Three-phase 25 kW Solar Inverter - Tabuchi America 25kW Three-phase... · 6 MPPT Inverter...
-
Upload
nguyenliem -
Category
Documents
-
view
223 -
download
2
Transcript of Three-phase 25 kW Solar Inverter - Tabuchi America 25kW Three-phase... · 6 MPPT Inverter...
Designed for Distributed Solar
6 MPPT Inverter
Three-phase 25 kW Solar Inverter
Easy maintenance6 Individual MPPT DC Input Strings98.7% Efficiency Three-phase 480V AC Output – Lower BOS costNEMA3Eliminates the need for combiner boxes – All PV strings terminate at the inverter Remote setup and monitoring
TPD-T250P6-US
Some specifications or aspects of appearance may be changed without notice to improve the product.
Max. input voltage Operation voltage rangeMPPT voltage rangeMin. input voltage / starting voltageOperating input current per stringNumber of MPP tracker inputs
1000 V
Input (DC)
Nominal Input power per string 4300 W (5200 W / output limited)
200-1000 V500 to 800 V200 V/200 V10 A6
Output (AC: Grid connected)Rated output power*Grid connection typeRated AC voltageRated power frequencyRated output currentPower factor at rated output power
25000 WThree-phase, 4-wire type480 V (277 V WYE)60 Hz 30 A≧ 0.99
General DataDimensions W x H x DWeightOperating temperature range
Internal consumption (night)Cooling conceptEnclosure RatingController/InterfaceCertification
Topology
950 x 640.6 x 300 mm (37.4 x 25.2 x 11.8 in)69 kg (152.1 lb)
< 8 WCooling FanNEMA3Master Box* (Required)/RS485ETL(UL 1741/1699B, CSA C22.2 No. 107.1-01,IEEE 1547a, CEC) , FCC class ATransformer-less
Three-phase 25 kW Solar Inverter
T250P6-US.2016.11.TA-1
http://www.tabuchiamerica.com
EfficiencyMax. Efficiency 98.7%
ProtectionIslanding Operation Detection: ActiveIslanding Operation Detection: Passive
Frequency shifting methodFrequency change detective method
-20℃ to +60℃ (-4°F to +140°F)Rated output until +40℃ (+104°F)
* When the Power factor is 100% during inverter operation.
* Master Box is required to use three-phase 25 kW inverter.
TABUCHI ELECTRIC COMPANY OF AMERICA, LIMITEDSAN JOSE OFFICE5225 Hellyer Avenue, Suite150 San Jose, CA 95138 USAPHONE: (408) 224-9300
Dimensions
AC UnitInverter Circuit
AC Reactor
*Required
Block Diagram
PV
String 1
Wire Box Inverter Unit
String 2
String 3
String 6
DC/DC Converter①Output limited at 5200W
With MPPT controlDC/DC Converter②
DC/DC Converter⑥
Control CircuitDetector Circuit
Master Box
DC/DC Converter③
Cooling Fan(External) Cooling Fan
(Internal)
OperatingPanel
Output
Grid
Remote Control(ON/OFF)
External Communication(RS-485)
Alarm Contact(Normally Open, Normally Closed) EMI Filter
Protector Circuit
TORONTO BRANCH OFFICE151 Yonge Street, 11th FloorToronto, Ontario, M5C 2W7, CanadaPHONE: (408) 224-9300
900 (35.4)
850 (33.5)950 (37.4)
6-M10 (6-7/16) For hole
34.6 (1.4)[SW]
134 (5.3)
308 (12.1)
300 (11.8)
640.6 (25.2)
270 (10.6)
4-φ43.7 (1.7)2-φ34.5 (1.4)
49.8 (2.0) Unit: mm (in)
CEC Efficiency 97.5%
Output limited at 5200WWith MPPT control
Output limited at 5200WWith MPPT control
Output limited at 5200WWith MPPT control