MAKE SCHNEIDER ELECTRIC INFRASTRUCTURE LIMITED …
Transcript of MAKE SCHNEIDER ELECTRIC INFRASTRUCTURE LIMITED …
INFORMATION SHEET: SWITCHBOARD DETAILS :MAKE SCHNEIDER ELECTRIC INFRASTRUCTURE LIMITED
VARIANT : TYPE SF6 INSULATED RMU - INDOOR (NON EXTENSIBLE)SYSTEM 12 kV, 3 PHASE
PAGE NOS: RATED CURRENT AT BUSBAR 630 A (ALL RATINGS AT BELOW MENTIONED AMBIENT CONDITIONS)
STC 21 kA/3sINTERNAL ARC AFL 21kA/1s
INFORMATION SHEET 1- 1 DIELECTRIC WITHSTAND 28 kV AC/1 MINUTE
GENERAL ARRANGEMENT 2- 4 IMPULSE WITHSTAND 75 kVP
SINGLE LINE DIAGRAM 5- 6 RATED PEAK CURRENT 52.5 kAP
SCHEMATIC DIAGRAM 7- 10 RATED FREQUENCY 50 Hz
BILL OF MATERIAL 11- 11
FOUNDATION DRAWING 12- 13 T2-FUNCTION CIRCUIT BREAKER- 12kV, 3 PHASE,630 A,21 kA/3s
R-FUNCTION RISER- 12kV, 3 PHASE,630 A,21 kA/3s
NOTE:1. CT suitable for Transformer rating : DEGREE OF PROTECTION
11kV, 500kVA to 11kV,2.4MVA TANK IP 67 SS TANK THICKNESS: 2 MM2. Cable Sizes considered for R functions: MECHANISM CHAMBER IP 2X 1RX3C- AL XLPE 11kV(E) cable having size 185 to 400 sq. mm CABLE CHAMBER IP 3X Suitable Bushing studs of M16 size for above cable sizes will be provided. PAINT SHADE3. Cable Sizes considered for T2 functions: CABLE CHAMBER RAL 7032 THICKNESS: MIN 60 MICRONS 1RX3C- AL XLPE 11kV(E) cable having size 70 to 150 sq. mm LV CHAMBER RAL 7032 THICKNESS: MIN 60 MICRONS Suitable Bushing studs of M12 size for above cable sizes MIMIC (STICKER) RAL 9003 will be provided. MATERIAL (CRCA/Aluzinc) LOAD BEARING: 2 to 2.5 mm thick4. As RMU is for PSS application, mounting of Base frame NON LOAD BEARING: 1 to 1.6 mm thick along with base sheet will be in PSS (Client) Scope. OPERATING CONDITIONS5. Sufficient height of cable trench to be considered for proper AMBIENT TEMPERATURE -5 TO +40 DEG C termination of customer cable. ALTITUDE UPTO 1000 METRES ABOVE SEA LEVEL
RMU PARAMETERSGAS PRESSURE OPERATING: 1.3 BAR (ABSOLUTE) OR 0.3 BAR (RELATIVE) AT 20 DEG CBUSBAR COPPERAUX. SUPPLY 230V AC (NOT IN RMU SCOPE OF SUPPLY)
DRAWN CS 11.07.2018 DRAWING NO. SHEET NO. REV.CHECKED CS 11.07.2018 1APPV'D CS 11.07.2018 TOTAL :13
FBX2NC0512A21WOC6I 0
ALL DIMENSIONS ARE IN MM UNLESS AND OTHERWISE STATED
This document is the exclusive property of SEIL and shall not be used, copied or communicated to third parties without its prior authorization.
TITLE: INFORMATION SHEET
FBX-C/12-21/RT2-INDOOR-MANUAL
LIST OF CONTENTS PAGE NO.
INDUSTRIAL BOM REFERENCE : RMU2NC0512A21WOC6I
Sl. No. Nomen. Description Make Type
12 kV, 21 kA/3s 3 Pole Vacuum Circuit Breaker with 3 Pole Manual Disconnector, 3 Pole Manual Earth Switch,
Low energy Trip Coil, Mechanical Emergency Push Button & Counter.
Breaker Operation: Manual
Breaker Current Rating: 630 A
Shunt Trip coil voltage: 230 V AC
Auxilliary contacts : Breaker : 2NO+2NC
Range: To cover 1.3 Bar (absolute) or 0.3 Bar (relative) @20 deg C
Remote contacts : Not available
Temperature Scale: Multiscale
Manual operating handle For manual operation
Screw type - (Single T.B or double deck type) For Control CircuitSUT4/KU2D4/KUDD4/MSTB/eq.
Disconnecting type For Instrument Trafo CircuitKUTSD6/KLTDM4/eq.
Disconnecting type For Protection CTKLTDM4/eq.
Suitable for XLPE Al cable
1R X 3C upto 400 sq mm
2.5 Sq.mm, PVC Multistrand Cu Wire, 660V Grade For Instrument Trafo Circuit Colour Coded
1.5 Sq.mm, PVC Multistrand Cu Wire, 660V Grade For Control Circuit Black colour
1.0 Sq.mm, PVC Multistrand Cu Wire, 660V Grade For Remote/ Aux. Contacts Black colour
1 to 2.5 Sq.mm, PVC Multistrand Cu Wire, 660V Grade For Earthing Green/Yellow-green colour
Suitable for XLPE Al cable
1R X 3C upto 400 sq mm9 R Riser SEIL 12 kV, 21 kA/3s 3 Phase Riser Function FBX
3 Pole over current + earth fault relay with selectable characteristics For breaker feeder
Mounting: Base Mounted
Display: LCD
Settings Range:
I>:0.2 to 2.5, t>:0.1-150s in steps of 0.01s & ti>: 0.01-1.500 in steps of 0.005; I>>:0.5 to 30,t>>: 0.03-20s in steps of 0.01s
Ie>:0.05 to 2.5,te>:0.05-150s in steps of 0.01s & tie>:0.01-1.500 in steps of 0.005;Ie>> : 0.5 to 15,te>>:0.04-20s in steps of 0.01s
RS485 port on MODBUS protocol
CTR: 50-100-150/1A, 5P10, 2.5VA
Resin CastRev. No. Date Revised By
SYSTEM VOLTAGE : 12 kV Prepared by : CS 11.07.2018
SYSTEM STC RATING: 21 kA/3s Checked by : CS 11.07.2018
Approved by: CS 11.07.2018
Document No.:
Sheet No:
DPX-V5
-Schneider Electric Infrastructure Limited (SEIL), Vadodara RMU
Division, MV Switchgears - FBX2NC0512A21WOC6I
TITLE : BILL OF MATERIAL OF FBX RMU
(Protection) 1 set11 CT
1
10 Relay
2
3
4
SEIL/eq.
Handle
SEILProtection Relay
28
1
LOT
2 Sets
LOT
Operating handle
1
Qty
1
2
Q01 Vacuum circuit breaker
A01
FBX 1
VPIS-V2Voltage Presence Indicator SEIL
SEIL
Rating/specification
Manometer Manometer
LED type as per IEC 62271-206 (old ref. IEC61958)
Regency/Konly/Electron System/Schneider approved make
Metal
LOT
LOT
1
SEIL
Push-on typeRaychem
Cable Clamp Cable Clamps
5 T.B Terminal blocks Elmex/ Phoenix/ Connectwell/ eq
7
6
LOTWiresWiresFinolex/ Polycab/ KEI/ Relicab/ Ultracab/ Gemtech/ SBEE/ Schneider Approved
make
LOT
LOT
Cable bootsCable boots
Current transformer NPT/ECS
Revision Details
11
This document is the exclusive property of SEIL and shall not be used, copied or communicated to third parties without its prior authorization.
Customer Name:
P.O. No. :
S.O. No. : -