Ma Unigear Dl(en) 1vcd003415

68
UniGear type ZS1 double level Installation, service and maintenance instruction manual

Transcript of Ma Unigear Dl(en) 1vcd003415

Page 1: Ma Unigear Dl(en) 1vcd003415

UniGear type ZS1 double levelInstallation, service and maintenanceinstruction manual

Page 2: Ma Unigear Dl(en) 1vcd003415

1

Page 3: Ma Unigear Dl(en) 1vcd003415

1/64

Your safety first – at all times!

This is why our instruction manual begins with the following recommendations:

• Only install switchgear and/or switchboards in closed rooms suitable for electrical equip-ment.

• Ensure that installation, operation and maintenance are carried out by specialist electriciansonly.

• Fully comply with the legally recognized standards (IEC or local), the connection conditionsof the local electrical utility and the applicable safety at work regulations.

• Observe the relevant information in the instruction manual for all actions involving switchgearand switchboards.

• Danger!

Pay special attention to the hazard notes in the instruction manual marked with this warningsymbol.

• Make sure that the specified data are not exceeded under switchgear or switchboardoperating conditions.

• Keep the instruction manual accessible to all personnel involved in installation, operationand maintenance.

• The user’s personnel must act responsibly in all matters affecting safety at work and correcthandling of the switchgear.

WARNING

Always follow the instruction manual and respect the rules

of good engineering practice !

Hazardous voltage

can cause electrical shocks and burns.

Disconnect power, then earth and short-circuit before proceeding

with any work on this equipment.

If you have any further questions about this instruction manual, the members of our fieldorganization will be pleased to provide the required information.

We reserve all rights to this publication. Misuse, and including in particular, duplication andmaking this manual - or extracts thereof available to third parties is prohibited. We do notaccept any responsibility for the information provided, which is subject to alternation.

Page 4: Ma Unigear Dl(en) 1vcd003415

2/64

ContentsPage

1 Summary ........................................................... 31.1 General ............................................................... 31.2 Standards and specifications ............................. 31.3 Operating conditions ........................................... 31.3.1 Normal operating conditions ............................... 31.3.2 Special operating conditions .............................. 3

2 Technical data ................................................... 42.1 Electrical data ..................................................... 42.2 Resistance to internal arc faults ......................... 42.3 Dimensions and weights..................................... 42.3.1 Dimensions and weights of 12/17.5 kV units ..... 5

3 Panel design and equipment ........................... 63.1 Basic structure and variants ............................... 63.2 Enclosure and partitioning .................................. 63.2.1 Ventilation of the panels ..................................... 73.3 Compartments in the panels .............................. 73.3.1 Busbar compartment .......................................... 73.3.2 Circuit-breaker compartment .............................. 83.3.3 Withdrawable parts ............................................. 83.3.4 Cable connection compartment ......................... 93.3.5 Control cabinet ................................................... 93.4 Interlock/protection against erroneous

operation ............................................................. 93.4.1 Panel internal interlocking .................................. 93.4.2 Doors interlocking ............................................. 103.4.3 Interlocks between panels ................................ 103.4.4 Locking devices ................................................ 103.5 Control wiring plug connector coding ............. 103.6 Fast recovery .................................................... 10

4 Dispatch and storage ..................................... 224.1 Condition on delivery ........................................ 224.2 Packing ............................................................. 224.3 Transport ........................................................... 224.4 Delivery ............................................................. 224.5 Intermediate storage ........................................ 23

5 Assembly of the switchgear at site ................. 245.1 General site requirements ................................ 245.2 Foundations ...................................................... 245.2.1 Anchoring bolts and base iron fixing systems .. 245.3 Assembly of the switchgear panels .................. 255.4 Installation of the busbars and bushings .......... 265.4.1 Busbars and bushings for units 12/17.5 kV ...... 265.5 Installation of the top-mouted boxes ................ 265.6 Cable connection.............................................. 265.6.1 Power cables .................................................... 265.6.2 Control cables ................................................... 27

Page

5.7 Earthing the switchgear .................................... 285.8 Laying the ring circuits ...................................... 285.9 Final erection work ........................................... 28

6 Operation of the switchgear .......................... 366.1 Commissioning ................................................. 366.1.1 Preparatory work .............................................. 366.1.2 Start-up ............................................................. 376.2 Switching operations ........................................ 376.2.1 Withdrawable circuit-breaker part ..................... 376.2.2 Circuit-breaker - type VD4................................ 396.2.3 Circuit-breaker - type VM1 ............................... 406.2.4 Circuit-breaker - type HD4 ............................... 426.2.5 Vacuum contactor - type V-Contact ................. 436.2.6 Withdrawable metering parts ............................ 436.2.7 Earthing switch - type EK6 ............................... 436.2.8 Earthing and short-circuiting with

earthing module ................................................ 446.3 Test procedures ................................................ 446.3.1 Testing the off-circuit condition ......................... 446.3.2 Current and voltage tests ................................. 446.4 Service trucks ................................................... 45

7 Maintenance .................................................... 547.1 General ............................................................. 547.1.1 Intervals for inspection, servicing and repairs . 547.2 Inspection ......................................................... 557.3 Servicing ........................................................... 557.4 Repair ............................................................... 567.4.1 Switchgear in general ....................................... 567.4.2 Replacement of complex functional groups ..... 577.5 Testing withdrawable parts ............................... 587.5.1 Motor-driven withdrawable parts ...................... 587.5.2 Checking correctness of dimensional

settings ............................................................. 587.5.3 Checking auxiliary switch settings on

withdrawable parts ............................................ 587.5.4 Checking the direction of rotation of the travel

motors on motor-driven withdrawable parts ..... 597.5.5 Testing of interlock conditions .......................... 597.6 Tests on the panel ............................................ 607.6.1 Auxiliary switch settings on the

earthing switch .................................................. 607.7 Spare parts, auxiliary materials, lubricants ...... 607.7.1 Spare parts ....................................................... 607.7.2 Auxiliary materials, lubricants ........................... 60

8 Product quality and enviromentalprotection ........................................................ 64

Page 5: Ma Unigear Dl(en) 1vcd003415

3/64

1. Summary

1.1 General

UniGear is the new name of the ZS1 switchgear in release 1.2 (ZS1.2). The UniGear Double Level isa three-phase, metal-clad, air-insulated switchgear and all the units are factory-assembled, type-testedand suitable for indoor applications up to 17,5 kV. The units are designed as withdrawable modules on2 levels and are fitted with a single busbar system. The withdrawable parts are equipped with circuit-breakers and contactors.

Details of the technical design and configuration of individual switchgears, such as the technical data,detailed equipment lists for the individual panels and comprehensive circuit documentation etc., can befound in the relevant order documents.

1.2 Standards and specifications

UniGear switchgear panels comply with the standards and specifications for factory-assembled, metal-clad and type tested high voltage switchgears to IEC publications 62271-200 and 60694. In addition,in accordance with IEC 60529, the switchgear panels have the following degrees of protection:

IP 4X for the enclosure and IP 2X for the partitions.

All other corresponding IEC publications, national or local safety at work regulations and safetyregulations for production materials must followed during erection and operation of these systems.Above and beyond this, the order-related data from ABB must be taken into account.

1.3 Operating conditions

1.3.1 Normal operating conditions

The switchgears are basically suitable for normal operating conditions for indoor switchgears andswitchboards in accordance with IEC 60694. The following limit values, among others, apply:

Ambient temperature:

Maximum + 40 °C

Maximum 24 h average + 35 °C

Minimum (according to “minus 5 indoor class”) - 5 °C

The maximum site altitude is 1000 m above sea level.

1.3.2 Special operating conditions

Switchgears are suitable for operation in the climate of Wda type according to IEC 60 721-2-1. Specialoperating conditions must be discussed with the manufacturer in advance. For example:

• At site altitudes above 1000 m, the effects of the reduction in dielectric strength of the air on theinsulation level must be taken into account (please refer to diagram in figure 1/1).

• Increased ambient temperatures must be compensated for in the design of the busbars and branchconductors as well as for the withdrawable parts, otherwise the current carrying capacity will belimited. Heat dissipation in the switchgear panel can be assisted by fitting additional ventilationfacilities.

Note on any special climatic operating conditions:

When switchgears are operated in areas with high humidity and/or major rapid temperature fluctuations,there is a risk of dew deposits which must remain an exception in normal operating conditions for indoorswitchgear. Preventive action (e.g. fitting electric heaters) must be taken in consultation with themanufacturer to avoid this condensation phenomenon and any resulting corrosion or other adverseeffects. The control of the heaters depends on the relevant project and details must be taken from theorder documents.

Figure 1/1: Curve for determination of the altitude factor k in relation to the altitude H.

Page 6: Ma Unigear Dl(en) 1vcd003415

4/64

Rated voltage kV 12 17.5

Rated power frequency withstand voltage kV 28 38

Rated lightning impulse withstand voltage kV 75 95

Rated frequency Hz 50/60

Rated current of busbars A …1600 …1600

Rated current of circuit-breaker branches A …1600 …1600

Rated peak withstand current1) kA …125 …100

Rated short-circuit breaking current of circuit-breaker kA …50 …40

Rated short- time current 3 s 1) kA …50 …40

1) The short-circuit withstand capacity of the instrument transformers must be taken into account separately.

2. Technical data

2.1 Electrical data

For individual switching device data, see the instruction manual for the relative switching device, aslisted under 7.1.

2.2 Resistance to internal arc faults

The fault withstand capacity is as follows: 12 kV - 40 kA 1s - 50 kA 0.5s

17.5 kV - 40 kA 1s

The switchgear units have been tested according to IEC 62271-200 Standards (appendix AA, class A,criteria 1 to 5). In individual cases, depending on the configuration of the switchgear panels and/or theswitchroom conditions (e.g. low ceiling height), additional measures may be necessary to ensurecompliance with criterion 5.

2.3 Dimensions and weights

Page 7: Ma Unigear Dl(en) 1vcd003415

5/64

Dimension mm

Height A 2700

Width B

- Feeder panels up to 1250 A (up to 31.5 kA) 1) 750 (650 + 100)

- Feeder panels up to 1250 A (above 31.5 kA) 900 (800 + 100)

- Feeder panels 1600 A 900 (800 + 100)

Depth C 1976

1) Feeders equipped with contactor «V-Contact» are 750 mm wide up to the 50 kA short-time current.

Rated current Mass

A Kg

...1250 1300

1600 1400

2.3.1 Dimensions and weights of 12/17.5 kV units

Weights of 12/17.5 kV panels (including withdrawable circuit-breaker parts):

Page 8: Ma Unigear Dl(en) 1vcd003415

6/64

3. Panel design and equipment

3.1 Basic structure and variants (Figures 3/1 to 3/3)

The basis for the UniGear double level panel is the CB compartment of the incoming/outgoing feeder panelwith SF6 or vacuum circuit breaker using insertion technology. It is divided into busbar compartment B1,circuit-breaker compartment A1, cable compartment C1, busbar compartment B2, circuit-breakercompartment A2, cable compartment C2, control cabinet D, control cabinet d (available in deeper versionon request) and gas exhaust duct E. Apart from this, there are variants for all operating needs. Pictures3/1 and 3/2 show examples of possible configurations of a panel including electrical equipment.

For busbar sectionalising, two panels are necessary, the coupling panel with the withdrawable circuit-breaker part and a bus riser panel (optional with busbar metering and earthing). In equipment withoutbusbar sectionalising, a direct bar connection between the busbars will be established.

Further details about installation and equipping the switchgear can be obtained from the orderdocuments.

3.2 Enclosure and partitioning (Figure 3/3)

The enclosure and internal partitions of the panels are of 2mm thick high quality aluminium-zinc coatedsteel sheets.The six high voltage compartments (busbar compartments, circuit-breaker compartments and cableconnection compartments) are equipped with secured pressure relief flaps. These open in case ofinternal arc fault. In order to premit the exhaust of the hot gases from high voltage compartments anadditional channel has been added on the side of the panels.The additional panel is 100 mm width and it is placed within each panel and on both extremities of theswitchboard (also in case of junction with UniGear single level panels).The front of the panel is closed off by pressure resistant doors which open to an angle of almost 180°.

Each circuit-breaker compartments have their own doors. The circuit-breaker compartments areequipped with inspection windows made of security glass. Neighbouring panels are partitioned from oneanother by the side walls of each panel and, as a result of the design, the air cushion remains betweenthese walls when the panels are jointed together.

The enclosure is completed pressure-relief flaps which, are made of sheet steel or expanded metal andbelow by means of floor-covering 17, made of sheet steel which cannot be magnetized. The pressure-relief flaps are secured with plastic screws. In the case of internal overpressure, the plastic screws arethe point of rupture.

Arc fault current limitation can be achieved by undelayed circuit-breaker release, carried out by auxiliaryswitches operated by the pressure wave.

The switchgear can be equipped with the Fast recovery device: the auxiliary switches are mounted onthe pressure sensors and operated by the sensor stroke pin (see chapter 3.6 - page 10/72)

The necessary safety measures to counteract the effects of an internal arc fault must be ensured inrelation to the ceiling height. In individual cases, this may require additional operator protectionmeasures on the switchgear panels.

The pressure relief duct is integrated in the design of the panel.

The rear wall of the busbars of busbar compartment 84, intermediate wall 9, mounting plate 12 withshutters 12.1/12.2 and horizontal partition 20, form part of the internal partitioning.

The internal partitioning makes safe access to the circuit-breaker and cable compartments possibleeven when the busbars are live.

The low voltage compartment for the secondary equipment is completely protected from the high voltagearea thanks to its steel-sheet casing.

On the end sides, cover plates ensure good appearance and are mechanically and thermally arc faultproof should such an event occur in the end panel.

Doors and cover plates are thoroughly cleaned and treated against corrosion before receiving a highquality double coating of paint. The finishing coat is in the standard RAL 7035 colour (special coloursby agreement). Stoving completes the procedure and provides considerable insensitivity to impact andcorrosion.

The circuit-breaker compartment doors are pressure resistant and can either be fitted with screws ormanual closing systems.

Page 9: Ma Unigear Dl(en) 1vcd003415

7/64

Rated voltage Rated short-time withstand current Partitions

25 kA No 1)

12/17.5 kV31.5 kA Every third panel 2)

40 kA - 50 kA Every panel 3)

Marina application Every panel 3)

1) In these panels, busbar bushings 29 and bushing plates 28 need not be mounted - the dynamic strength of the busbar system issufficient.

2) In these panels, busbar bushings 29 and bushing plates 28 must be mounted in every third panel.3) In these panels, busbar bushings 29 and bushing plates 28 must be mounted in every panel.

According to customer requirements, this separation into individual panels by means of busbar bushings29 and bushing plates 28 can also be provided in switchgear panels where it is not technically necessary.

3.2.1 Ventilation of the panels (Figures 3/3, 6/20, 6/21)

Openings in the outer enclosure are needed for the purpose of ventilation in the case of certain ratedcurrents in the busbars and branch bars.

For incoming air to the circuit-breaker compartment, the horizontal partition is provided with air-vents20.2. IP4X degree of protection and safety in the case of any release of hot gas due to an arc fault areprovided by flap 20.3 in the horizontal partition 20.

3.3 Compartments in the panels

3.3.1 Busbar compartments (Figures 3/3, 5/21 to 5/26, 5/29 to 5/34)

The busbars have a flat cross-section made of copper and are laid in sections from panel to panel.According to the current rating, either single or double configuration is used. They are held by flat branchconductor 2 and, if installed, by busbar bushings 29. No special connection clamps are needed.

Busbars and branch conductors for 17.5 kV are insulated by means of shrink-on sleeves. The boltconnections in the 17.5 and 24 kV busbar system are covered by insulating covers 58. The busbars for12 kV units up to 1600 A are without any covers.

By means of bushing plates 28 and busbar bushings 29, partitions can be created between panels.These partitions are necessary for higher rated short-time currents – see the following table.

Page 10: Ma Unigear Dl(en) 1vcd003415

8/64

3.3.2 Circuit-breaker compartment (Figures 3/3, 3/8, 3/9, 3/10, 3/11, 5/20, 6/22)

The circuit-breaker compartment contains all the necessary equipment for reciprocal operation of thewithdrawable part and the panel. Like the busbar compartment, it is metallically partitioned on all sides.

The tulip isolating contacts 5, together with the fixed isolating contacts, are located in mounting plate12. The metal shutters 12.1/12.2, covering the insertion openings, are also included. The shutters areopened by means of actuating bars 13.16 of the withdrawable circuit-breaker part, using lever 38 wheninserting into the service position, and are closed when the latter is removed. In the test/disconnectedposition of the withdrawable part, partitioning by separation is established in the main current circuit.Connection of the control wiring, required for test purposes, need not be interrupted when in the test/disconnected position.

In the test/disconnected position, the withdrawable part is still completely inside the panel with the doorclosed. The ON/OFF pushbutton located on the circuit-breaker, and the mechanical indicators for ON/OFF and CHARGED/DISCHARGED can be observed through an inspection window.

The switching operations are carried out with the doors closed. Installation of an additional mechanicalswitching device for manual operation of the circuit-breaker in the service position is also possible (seeFig. 3/14, 3/15).

The socket 10.1 for the control wiring is mounted fixed in the circuit-breaker compartment.

3.3.3 Withdrawable parts (Figures 3/3, 3/9, 3/10, 3/12, 3/13, 3/16 to 3/19, 3/22, 3/25)

1. Withdrawable circuit-breaker parts

The withdrawable circuit-breaker forms a complete module consisting of the VD4 type vacuum circuit-breaker, VM1 or SF6 type HD4 circuit-breaker, the withdrawable assembly 13.15, isolated contact arm4.2 with contact system 4.3 and control wiring plug 10.2.

The withdrawable assembly 13.15 and the circuit-breaker are coupled via a multi-pole control wiring plugconnector 10.3.

The withdrawable assembly establishes the mechanical connection between the panel and the circuit-breaker. The fixed part is connected to the panel by forking, which is form coded on both sides. Themoving part with the circuit-breaker is moved manually or by a motor by means of a spindle, betweenthe service or test/disconnected positions with the front doors closed. Service and test disconnectedpositions are set precisely by means of auxiliary switches, which register the final position reached andthe angular position of the spindle.

The earthing connection between the withdrawable part and the panel is established by its rollers andtravel rails 42, which are bolted onto the panel.

Withdrawable parts of the same design are interchangeable. In the case where the withdrawable partshave the same dimensions, but different circuit-breaker fittings, the control wiring plug coding preventsany erroneous connections between the withdrawable part and the panel. The coding is indicated in theorder documents (see Fig. 3/25).

2. Withdrawable contactor parts (Figures 3/3, 3/20, 3/21)

In place of the circuit-breaker type, the withdrawable part can also be fitted with the V-Contact typevacuum contactor.

V-Contact is fitted with MV fuses 91.15 and can be used for rated voltage up to 12 kV.

All the data mentioned in this chapter for circuit-breakers also apply to the contactors.

3. Other withdrawable parts

The withdrawable part can also be fitted with the following trucks:

– metering voltage transformers truck with fuses;

– earthing truck without making capacity (for main busbar system and power cables);

– earthing truck with making capacity (for main busbar system and power cables);

– power cable testing truck;

– isolation truck;

– isolation truck with fuses.

Page 11: Ma Unigear Dl(en) 1vcd003415

9/64

3.3.4 Cable connection compartment (Figures 3/3, 5/18 to 5/20, 5/41, 5/42)

The cable compartment contains current transformers 7, fixed and withdrawable voltage transformers8, and earthing switch 6, according to individual operating requirements in each case.

The cable compartment is constructed for installation of three current transformers. Should all threecurrent transformers not be required, dummies will be installed in their place, using the same installationand connection procedures.

The voltage transformers mounted fixed are connected on the primary side with flexible, fully- insulatedcables which are inserted into the transformers.

The EK6 type earthing switch can be used with either a manual or motor-operated mechanism. Itsswitching position will be indicated both mechanically and electrically by means of the auxiliary switch.

Three surge arrestors can be mounted fixed, instead of the three-core cables.

Cable connection of 12/17.5 kV units:

In the 650 mm wide panel, up to three parallel plastic cables can be connected with single-core cableprotection and push-on sealing ends with a maximum cross-section of 630 mm2.

In the 800 mm wide panel, up to six parallel plastic cables can be connected with single-core cableprotection and push-on sealing ends with a maximum cross-section of 630 mm2.

Customer requests regarding connections to bars, three-core cables, special cables or sealing ends ofdifferent types must be considered during the order-planning stage.

3.3.5 Control cabinet (Figures 3/3, 3/7, 5/20, 5/39)

The control cabinet is for all control and protection aspects, suitable for both conventional ormicroprocessor control technology.

For details, see chapter 2.3.

If the secondary devices are not intended for door installation, they are mounted on special metal strips.

3.4 Interlock/protection against erroneous operation

3.4.1 Panel internal interlocking (Figure 3/3, 3/18)

To prevent hazardous situations and erroneous operation, there is a series of interlocks to protect bothpersonnel and equipment:

• The withdrawable part can only be moved from the test/disconnected position (and back) when thecircuit-breaker and earthing switch are off (i.e. the switch must be off beforehand.) In the intermediateposition, the switch is mechanically interlocked. When the circuit-breakers have an electrical release,the interlock is also electrical.

• The circuit-breaker can only be switched on when the withdrawable part is in the test or serviceposition. In the intermediate position, the switch is mechanically interlocked. When the circuit-breakers have an electrical release, the interlock is also electrical.

• In panels with digital control technology, prevention of malfunction of the switch can also be achievedby means of the panel software.

• In the service or test positions, the circuit-breaker can only be switched off manually when no controlvoltage is applied and it cannot be closed (electromechanical interlock).

• Connecting and disconnecting the control wiring plug 10.2 is only possible in the test/disconnectedposition of the withdrawable part.

Page 12: Ma Unigear Dl(en) 1vcd003415

10/64

1) In the case of a motor operator, the mechanical interlock or the locking magnet is replaced by an electrical interlock of theearthing switch. The manual emergency switch is not locked!

2) The locking magnet is not installed in the case of a motor operator; busbar earthing switches or the withdrawable parts areelectrically locked. The manual emergency switch is not locked!

• The earthing switch 6 can only be switched on if the withdrawable part is in the test/disconnectedposition or outside of the panel (mechanical interlock 1) ).

• If the earthing switch is on, the withdrawable part cannot be moved from the test/disconnected positionto the service position (mechanical interlock).

• Details of other possible interlocks, e.g. in connection with a locking magnet on the withdrawable partand/or earthing switch drive, can be obtained from the relevant order documents.

3.4.2 Doors interlocking (Figure 3/4-1 to 3/4-8)

The panels can be equipped with the following interlocks:

• The apparatus (circuit-breaker or contactor) cannot be racked-in if the apparatus compartment dooris open (3/4-1 and 2).

• The apparatus compartment door cannot be opened if the apparatus (circuit-breaker or contactor) isin service or in an undefined position (3/4-3 and 4).

3.4.3 Interlocks between panels (Figure 3/1-6, 3/1-7, 3/2-6, 3/2-7)

• The busbar earthing switch can only be closed when all the withdrawable parts in the relative bus-barsection are in the test/disconnected position (electromechanical interlock).

• When the busbar earthing switch is closed, the withdrawable parts in the earthed busbar sectioncannot be moved from the test/disconnected position to the service position (electromechanical 2)interlock).

3.4.4 Locking devices (Figures 3/3, 6/13, 6/22)

• The shutters 12.1/12.2 can be secured independently of each other with padlocks when thewithdrawable circuit-breaker part has been removed.

• Access to the operating-shaft 14.1 of the earthing switch can be restricted with a padlock.

• Access to the circuit-breaker racking slot can be restricted with a padlock.

• Access to the circuit-breaker compartment and the cable compartment from the backside of the panelcan be restricted with a padlock.

3.5 Control wiring plug connector coding (Figure 3/25)

The control wiring plug connector coding allows withdrawable parts for switching devices to be assignedto particular panels. This ensures, for example, that withdrawable parts with different rated currents ordifferent control wiring circuits can only be used in the panels they are intended for.

Coding pins are fitted in the control wiring sockets 10.1 or control wiring plugs 10.2, and engage withthe corresponding bores of the relevant plug 10.2 or socket 10.1 when the two parts are connected.

The plug connector coding is order-related, and is noted in the relevant wiring documentation.

3.6 Fast recovery (Figure 3/5-1 to 3/5-4)

UniGear switchgears can optionally be equipped with “Fast Recovery”, a specific protection system.

This system is based on pressure sensors 3/5-1, suitably located in the switchgear and directlyconnected to the shunt opening release installed in the circuit-breaker operating mechanism 3/5-2.

The sensors detect the pressure rise front at the moment of an internal arc and promptly open the circuit-breaker.

Thanks to the “Fast recovery” system, only the part involved in the fault is selectively excluded in under100 ms (including the circuit-breaker opening time). Rapid elimination of the fault along with the metalsegregation between compartments and the use of self-extinguishing materials drastically reduces anypossible damage.

Page 13: Ma Unigear Dl(en) 1vcd003415

11/64

Figures 3/1-1 to 3/1-8: examples of 12-17.5 kV panel variants.

Figure 3/1-1: Bustie/Feeder unit - 12 kV, 1250 A, 31.5 kA -with fixed voltage transformers

Figure 3/1-2: Feeder/Feeder unit - 12 kV, 1250 A, 31.5 kA -with fixed voltage transformers

Figure 3/1-3: Feeder unit - 12 kV, 1250 A, 31,5 kA -with fixed voltage transformers

Figure 3/1-4: Riser/Feeder unit - 12 kV, 1250 A, 31.5 kA -with withdrawable voltage transformer

Page 14: Ma Unigear Dl(en) 1vcd003415

12/64

Figure 3/1-5: Bustie/Feeder unit 12 kV, 1600 A, 40 kA, withfixed voltage transformer

Figure 3/1-6: Feeder/Feeder unit - 12 kV, 1600 A, 40 kA -with fixed voltage transformer

Figure 3/1-7: Joint/Feeder unit - 12 kV, 1600 A, 40 kA, withwithdrawable voltage transformers on Jointand with fixed voltage transformer on Feeder

Figure 3/1-8: Bus riser/Feeder - 12 kV, 1600A, 40 kA - withwithdrawable voltage transformers on bus riser,fixed voltage transformer on Feeder anddeeper low voltage upper box

Page 15: Ma Unigear Dl(en) 1vcd003415

13/64

1.1

1818.118.2

1414.114.2

C2

C1

A1

D

D1

B1

D

B2

A2

75

5

8

8

75

5

3 2 1 1.2

84

16

3

2

16

21

17

21 6

12.1

12.2

13

18

1

12.1

13

12.2

18

6

84

A1 Upper busbar compartmentB1 Upper circuit-breaker compartmentC1 Upper cable compartmentA2 Lower busbar compartmentB2 Lower circuit-breaker compartmentC2 Lower cable compartment

D Control cabinetD1 Control cabinet (available in deeper version on

request)

Figure 3/3: Example of UniGear Doble Level feeder unit

1 Enclosure1.1 Pressure relief flap1.2 Control wiring duct

2 Branch conductor3 Busbar5 Isolating bushing6 Earthing switch7 Current transformer8 Voltage transformer

12.1 Top shutter12.2 Lower shutter

13 Withdrawable part14 Earthing switch operating mechanism

14.1 Operating shaft for earthing switch14.2 Slide

16 Cable sealing end17 Floor cover – split18 Spindle mechanism

18.1 Spigot on spindle18.2 Hole in spindle for insertion lever

21 Cable clamp84 Partition

Page 16: Ma Unigear Dl(en) 1vcd003415

14/64

A

A

B

B

Figure 3/4-1: Circuit-breaker compartment door enabling device (A)

Figure 3/4-2: Circuit-breaker truck enabling slot (A)

Figure 3/4-4: Circuit-breaker compartment door locking pin (B)

Figure 3/4-3: Circuit-breaker compartment door locking device (B)

Page 17: Ma Unigear Dl(en) 1vcd003415

15/64

1

2

3

Figure 3/5-1: Pressure sensor Figure 3/5-2: Shunt opening release

Figure 3/5-3: Fast recovery system

Figure 3/5-4: Testing equipment

Resetting the auxiliary contacts

1 Pressure reducer2 Lever for opening the air valve3 Manometer

Compressed air system

Page 18: Ma Unigear Dl(en) 1vcd003415

16/64

10.2

13.1

18.1

14

Figure 3/6: Feeder unit (with deeper version of low voltageupper box)

Figure 3/7: Low-voltage compartment, internal view

Figure 3/8: Circuit-breaker compartment, open.Withdrawable part in service position

Figure 3/9: Circuit-breaker compartment, open.Withdrawable part in disconnected position,control wiring plug connector open10.2 Control wiring plug13.1 Withdrawable part14 Earthing switch operating mechanism18.1 Square spigot

Page 19: Ma Unigear Dl(en) 1vcd003415

17/64

5

4.1

12.2

12.1

4.3

4.2

5

12.2

13.10

13.16

13.15

13.1313.13

Figure 3/10: Withdrawable part during insertion into theservice position, shutters not yet fully open4.2 Contact arm, with insulating sleeve4.3 Contact system5 Isolation tulip12.1 Top shutter12.2 Lower shutter

Figure 3/11: View inside the circuit-breaker compartment,withdrawable part removed, shutters open

4.1 Isolating contact5 Isolating tulip12.2 Lower shutter

Figure 3/12: Withdrawable part with circuit-breaker, typeVD4, operating mechanism side

13.15 Withdrawable assembly

Figure 3/13: Withdrawable part with VD4 type circuit-breaker, - pole side13.10 Pole tube cover13.13 Lifting eyebolts13.16 Actuating bars

Page 20: Ma Unigear Dl(en) 1vcd003415

18/64

45.2 45.1

45.3

31.9

31.16

31.2

31.3

31.4

31.531.6

Figure 3/17: Withdrawable part with VM1circuit-breaker -pole side

Figure 3/14: Push button for mechanical ON/OFF breakeroperation with the door closed (on request).If the withdrawable part is in the serviceposition, operation is carried out using theknob which swings a push rod extension out.45.1 Mechanical pushbutton45.2 Turning knob

Figure 3/15: View of the push rod extension swung out bythe knob at the front, with the withdrawablecircuit-breaker part in service position and thedoor open

45.3 Swivelling push rod

Figure 3/16: Withdrawable part with VM1 type circuit-breaker - operating mechanism side31.2 “Ready” display31.3 ON pushbutton31.4 OFF pushbutton31.5 Mechanical operating cycle counter31.6 Mechanical switch position indicator31.9 Catch for emergency manual operating

lever31.16 Front cover plate

Page 21: Ma Unigear Dl(en) 1vcd003415

19/64

10.2

13.15

90.1

90.2

90.3

90.4 90.5

90.7

90.6

91.15

91.14

91.13

Figure 3/18: HD4 type circuit-breaker - side view

10.2 Control wiring plug13.15 Withdrawable assembly

Figure 3/19: Operating and signalling parts of HD4 circuit-breaker90.1 Signalling device for state of SF6

pressure (on request)90.2 Opening pushbutton90.3 Closing pushbutton90.4 Operation counter90.5 Circuit-breaker open/closed indicator90.6 Shaft for manual closing spring

charging90.7 Signalling device for closing springs

charged/discharged

Figure 3/20: V-Contact type vacuum contactor - front view91.13 Signalling device ON/OFF91.14 Operating cycle counter

Figure 3/21: V-Contact type vacuum contactor - pole side

91.15 MV fuses

Page 22: Ma Unigear Dl(en) 1vcd003415

20/64

95.2

95.1

18.2 18.1 S9 S8 10.3

Figure 3/22: Withdrawable assembly for circuit-breaker, withauxiliary switchesS8 Test position indicatorS9 Service position indicator10.3 Control wiring plug connector for

withdrawable assemly18.1 Square spigot18.2 Hole in spindle for insertion lever spindle

Figure 3/23: Withdrawable part with metering unit95.1 Voltage transformer95.2 Cast resin tube (with fuse cartridge)

Page 23: Ma Unigear Dl(en) 1vcd003415

21/64

4745 49 46

48

4310 21

44

4211 22

32

112 23

33

213 24

34

314 25

35

415 26

36

516 27

37

617 28

38

718 29

39

819 30

40

920 31

41

50

51

52

53

54

55

56

57

58

B3(B4)

B6(B6)

B4(B3)

B1(B2)

B5(B5)

B2(B1)

10.410.5

10.4

(...)

10.1

Figure 3/25: Control wiring plug connector coding, shown for a 58-pole connector10.1 Control wiring socket10.4 Centring striking tabs10.5 Bore for actuating pin of the control wiring plug for controlling the auxiliary switch

Coding:

The corresponding codingdesignation for the control wiringplug is given in brackets (10.2)

The coding pins can be fitted inthe control wiring socket (10.1)and/or in the control wiring plug(10.2).

Basic design:

The number of sockets isoptional, but the basic assign-ment is 1, 8, 10, 20, 21, 31, 33and 40.

Sockets and pins can be mixedas required in the control wiringsocket (10.1) and control wiringplug (10.2).

Circuit breakers and contactors

12-17,5kV 650mm 800mm 1000mm

400A V

630A VD4 VM1 HD4

1250A VD4 VM1 HD4 VD4 VM1 HD4 VD4 VM1

1600A VD4 VM1 HD4 VD4 VM1

Isolating trucks

12-17,5kV 650mm 800mm 1000mm

400A

630A

1250A 17.12.32

1600A

Socket pin coding (apparatus)

B1 B2 B3 B4 B5 B6

O O

O O

O

O O

Plug hole coding (panel)

B1 B2 B3 B4 B5 B6

O O

O O

O

O O

Socket pin coding (apparatus)

B1 B2 B3 B4 B5 B6

O O

Plug hole coding (panel)

B1 B2 B3 B4 B5 B6

O O

Page 24: Ma Unigear Dl(en) 1vcd003415

22/64

4. Dispatch and storage

4.1 Condition on delivery

At the time of dispatch, the UniGear Double Level panels are factory-assembled, the withdrawableparts are in the service position and the doors are closed.

The factory-assembled panels are checked at the works for completeness in terms of the order andsimultaneously subjected to routine testing (normally without AC voltage testing of the busbars) to IECpublication 62271-200, and are therefore tested for correct structure and function.

The busbars are not assembled. The busbar material, fasteners and accessories are packedseparately.

4.2 Packing

According to the kind of transport and country of destination, the panels remain unpacked or are weldedin foil and packed in seaworthy crates. A drying agent is provided to protect them against moisture:

• Panels with basic packing or without packing.

• Panels with seaworthy or similar packing (including packing for containerised shipments):

- Sealed in polyethylene sheeting

- Transport drying agent bags included

- Moisture indicator included

- When aluminium composite sheeting is used, an inspection window is fitted for checking.

• Observe the directions for use of the drying agent bags. The following applies:

- Coloured indicator blue: contents dry

- Coloured indicator pink: contents moist (relative humidity above 40%).

4.3 Transport (Figure 4/1)

The transport units normally comprise individual panels and, in exceptional cases, small groups ofpanels. The panels are each fitted with four lifting lugs.

Transport panels upright. Take the high centre of gravity into account. Only ever carry out loadingoperations when it has been ensured that all precautionary measures to protect personnel andmaterials have been taken and use the following:

• Crane

• Fork-lift truck and/or

• Manual trolley jack.

Loading by crane:

• Fit lifting ropes of appropriate load capacity with spring catches (eyebolt diameter: 30 mm)

• Keep an angle of at least 60° from the horizontal for the ropes leading to the crane hook.

4.4 Delivery

The responsibilities of the consignee when the switchgear arrives at site include, but are not limited to,the following:

• Checking the consignment for completeness and lack of any damage (e.g. also for moisture and itsdetrimental effects). In case of doubt, the packing must be opened and then properly resealed, puttingin new drying agent bags, when intermediate storage is necessary.

• If any quantities are short, or defects or transport damage are noted, these must be:

- documented on the respective shipping document.

- notified to the relevant carrier or forwarding agent immediately in accordance with the relativeliability regulations.

Note:

Always take photographs to document any major damage.

Page 25: Ma Unigear Dl(en) 1vcd003415

23/64

1.5

Figure 4/1: Handling by crane1.5 Lifting eyebolt

4.5 Intermediate storage

Optimum intermediate storage, where it is necessary, without any negative consequences depends oncompliance with a number of minimum conditions for the panels and assembly materials.

1.Panels with basic packing or without packing:

• A dry well-ventilated store room with a climate in accordance with IEC 60694.

• The room temperature must not fall below –5 °C.

• There must not be any other negative environmental influences.

• Store the panels upright.

• Do not stack panels.

• Panels with basic packing:

- Open the packing, at least partially.

• Panels without packing:

- Loosely cover with protective sheeting.

- Ensure that there is sufficient air circulation.

• Check regularly for any condensation until installation is started.

2. Panels with seaworthy or similar packing with internal protective sheeting:

• Store the transport units:

- protected from the weather,

- in a dry place,

- safe from any damage.

• Check the packing for damage.

• Check the drying agent (also see section 4.2):

- on arrival of the consignment,

- subsequently at regular intervals.

• When the maximum storage period, starting from the date of packing, has been exceeded:

- the protective function of the packing can no longer be guaranteed,

- take suitable action if intermediate storage is to continue.

Note:

Do not walk on the roof of the panels (rupture points in pressure relief devices!).

Page 26: Ma Unigear Dl(en) 1vcd003415

24/64

Rated voltage kV 12/17.5 kV

Panel width FT mm 650 800

Aisle width 1) G mm 1350 1500

Door width mm 850 1000

Door height 2) mm 2400 2400

Assembly opening in celing:

Width mm 1000 1000

Length mm 1500 1500

Ceiling load 3) kg/m2 1200 1400

1) Pay attention to appropriatenational standards.

2) Applies to low voltagecompartments of standardheight.

3) Approximate numbersdepending on the type ofpanels.

5. Assembly of the switchgear at site

Always use protection gloves during assembly of the switchgear at site.

In order to obtain an optimum installation sequence and ensure high quality standards, site installationof the switchgear should only be carried out by specially trained and skilled personnel, or at least bypersonnel supervised and monitored by responsible persons.

5.1 General site requirements

On commencement of installation on site, the switch-room must be completely finished, provided withlighting and the electricity supply, lockable, dry and with facilities for ventilation. All the necessarypreparations, such as wall openings, ducts, etc., for laying the power and control cables up to theswitchgear must already be complete.

The ceiling height must also be checked considering the top-mounted pressure relief duct.

Compliance with the conditions for indoor switchgear according to IEC 60694, including the conditionsfor the “minus 5 indoor” temperature class must be ensured.

5.2 Foundations (Figures 5/1 to 5/14)

The switchgear must preferably be erected on a floor frame set into the switchroom floor or on a raisedfalse floor.

The structural data guideline listed below is to facilitate a rough calculation of the space required andfor preliminary planning of the room design for a switchgear project. When the final constructiondocuments are compiled, the binding data supplied by ABB must always be taken into account!

Dimension chart of structural data (also see figures 5/1 to 5/14)

5.2.1 Anchoring bolts and base irons fixing systems (Figure 5/5 to 5/7, 5/9 to 5/14)

Before installation, through holes must be drilled underneath each unit of the switchboard.

A general foundation drawing is given in figures 5/9 to 5/14:

The switchboard can be fixed either to the floor or to special base irons (supplied on request):

• For floor fixing, put the expansion and anchoring bolts in the fixing holes.

• Special bolt blocks are supplied for base iron fixing. The base irons must be fixed and buried inconcrete.

Four fixing holes are drilled in each unit base.

Before positioning the different switchboard units, check both the levelness of the floor, with particularattention to longitudinal levelling (maximum planarity 2/1000).

Fixing with anchoring bolts to concrete floor:

• Clean the installation area.

• On the slab, visibly trace the perimeter of all the units making up the switchboard, taking the minimumwall and obstacle clearances into account.

• Level the floor both longitudinally and transversally.

Page 27: Ma Unigear Dl(en) 1vcd003415

25/64

• Drill the floor at the foreseen fixing points, referring to the slab drilling drawings. To make the holes,use a hammer drill with a Ø = 16 mm bit.

• Insert the expansion anchoring bolts in the holes.

Fixing with base irons to concrete floor:

The base irons, which can be supplied on request, must be installed in the slab before finishing thefloor:

• Rest the irons on the floor and line them up so that they are parallel and are spaced from each otheras shown in the foundation drawing.

• Level the base irons both longitudinally and transversally.

• Fix the base irons in this position with expansion anchor bolts, using the holes provided in the baseirons.

• Complete the flooring so that the base irons extend out by at least 0.5 mm from the finished floorsurface.

Fixing to a floating floor:

• Clean the installation area.

• On the slab, visibly trace the perimeter of all the units making up the switchboard, taking the minimumwall and obstacle clearances into account.

• Drill the floor at the foreseen fixing points, referring to our slab drilling drawings. To make the holes,use a drill with a suitable bit for the type of fixing to be made (through or threaded hole).

5.3 Assembly of the switchgear panels (Figures 3/3, 5/15 to 5/41)

Use screws of tensile class 8.8. The tightening torques for the busbar screw connections with dishedwasher are as follows:

Recommended tightening torque 1) 2) Nm

Lubricant 3)

Thread Without Oil or grease

M6 10.5 4.5

M8 26 10

M10 50 20

M12 86 40

M16 200 80

1) The rated tightening torques for fasteners without lubrication are based on a coefficient of friction for the thread of 0.14 (the actualvalues are subject to an unavoidable range, in part not inconsiderable).

2) Rated tightening torques for fasteners with lubrication in accordance with DIN 43 673 Standard .3) Thread and head contact surface lubricated.

Any tightening torques which deviate from those in the general table (e.g. for contact systems or deviceterminals) must be taken into account as stated in the detailed technical documentation.

It is recommended that the threads and head contact surfaces of bolts should be lightly oiled or greased,so as to achieve a precise rated tightening torque.

The individual installation stages are as follows:

• Remove withdrawable parts 13 from the switchgear panels and store them with suitable protection.

• Dismantle lifting eyebolts 1.5.

• Transport the switchgear panels to the prepared installation point following the sequence shown onthe switchgear plan.

• Remove vertical partitions 9 in front of the busbar compartments by releasing the fixing screws.

• Release the fixing screws and draw out horizontal partition 20 below the withdrawable part travel rails.

• Release and remove floor cover 17.

• Remove covers 43.2 and 43.3 from the vertical control wiring ducts at the front right and left of thepanel.

Page 28: Ma Unigear Dl(en) 1vcd003415

26/64

5.5 Pressure relief ducts (Figure 3/1-1, 5/5 to 5/7, 5/17)

• The pressure relief duct is integrated in the design of the panel.

• The screw fixing material is contained in the “pressure relief duct” set of bags. Rivet nuts are alreadyprovided in the metal sheets.

5.6 Cable connection

5.6.1 Power cables (Figures 5/18, 5/19, 5/41)

The standard method for entry of power cables in the switchgear is shown in Fig. 5/18 and 5/19. Thecables are conveyed from below rear through floor covering 17, which is divided at the cable entry point.The cables go through rubber reducer rings 17.2, which can be adapted to the required cable diameterin a range from 27 to 62 mm. Cables are fastened in the panel by means of cable clamps mounted oncable strips, which are part of the panel floor covering. The clamps make it possible to fasten cableswith diameters between 35 and 54 mm.

5.4.1 Busbars and bushings for units 12/17.5 kV (Figures 5/21 to 5/24)

Busbars are made of copper and have a flat cross-section for rated current up to 1600 A.Branch conductors always have a flat cross-section.

12/17.5 kV bushings are made of epoxy resin castings and are arranged as a single casting for all threephases (see fig 5/22).

For 12 kV, the busbars are bare (without insulation) and without insulating covers up to 1600 A.For 17.5 kV, the busbars are insulated and fitted with covers over the whole current range.

5.4 Installation of the busbars and bushings (Figures 3/3, 5/22 to 5/24)

Access to busbars is possible from the back of the panel, after dismounting of the back plate of thebusbar compartment (this is valid for upper and lower busbar compartments).

• Install bushings 29 (for switchgears with busbar barriers only).

• Clean the insulation on the busbar sections with a soft, dry cloth, and check for insulation damage.

Remove greasy or adhesive dirt as described in section 7.3.

• Busbar connections:

– The silver plated surfaces of the connections must be cleaned with a metal-free non-wovencleaning cloth and thinly and evenly coated with vaselin grease.

– The non-silver plated surfaces of the connections are either brushed with a wire brush, preservingthe grease film, or cleaned with a metal-free non-woven cleaning cloth and evenly greased with athin coat of vaselin grease.

• Prepare insulating covers 58 and lids 58.5 to suit the relevant busbar connections and thread themonto the busbar. (For insulated busbars only).

• Install the busbars panel by panel. Screw on the individual busbar elements one above the other(depending on the system layout) and in line with the flat branch conductor. Use the hexagonal sockethead screws 163 provided. See the table above for the tightening torque. Use two dished washersfor each screw.

• Bolt one holder 58.1 to each end of the busbars to support insulating cover 58. The screws for holder58.1 must be tightened with a lower torque. (For insulated busbars only).

• Position insulating covers 58 and lids 58.5 over the relevant bolted joint, and slide the lid onto thecover until it clicks into place. (For insulated busbars only).

Note:

The connection of busbars is carried out with so called “stabilized connections”. This means that qualityof the copper busbar connections does not change depending on the operating time and therefore itis not necessary to inspect tightness of busbar connections regularly. But this is on condition that correctassembly is carried out as described above and especially that all connections are tightened with theprescribed torque according to the table in sect. 5.3.

We recommend only inspecting tightness of busbar connections during repairs - see sect. 7.4.1.

Page 29: Ma Unigear Dl(en) 1vcd003415

27/64

Rated Panel Max. number Max. cross Range of Range ofvoltage width of parallel section of cable clamp reducer ring

cables cables

(kV) (mm ) in phase (mm2) (mm) (mm)

650 3 1)

12/17.5 800 6 2) 630

1000 35 - 54 27 - 62

24 800 3 1) 500

1000 6 2)

1) In the case where there are removable voltage transformers on the truck, or surge arresters are used, the number of parallel cablesis reduced to a max. of 2 per phase.

2) In the case where there are removable voltage transformers on the truck, or surge arresters are used, the number of parallel cablesis reduced to a max. of 4 per phase.

Important note!

Connection with single-core plastic insulated cables is presumed in the typical panels. In the case ofany atypical cable connections or of special cables (e.g. three-core cables, cables with paper or specialinsulation etc.), an agreement must be reached between the customer and manufacturer.

Mounting procedure for power cables:

• Power cables must be inserted, cut to length and stripped.

• Reducer rings 17.2 must be adapted to the cable diameter and fitted onto the cable.

• Cable sealing ends 16 must be prepared and mounted on cable cores according to manufacturer’sinstructions.

• Cable eyes must be connected to the prepared connections bars 23 with strain relief.

• Earthing of cables must be connected.

• Individual parts of the floor covering must be mounted.

• Reducer rings 17.2 must be moved down so that nuts in the rings fit into the corresponding recessesin the floor coverings. In this way, the cable passages are sealed.

• Cables must be fastened in the prepared cable clamps 21 (the maximum tightening torque applicableto the clamp screws is 9 ± 2 Nm).

5.6.2 Control cables (Figures 3/3, 5/1, 5/20)

The control cables are conveyed into the panel through the control wiring duct 1.2 on the left-handpanel side and through the wiring duct placed in the intermediate 100mm width panel.Mounting procedure:

• Insert the cables into the control wiring duct 1.2 on the left-hand side (Fig. 3/3). The duct is coveredby covers 43.1, 43.2 (Fig. 5/20).

• Connect control cables to the terminal strip according to the circuit diagram.

• Make the control wiring connections to adjacent panels using bushing 24 (Fig. 5/15).

Cable sealing ends are mounted on the cable cores according to the manufacturer’s instructions. It ispossible to use cable sealing ends of different manufactures (e.g. Pirelli, Raychem etc.), but it isnecessary to keep the length of the cable ends, including cable sealing ends, which is given by thedistance of cable connecting bars 23 from the panel floor covering. These bars have different versions,which differ in their number of parallel cables and the values of rated and short-circuit currents. See Fig.5/41, 5/42.

The bars are equipped with holes for M16 screws. If M12 screws are used for cable connections, specialwashers with the diameter for M12 screws are supplied. In all cases, the earthing of cable screens iscarried out on the strip-holding cable clamps. The cable strip is connected to the earth potential.

Three fixed mounted surge arresters can also be installed here. But in both these cases the number ofparallel cables must be reduced – see the table.

Connection of cables in typical panels:

Page 30: Ma Unigear Dl(en) 1vcd003415

28/64

5.7 Earthing the switchgear (Figures 3/3, 5/19)

• Connect main earthing bar 19 with connections 19.1 provided in every panel.

• Protection wiring connection of the floor frame or the erected raised false floor respectively, shouldbe made.

• Connect the earthing conductor coming from the earth electrode, preferably via a removable boltedconnection for testing purposes, to the main earthing bar 19 of the switchgear.

5.8 Laying the ring circuits

The ring circuits are supplied rolled up in a bundle in the control cabinet. They are marked and fittedwith ferrules at both ends. Openings are provided in the side walls of the control cabinet for these linesto be looped through from panel to panel.

5.9 Final erection work

• Check painted areas of the switchgear for possible damage, touching up where required (see alsosection 7.4.1).

• Check bolt connections and tighten where required, in particular all those carried out during on-siteerection of the busbars and earthing system.

• Clean the switchgear thoroughly.

• Remove all foreign bodies from the panels.

• Correctly replace all coverings, etc. removed during erection and connection.

• In the enclosure, any remaining openings must be closed if they are no longer needed.

• Check the isolating contacts and interlocking mechanisms for smooth motion, and grease again withvaselin where necessary (see section 7.4.1).

• Withdrawable circuit-breaker parts must be inserted and the control wirings connected.

• Panels doors must be properly closed.

Page 31: Ma Unigear Dl(en) 1vcd003415

29/64

Figure 5/1: Structural guideline data for foundation frame on concrete floor - UniGear Double Level -12/17.5 kV, panel depth1976 mm

G Control cables entranceP Power cables entrance

Structural data

Top view

Page 32: Ma Unigear Dl(en) 1vcd003415

30/64

Figure 5/9-1: 12-17.5 kV - 650 mm wide units - anchoring bolt fixing system

Figure 5/9-2: 12-17.5 kV - 650 mm wide units - base iron fixing system

Figure 5/10-1: 12-17.5 kV - 800 mm wide units - anchoring bolt fixing system

Page 33: Ma Unigear Dl(en) 1vcd003415

31/64

Figure 5/10-2: 12-17.5 kV - 800 mm wide units - base iron fixing system

Figure 5/14-3: through hole on metal structure Figure 5/14-4: threaded hole on metal structure

Figure 5/14-1: anchoring bolts on concrete floor Figure 5/14-2: base irons on concrete floor

Page 34: Ma Unigear Dl(en) 1vcd003415

32/64

1.9

26

1.11

1.5

1.3

28

50 50

Figure 5/16: End panel of a switchboard with bolted-on coverplate26 Cover plate

Figure 5/17: Schematic diagram of the pressure relief duct.The components are assembled panel by paneland bolted together with overlaps at the paneljoints.50 pressure relief duct1) If the switchgear is equipped with a pressurerelief duct, the pressure relief flap for the cableconnection compartment is fixed to the rear sideof the panel and will open to the front (into theduct) in case of an arc fault.

Figure 5/15: For bolting the switchgear panels together, through holes are provided on the left-hand side and threaded busheson the right-hand side, near the front and rear edges of the side walls, and through holes on both sides in the centralpart of the walls

1.3 Main earthing bar1.5 Lifting huck1.9 Threaded bush, for switchgear assembly1.11 Bore, for control wiring bushing 2428 Bushing plate

Page 35: Ma Unigear Dl(en) 1vcd003415

33/64

23

17

3921

19.2

19

1.8

43.1

20 2

3

Figure 5/18: View into the cable connection compartment,max. six parallel cables possible17 Floor cover, split23 Cable connec

Figure 5/19: Partial view of the cable compartment, preparedhere for connection of triple cables19 Main earthing bar19.2 Earthing connection pin21 Cable clamp39 Mounting rail, conncted to earth potential

Figure 5/20: View into the high voltage area at the front1.8 Central catch20 Horizontal partition, removable43.1 Duct cover for external control cables

Figure 5/21: View into the busbar compartment, shown with-out insulating covers2 Branch conductor3 Busbar

Page 36: Ma Unigear Dl(en) 1vcd003415

34/64

L1 L3L2

3 28

29

9.3

2

≤ 1250 A ≤ 2500 A ≤ 2500 A

Figure 5/24: Pannels 12/17.5 kV – Busbar junctions

2 Branch conductor3 Busbar section3.2 Spacer plate, 5 mm thick3.3 Spacer plate, 15 mm thick3.4 M 10 Bolt58 Insulating cover

Rated branch current

Rated busbar current

Figure 5/22: Panels - 12/17.5 kV - Arrangement of the bushing plate and busbar bushing on the right-hand panel side wall. Viewof the inside2 Branch conductor3 Busbar section9.3 Partition28 Bushing plate29 Busbar bushing

b) Bushings with busbar supports with single flat conductora) Bushings with busbar supports with double D-shaped conductor

Page 37: Ma Unigear Dl(en) 1vcd003415

35/64

23

23

21

21

17.2 17.2

Figure 5/41: Dimensions of power cable connection of UniGear Double Level 12/17.5 kV panels

17.2 Reducer ring21 Cable clamp23 Cable connection bar

In

A

630

1000

1250

1600

with

mm

Ith

kA

max. numberof cables

in one phase

A

mm

B

mm

C

mm

750 31,5

900 40-50

3/6 575 1320 90

Page 38: Ma Unigear Dl(en) 1vcd003415

36/64

6. Operation of the switchgear

Note on safety at work

The relative work and operating procedures must be carried out carefully by trained specialists familiarwith the installation, taking into account all the relative safety regulations according to the IEC and otherrelevant professional bodies, as well as any local and work regulations and instructions.

Note:

Do not walk on the top surfaces of the switchgear panels (rupture points for pressure relief).

6.1 Commissioning

6.1.1 Preparatory work (Figures 3/13, 3/23)

In preparation for commissioning, the following work must be carried out prior to connection with thehigh voltage power supply:

• Check the general condition of the switchgear for any damage or defects.

• Visually inspect the switching devices, withdrawable parts, isolating contacts, insulating parts, etc.

• Check connection of the main earthing bar to the installation earthing conductor (following theappropriate safety regulations).

• Check the paintwork for damage and, where necessary, touch up as described in section 7.4.

• Remove all residues of materials, foreign bodies and tools from the switchgear.

• Clean the switchgear, rubbing down insulating parts with a soft, dry, clean, non-fraying cloth. Removeany greasy or sticky dirt as described in section 7.3.

• Correctly remount all covers etc. removed during assembly and testing procedures.

• Transport caps 13.9 on vacuum circuit-breakers - if still fitted - must be removed.

• Pole tube lids 13.10 on vacuum circuit-breakers may be fitted in certain systems and on certain circuit-breakers. Check that they are fitted correctly.

• Lifting eyebolts 13.13 on high current vacuum circuit-breakers must be removed if still fitted.

• Preparatory works for SF6 circuit-breakers:

- Clean the insulating parts with clean dry cloth.

- Check that the upper and lower terminals are clean and free of any deformation caused by shocksreceived during transport and storage.

- It is advisable to check the SF6 gas pressure.

• Perform AC voltage testing of the main circuits according to IEC 60298 where necessary. Pay specialattention to voltage transformers and cables, etc. during this procedure. A testing and earthingmodule 142 can be used to make the connections (see section 6.3.2).

• Switch the auxiliary and control voltage on.

• Carry out testing operations on switching devices manually or by electrical control, and simultane-ously observe the relative position indicators.

• Check mechanical and electrical interlocks for effectiveness, without using force.

• Set the protective devices in the switchgear to the required values and check their function with testequipment.

• On motorized withdrawable parts, check the direction of rotation of the travel motor in accordancewith section 7.5.4.

• For any other matters regarding operation of the withdrawable circuit-breaker part and testingfacilities for the withdrawable part, see section 7.5.

• Instruct local operators regarding the basic details of regular handling of the switchgear.

• Check readiness for operation and switching status of electrical systems upstream and downstreamof the switchgear.

Page 39: Ma Unigear Dl(en) 1vcd003415

37/64

Depending on allocation of responsibilities, it may also be necessary to check the following equipmentin areas adjacent to the switchgear:

• power cables

• auxiliary cables

• auxiliary power source

• remote control system

• complete earthing system

• switchroom equipment

• switchroom conditions

6.1.2 Start-up

• Comply with all relevant safety regulations.

• Ensure that the circuit-breakers in the system are in the OFF position.

• Remove any existing earthing and short circuiting connections in the critical switching area.

• Energize the feeder cables.

• Connect the switchgear step by step, observing the signals and indicators.

• Check that relative conductors are in phase, where necessary, when there are several incomingfeeder cables and switchgear sections (also see section 6.3.2).

• Carry out all measurements and check all functions which depend on high voltage power supplybeing connected.

• Watch out for irregularities of any kind.

6.2 Switching operations

Carry out switching operations with the front doors closed.

6.2.1 Withdrawable circuit-breaker part (Figures 3/18, 3/22, 6/1, 6/5 to 6/12)

Manual insertion from the test/disconnected position to the service position:

• Connect control wiring plug 10.2

• Close the front door.

• Ensure that the circuit-breaker is in the OFF position.

• Fit hand crank 121 on square spigot 18.1 of the spindle mechanism 18, after opening the hole forthem by turning slide 121.1.

• Turn the crank clockwise (approx. 20 turns at 12 - 17.5 kV and 30 at 24 kV) until the stop is reachedand the withdrawable part is in the service position.

• Observe the position indicator.

• Remove hand crank 121.

It must be considered that the spring loaded pin head 18.2 will lie completely on the rear side of thepanel door when the hand crank is moved from square spigot 18.1 of spindle mechanism 18. Thisensures that the rear part of the pin head has been shifted onto the hexagonal cap of the spindle andprevents unintentional wrenching of the spindle during panel service. Wrenching may lead to thecircuit-breaker blocking.

Note:

The withdrawable part must not be stopped in any intermediate position in the travel range betweenthe service and test/disconnected position!

Page 40: Ma Unigear Dl(en) 1vcd003415

38/64

Manual withdrawal from the service position into the test/disconnected position:

• Ensure that the circuit-breaker is in the OFF position.

• Reverse the procedure described above for insertion into the service position.

Important note

Insertion and withdrawal of circuit-breakers (and other withdrawable parts) must be gradual, in orderto avoid any shocks which could deform the mechanical interlock. If the operations are prevented, donot force the interlocks and check that the operating sequence is correct. The force normally applicableto the insertion/withdrawing lever is 260 N. In any case, the maximum applicable force must neverexceed 400 N. Please also refer to the technical documentation of the circuit-breakers for installationoperations.

Caution: the insertion and withdrawal must always be carried out with the circuit-breaker open!

Do not use force to move withdrawable parts with locking magnet YO in the event of an auxiliary voltagedrop. If this occurs, they are locked along the whole travel range between the service and test positions.To remove the interlock, consult the technical documentation of the circuit-breakers.

Motorized movement of the withdrawable part:

• Briefly operate the electrical control for insertion or withdrawal (the withdrawable part thenautomatically moves into the opposite position).

• Observe the position indicator.

Note

When the drive motor is faulty, the withdrawable part can be moved using the emergency manualoperation.

If the drive motor fails during movement of the withdrawable part, the withdrawable part must be movedinto a limit position using emergency manual operation.

Emergency manual operation is carried out with hand crank 121 on spindle mechanism 18, in a similarway to operation of a withdrawable circuit-breaker part with manual systems. To disengage themotorized withdrawable part, consult section 7.5.1.

• Switch off the auxiliary power (m.c.b.), since the motor would otherwise be braked electrically.

• Turn hand crank 121 in the required direction.

When the withdrawable part moves, the motor turns. In this case, the motor functions like a generator,i.e. it can lead to reserve voltages in the terminals.

The motor fuse must not be changed from the specified type and rated value, otherwise the behaviourof the permanent magnet motor could be irreversibly impaired!

Caution

In emergency manual operation of a motorized withdrawable circuit-breaker part, the interlock with theearthing switch is not effective!

Withdrawal from the test/disconnected position onto the service truck:

• Open the door of the circuit-breaker compartment.

• Release control wiring plug 10.2 and place it in the storage position on the withdrawable part.

• Position service truck 124 with guide pins 124.2 of the adjustable bench top at the correct heightfacing the panel front, and allow catch 124.3 to engage.

• Move sliding handles 13.11 inwards against the springs to release withdrawable part 13, draw thewithdrawable part out onto the service truck and secure it in the catches on the truck.

• Press release lever 124.4 (at the front underneath the bench top) and release the service truck fromthe switchgear panel.

• Secure the position of the shutters with padlock 130 (Fig. 6/22).

Insertion from the service truck into the test/disconnected position:

• Carry out the procedure described above for withdrawal in reverse order.

Page 41: Ma Unigear Dl(en) 1vcd003415

39/64

2 5 4

6 7

Circuit-breaker closing and opening operations

Circuit-breaker operation can be either manual or electrical

a) Manual spring charging operation

To manually charge the closing springs, it is necessary to repeatedly activatethe charging lever (2) (maximum rotation angle of the lever: about 90°) untilthe yellow signalling device (7) appears which indicates completion ofcharging.

The maximum forces which can normally be applied to the lever are <150N for the EL1operating mechanism and <200 N for the EL2 operatingmechanism. For the type of operating mechanism, please refer to the ratingplate in fig. 5/42.

b) Electrical spring charging operation

On request, the circuit-breaker can be fitted with the following accessoriesfor electrical operation:

– geared motor for automatic closing spring charging

– shunt closing release

– shunt opening release.

The geared motor automatically recharges the springs after each closingoperation until the yellow signalling device (7) appears.

If the power is cut off during charging, the geared motor stops and automati-cally starts recharging the springs again when the power returns.

In any case, it is always possible to complete the recharging operationmanually.

Figure 5/42: VD4 Circuit-breaker.

c) Circuit-breaker closing

The operation can only be carried out with the closing springs completely charged.

For manual closing, press the pushbutton (5).

When there is a shunt closing release, the operation can also be carried out remotely by means of aspecial control circuit. Closing having taken place is indicated by the signalling device (6).

d) Circuit-breaker opening

For manual opening, press the pushbutton (4).

When there is a shunt opening release, the operation can also be carried out remotely by means ofa special control circuit. Opening having taken place is indicated by the signalling device (6).

For further details, please refer to specific manual N. 647654.

6.2.2 Circuit-breaker - type VD4

Instructions for operating the circuit-breaker

Safety indications

The VD4 circuit-breakers guarantee a minimum IP2X degree of protection when installed in thefollowing conditions:

– fixed version, installed behind metallic grid

– withdrawable version, installed in switchgear.

Under these conditions the operator is totally guaranteed against accidental contact with moving parts.

Should mechanical operations be carried out on the circuit-breaker outside the switchgear, bevery careful of the moving parts.

If the operations are prevented, do not force the mechanical interlocks and check that the operatingsequence is correct.

Racking the circuit-breaker in and out of the switchgear must be done gradually to avoid shocks whichmay deform the mechanical interlocks.

Page 42: Ma Unigear Dl(en) 1vcd003415

40/64

8 9

Opening and closing operations

The opening and closing operations can either be remotely controlled bymeans of the special inputs provided in the control module, or locally bypressing the pushbuttons (8 - 9) (fig. 5/43). During the operations, the movinganchor of the actuator acts directly on the moving contact by means of thekinematics.

Reclosing function

Thanks to the short duration of capacitor recharging, the drive is suitable formultiple reclosing operations with O-0.3s-CO-15s-CO cycle.

Control module

The control module is available in the standard version and in the completeversion.

Functions of the control module - standard version

All the conditions for controlling the opening and closing commands givento the magnetic actuator are managed by a microprocessor:

• the power supply voltage must be applied to the AC/DC converter.

• the capacitor must be sufficiently charged for the next operation:

Circuit-breaker position Operations

Open Closes and Opens

Closed Opens

6.2.3 Circuit-breaker - type VM1

Operation of the circuit-breaker drive

Magnetic actuator

The magnetic actuator used in the VM1 circuit-breakers generates the run required to operate themoving contacts of the interrupters and integrates all the functions of a traditional operating mecha-nism. The magnetic actuator is a bistable system where end-of-run positions of the moving armatureare reached by means of magnetic fields generated by two coils (one for closing and one for opening).The moving armature is kept in position by permanent magnets.

The circuit-breaker operations are obtained by means of energisation of the opening or closing coilrespectively. The magnetic field generated by each coil attracts the moving armature and therebymoves it from one of the latching points of the permanent magnets to the other. The capacitors whichallow circuit-breaker operation, for a maximum time of two minutes, even in the case of a drop in theauxiliary voltage, are provided in the control circuit. In case of emergency, the circuit-breaker can inany case be opened by means of a special crank handle which acts directly on the moving armatureof the drive.

Compared to a traditional operating mechanism, the magnetic actuator has few moving parts andgreatly reduced wear even after a high number of closing and opening cycles. These characteristicstherefore make it practically maintenance-free.

• the closing coil can only be activated when the circuit-breaker is open

• the opening coil can only be activated when the circuit-breaker is closed

• closing is disabled when an opening command is active at the same time

• de-activation of the opening or closing coil takes place when the relative limit position has beenreached.

• WRONG POSITION (auto trip) function: if the final CLOSED (or OPEN) position is not reached within70 ms during a closing (or opening) operation, an opening operation is immediately started toguarantee reaching a defined safe position in any case.

• The anti-pumping function ensures that only one closing-opening cycle is carried out when a closingcommand followed by an opening command is active. The active closing command must becancelled and reset for the next closing operation.

• Activation of the input for the closing command can be locked by means of an external locking signal.

• The input for the “lock on closing” command must be energised to be able to close the circuit-breaker(without power it inhibits closing).

Figure 5/43: VM1 Circuit-breaker.

Page 43: Ma Unigear Dl(en) 1vcd003415

41/64

Additional functions of the control module - complete version

When the “FULL OPTION” control module is requested, the following functions are also available:

• Undervoltage function: controls circuit-breaker opening if the voltage applied drops below the limitof tolerance (established by the Standards).

The rated voltage value to be monitored is set in the factory in conformity with the order specifications.

To prevent the function intervening when the voltage drops below the specified level (e.g. in the caseof motor starting), it is possible to set a trip time.

If no voltage is applied to the undervoltage function input, it is impossible to close the circuit-breaker.

The undervoltage function can be disabled. In this case, it is possible to open and close the circuit-breaker without applying voltage to the input of the function.

• Monitoring function of the actuator closing and opening coil. This function serves to monitor thecontinuity of the closing and opening coils of the magnetic actuator to detect any faults.

If a fault is detected, the luminous “READY” signal on front of the circuit-breaker turns off and the“READY/NOT READY” signalling contacts are activated.

• Additional safety opening command function. The second input of the control module for theopening function is designed so that an opening command is carried out directly even in the caseof a fault in the microprocessor.

“READY” signalling

The luminous signal and relative “READY/NOT READY” contacts signal:

• capacitor charged

• detection of the correct “CLOSED” and “OPEN” positions by the position sensors

• watchdog (function only present on the FULL OPTION control module)

If the luminous “READY” signal is off or flashing, please refer to the following table to find the cause.

Truck locking magnet (compulsory device)

The locking magnet is inserted in withdrawable circuit-breakers with manual movement and preventstraverse of the withdrawable truck when there is no power supply voltage.

It is always provided as part of the safety interlock against withdraval of the circuit-breaker if closedfor any fault.

Circuit-breaker closed Circuit-breaker open Capacity of the capacitor/s

Ready signal: lit Ready signal: lit Sufficient energy for an O-C-O cycle

Ready contact: closed Ready contact: closed

Not Ready contact: open Not Ready contact: open

Ready signal: flashing Ready signal: flashing Sufficient energy for a C-O cycle

Ready contact: closed Ready contact: closed

Not Ready contact: open Not Ready contact: open

Ready signal: flashing Ready signal: off Sufficient energy for one opening

Ready contact: closed Ready contact: open

Not Ready contact: open Not Ready contact: closed

Ready signal: off Ready signal off: Insufficient energy for opening

Ready contact: open Ready contact: open

Not Ready contact: closed Not Ready contact: closed

Meaning of the signals according to the charging state of the capacitor/s

Circuit-breaker closed Circuit-breaker open State of the coils

Ready signal: flashing Ready signal: off No continuity

Ready contact: closed Ready contact: open in the closing coil

Not Ready contact: open Not Ready Contact: closed

Ready signal: off Ready signal off: No continuity

Ready contact: open Ready contact: open in the opening coil

Not Ready contact: closed Not Ready contact: closed

Meaning of the signals according to the state of continuity of the coils

For further details, please refer to specific manual N. 1VCD 600182.

Page 44: Ma Unigear Dl(en) 1vcd003415

42/64

2

3 4 6

7 Operating and signalling parts

Circuit-breaker closing and opening operations (fig. 5/44)

Circuit-breaker operation can be manual or electrical.

a) Manual operation for spring charging

To manually charge the closing springs, it is necessary fully insert thecharging lever into the seat (6) and turn it clockwise until the yellowindicator (7) appears.

The force which can normally be applied to the charging lever fitted is 130N. In any case, the maximum force which can be applied must not exceed170 N.

b) Electrical operation for spring charging

On request the circuit-breaker can be fitted with the following accessoriesfor electrical operation:

– geared motor for automatic charging of the closing springs

– shunt closing release

– shunt opening release.

The geared motor automatically recharges the springs after each closingoperation until the yellow indicator (7) appears. Should there be no voltageduring charging, the geared motor stops and then starts recharging thesprings automatically when the voltage is on again. It is, however, alwayspossible to complete the charging operation manually.

6.2.4 Circuit-breaker - type HD4

Instructions for circuit-breaker operation

Safety indications

HD4 circuit-breakers ensure a minimum degree of protection IP2X if installed under the followingconditions:– fixed version, with protection netting– withdrawable version, installed in a switchboard.

Under these conditions, the operator is fully guaranteed against accidental contact with moving parts.

Should any mechanical operations be carried out on the circuit-breaker outside the switchboard or withthe protection netting removed, be very careful of any moving parts. If the operations are prevented,do not force the mechanical interlocks and check that the operation sequence is correct.

The racking-in and racking-out operations of the circuit-breaker must be carried out gradually toprevent any impacts which might deform the mechanical interlocks.

c) Circuit-breaker closing

This operation can only be carried out with the closing springs completely charged.

For manual closing, push the push button (3).

When there is a shunt closing release, the operation can also be carried out with remote control bymeans of a control circuit. The indicator (4) shows that closing has been accomplished.

In case of earthing truck with making capacity, activate the key lock (in the closed position) and removethe key. This is to prevent accidental opening operations during any maintenance work on theinstallation.

d) Circuit-breaker opening

For manual opening, push the push button (2).

When there is a shunt opening release, the operation can also be carried out with remote control bymeans of a control circuit. The indicator (4) shows that opening has been accomplished.

For further details, please refer to specific manual N. 647016.

Figure 5/44: HD4 Circuit-breaker.

Page 45: Ma Unigear Dl(en) 1vcd003415

43/64

6.2.6 Withdrawable metering parts (Figures 3/1-3, 3/1-4, 3/1-7, 3/1-8, 3/23)

Handling of the withdrawable metering part in the metering panel is as described in section 6.2.1,without, however, the switching operations and interlocking functions.

Withdrawable metering parts in incoming and outgoing feeder panels are put into the cable compart-ment using a ramp. They reach their service position immediately and engage in the panel earthingby means of the two locking pins at the sides. The voltage transformers used correspond to the typeused in the metering panel, and therefore HRC fuses can also be used along with the voltagetransformers.

6.2.7 Earthing switch - type EK6 (Figures 3/1, 3/3, 6/9, 6/12, 6/13, 6/14, 6/24)

The earthing switch - type EK6 - has a snap closing mechanism which is independent of the rotationof the drive shaft. An earthing switch 6 allocated to a circuit-breaker is only enabled for switching whenwithdrawable part 13 is in the test/disconnected position or removed from the switchgear panel. Onlyturn earthing switches on when the doors are closed.

Manual opening and closing:

• Press slide 14.2 onto the operating lever recess socket downwards. (When the switch is closed, itis already in this position!)

Caution!

If the operation is prevented, do not force the interlock and check that the operation sequence is correct.

• Fit operating lever 122 onto hexagonal shaft 14.1,which is now released for operation.

Note

Put operating lever 122 in pointed upwards or downwards on the hexagonal shaft so that there issufficient room for movement of the operating lever even if space is limited at the sides.

• Turn the lever clockwise through approx. 180° until the stop is reached to close the earthing switch,or anticlockwise until the stop is reached to open the earthing switch.

• Observe the mechanical/electrical switch position indicator.

• Remove operating lever 122. Slide 14.2 remains open if the earthing switch is in the closed position.

Make sure that the operating lever is turned right up to the stop in the opening process, to ensure thatthe earthing switch is in its defined limit position. The manual operating mechanism can also be fittedwith a locking magnet.

The earthing switch for the lower cable compartment is provided with a special operating lever withthe hexagon bush rotated of 90° with respect to the standard lever, in order to permit the 180° rotationof the hexagonal shaft which is placed at floor level.

Figure 5/45: V-Contact vacuum contactor.

6.2.5 Vacuum contactor - type V-Contact

The V-Contact type vacuum contactor is ideal for controlling users in a.c.requiring a high number of operations. The contactors basically consist ofa moulded resin monoblock, where the vacuum interrupters, moving appa-ratus, control electromagnet, multivoltage control feeder and auxiliaryaccessories are housed. The monoblock is also the support for assembly ofthe fuse-holder frame. Closing of the main contacts is carried out by meansof the control electromagnet. Opening is carried out by means of a specialopposing spring. The contactor can be equipped with electrical or mechani-cal latching.

The fuses are positioned in special supports to be connected in seriesbetween the contactor and the user. The supports can house fuses incompliance with DIN or BS standards.

For details, please refer to manual 647011.

Page 46: Ma Unigear Dl(en) 1vcd003415

44/64

6.2.8 Earthing and short-circuiting with earthing module (Figures 6/17 to 6/19)

• Isolate the area to be earthed and secure it against reconnection.

• Carefully follow all safety regulations.

• Remove the withdrawable circuit-breaker part from the relative switchgear panel.

• Secure the shutter in front of the live contact pins by means of the padlock. Screw on the earthingmodule 142 actuating bars 142.1 as follows:- To the top position for opening of bottom shutter.- To the bottom position for opening of top shutter.

• Further screw on the earthing module 142 insulating plate 142.5 with 3 removable bushings asfollows:- Contact arms 142.2 in the bottom position for earthing of cable output feeder.- Contact arms 142.2 in the top position for earthing of busbars.

• Insert the earthing module 142 into the test/disconnected position and then move it into the serviceposition with the hand crank 121 (for procedure - see sect. 6.2.1).

• Using a high voltage tester, check that contact pins 142.7 of the earthing module are definitely off-circuit.

• Withdraw the earthing module back into the test/disconnected position (see sect. 6.2.1).

• Mount a complete short circuit link 142.8 on the earthing module 142. Connect one end of earthingcable 133.1 under one of three screws M12, with which short circuit link 142.8 is connected to contactpins 142.7. Connect the second end of this cable to the earthing terminal 19.3 in the panel.

• Insert the earthing module 142 with short-circuit link 142.8 mounted and earthing cable 133.1returned from the test/disconnected position into the service position in the panel with hand crank121. For safety reasons, insert the module only with the circuit- breaker compartment door closedand with door catches 1.8 locked (see Fig. 5/20).

• Display earthing warning label on the switchgear panel door.

• Secure neighbouring areas to prevent inadvertent contact with live parts (e.g. feeder cables).

The procedure for removing earthing is the same, only in reverse order.

6.3 Test procedure

6.3.1 Testing the off-circuit condition (Fig. 3/10, 3/11, 6/16, 6/17)

In switchgear panels which are not equipped with capacitive voltage indication, checking the off-circuitcondition is carried out with a HV tester on the isolating contacts 4.1 in the isolating tulips 5, after thecorresponding upper shutter 12.1 or lower shutter 12.2 has been opened. Shutter opening can becarried out by means of module 129 - see Fig. 6/17.

If the panels are equipped with capacitive voltage indication 125, checking the off-circuit condition canbe carried out by means of this device. In this case, proceed according to the manufacturer’s instructionsor the indicators. (Optionally, switchgear can be equipped with various types of indicators coming fromvarious manufacturers). In case of any doubt about correct operation of capacitive voltage indication,the off-circuit condition must be checked using a HV tester.

Checking the off-circuit condition must always be carried out in compliance with the relevant safetyregulations and local operating conditions!

6.3.2 Current and voltage tests (Figures 6/4 , 6/16, 6/18, 6/19, 6/20)

The testing and earthing module 142 is available for carrying out current and voltage tests. It is alsosuitable for supplying primary current to any current transformers which may be fitted duringmeasurements in the protection circuit and, for example, for application of a test voltage duringinsulating tests.

• Isolate and secure the working area in accordance with the IEC safety regulations.

• For primary current supply, fix the connecting cable of the test transformer to the contact pins 142.7.

• For AC voltage tests, ball 142.4 is required on the contact pin. The bore in the ball is used forconnection of the voltage supply.

• For current tests, for example of small connected generators, the short-circuit bridge 142.8 must befixed onto the contact pins.

Note:

With voltage tests at power frequency withstand voltage and/or impulse voltage, carry out the followingprocedure:

• Disconnect any voltage transformers and capacitive dividers and cover them with an insulating plate.

Page 47: Ma Unigear Dl(en) 1vcd003415

45/64

6.4 Service trucks

Instead of earthing, short-circuiting and testing with module 142 (see Fig. 6/18, 6/19 and chapters 6.2.9,6.3.1, 6.3.2), it is possible to use the service trucks.

These trucks are divided into four different types:

Earthing truck without making capacity

These trucks carry out the same function as the earthing switches without making capacity. Thereforethey do not have any capacity to earth the live circuits under fault conditions. They are used to ensurefixed additional earthing, as required by the plant service and maintenance procedures, as at furtherguarantee for personnel. The use of these trucks foresees removal of the switching device from theswitchgear (circuit-breaker or contactor) and its replacement with the truck. The units preset for useof earthing trucks are fitted with a key lock which, if activated, prevents their racking-in.

This truck is available in two versions:

• main busbar system earthing;

• power cable earthing.

During the racking-in phase, the main busbar earthing truck only lifts the top shutter and earths thecontacts connected to the top branches (and therefore to the main busbar system) by means of theswitchgear structure.

During the racking-in phase, the power cable earthing truck only lifts the bottom shutter and earths thecontacts connected to the bottom branches (and therefore to the power cables) by means of theswitchgear structure.

These trucks can also be used in the bus-tie units. In this case, they earth the two sides of the mainbusbar system.

Earthing truck with making capacity

These trucks carry out the same function as the earthing switches with making capacity. They consistof circuit-breakers only fitted with top (main busbar earthing) or bottom (power cable earthing)terminals. The contacts without terminals are short-circuited by means of a copper bar and connectedto earth by means of the apparatus truck. They keep all the characteristics of the circuit-breakers, suchas full making capacity and opening of the live circuits under fault conditions. They are used to ensureextremely efficacious earthing on circuits stressed by a fault. They allow opening and closingoperations to be carried out rapidly with remote electric control.

The use of these trucks foresees removal of the switching device from the switchgear (circuit-breakeror contactor) and its replacement with the truck. The units preset for use of earthing trucks are fittedwith a key lock which, if activated, prevents their racking-in.

This truck is available in two versions:

• main busbar system earthing;

• power cable earthing.

During the racking-in phase, the main busbar earthing truck only lifts the top shutter and presets thecontacts connected to the top branches (and therefore the main busbar system) for closing to earth bymeans of a control.

During the racking-in phase, the power cable earthing truck only lifts the bottom shutter and presetsthe contact connected to the bottom branches (and therefore to the power cables) for closing to earthby means of the control.

These trucks can also be used in bus-tie units. In this case, they earth the two sides of the main busbarsystem.

Power cable test truck

These trucks allow the insulation tests to be carried out on the power cables without accessing thefeeder unit or disconnecting the cables from the switchgear.

The use of this trucks foresees removal of the switching device from the switchgear (circuit-breakeror contactor) and its replacement with the truck.

During the racking-in phase, the truck only lifts the bottom shutter and, by means of the connectors itis fitted with, allows connection of the test apparatus cables.

This truck can only be used in the incoming/outgoing units.

Page 48: Ma Unigear Dl(en) 1vcd003415

46/64

1.17

46

≈ 90°

1.18

145

13.2

13.8

13.5

128

13.4

13.11

Figure 6/1: Operation of the door screw1.18 Door screw145 Double bit screw

Figure 6/2: Operation of the door catch1.17 Door catch

Figure 6/3: Operation and communication via digital controlsystem

46 REF542 Bay control and protection unit

Figure 6/4: Manual operation of withdrawable part with VD4circuit-breaker13.2 Mechanical OFF push-button13.4 Mechanical switch position indicator13.5 Mechanical operating cycle counter13.8 Charging condition indicator13.11 Sliding handle, connected with the catch

on the withdrawable assembly128 Charging lever

Isolation truck

The isolation truck allows the switchgear top and bottom contacts to be connected directly.

Connection is made extremely safe by using the poles of the HD4 circuit-breakers to insulate theconnection bars from the external environment. In the incoming/outgoing units, it connects the mainbusbar system to the power cables, whereas in the bus-tie units, to the two sides of the busbar system.

This truck is used in the UniGear switchgears to make incoming/outgoing units without circuit-breakersin radial networks, to make cable connections between two switchgears placed in front of each other,and for constructing interconnection units and creating bus-tie-riser units with double insulation (in thiscase, both the units are made from bus-ties, the first fitted with a circuit-breaker and the other with anisolation truck).

Page 49: Ma Unigear Dl(en) 1vcd003415

47/64

145 121.1 121

32

10.2

10.145.2

45.1

Figure 6/5: Before inserting the hand crank, it is necessaryto open the hole for it - turn the slide by meansof the key

121.1 Slide145 Double bit key

Figure 6/6: Movement of the withdrawable part between thetest/disconnected position and the serviceposition, clockwise up to the stop to the to theservice position and anti-clockwise for the test/disconnected position

121 Hand crank

Figure 6/7: Control wiring plug connector blocked to preventdisconnection with the withdrawable part in theservice position

10.1 Control wiring socket10.2 Control wiring plug32 Interlock

Figure 6/8: Handling of the mechanical circuit-breakeroperation in the switchgear panel door (non-standard equipment) with the withdrawable partin the service position

45.1 Mechanical pushbutton45.2 Knob

Page 50: Ma Unigear Dl(en) 1vcd003415

48/64

13

13.11

124.1124

10.1

12.1

43.3

12.2

42

14/14.1

124.2

124.3

124.1

124 13 13.11

124.4

13.12

Figure 6/9: Service truck engaged with the switchgear panel.Withdrawable part released for withdrawal withthe handles slid inwards

13 Withdrawable part13.11 Sliding handle124 Service truck

Figure 6/10: Withdrawable part standing on service truckand secured in the catches

13 Withdrawable part13.11 Sliding handle13.12 Catch (connected to sliding handle

13.11)124 Service truck124.1 Height adjuster124.4 Release lever for catch pin (124.3)

Figure 6/11: Positioning the service truck with the guide pinson the adjustable height bench top at the correctheight for approach to the switchgear panel, andengaging the catch

124.1 Height adjuster124.2 Guide pin124.3 Catch pin

Figure 6/12: View into the circuit-breaker compartment10.1 Control wiring socket12.1 Top shutter12.2 Lower shutter14 Earthing switch operating mechanism14.1 Drive shaft42 Right-hand travel rail43.3 Duct cover, top right

Page 51: Ma Unigear Dl(en) 1vcd003415

49/64

14.1

14.2

122

90

90.8 125

Figure 6/13: Preparation for operation of branch earthingswitch - press the slide downwards.

14.1 Hexagonal shaft of earthing switchoperating mechanism

14.2 Slide

Figure 6/14: Preparation for operation of branch earthingswitch - operating lever prepared for switchingon/off

122 Operating lever

Figure 6/15: Manual charging of HD4 circuit-breaker springs.

90 SF6 circuit-breaker type HD490.8 Charging lever

Figure 6/16: Voltage indicator, placed on door of controlcabinet. It is possible to use various types ofindicators from various manufacturers.

125 Voltage indicator

Page 52: Ma Unigear Dl(en) 1vcd003415

50/64

142

135

19.3

12.1

133.1

Figure 6/17: Shutter operating module, side view- actuatingbars must be bolted in the top position (foroperation of the bottom shutters) or in the bottomposition (for operation of the top shutters), asrequired (example version)

129 Shutter operating module129.1 Actuating bars (one pair), removable

Figure 6/18: Earthing at the bottom pins

12.1 Shutter19.3 Earthing terminal133.1 Earthing cable135 Warning label142 Earthing module

NoteThe drawing represents the hearting of the power cable throughcircuit-breaker compartment and it is applicable on double level, too.

Page 53: Ma Unigear Dl(en) 1vcd003415

51/64

133.1

Figure 6/19: Testing and earthing module with:

- Actuating bars, removable - top position for bottom shutter- bottom position for top shutter

- Contact arms, removable - bottom position for cable area- top position for busbar area

- Insulating plate with alternative mounting positions for cable or busbar earthing(turn through 180o for busbar earthing)

- Contact systems, replaceable for different contact pin diameters on the switchgear- Ball handles, removable, for voltage tests- Short-circuiting connection - can be replaced with ball handles

133.1 Earthing cable142 Testing and earthing module with manual mechanism142.1 Actuating bars (1 pair)142.2 Contact arms (3 pcs.)142.3 Contact systems142.4 Ball handles (3 pcs.)142.5 Insulating plate with 3 removable bushinghs142.6 Bushings142.7 Contact pin142.8 Short-circuiting connection, complete

Page 54: Ma Unigear Dl(en) 1vcd003415

52/64

38130

31.28

Figure 6/22: Lower shutter secured with padlock to preventunauthorized operation

38 Lever for shutter operation130 Padlock (customer component)

Figure 6/23: Manual emergency - off operation of the VM1vacuum circuit-breaker with magnetic actuator31.28 Emergency manual operating lever (forswitching off VM1 type circuit-breaker)

Note:During operation with the emergency operationlever 31.28, a mechanical resistance must beovercome following tension of the auxiliaryspring 31.29 and at the end of the turningmovement

Page 55: Ma Unigear Dl(en) 1vcd003415

53/64

128

145 147

31.28

31.29

122 121

90.8

Figure 6/24: Operating accessories

31.28 Emergency manual operating lever (for switching off VM1 type circuit-breaker)31.29 Auxiliary spring to secure the opening capacity (for VM1 type circuit-breaker)90.8 Charging lever (for HD4 type circuit-breaker)121 Hand crank (for moving the withdrawable part inside the panel)122 Operating lever (for earthing switch)128 Charging lever (for HD4 type circuit-breaker)145 Double bit key (for using the central catch and screw type door catch)147 Hand crank (for using the central catch or screw type door catch)

Page 56: Ma Unigear Dl(en) 1vcd003415

54/64

1) Under more demanding service conditions, we recommend shortening this interval appropriatel – also sect. 7.1 and 7.2.2) According to results of inspection.3) See the instruction manual of the circuit-breakers.

Activity performed According to section Time interval in years According to number

of switching operations

Inspection 7.2 4 1)

Servicing 7.3 4 2) 10 000 3)

Repair 7.4 As required As required

7. Maintenance

7.1 General

Maintenance serves to preserve trouble-free operation and achieve the longest possible working lifeof the switchgear. It comprises the following closely related activities:

Inspection: Determination of the actual condition

Servicing: Measures to preserve the specified condition

Repair: Measures to restore the specified condition

Note:

When carrying out all maintenance work, the regulations in the country of installation must be strictlycomplied with.

Maintenance work may only be performed in a careful manner by trained personnel familiar with thecharacteristics of the individual switchgear, in accordance with all relevant IEC safety regulations andthose of other technical authorities, and with other overriding instructions. It is recommended that ABBservice personnel be called in to perform the servicing and repair work detailed below.

The inspection and servicing intervals for some of the equipment/components (e.g. parts subjects towear) are determined by fixed criteria, such as switching frequency, length of service and number ofshort-circuit breaking operations. On the other hand, for other parts the length of the intervals maydepend, for example, on the different modes of operation in individual cases, the degree of loading,and also environmental influences (including pollution and aggressive air).

The following operating instructions must also be followed, together with this instruction manual in theindividual cases concerned:

Vacuum circuit-breaker: type VD4 647654

Vacuum circuit-breaker: type VD4- high-current BA 359/10E

Vacuum circuit-breaker with magnetic actuator mechanism: type VM1 1VCD 600182

SF6 circuit-breaker: type HD4 647016

Vacuum contactor: type V-Contact 647011

If necessary, further details can be taken from the technical documentation for the switchgearinstallation (including, for example, any special operating conditions agreed on).

7.1.1 Intervals for inspection, servicing and repairs

Time intervals for maintenance work to be carried out always depend on the operating conditions ofthe switchgear, and mainly on the mode of operation, the number of rated and short-circuit currentswitching operations, ambient temperature, pollution etc. We recommend carrying out the maintenancework at the following intervals:

Page 57: Ma Unigear Dl(en) 1vcd003415

55/64

7.2 Inspection

• Where necessary, the working area must be isolated and secured against reconnection in accordancewith the “Safety Regulations” specified by IEC and appropriate national standards before inspection.

• Correct condition of the switchgear should be monitored by regular inspections.

• Under normal operating conditions, inspection should be carried out once every four years byspecially trained professional electricians.

• Under abnormal operating conditions (including adverse climatic conditions) and/or specialenvironmental stresses (heavy pollution and aggressive atmosphere, among others), inspectionmay be necessary at shorter intervals.

• Inspection is primarily to carry out a visual check for grime, corrosion and moisture:

- Effects of high temperature on the main circuits,- Traces of partial discharge on the insulating material parts,- Traces of leakage current on the insulating material parts,- Surfaces of the contact systems.

• However, inspection must also to include correct mechanical/electrical operation of the followingparts: switching devices, actuating, interlocking, protection and signalling devices.

Caution: instrument transformer circuit.

• With regard to the switching devices, their separate Instruction manual should be followed.

• Check all switchgear accessories and auxiliary devices (e.g. storage batteries).

• No partial discharge must occur on the surfaces of equipment at operating voltage. This can, forexample, be detected by characteristic noises, a clearly perceptible smell of ozone, or visible glowingin the dark.

• Visually checking the contact system. We recommend to turn the contact system alternately in orderto clean the inner contact points of the contact system.

The contact points should be cleaned if signs of overheating (discoloured surface) are visible (seesection 7.4).

• If any irregular conditions are detected, then relative repair measures must be taken.

7.3 Servicing

If, during the course of an inspection in accordance with section 7.2, the need for cleaning measureshas been established, proceed as follows:

• Where necessary, the working area must be switched off and secured against reconnection inaccordance with the “Safety Regulations” specified by IEC and appropriate national standardsbefore cleaning.

• Clean the surfaces in general:- Weakly adhering dry dust deposits: with a soft dry cloth.- More strongly adherent grime: with mildly alkaline household cleanser or with ETHANOL F 25 M.

• Clean insulating surfaces and conductive components with ETHANOL F 25 M.

• Wipe down after cleaning, using clean water, and dry properly.

• Should partial discharges occur as a result of condensation, application of a thin silicone film on thesurface concerned is often effective as a temporary remedy. It is advisable to ask the ABB after-salesservice department for advice regarding permanent solutions to this type of unusual problem.

Page 58: Ma Unigear Dl(en) 1vcd003415

56/64

7.4 Repair

7.4.1 Switchgear in general

Repair of surface damage:

• Carry out repair work immediately after a defect has been discovered.

• Completely remove all rust from damaged paintwork areas on steel sheet and other steel parts bymechanical means, e.g. with a wire brush.

• Lightly grind the surrounding paint coat and carefully degrease the entire area. Then immediatelyapply an anti-rust primer and, after an appropriate hardening time, apply the top coat. Only usesuitable and compatible paint products.

• Apply the top coat in standard RAL 7035 colour, or the relevant special colour.

• Carefully remove any white rust on aluminium/zinc surfaces with a wire brush or cleaning pad, e.g.Scotch-Brite, and clean loosely adhering particles with a dry, non-fraying cloth. Next treat the cleanedparts with zinc spray or zinc powder paint and, finally, treat with aluminium spray for colour matching.

• Carefully remove any white rust from passivated operating parts and rust formation on phosphatisedparts with a wire brush or metal-free cleaning pad, e.g. Scotch-Brite, and clean with a dry cloth. Thengrease evenly (vaseline).

Switchgear in general:

• Follow the maintenance instructions in the manuals for individual equipment components.

• Check that the bolt connections at the contact points in the busbar system and the earth connectionsare tight, and that the contact system functions correctly.

• Where necessary, grease slide plates and bearings in the panel again or thoroughly clean them.Then grease them again with vaseline lubricant.

• Top up grease on contact areas in the contact system when corroded or otherwise as necessary,or, when lubrication is inadequate or missing, thoroughly clean the areas concerned and greasethem again with vaseline lubricant.

• Remove the contact system for thorough cleaning as described below (Figures 7/1, 7/3):- Slide in the two inner ring tension springs 4.4 facing the breaker pole to a position beside the other

two outer ring tension springs, thus releasing contact system 4.3, and remove the contact system- The contact pin of the contact system and the slot on the contact arm must be cleaned and greased.

Fit contact system back to front on the thin end of arbor 127 and slide it forwards onto the thickerpart of the shank.

- Fit arbor 127 onto the relative contact arm 4.2, slide the contact system 4.3 over onto the contactarm, and withdraw the arbor.

- Check that all contact fingers and ring tension springs have a perfect fit.

Note:

The set installation position of contact arms 4.2 must not be changed by undue use of force

Replacement of the contact pins when the surface is damaged:

(Figure 3/11)

After any required replacement of contact pins 4.1, the latter should be retightened using the sockethead bolts.

Thread Rated tightening torque ungreased

M10 46 Nm

M20 250 Nm

Page 59: Ma Unigear Dl(en) 1vcd003415

57/64

7.4.2 Replacement of complex functional groups (Figures 3/3, 3/11, 7/3 to 7/11)

Precise matching of functions for control, interlocking and signalling only permits replacement ofindividual components to a limited extent.

The following assemblies are prefabricated and tested at the works, maintaining high qualitystandards. In the case of faults, they must therefore be completely replaced.

1. Withdrawable assembly:

• Disconnect plug connector 10.3.

• Remove interlock rod 13.91 with pin 13.27 from the withdrawable assembly.

• For motor-operated withdrawable assemblies, remove the two socket head bolts (M4), which areaccessible from below the assembly.

• Remove the circuit-breaker from the withdrawable assembly (4 x M12 bolts).

• Mount the circuit-breaker on a new withdrawable assembly in the reverse order, using new circlipsand special pliers for pin 13.27.

• Check the setting of interlocking rod 13.91.

- Turn spindle 18 anti-clockwise to the stop for the disconnected position:The distance between lever 13.26 and cam 13.25 must be 2±1 mm.The distance between roller 13.24 and angle lever 13.92 must be 0.5 mm.

- Turn spindle 18 clockwise to the stop for the service position:The distance between lever 13.26 and cam 13.25 must be 2±1 mm.The distance between roller 13.24 and angle lever 13.92 must be 0.5 mm.

- Loosen bolts 13.91.2 or 13.92.1 for any necessary adjustment.

Note:

The auxiliary switches of the interchangeable groups are adjusted at the works.

When final installation of the earthing switch and operator takes place on site, it may be necessaryto carry out further precise adjustment of the auxiliary switch. In this case, the following should be takeninto account:

• There must be a run-on of 0.5 mm in the fully operated position before the plunger reaches the stop(for safety reasons).

• Auxiliary limit switch 11.4 for earthing switch ON must be operated immediately after the dead centreposition of the toggle spring mechanism has been reached in the closing process and the automaticquick-closing process has started.

• Auxiliary limit switch 11.3 for earthing switch OFF must

a) be operated on earthing switches with manual mechanisms during the opening movement ofslide 14.2 before half of the hexagonal shaft has become visible, or 1 mm before the tab of theslide makes contact with the armature of the de-energised locking magnet.

b) be operated on earthing switches with motor operator (no slide 14.2 fitted) immediately afterthe toggle spring mechanism has passed the dead centre position during rotation to the OFFposition.

Page 60: Ma Unigear Dl(en) 1vcd003415

58/64

7.5 Testing withdrawable parts (Figures 7/3, 7/4)

When functional tests are carried out on withdrawable parts, compliance with the conditions listedbelow should also be checked.

7.5.1 Motor-driven withdrawable parts (not standard)

Carry out testing of motor-driven withdrawable parts in the same way as for manually operatedwithdrawable parts:

• Switch off the auxiliary power (m.c.b.), since the motor could otherwise be braked electrically.

• Turn hand crank 121 (fig. 6/24) in the required direction.

• Ensure that the spindle nut is correctly lubricated.

Note

When the withdrawable part moves, the motor turns. The motor functions like a generator in thesecases, i.e. it can lead to reverse voltages in the terminals.

7.5.2 Checking correctness of dimensional settings (Figures 7/3, 7/9, 7/10)

1. The distance between lever 13.26 operated by tie-rod 13.91 and plastic cam 13.25 should be2±1 mm.

If adjustment is required, loosen the two bolts 13.91.1 and 13.91.2. Deviations from the specifiedvalue can have the following effects:

• Dimensions too large, locking system for the drive spindle deactivated.

• Dimensions too small, proper action of the electrical interlock no longer guaranteed.

2. The distance between roller 13.24 and angle lever 13.92 should be 0.5 mm when the circuit-breaker is closed.

If adjustment is required, loosen the two bolts 13.91.2 and 13.92.1.

7.5.3 Checking auxiliary switch settings on withdrawable parts (Figures 3/22, 7/3)

Compliance with the interlock conditions in the test/disconnected and service position areas is ensuredby position signalling switches S8 and S9 located in the withdrawable assembly and factory-set.

During testing operations, the withdrawable part must be moved by hand with the crank fitted and withthe motor power switched off.

1.Settings in the area of the test/disconnected position:

• Move the withdrawable part out of the test/disconnected position towards the service position witha few turns of the crank.

• Slowly move the withdrawable part back to the stop.

Auxiliary switch S8 must then switch over just before the stop is reached.

• Slowly insert the withdrawable part from the test/disconnected position towards the service positionuntil auxiliary switch S8 just operates.

In this position, it must still just be possible to move closing push-rod 13.2.1. For this test, the functionof the locking magnet Y0 must be deactivated manually.

This condition ensures that the electrical interlock takes effect before the mechanical interlock inthe motion sequence involved.

2.Settings in the area of the service position:

• Move the withdrawable part out of the limit position towards the test/disconnected position with afew turns of the crank.

• Slowly move the withdrawable part forward again to the stop. Auxiliary switch S9 must then switchover just before the stop is reached.

Page 61: Ma Unigear Dl(en) 1vcd003415

59/64

7.5.4 Checking the direction of rotation of the travel motors on motor-driven withdrawable parts

• Move the withdrawable part by hand into a central position between the test/disconnected positionand the service position.

• Remove the hand crank.

• Switch the auxiliary voltage for the travel motor on.

• Use the local electrical controls to check that the withdrawable part moves in the correct direction.

Caution:

Do not allow the withdrawable part to run up against a lock when the travel direction is incorrect! Switchthe motor power off immediately (the travel process functions electrically by a seal-in system with limitposition switch-off).

There may be a danger of injury when the door is open!

7.5.5 Testing interlock conditions (Figures 3/9, 3/22, 6/6 to 6/8, 7/7)

1. The withdrawable part must only be movable from the test/disconnected position into the serviceposition when the circuit-breaker is open and the earthing switch is open.

Check the following conditions individually:

• With the circuit-breaker closed, insertion of the withdrawable part towards the service positionmust be locked after only half a turn of the crank in the clockwise direction, and it must not bepossible to switch on the travel motor on motor-operated withdrawable parts.

• With the earthing switch closed, insertion of the withdrawable part towards the service positionmust be locked after only two clockwise turns of the crank, and it must not be possible to switchon the travel motor on motor-operated parts.

Use no force! Also see the note in chapter 6.2.1!

2. The withdrawable part must only be movable from the service position into the test/disconnectedposition with the circuit-breaker open.

Check this condition as follows:

• With the circuit-breaker closed, withdrawal movement of the withdrawable part must be lockedafter only half a turn of the crank in anti-clockwise direction, and it must not be possible to switchon the travel motor on motor-operated withdrawable parts.

3. Closing of the circuit-breaker must only be possible when the withdrawable part is in the definedtest/disconnected position or service position.

The control wiring plug 10.2 must previously have been inserted.

Check this condition as follows:

• It must not be possible to close the circuit-breaker with the withdrawable part in any positionbetween the test/disconnected position and the service position.

Enabling of switching when the withdrawable part moves into the service position is carried outelectrically by operation of auxiliary switch S9 in the withdrawable assembly, and slightly earliermechanically - this corresponds to a position approximately half a turn of the crank before the stop.

• For movement into the test/disconnected position, the same enabling conditions apply in the sameway, in this case by means of auxiliary switch S8 in the withdrawable assembly.

4. It must only be possible to open the circuit-breaker (manually) when the withdrawable part is in theservice position or test/disconnected position and the control voltage has failed.

Check this condition.

5. Withdrawable parts with order-related locking magnet Y0 may not be moved in case of control powerfailure, or when there is no control power. Do not forcibly move locked withdrawable parts! Thelocking magnet Y0 is only present on manually operated withdrawable parts.

Releasing the locking magnet Y0:

• Remove front plate 13.17.

• Disengage locking magnet Y0 by pulling the magnet armature,

• While doing so, turn crank 121 about one half turn (either direction of rotation is permissible).

The locking magnet is only active in the test position and service position. In intermediate positionsit has no effect.

6. Disconnection of the control wiring plug 10.2 as well as later insertion must be locked in thewithdrawable part service position.

Page 62: Ma Unigear Dl(en) 1vcd003415

60/64

Check this condition:

7. Operation of the earthing switch must only be possible when withdrawable part 13 is in the test/disconnected position or the removed position (subject to any additional electro-magnetic inter-locks in individual cases).

Check this condition:

• With the withdrawable part in the test/disconnected position, it must be possible to press slide 14.2,in front of the earthing switch operating shaft 14.1, downwards to the opening position. Theearthing switch can then be operated.

• With the slide pressed down, it must also be impossible to start the travel motor on motor-drivenwithdrawable parts.

• If the slide is pressed down slightly when the travel motor is running, the motor must thenautomatically switch off immediately.

The selected travel direction is continued by pressing the button.

It is only possible to press slide 14.2 down fully with a running travel motor when the latter is inthe start-up phase.

• When the withdrawable part is moved inwards towards the service position, pressing down of slide14.2 must be locked after only one and a half clockwise turns on the crank.

7.6 Tests on the panel

7.6.1 Auxiliary switch settings on the earthing switch (Figures 7/7, 7/8)

1.There must be a run-on of 0.5 mm in the fully operated position before the plunger reaches the stop(for safety reasons).

2.Auxiliary limit switch 11.4 (Q8S2) for earthing switch ON must be operated immediately after the deadcentre position of the toggle spring mechanism is reached in the closing process and the automaticrapid closing process has started.

3.Auxiliary limit switch 11.3 (Q8S1) for earthing switch OFF must

a) be operated on earthing switches with manual mechanisms during the opening movement of theslide 14.2 before half of the hexagonal shaft has become visible, or 1 mm before the tab of theslide makes contact with the armature of the de-energised locking magnet.

b) be operated on earthing switches with motor operators (no slide 14.2 fitted) immediately after thetoggle spring mechanism has passed the dead centre position during rotation to the OFF position.

Note:

Check the direction of rotation of the motor after repair work.

Do not allow the motor to run up against a lock if the direction of rotation is incorrect (also see section7.5.4).

7.7 Spare parts, auxiliary materials, lubricants

7.7.1 Spare parts

A spare parts list is available on request for procurement of spare parts. It basically includes movingparts and parts subject to wear. When parts are required, the serial number of the relative switchgearor switching device should always be quoted.

7.7.2 Auxiliary materials, lubricants

Lubricant:

• Vaseline

Halogen-free cleansers:

• ETHANOL F 25 M (for general cleaning)

Touch-up paint:

Standard colour RAL 7035

Page 63: Ma Unigear Dl(en) 1vcd003415

61/64

127.1 4.3127 4.6 4.2 (4.5) 4.3 4.4 127

13.2.1

13.26

13.3

13.92

13.24

Y 1

13.2.1

13.26

13.25

10.3

Figure 7/1: Fit the contact system back-to-front on the thinend of the arbor and slide it onto the thickershank area

4.3 Contact system127 Arbor127.1 Journal

Figure 7/2: Slide the contact system over from the arboronto the isolating contact arm and allow it toengage there

4.2 Contact arm4.3 Contact system4.4 Internal tension spring4.5 Hexagon socket head screw127 Arbor

Figure 7/3: Motorized withdrawable part with VD4 type cir-cuit-breaker in an intermediate position close tothe test/disconnected position, with fitted crankfor manual operation and circuit-breaker frontpanel removed

10.3 Control wiring plug connector of with-drawable assembly

13.2.1 ON push rod13.24 Roller13.26 Lever13.92 Angle lever

Figure 7/4: Detailed view of the opening and closingmechanism (VD4 type circuit-breaker)

13.2.1 ON push rod13.25 Plastic cam13.26 LeverY1 Blocking magnet

Page 64: Ma Unigear Dl(en) 1vcd003415

62/64

31.6 31.15 31.16 31.2631.9

31.27

31.6

31.5

31.10

31.26

11.3

11.4

14.2

14.3

14.1

Figure 7/5: View of the magnetic actuator mechanism withauxiliary systems, front plate removed (VM1type circuit-breaker)31.5 Mechanical operating cycle counter31.6 Mechanical switch position indicator31.9 Catch for emergency manual operation

lever31.10 Actuator31.26 Storage capacitor31.27 Circuit-breaker control unit

Figure 7/6: VM1 type circuit-breaker, switch positionindicator

31.6 Mechanical switch position indicator31.15 Sensor for VM1 circuit-breaker

OFF signal31.16 Sensor for VM1 circuit-breaker

ON signal31.26 Storage capacitor

Figure 7/7: Manual earthing switch mechanism with auxiliary switches, side cover removed

11.3 Auxiliary switch Q8S1 - earthing switch OFF11.4 Auxiliary switch Q8S2 - earthing switch ON14.1 Drive shaft (earthing switch)14.2 Slide14.3 Cam plate, adjustable

Page 65: Ma Unigear Dl(en) 1vcd003415

63/64

13.91

13.27

13.91.1

13.92.1

13.90

13.25

13.26

13.24

13.92 max

. 0.5

13.91.2

13.25

13.26

13.24

13.92

13.27

13.91.1

13.92.1

13.91

13.91.2

41.3

41.2

41.1

35.5

0.1

+0.

4

max

. 0.5

Figure 7/9: Detail in the area of a withdrawable part with VD4type circuit-breaker with travel motor, viewedfrom the left-hand side

13.24 Roller13.25 Plastic cam13.26 Lever13.27 Pin13.90 Travel motor13.91 Tie-rod13.91.1 Bolt13.91.2 Bolt13.92 Angle lever13.92.1 Bolt

Figure 7/10: Mechanical interlock, withdrawable assembly/VD4 type circuit-breaker, with manuallyoperated withdrawable part

13.24 Roller13.25 Plastic cam13.26 Lever13.27 Pin13.91 Tie- rod13.91.1 Bolt13.91.2 Bolt13.92 Angle lever13.92.1 Bolt

Figure 7/11: Mechanical interlock between the withdrawableassembly and the VM1 type circuit-breaker,setting the side lock

• Circuit-breaker in closed position35.5 Pawl in the withdrawable assembly41.1 Link to the actuator41.2 Side blocker41.3 Screw

Page 66: Ma Unigear Dl(en) 1vcd003415

64/64

RAW MATERIAL RECOMMENDED METHOD OF DISPOSAL

Metal material (Fe, Cu, Al, Ag, Zn, W, others) Separation and recycling

Thermoplasts Recycling or disposal

Epoxy resin Separation of metal material and the disposal of rest

Rubber Disposal

Oil as dielectric (transformer oil) Draining from equipment and further recycling or disposal

SF6 gas Discharging from equipment and further recycling or disposal

Packing material – wood Recycling or disposal

Packing material – foil Recycling or disposal

8. Product quality and environmental protection

The UniGear Double Level type panels are produced in compliance with the requirements ofinternational standards for the quality management system and environmental management system.In these fields, the excellent level is proved by quality certificates according to ISO 9001 and by theEMS according to ISO 14 001.

End of life of product

The ABB company is committed to complying with the relevant legal and other requirements forenvironment protection according to the ISO 14 001 standard.

The duty of company is to facilitate subsequent recycling or disposal at the end of product life.

During disposal of the product, it is always necessary to act in accordance with local legal requirementsin force.

We the following methods of disposal:

Disposal can either be carried out thermally in an incineration plant or by storing on a waste site.

Page 67: Ma Unigear Dl(en) 1vcd003415

1

Page 68: Ma Unigear Dl(en) 1vcd003415

ABB Power Techmologies S.p.A.Unità Operativa SaceVia Friuli, 4I-24044 DalmineTel: +39 035 395111Fax: +39 035 395874E-mail: [email protected]://www.abb.com

ABB s.r.o.Org. unit EJFVidenská 117, 619 00 BrnoCzech RepublicTel: +420 5 4715 2413, 1111Fax: +420 5 4715 2190E-mail: [email protected]://www.abb.com

∨∨∨∨∨

The

dat

a an

d ill

ustr

atio

ns a

re n

ot b

indi

ng.

We

rese

rve

the

right

to

mak

e ch

ange

sin

the

cou

rse

of t

echn

ical

dev

elop

men

t of

the

pro

duct

.

1VC

D00

3415

- R

ev.-

, en

- I

nstr

uctio

n M

anua

l -

2006

.01

(Uni

Gea

r D

oubl

e L

evel

)