to rated voltage of the motor as indicated on the motor nameplate. If rated

    voltage of the motor is 440V, this parameter must be set to 440V. If rated voltage of the motor is

    380V, this parameter must be set to 380V.

    If this setting is greater than the rated voltage of the motor, nuisance over current faults or

    damage to the drive may occur.

    This parameter must be set to the motors nameplate voltage rating.

    1-05 Motor1 Upper Midpoint Factory Setting 0.50

    Settings 0.00600.00 Hz

    This parameter sets the Upper Mid-point Frequency of the V/F curve.

    This parameter must meet the following argument. Pr1-03>= Pr1-05 >= Pr1-07.

    1-06 Motor1 Upper Midpoint Setting resolution 0.1

    230V models Settings 0.0255.0V Factory Setting 5.0

    460V models Settings 0.0510.0V Factory Setting 10.0

    This parameter sets the Upper Mid-point Voltage of the V/F curve.

    1-07 Motor1 Lower Midpoint Factory Setting 0.50

    Settings 0.00600.00 Hz

    This parameter sets the Lower Midpoint Output Frequency of the drive. This parameter must

    be lower than or equal to the Upper Mid-point frequency.

    1-08 Motor1Lower Midpoint Setting resolution 0.1

    230V models Settings 0.0255.0V Factory Setting 5.0460V models Settings 0.0510.0V Factory Setting 10.0

    This parameter sets the Lower Midpoint Output Voltage of the dive.

    1-09 Motor1 0Hz Voltage Setting resolution 0.1

    230V models Settings 0.0255.0V Factory Setting 0.0

    460V models Settings 0.0510.0V Factory Setting 0.0

    Setting of the V/F curve figure is usually based upon the motors allowable loading characteristics.

    Pay special attention to the motors heat dissipation, dynamic balance, and bearing lubricity, if theloading characteristics exceed the loading limit of the motor.

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    23/78

    1-10 Voltage Curve Selection Factory Setting 0

    0 V/F Curve determined

    1 1.5 Power CurveSettings

    2 Square Curve

    Input current of the motor could divide into two orthogonal vectors: magnetic vector and torque

    vector. Gap flux, which is produced by Magnetic vector, is in direct proportion with output voltage

    of motor. Torque vector produces torque. Torque is in direct proportion with the result of

    magnetic vector multiply by torque vector. In theory, if the value of magnet vector is the same

    with torque vector (in unsaturated flux condition), the input current is inimum. If motor loading is

    unsteady torque loading (loading torque is in direct proportion ith speed. For example, the

    loading of fan or pump), loading torque is low during low speed, suitable lower input voltage will

    decrease input current of magnetic field to lower flux oss and iron loss of the motor and promote

    whole efficiency.

    When this parameter is set to high power V/F curve and low frequency torque is lower, it is not

    suitable for drive to accel/decel quickly. If it needs to accel/decel quickly, it is not ecommended

    to use this parameter.

    Please ensure the at-site loading, and then select the proper V/F curve.

    1-11 Auto Voltage Regulation (AVR) Function Factory setting b00000Bit0 1 AVR disable during DEC

    Bit1 1 AVR disabledSettings

    Bit2 1 Output Voltage restricted by input

    This parameter selects the AVR mode. AVR is used to regulate the output voltage to the motor.

    BIT0,1 =0: AVR function is enabled, The drive will calculate output voltage by actual voltage value

    of DC Bus. Output voltage wont vary by DC Bus varying.

    BIT0 =1: The drive will disable AVR function during decelerate to stop. It can speed up deceleration

    in some degree

    Pr1-04,1-14

    Pr1-06,1-16

    frequency

    voltage1 power curve

    1.5 power curve

    2 power curve

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    24/78

    BIT1 = 1: AVR function is disabled, The drive will calculate input voltage by DC Bus value.

    Output voltage will vary by DC Bus varying and may cause output current insufficiently,

    over current or oscillation.

    BIT2 = 0 : ouput voltage can large than input ,due to sin wave distortion

    BIT2 =1 : output voltage max equal to input. Sin wave doesnt distortion.

    1-12 Automatic Energy-Saving

    Settings 0 30% Factory setting 0

    When the Auto Energy-Saving function is enabled, the drive will operate with full voltage during

    acceleration and deceleration. At constant speed the Drive will calculate the optimal output voltage

    value for the load. It is possible for the output voltage to be 0~30% below Maximum Output Voltage

    during auto energy saving operation. This function should not be used with variable loads or

    continuous rated output loads. During these types of conditions, the operation will cycle on and off,

    giving poor energy saving results.

    1-13 Motor 2Base Frequency

    Settings 0.00600.00 Hz Factory Setting 50.00

    1-14 Motor 2 base Voltage Setting resolution 0.1

    230V models Settings 0.0255.0V Factory Setting 220.0

    460V models 0.0510.0V Factory Setting 380.0

    frequency

    100%

    Pr1-12 =0~30%

    Pr1-03,1-13

    Pr1-04,1-14

    voltage

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    25/78

    1-15 Motor 2Upper Midpoint Factory Setting 0.50

    Settings 0.00600.00 Hz

    1-16 Motor 2Upper Midpoint Setting resolution 0.1

    230V models Settings 0.0255.0V Factory Setting 5.0

    460V models 0.0510.0V Factory Setting 10.0

    1-17 Motor 2Lower Midpoint Factory Setting 0.50

    Settings 0.00600.00 Hz

    1-18 Motor 2Lower Midpoint Setting resolution 0.1

    230V models Settings 0.0255.0V Factory Setting 5.0

    460V models 0.0510.0V Factory Setting 10.0

    1-19 0Hz Output Voltage Setting resolution 0.1

    230V models Settings 0.0255.0V Factory Setting 5.0460V models 0.0510.0V Factory Setting 10.0

    Pr1-13~Pr1-19 is V/F curve for motor2 .refer to motor1 Pr1-03~pr1-09.

    Pr1-13>= Pr1-15 >= Pr1-17

    1-20 Startup Frequency Factory Setting 0.50

    Settings 0.00600.00 Hz

    The Start-up Frequency is the initial frequency output upon a RUN command. If the startup

    frequency setting is higher than the Maximum Output Frequency (Pr1-00), the drive will default toPr1-00 as the start point.

    When the Pr4-45 (Speed-Tracing Function) is enabled, Pr1-20 (Start-up frequency) is disabled.

    1-21 Upper Bound Frequency Factory Setting 100.00

    Settings 0.00650.00Hz

    1-22 Lower Bound Frequency Factory Setting 0.0

    Settings 0.00600.00HzThese parameters set the upper and lower bound of the output frequency.

    If the command frequency is lower than the Start-up frequency, the motor will be operating at

    ZERO speed(0Hz);

    If the command frequency is lower than the lower bound frequency, the motor will be operating

    at lower bound frequency;

    If the command frequency is higher than the Upper Bound frequency, the motor will then operate

    at the Upper Bound frequency.

    This function is disabled if the Lower Bound > the Upper Bound.

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    26/78

    111-23 Optimal Acceleration / Deceleration Factory Setting b00000

    Bit0 0 Optimal acceleration

    Bit1 1 OptimalDecelerationSettingsBit4 1 High speed curve acc/dec

    Optimal Acceleration/Deceleration settings could ease the drive vibration during loaded

    starts and stops. Also if the detected torque is small, the processor will speed up the

    acceleration time and reach the set frequency at the fastest and smoothest startup possible.

    At deceleration, the processor will monitor regenerated voltage and automatically stop the

    drive at the fastest and smoothest time possible. Pr4-44 of Maximum Current Level for

    Speed Search is regarded as the target of the output current upon acceleration.

    Pr1-20 Pr1-07

    Pr1-17

    Pr1-09

    Pr1-19

    Pr1-08

    Pr1-18

    Pr1-06

    Pr1-16

    Pr1-05

    Pr1-15

    Pr1-03

    Pr1-13

    Pr1-04Pr1-14

    Pr1-21Pr1-22 Fre uenc out ut limit

    Pr1-00

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    27/78

    1-24 S-Curve for Acceleration Departure Factory Setting 0.000

    1-25 S-Curve for Acceleration Arrival Factory Setting 0.000

    1-26 S-Curve for Deceleration Departure Factory Setting 0.000

    1-27 S-Curve for Deceleration Arrival Factory Setting 0.000

    7 Settings 0.00030.000 Sec

    This parameter determines the S curve strength. A large S curve time will give the smoothest

    transition between speed changes. Please note the S curve settings increase the actual

    acceleration/deceleration times as follows:

    Actual acceleration time = [(Pr1-24) + (Pr1-25) + Pr1-30]

    The S curve is disabled when Auto Acceleration/Deceleration Speed Selection is set to Auto or

    Acceleration /Deceleration times are set to 0.

    1-28 Acceleration Deceleration timer Gain

    Settings 0.1 100.0 Factory Setting 1.0

    This parameter determines the time unit for the Acceleration/Deceleration setting.

    This allows the user to choose either high resolution or long acceleration/deceleration time.

    Refer to parameters (Pr1-30~Pr1-37), the 1st to the 4th Acceleration/Deceleration Time,

    (Pr1-38, Pr1-39) the JOG Acceleration/Deceleration Time .

    1-29 1st/4thDeceleration switch Frequency

    Settings 0.00600.00 Hz Factory Setting 0.00

    This parameter selects the frequency point for transition from acceleration/ deceleration time 1

    to acceleration/deceleration time 4.

    The transition from acceleration/deceleration time 1 to acceleration/ deceleration time 4, may also

    Frequency

    time

    Pr1-03,Pr1-13

    Bit4 = 0

    Bit4=1

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    28/78

    be enabled by the external terminals. The external terminal has priority over Pr1-29.

    1-30 The 1st Acceleration Time Factory Setting 10.00/60.00

    1-31 The 1st Deceleration Time Factory Setting 10.00/60.00

    1-32 The 2nd Acceleration Time Factory Setting 10.00/60.00

    1-33 The 2nd Deceleration Time Factory Setting 10.00/60.00

    1-34 The 3rd Deceleration Time Factory Setting 10.00/60.00

    1-35 The 3rd Deceleration Time Factory Setting 10.00/60.00

    1-36 The 4th Deceleration Time Factory Setting 10.00/60.001-37 The 4th Deceleration Time Factory Setting 10.00/60.00

    1-38 JOG AccelerationTime Factory Setting 10.00/60.00

    1-39 JOG DecelerationTime Factory Setting 10.00/60.00

    Settings 0.0060000 Sec

    The Acceleration time is the time required for the Drive to ramp from 0 Hz to its Maximum

    Operation Frequency (Pr1-00). Deceleration time is the time required for the Drive to decelerate

    from Maximum Operation Frequency (Pr1-00) down to 0 Hz.

    An Acceleration or Deceleration time that is too quickly, may cause the Drive protection features toenable (over-current stall prevention during Accel Pr4-17 or over-voltage stall prevention Pr4-14).

    If this occurs, the actual Accel/Decel time will be longer than this setting.The

    acceleration/deceleration times will be disabled if Pr1-23. (Auto acceleration/deceleration

    Selection) is set for automatic operation.

    Acceleration/Deceleration times 2,3,4 is enabled by using a multi-function terminal set to 7,8.

    Acceleration/Deceleration time 1 is the factory default for out-of-the-box operation.

    Warning:An acceleration or deceleration that is too quickly, may cause excess loads on

    the drive and may permanently damage the drive. If you want to decelerate the Drive in short time period, we recommend adding an external

    frequency

    time

    Pr1-29

    1st Acceleration Time1st deceleration Time

    4th Acceleration Time 4th Deceleration Time

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    29/78

    braking module and braking resistor.

    1-40 JOG Frequency Factory Setting 10.00/60.00

    Settings 0.00600.00 Hz

    This parameter determines the Jog frequency. The Jog function may be selected by the JOG key

    on the PU05 keypad or the external I/O terminals. When the drive is operating under a RUN

    command, the JOG operation is disabled. Likewise, the drive will not accept a RUN commandwhile the JOG command is enabled.

    1-41 Skip Frequency 1 (upper limit) Factory Setting 0.00

    1-42 Skip Frequency 1 (lower limit) Factory Setting 0.00

    1-43 Skip Frequency 2 (upper limit) Factory Setting 0.00

    1-44 Skip Frequency 2 (lower limit) Factory Setting 0.00

    1-45 Skip Frequency 3 (upper limit) Factory Setting 0.00

    1-46 Skip Frequency 3 (lower limit) Factory Setting 0.00Settings 0.00600.00 Hz

    These parameters determine the skip frequencies of the Drive.

    Please use the following hierarchy when setting these parameters:

    Pr1-41 > Pr1-42 >Pr1-43 > Pr1-44> Pr1-45 > Pr1-46.

    The Skip frequency will be disabled if this rule is not followed.

    The Skip Frequencies are useful when a motor has vibration at a specific frequency bandwidth. By

    skipping this frequency, the vibration will be avoided.

    frequency

    Command

    frequency

    acc

    dec

    runstop

    Pr1-24

    Pr1-25 Pr1-26

    Pr1-27

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    30/78

    3.3 Parameter 2-Multi-step speed and procedural operation parameter

    2 Multi-Step Speed (MSS) and Process Control Operation (PCO)

    2-00 Process Control operation Cycle (PCO RUN) Factory Setting 0

    0: PCO RUN disabled

    1~60000 cycleSettings

    60001 endless

    When 2-00 != 0 RUN command will trig PCO process

    2-01 End speed

    0~16step speed Factory Setting 16Settings

    16stop

    After PCO process (2-00=1~60000) ,Jump to 0(main)~15 step speed OR stop(2-01=16)

    2-02 Process Control Operation Mode (PCO RUN) Factory Setting b01000

    0 direction determined by 1~15 Step Direction (2-06,2-09 )Bit0 1 direction determined by the master speed control

    0 continuously execute the process control operationBit1 1 zero speed intervals enabled

    Bit2 1 PCO HOLD run 0Hz

    Settings

    Bit3 1 RUN state can trig jog run

    2-03 PCO Time Gain Factory Setting 1

    04-2804 Settings 110

    2-04 Time Duration of the PCO RUN Master Speed Factory Setting 0.0

    Settings 0.065500 Sec

    2-05 The 1st Step Speed Factory Setting 0.00

    04-2804 Settings 0.00600.00Hz

    2-06 The 1st Step Direction Factory Setting b11000

    Bit0:dir 0=fwd 1=rev

    Bit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-07 Time Duration of PCO RUN Step 1 Factory Setting 0.004-2804 Settings 0.0~65500 Sec

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    31/78

    2-08 The 2nd Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    2-09 The 2nd Step Direction Factory Setting b11000

    Bit0:dir 0=fwd 1=rev

    Bit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-10 Time Duration of PCO RUN Step 2 Factory Setting 0.00

    2-11 The 3rd Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    2-12 The 3rd Step Direction Factory Setting b11000

    Bit0:dir 0=fwd 1=rev

    Bit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-13 Time Duration of PCO RUN Step 3 Factory Setting 0.00

    Settings 065500 sec

    2-14 The 4th Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    2-15 The 4th Step Direction Factory Setting b11000

    Bit0:dir 0=fwd 1=rev

    Bit1:ACD1Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-16 Time Duration of PCO RUN Step 4 Factory Setting 0.00

    Settings 065500 sec

    2-17 The 5th Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    32/78

    2-18 The 5th Step Direction Factory Setting b11000

    Bit0:dir 0=fwd 1=rev

    Bit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-19 Time Duration of PCO RUN Step 5 Factory Setting 0.00

    Settings 065500 sec

    2-20 The 6th Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    2-21 The 6th Step Direction Factory Setting b11000

    Bit0:dir 0=fwd 1=rev

    Bit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-22 Time Duration of PCO RUN Step 6 Factory Setting 0.00

    04-2804 Settings 065500 sec

    2-23 The 7th Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    2-24 The 7th Step Direction Factory Setting b11000

    Bit0:dir 0=fwd 1=rev

    Bit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-25 Time Duration of PCO RUN Step 7 Factory Setting 0.00

    04-2804 Settings 065500 sec

    2-26 The 8th Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    2-27 The 8th Step Direction Factory Setting b11000

    04-2804 Settings Bit0:dir 0=fwd 1=rev

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    33/78

    Bit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    Bit4:Pid Off

    2-28 Time Duration of PCO RUN Step 8 Factory Setting 0.00

    04-2804 Settings 065500 sec

    2-29 The 9th Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    2-30 The 9th Step Direction Factory Setting b11000

    Bit0:dir 0=fwd 1=revBit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-31 Time Duration of PCO RUN Step 9 Factory Setting 0.00

    04-2804 Settings 065500 sec

    2-32 The 10th Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    2-33 The 10th Step Direction Factory Setting b11000

    Bit0:dir 0=fwd 1=rev

    Bit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-34 Time Duration of PCO RUN Step 10 Factory Setting 0.00

    04-2804 Settings 065500 sec

    2-35 The 11th Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    2-36 The 11th Step Direction Factory Setting b11000

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    34/78

    Bit0:dir 0=fwd 1=rev

    Bit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-37 Time Duration of PCO RUN Step 11 Factory Setting 0.00

    04-2804 Settings 065500 sec

    2-38 The 12th Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    2-39 The 12th Step Direction Factory Setting b11000Bit0:dir 0=fwd 1=rev

    Bit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-40 Time Duration of PCO RUN Step 12 Factory Setting 0.00

    04-2804 Settings 065500 sec

    2-41 The 13th Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    2-42 The 13th Step Direction Factory Setting b11000

    Bit0:dir 0=fwd 1=rev

    Bit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-43 Time Duration of PCO RUN Step 13 Factory Setting 0.00

    04-2804 Settings 065500 sec

    2-44 The 14th Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    35/78

    2-45 The 14th Step Direction Factory Setting b11000

    Bit0:dir 0=fwd 1=rev

    Bit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-46 Time Duration of PCO RUN Step 14 Factory Setting 0.00

    04-2804 Settings 065500 sec

    2-47 The 15th Step Speed Factory Setting 0.00

    04 Settings 0.00600.00 Hz

    2-48 The 15th Step Direction Factory Setting b11000Bit0:dir 0=fwd 1=rev

    Bit1:ACD1

    Bit2:ADC2

    Bit3:No Skip Function

    04-2804 Settings

    Bit4:Pid Off

    2-49 Time Duration of PCO RUN Step 15 Factory Setting 0.00

    04-2804 Settings 065500 sec

    Pr2-05,08,11,14,17,20,23,26,29,32,35,38,41,44,47 = muti speed 1~15 ,The multi-function input

    terminals (refer to Pr3-02 to Pr3-07) are used to select one of the Drive Multi-Step Speeds above.

    These speeds may also be used in conjunction with Pr2-00 ~ Pr2-03 to run the process control

    operation (PCO).

    Pr2-06,09,12,15,18,21,24,27,30,33,36,39,42,45,48,determide multi speed or PCO step This

    parameter controls the direction of Pr4-00~Pr4-14, for the Process Control Operation.

    Programming: A 15bit binary number determines the PCO Run direction. The binary number is

    then converted to decimal and entered into Pr4-32.

    Below is an example on how to generate the decimal value needed for this parameter.

    2-50 Interfere Jump Width Factory Setting 0.00

    Settings 0.00~100.00Hz

    2-51 Skip Frequency Width Factory Setting 0.00

    Settings 0.00~200.00Hz

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    36/78

    2-52 Skip Frequency ACC/DEC Factory Setting b00000

    Bit0:ADC104-2804 Settings

    Bit1:ACD2

    2-53 sleep frequency Factory Setting 0.00

    Settings 0.00600.00 Hz (H1:00.00 6000.00Hz)

    2-54 Revival Frequency Factory Setting 0.00

    Settings 0.00600.00 Hz (H1:00.00 6000.00Hz)

    2-55 sleep Period Factory Setting 0.0

    Settings 0.06000.0 Sec

    These parameters determine Dwell (sleep) functions of the Drive. If the command frequency falls

    below the Dwell frequency, for the specified time in Pr8-07, then the drive will shut off the output

    and wait until the command frequency rises above Pr8-06.

    Please see the below diagram.

    Command fre uenc

    0Hz/slee

    Revival fre uenc

    Actual out ut fre uenc

    Slee eriod

    Command frequency

    Pr2-50

    Pr2-51

    Pr2-51

    Pr2-50

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    37/78

    3.4 Parameter 3-Digital/analog output/input function parameter

    3 Multi IO & Analog IO

    3-00 Digital Input Operation Direction Factory Setting h00000

    0255Settings

    Bit 0~7 0~1 0=Low active 1=High active

    This parameter determines the level of the input signal operation.

    3-01 Digital Input Responding Time Factory Setting 0.005

    Settings 0.00130.000 Sec

    Function of this parameter is to delay or confirm the message of the digital input terminals; the

    delayed time is the confirmation time, which will be helpful in preventing some uncertain

    interferences that would consequently result in erroneous motions (except for the counter input) in

    the input of the digital terminals (FWD, REV, and MI1~6), and under this condition, confirmation for

    this parameter could be improved effectively, but the responding time will be somewhat delayed.

    3-023 Multi-Function Input Command 1 (MI1) Factory Setting 1

    3-03 Multi-Function Input Command 2 (MI2) Factory Setting 2

    3-04 Multi-Function Input Command 3 (MI3) Factory Setting 3

    3-05 Multi-Function Input Command 4 (MI4) Factory Setting 4

    3-06 Multi-Function Input Command 5 (MI5) Factory Setting 5

    3-07 Multi-Function Input Command 6 (MI6) Factory Setting 14

    20

    21

    22

    23

    20

    21

    22

    23

    0 = Low active ( Terminal short circuit )

    1 = High active ( Terminal open circuit )

    Operation Direction of MI1

    Operation Direction of MI2

    Operation Direction of MI3

    Operation Direction of MI4

    Operation Direction of MI5

    Operation Direction of MI6

    Operation Direction of FWD

    Operation Direction of REV

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    38/78

    Setting Functions Explanations

    1 multi-step speed command 1

    2 multi-step speed command 2

    3 multi-step speed command 3

    4 multi-step speed command 4

    15 step speeds could be conducted through the digital

    statuses of the 4 terminals, and 17 in total if the masterspeed and JOG are included.

    5 ResetAfter the error of the drive is eliminated, use this terminal

    to reset the drive

    6 clear counter

    When this terminal is functioning, the currently displayed

    counter value will be cleared and 0 is then displayed;

    the drive could only accept the trigger signals to keep

    counting upward after this signal disappeared.

    7the 1st, 2ndacceleration/

    deceleration time selection

    8the1st, 3rd acceleration/

    deceleration time selection

    The acceleration/deceleration time of the drive could be

    selected from this function or the digital statuses of the

    terminals; there are 1,2,3,4 acceleration/ deceleration

    speeds in total for selection.

    9 Disable acc/dec

    When the acceleration/deceleration speed inhibition

    function is executed, the drive will stop the acceleration/

    deceleration immediately; the drive will go on with the

    acceleration/ deceleration from where it stopped earlier

    after this command is removed

    10Frequency command form

    AVI

    When this setting is enabled, forced drive operation

    speed command from AVI

    11Frequency command form

    ACI

    When this setting is enabled, forced drive operation

    speed command from ACI

    12Frequency command form

    AUI

    When this setting is enabled, forced drive operation

    speed command from AUI

    13 PID function disabled

    When this setting is enabled, PID feedback control

    function will be disabled..

    14 External fault The function is identical to the external terminal (EF)

    15B.B. traces from the bottom

    upward

    If the ON/OFF function of the terminal is pre-determined,

    output of the drive will be cut off immediately, and the

    motor will then be of the B.B. status. And once the

    ON/OFF function is restored, the drive will then trace

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    39/78

    16B.B. traces from the top

    downward

    from the bottom upward to catch up with its mutual

    rotation speed with the same frequency before B.B.,

    then speed up to the pre-set frequency. Even if the

    motor is of a complete stop after B.B., as long as the

    ON/OFF status is restored, the speed-tracing function

    could still be operated.

    17

    Operation Command

    selection

    Keypad /MI(FWD/REV)

    External selection of the Operation Command Source.

    Pr0-15 will automatically be disabled once this

    parameter value is enabled; the situation will be

    determined by the terminals. If the terminal is open,

    it is via keypad; if closed, it is via the external terminals

    otherwise.

    18

    Disable the optimal

    acceleration/ deceleration

    time

    If enables, the auto accel/decal mode set by Pr1-23

    will be disabled, Then the drive willrun in Linear

    acceleration/deceleration

    19 FWD JOG commandFWD JOG operation, Neglects the existing direction

    command

    20 REV JOG commandREV JOG operation, Neglects the existing direction

    command

    21 JOG commandJOG operation. Enables the JOG command.

    Works identical to the JOG key on the digital keypad.22 Disable PCO RUN To disable the drive internal PCO RUN program.

    23 Pause PCO RUN To pause the drive internal PCO RUN program.

    24 Frequency Up command

    25 Frequency Down command

    Enables the external terminals to increase or decrease

    the Master Frequency command each time an input is

    received. Terminals are not active during a stop

    command. Refer to Pr0-14, Pr3-14, Pr3-15

    26 DC current control

    It is a zero speed command and it is valid during running.

    It is used to improve the vibration by using DC mode atzero speed when drive is not matched with motor or

    parameter settings of motor is not very well. Refer to

    Pr4-35

    27 Pause StopDrive stops at this moment and it will run after closing the

    function of this terminal.

    28 Stop Drive stops

    29Frequency Command from

    RS485

    Frequency Command from RS485. Pr0-14 will be

    disabled

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    40/78

    30Frequency Command from

    keypad

    Frequency Command from keypad. Pr0-14 will be

    disabled

    31 disable speed search Same as Pr4-15 = 0

    32 Counter input(MI2)

    When this setting is enabled, external counter trigger

    signal is input from MI2

    33 No eeprom writeWhen this setting is enabled, EEPROM write function

    is disabled

    34 Disable AVI function Same as Pr3-30 = 0

    35 Disable ACI function Same as Pr3-31 = 0

    36 Disable AUI function Same as Pr3-32 = 0

    37Disable Interfere jump

    function

    When this setting is enabled, Interfere jump function is

    disabled Refer to Pr2-50 , Pr2-51

    38 Disable DwellWhen this setting is enabled, Dwell function is disabled

    Refer to Pr3-16 , Pr3-17,Pr3-18,Pr3-19

    39 Reload freq as power on

    40 Motor switch

    41 motor switch feedback

    This parameter selects the functions for each multi-function terminal.

    Note 1: If Pr0-16 is set to 3-wire operation control. Terminal MI1 is needed for the third wire

    position. Therefore MI1 is not allowed for any other operation.Full List of the Functions

    3-08 Pre-set Arrival Frequency 1 Factory Setting 50.00

    Settings 0.00600.00 Hz

    3-09 Pre-set Arrival Frequency 1 band Factory Setting 2.00

    Settings 0.00600.00 Hz

    3-10 Pre-set Arrival Frequency 2 Factory Setting 50.00

    Settings 0.00600.00 Hz

    3-11 Pre-set Arrival Frequency 2 band Factory Setting 2.00

    Settings 0.00600.00 Hz

    Once the drive output speed (frequency) achieves the arbitrary designated (speed) frequency, and

    that if the corresponding multi-function output terminal is set as 2~7 (Pr3-23~Pr3-26), then the

    multi-function output terminal contact will be closed.

    3-12 Pre-set target Counter Values Factory Setting 0

    Settings 0

    60000The input contact of the counter could set the multi-function terminal MI2 (with the designated

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    41/78

    terminal Pr3-03 as 32) as the trigger terminal, and when the counting is over (which reaches

    the destination), the signals could select one among the multi-function output terminals (with

    Pr3-23~Pr3-26 set as 15) to be the motion contact.

    3-13 Pre-warn Counter Value Factory Setting 0

    Settings 060000

    When the counter value starts counting upward from 1 to the setting of this parameter, its

    corresponding multi-function output terminal contact with the arbitrary counting achieves the

    output indication function would start functioning. This parameter could be utilized at the

    moment when the counting is almost to an end, and then, set the output signal to enable the

    drive operating at a low speed till it stopped.

    This signals could select one among the multi-function output terminals (with Pr2-19~Pr2-22

    set as 16) to be the motion contact.

    The Time-and-Order Diagram is shown as follows

    Pr0-03=10 display input counter number.

    Pr3-12 =5,Pr3-13=2

    3-14 UP/DOWN key mode Factory Setting b00000

    Bit00 UP following the acceleration time

    Bit01 UP following the constant speed,

    Bit10 DOWN following the tdecelerationSettings

    Bit11 DOWN following the constant speed

    The maximum Up/Down acceleration/deceleration speed is 10.00Hz/Sec.

    3-15The Acceleration /Deceleration Speed of the

    UP/DOWNFactory Setting 0.01

    Settings 0.011.00Hz/msec

    Function of this parameter is to delay or confirm the message of the digital input terminals; the

    delayed time is the confirmation time, which will be helpful in preventing some uncertain

    Pr3-23=15

    Pr3-24=16

    Counter 0 1 2 3 4 5 0 1 2

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    42/78

    interferences that would consequently result in erroneous motions (except for the counter input) in

    the input of the digital terminals (FWD, REV, and MI1~6), and under this condition, confirmation for

    this parameter could be improved effectively, but the responding time will be somewhat delayed.

    3-16 Dwell Time of Acceleration Factory Setting 0.00

    Settings 0.00~60.00 Sec

    3-17 Dwell Frequency of Acceleration Factory Setting 5.00

    Settings 0.00600.00 Hz

    3-18 Dwell Time of Deceleration Factory Setting 0.00

    Settings 0.00~60.00 Sec

    3-19 Dwell Frequency of Deceleration Factory Setting 5.00

    Settings 0.00600.00 Hz

    These parameters determine the time and frequency point for the drive to stop acceleration or

    deceleration to allow the motor to catch up to the drive output frequency. This is commonly used

    with heavy loaded applications where the motors rotor is lagging the stator.

    3-20 Dwell output current Factory Setting A(0%)

    Settings Amp (0~150%)

    The motor current of Pr3-16 and 3-18

    3-21 Multi-Function Output Direction Factory Setting b00000

    Settings 015 ( 1 high)

    Bit 3 Bit 2 Bit 1 Bit 0Settings MO2 3-26 MO1 3-25 2 Relay2 3-24 Relay 1 3-23

    frequency

    time

    Pr3-16

    Pr3-18Pr3-17

    Pr3-19

    Command frequency

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    43/78

    This function uses the Bit setting method.

    Example: If Pr3-23 is 1 (Drive running), and Relay 1 is set to N.O., then R1 close when the drive

    has an output and will open when the drive has stopped.

    3-22 DO delay output time Factory Setting 0.003

    Settings 0~60.000 Sec

    3-23 Multi-Function Output 1 (Relay 1) Factory Setting 11

    3-24 Multi-Function Output 2(Relay 2) Factory Setting 1

    3-25 Multi-Function Output 3 (MO1) Factory Setting 5

    3-26 Multi-Function Output 4 (MO2) Factory Setting 9

    Settings Functions Explanations

    1 Drive running The corresponding output will be closed during operation

    (including DC braking time).

    2 Operation speed

    attained 1

    (Forward and Reverse)

    The corresponding output will be closed when output

    frequency equal to master command frequency or within the

    band width (Pr3-09). Effective both Forward and Reverse

    0 Normal On Normal On Normal On Normal On

    1 Normal Close Normal Close Normal Close Normal Close

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    44/78

    Operation speed

    attained 2

    (Forward and Reverse)

    The corresponding output will be closed when drive accel to

    master command frequency or within the band width

    (Pr3-11). But will neglects the band width (Pr3-11) while in

    decel.

    Effective both Forward and Reverse

    3

    Pr3-09

    Pr3-09

    fre uenc

    FWD command

    Frequency

    REV command

    Frequency

    onoff off on

    time

    Pr3-11

    fre uenc

    FWD command

    frequency

    REV command

    frequency

    onoff off on

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    45/78

    Pre-set speed attained

    1

    (Forward and Reverse)

    The corresponding output will be closed when output

    frequency equal to pre-set speed attained 1 (Pr3-08) or

    within the band width (Pr3-09).Effective both Forward and

    Reverse

    4

    5

    Pre-set speed

    attained 1

    (Forward only)

    The corresponding output will be closed when output frequency

    equal to pre-set speed attained 1 (Pr3-08) or within the band width

    (Pr3-09). Effective only in Forward .

    off on off on off on off on

    Pr3-09

    Pr3-09

    Pr3-08

    FWD

    Pr3-08REV

    time

    frequency

    Pr3-08

    FWDtime

    frequency

    off on off on off

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    46/78

    Pre-set speed attained 2

    (Both Forward and

    Reverse)

    The corresponding output will be closed when drive accel to

    pre-set speed attained 2(Pr3-10) .But will count in the band

    width (Pr3-11) while in decel. Effective both Forward and

    Reverse

    6

    Pre-set speed attained 2

    (Forward only)

    The corresponding output will be closed when drive accel to

    pre-set speed attained 2(Pr3-10) .But will count in the band

    width (Pr3-11) while in decel. Effective both Forward and

    Reverse. Effective only in Forward .

    7

    Pr3-11

    Pr3-10

    FWD

    Pr3-11Pr3-10

    REV

    Frequency

    time

    off on off

    Pr3-10

    FWD

    Frequency

    time

    off on off

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    47/78

    8 Drive in decel The corresponding output will be closed when the drive in decel.

    9 Drive ready for useThe corresponding output will be closed the when the drive is

    ready and has no faults.

    10

    Low voltage alarm

    (LV)

    The corresponding output will be closed when the DC Bus voltage

    drops below setted value in Pr5-06. The keypad will display Lu.

    11 Fault IndicationThe corresponding output will be closed when drive has

    experienced a fault.

    12Base block (B.B.)

    Indication

    The corresponding output will be closed when when the drive is

    shut off by external baseblock.

    13Zero Speed

    (including shutdown)

    The corresponding output will be closed when the drive has no

    output voltage.

    14 Zero speed(while in run)

    The corresponding output will be closed when the drive has no

    output voltage.Not including shutdown,must while run command

    active

    15Pre-set target Count

    Value AttainedThe corresponding output will be closed when Pre-set target

    Counter Values Achieved (Pr2-11)

    16Pre-warn Count Value

    AttainedThe corresponding output will be closed when Pre-warn Count

    Value Attained (Pr2-12)

    17 PCO RUN CommandThe corresponding output will be closed when PCO Program is

    running

    18 PCO RUN paused The corresponding output will be closed when PCO RUN

    operation is paused.

    19A step of PCO RUN

    completedThe corresponding otput will be closed for 0.5 sec when each

    multi-step speed is completed

    20 PCO RUN completedThe corresponding output will be closed for 0.5 sec when the PCO

    RUN cycle has completed

    21IGBT(OH1) over-heat

    indication

    The corresponding output will be closed when the heatsink

    temperature exceeds the over-heat value setted in Pr4-43

    22 Heatsink(OH2)over-heat indication

    The corresponding output will be closed when the heatsinktemperature exceeds the over-heat value setted in Pr4-44

    23Dwell Accel/Decel

    interruptionThe corresponding output will be closed when the Dwell

    Accel/Decel interrupted. Refer to Pr3-16~ Pr3-20

    24Operation Mode

    indication

    The corresponding output will be closed when the drive Operation

    Command is controlled by the external terminals..

    25 Over-torque1 (ot1)The corresponding output will be closed when the drive output

    current exceeds the over-torque detection level Pr4-24

    26 Over-torque1 (ot2) The corresponding output will be closed when the drive outputcurrent exceeds the over-torque detection level Pr4-27

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    48/78

    27 AVI>=0

    28 ACI>=0

    29 AUI>=0

    32DCBus brake on

    (MO1 only)For brake unit use

    33Digital frequency

    signal output (onlyMO2)

    Valid for Multi-Function Output 4 (Pr3-26),output gain can be

    adjust from (Pr3-27)

    3-27 Digital frequency Output signal Factory Setting 1

    Settings 130

    This parameter determines the signals of the Multi-Function Output 4 (when Pr3-26=33)

    (MO2-DCM) and of the digital frequency output (pulse duty cycle = 50%).

    The number of output pulses per second = actual output frequency (Pr3-27)The maximum output frequency is 2KHz.

    3-28 Addition Function of the Analog Factory Setting 0

    0 enable addition functionSettings

    1 disable addition function (AVI,ACI, AUI)

    If the addition between AVI, ACI and AUI are disabled, and that the selections on the analog input

    setting function are similar among the three, the priority order of the analog input will be: AVI > ACI

    > AUI.If the addition between a positive value and a negative value is meaning subtract

    3-29 Analog Input Noise Filter Factory Setting 0.10

    Settings 0.00~2.00 sec

    Interferences commonly exist with analog signals, such as those entering AVI, ACI and AUI.

    These interferences constantly affect the stability of analog control and using the Input Noise Filter

    will create a more stable system.

    If Pr3-29 is large, the control will be stable, yet the response to the input will be slow.If Pr3-29 is small, the control may be unstable, yet the response to the input will fast.

    3-30 Analog Input AVI Factory Setting 1

    3-31 Analog Input ACI Factory Setting 0

    3-32 Analog Input AUI Factory Setting 0

    0 No functions

    1 Frequency command

    Settings

    2 Acceleration/deceleration time gain (increase or decrease time base)

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    49/78

    3 Over-current stall prevention level during operation

    4 Over-current stall prevention level during Acceleration

    5 Over-torque current level (OT1)

    6 Torque compensation gain

    7 AVI auxiliary frequency (multiplication by the ratio of AVI)

    8 ACI auxiliary frequency (multiplication by the ratio of ACI)

    9 AUI auxiliary frequency (multiplication by the ratio of AUI)

    10 Auxiliary frequency of master frequency

    11 PID feedback

    12 PID offset

    13 DC Current level (4-35)

    14 Motor Upper Midpoint Voltage(1-06)

    15 Analog over error(thermal input)

    When 14 setted, a external analog voltage (0.0010.00V) signal can be use as a torque

    adjust command during run.

    The function is identical to the Upper Midpoint Output Voltage adjust (Pr1-06).

    3-33 AVI Analog Input Bias Factory Setting 0.00

    Settings -10.0010.00V

    This parameter determines the AVI voltage value that corresponds to 0Hz frequency.

    3-34 ACI Analog Input Bias Factory Setting 4.00

    Settings 0.0020.00mA

    This parameter determines the ACI current value that corresponds to 0Hz frequency.

    3-35 AUI Analog Input Bias Factory Setting 0.00

    Settings -10.0010.00V

    This parameter determines the AUI voltage value that corresponds to 0Hz frequency.

    3-36 AVI Analog Input Gain Factory Setting 100.0

    Settings -500.0+500.0%

    3-37 ACI Analog Input Gain Factory Setting 100.0

    Settings -500.0+500.0%

    3-38 AUI Analog Input Gain Factory Setting 100.0

    Settings -500.0+500.0%

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    50/78

    3-39 AVI Positive/Negative Bias Mode Factory Setting 0

    3-40 ACI Positive/Negative Bias Mode Factory Setting 1

    3-41 AUI Positive/Negative Bias Mode Factory Setting 0

    0 zero bias1 value lower than bias = biasSettings

    2 value higher than bias = bias

    3-42 Loss of the ACI signal Factory Setting 0

    0 No treatment

    1 operation at last known frequency

    3 Warm and ramp to stop

    Settings

    4 Warm and coast to stop

    This parameter determines the operation of the drive when the 4~20mA (ACI) signal is lost.

    3-43 AVO Analog frequency Factory Setting 0

    3-44 ACO Analog frequency Factory Setting 0

    Settings 0-15

    Full List of the Functions

    Setting Function Description0 output frequency Pr1-00=100%

    1 command frequency Pr1-00=100%

    2 Speed Pr1-00=100%

    3 Output Current rated current of the inverter =100%

    4 Output voltage Vac 200V400V=100%

    5 DC BUS voltage 400V800V=100%

    6 Vac output command -1.000~1.000=100%

    7 Power factor rated power of the inverter =100%

    Bias mode=0Bias mode=1 Bias mode=2

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    51/78

    8 AVI 0~10V=0~100%

    9 ACI 0~20mA=0~100%

    10 AUI -10~10V=0~100%

    11 counter

    12 Ano1 3-49

    13 Ano2 3-49 200V400V=100%

    14 Th1 Pr2-11=100%

    15 Th2

    3-45 Gain of AVO Factory Setting 100.0

    Settings -500.0500.0%

    3-46 Gain of ACO Factory Setting 80.0

    Settings -500.0500.0%

    This parameter adjusts the voltage level of the analog output signal (AFM = Pr3-43, Pr3-44).

    3-47 Bias of AVO Factory Setting 0.00

    Settings -10.0010.00V

    3-48 Bias of AVO Factory Setting 4.00

    Settings 0.0020.00mA

    AVO Value3-49

    3-50 ACO ValueFactory Setting 0.0

    Settings 0.0~100.0%

    When Pr3-43 or Pr3-44=15, this is the output value.

    Multi-input 0~15 switch Factory Setting h000003-51

    3-52 Multi-input 16~31 switch Factory Setting h00000

    3-53 Multi-input 32~47 switch Factory Setting h00000

    3-54 Multi-input 48~64 switch(not yet) Factory Setting h00000

    Settings 0~65535

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    52/78

    3.5 Parameter 4-Motor Parameters

    4 Motor and Protection Parameter

    4-00 Rate Current of Motor 1 Factory Setting A100%

    Settings ****A10~100%

    This parameter will limit the Drive output current in order to prevent the motor from overheating.

    The value entered must be in Amps, and should be found on the motor nameplate.

    This parameter must be programmed correctly if the drive is to operate in the Vector or Torque

    control mode, the Electronic Thermal Overload Relay is used, or if the Slip Compensation function

    is used.

    4-01 Motor1 resistance Factory Setting 0

    Settings m

    Stater resistance

    4-24-0244 Motor1 Torque Compensation

    Settings 0.025.0% Factory Setting 0.0

    This parameter increases the amount of voltage the drive will output to the motor during operation

    to increase motor torque. The V/F Torque Compensation is based on the setting

    of the parameter.Be careful when setting this parameter. Always start at the lowest setting and increase the

    value until sufficient torque is achieved. A large Torque Compensation may generate more

    voltage than needed and the motor will overheat and possibly be damaged.

    4-03 Motor1 rate speed(Slip Compensation) Factory Setting 1500

    04-2804 Settings 100%~75% of rate rpm

    While driving an asynchronous motor, an increasing load will cause an increase in slip. This

    parameter may be used to compensate the nominal slip within a range of 0.0-10.0% (Pr1-01).When the output current of the drive is higher than the motors no-load current, the drive will adjust

    the output frequency to the motor to compensate for slip.

    Note 1. If the motors no-load current > the rated current of the motor, the slip compensation

    will not work correctly.

    Note 2. To obtain effective slip compensation, use the auto tune feature Pr4-05.

    4-04 Poles number of Motor1 Factory Setting 404-2804 Settings 220

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    53/78

    This parameter sets the number of poles of your motor (must be an even number).

    4-05 auto-tuning (Selection of V/F mode or Sensorless vector control mode)

    Settings 1 tuning Factory Setting 0

    This parameter automatically measures the motors characteristics and enters the values into

    Pr04-01, Pr04-02, Pr1-08,Pr1-09(Motor1) or Pr04-07, Pr04-08, Pr1-18,Pr1-19(Motor2),

    respectively.

    Motor Auto Tuning Procedure:

    1. Make sure all the parameter settings are at the factory settings and all power wiring is correct.

    2. Enter the motor rated voltage in Pr1-03(Pr1-13) and motor rated frequency in Pr1-02(Pr1-12).

    And Full-Load current in Pr4-00(Pr4-06).

    3. Set Pr4-05 = 1, then press the RUN key on the keypad to execute the motor auto-tuning

    operation The execution time is about 15seconds.

    4. After the auto tuning procedure is complete, verify the parameters Pr04-01, Pr04-02,

    Pr1-08,Pr1-09(Motor1) or Pr04-07, Pr04-08, Pr1-18,Pr1-19(Motor2) have been updated. If not,

    set Pr4-05 = 1 and press the RUN key again.

    The drive is now switch to Sensorless Vector control mode.

    (Proper setting Slip Compensation of Motor1 in Pr4-03(Pr4-09), may get optimam control

    result)

    Note 1. The sensorless vector control mode is not intended for use with multiple motors connected

    to one Drive.Note 2. If two motors will be connected to one drive and both must be auto tuned, it is necessary to

    set a multi-function input terminal to switch between Motors 1 and 2.

    This will enable the drive to enter the calculated values into the correct parameter positions.

    4-06 Rate Current of Motor 2 Factory Setting A100%

    Settings ****A10~100%

    4-07 Motor2 resistance Factory Setting 0

    Settings m

    4-24-0844 Motor2 Torque Compensation

    Settings 0.025.0% Factory Setting 0.0

    4-09 Motor2 rate speed(Slip Compensation) Factory Setting 1500

    04-2804 Settings 100%~75% of rate rpm

    4-10 Poles number of Motor2 Factory Setting 4

    04-2804 Settings 220

    Motor2 parameter refer to motor1.

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    54/78

    4-11 Y-delta switch mode Factory Setting b00000

    Bit0=1:run can switch04-2804 Settings

    Bit1=1: do feedback

    4-12 Y-delta switch delay timer Factory Setting 0.050

    04-2804 Settings 0.000 60.000Sec

    4-13 Low Voltage Level

    230V models Settings 160220Vac Factory Setting 170

    460V models 320~440-Vac 340

    This parameter determines the level for LV fault.

    4-14 Over-Voltage Stall Prevention

    230V models Settings 350500Vdc Factory Setting 380

    460V models 700~1000Vdc 760

    This parameter sets the voltage limit for use with the Over Voltage Stall during deceleration; a

    heavy loaded motor will begin to regenerate voltage back to the drive. As the drive absorbs this

    regenerated voltage the DC bus will increase. If the DC bus reaches the value programmed in this

    parameter, the drive will stop deceleration, hold speed, and wait for the power to dissipate, beforedeceleration begins again.

    200Vdc/230Vmodels

    400Vdc/460Vmodels

    Pr4-13

    LV

    Vac input

    OutputFrequency

    Frequency sustained

    Over-Volt Stall Prevention

    Properties of decel when the function is activated

    Preset DecelerationTimeTime

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    55/78

    4-15 Braking Level of Vdc

    230V models Settings 350500Vdc Factory Setting 373

    460V models 700~1000Vdc 746

    The action level of the braking resistor could be set by this parameter. The value must be

    higher than the steady state DC-BUS voltage; otherwise the braking transistor will have a

    100% duty. At 100% duty the transistor and resistor will most likely fail.

    4-16 Phase-Loss Protection Factory Setting 0

    0 Warn and keep operating (below 50%)

    1 warn and ramp to stopSettings

    2 warn and coast to stop

    The phase-loss protection is for the input side of the power phase-loss protection. The drive will

    have influence on control characteristics and driver life when it operates the input phase-loss. But

    it can be operated if its output current is less than 50% of rated current.

    4-17 OC Stall Prevention during ACC

    Settings Amp (10250) Factory Setting A(170%)

    This value sets the current limit for the Over Current Stall Prevention function. During acceleration,

    a heavy loaded motor may require very high current. If the current reaches the value programmed

    in Pr4-17, the drive will stop acceleration, hold speed and wait for the current to dissipate in the

    motor. Once the current has fallen below the limit set in Pr4-17, the drive will begin to accelerate to

    command speed as shown in the graph below.

    Pr5-10 Over-current Stall

    Prevention during AccelerationCurrent

    Output FrequencyOver-current stall

    prevention during

    accel.

    Output frequency

    Keep conatant

    Function of the Over-Current Stall Prevention during Accel

    Time

    Output

    Frequency

    Pr4-13

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    56/78

    4-18 OC Stall of Acc low limit

    Settings Amp (0~250%) Factory Setting A(120%)

    4-19 OC Stall Prevention at speed attained

    Settings Amp (10250) Factory Setting A(170%)

    This parameter sets the current limit for the Over-Current Stall Prevention during Operation

    function.

    If the load on the motor causes the current to rise above the value set in this parameter, the drive

    will lower its output frequency (therefore lowering current) to avoid the motor from stalling.

    After the current has fallen below the value set in Pr5-12, the drive will begin to bring the motor

    back to command speed as shown in the graph below.

    4-20 OC Stall lower limit of speed attained

    Settings Amp (0~250%) Factory Setting A(120%)

    Pr5-12 Over-Current Stall

    Prevention level during operationCurrent

    Over-current stall prevention

    during constant speed;

    output freq kept decreasing

    Output Frequency

    Function of Over-Current Stall Prevention during Constant Speed

    Time

    Pr4-18

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    57/78

    4-21 Dec Time of OC Stall Factory Setting 3.00

    Settings 0.050~600.00 Sec

    4-21 Dec delay time during OC stall Factory Setting 0.020

    Settings 0.000~10.000 Sec

    4-23 Over-Torque1 Detection Selection Factory Setting 0

    0 Disabled ot1

    1 Warm ot1 during speed attained

    3 Stop ot1 during speed attained

    1 Warm ot1 during operation

    Settings

    3 Stop ot1 during operation

    4-24 Over-Torque1(OT1) Detection Level Factory SettingA(150%)

    Settings Amp(20250%)

    4-25 Over-Torque1 Detection Time Factory Setting 0.1

    Settings 0.060.0 Sec

    These parameters define the current level and detection time for the Over Torque Detection

    function.

    The Over Torque1 Detection is a current level .The factory setting, Pr4-24, is 150% of the drive

    rated current.

    The Over Torque1 Detection time is the length of time the drive may be in an over torque

    condition.

    Example: When the output current exceeds the over torque detection level (Pr4-24) and exceeds

    the over torque detection time (Pr4-25), the drive will display ot1 on the keypad and will follow the

    setting in Pr4-23.

    4-26 Over-Torque2 Detection Selection Factory Setting 0

    Output current

    Pr4-18,pr4-20

    Pr1-03

    Pr4-17,pr4-19

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    58/78

    0 Disabled ot2

    1 Warm ot2 during speed attained

    3 Stop ot2 during speed attained

    1 Warm ot2 during operation

    Settings

    3 Stop ot2 during operation

    4-27 Over-Torque2 Detection Level Factory Setting A(150%)

    4-28 Over-Torque2 Detection time Factory Setting 0.1

    Settings 0.060.0 Sec

    Refer to Over-Torque1

    4-29 Motor1 Thermal Realy function Factory Setting 0

    0 Disable OL11 Inverter/vector motorSettings

    2 Standard motor

    This parameter selects the type electronic thermal relay function based on the motor

    characteristics.

    Inverter/vector motor = windings designed for Drive output and low speeds with high currents.

    Standard motor = windings not designed for Drive. Motor has a shaft mounted fan which offers

    poor cooling at low speeds

    4-30 Motor1 Thermal Relay Time Factory Setting 60

    Settings 30600 Sec

    This parameter sets the time period for the Electronic Thermal Relay (I2t) function.

    The electronic thermal relay function is designed to protect the motor from overheating, due to low

    output frequency and high currents.

    Operation Time (min.)

    Load factor (%)

    1

    2

    3

    4

    5

    1 20 40 60 80 100 120 140 160 180 200

    60 Hz or more

    50 Hz

    10 Hz

    5 Hz

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    59/78

    4-31 Motor2 Thermal Realy function Factory Setting 0

    0 Disable OL2

    1 Inverter/vector motorSettings

    2 Standard motor

    4-32 Motor2 Thermal Relay Time Factory Setting 60

    Settings 30600 Sec

    Refer to Motor1 Thermal Realy function

    4-33 Over-Heat Warm(OH1) Factory Setting 85.0

    Settings 0.0~110.0 Unit

    The setting for parameters Pr3-23~Pr3-26 is 21.

    4-34 Over-Heat Warm(OH2) Factory Setting 75.0

    Settings 0.0~110.0 Unit

    The setting for parameters Pr3-23~Pr3-26 is 22.

    4-35 DC Braking Current Level Factory Setting A(0%)

    Settings Amp (0~125%)

    This parameter sets the DC braking current level in percentage, for use with DC injection braking.

    The percentage is based on the rated current of the Drive. When programming this parameter, be

    sure to increase the percentage slowly from 0, until sufficient braking torque is obtained. A current

    level too high may damage the motor.

    4-36 DC Braking Time at Start-up Factory Setting 0.00

    Settings 0.0060.00 Sec

    This parameter determines the duration of DC braking current applied to the motor immediately

    following a START command.

    3-37 DC Braking Time during stop Factory Setting 0.00

    Settings 0.0060.00 Sec

    This parameter determines the duration of DC braking current applied to the motor upon a STOP

    command. This is often used to hold a motor shaft in position for a short time.

    4-38 Start-point for DC Braking Factory Setting 0.00

    Settings 0.00600.00 Hz

    During deceleration, the drive will begin to output a DC current once the frequency reaches the

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    60/78

    value set in this parameter.

    Immediately following a RUN command, the drive will output a DC current until the output

    frequency reaches the value set in this parameter.

    The DC braking is commonly used to help decrease the deceleration time. For the best stopping

    performance, it is recommended to use the Deceleration Time to slow the motor and then applythe DC brake.

    4-39 Gain for DC Braking Factory Setting 20.00%

    Settings 0.01~300.00%

    This parameter determines the rate of increase for the DC voltage output during the DC injection

    braking function.

    4-40 Re-activate after Momentary Power Loss Factory Setting 0

    0 disable

    1 begins from command frequencySettings

    2 begins from minimum output frequency

    This parameter selects the speed search type after a momentary power loss.

    4-41 Maximum Allowable Power Loss Factory Setting 2.0

    Settings 0.130.0 Sec

    During a power loss, if the power loss time is less than the time defined by this parameter, the

    Drive will resume operation. If the Maximum Allowable Power Loss Time is exceeded, the Drive

    output is then turned off.

    If the power loss occurs while the drive is under heavy load, it is possible all available rides

    through power will be dissipated in the motor and the drive will shut down quickly (less than 1

    second).

    The Momentary Power Loss function is only enabled while the LV is displayed on the keypad.

    4-42 Base Block Time for Speed Search Factory Setting 0.5

    Settings 0.15.0 Sec

    4-36 4-37

    Output Frequency

    RUN/STOP

    DC BrakinTime at

    start-u 1-20Startu

    Fre uenc

    4-38Fre uenc ointfor DC Brakin

    DC Brakin Timedurin a STOP

    Time

    The Procedural Dia ram of the DC Brakin Out ut

    ON

    FinePrint - www.ahasoft.com.tw/FinePrint

  • 8/21/2019 MANUAL for Inverter 3.5 KW LNC

    61/78

    When a momentary power loss is detected, the Drive waits for a s