M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2...

90
Installation Manual M3 Sonar ® Portable Hydrographic System

Transcript of M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2...

Page 1: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

Installation Manual

M3 Sonar®

Portable Hydrographic System

Page 2: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2
Page 3: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2January 2019 © Kongsberg Mesotech Limited

M3 Sonar PHSPortable Hydrographic System (PHS)

Installation ManualRelease 1.2

This manual provides you with the basic information required toinstall the Kongsberg M3 Sonar PHS. The information is intended forpersonnel with basic mechanical skills.

For information about the practical use of the product, refer to theKongsberg M3 Sonar PHS Operator manual.

Page 4: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

Kongsberg Mesotech Limitedwww.kongsberg.com

Document information• Product: Kongsberg M3 Sonar PHS• Document: Installation Manual• Document number: 922-00037011• Revision: 1.2• Date of issue: 15 January 2019

CopyrightThe information contained in this document remains the sole property of Kongsberg Mesotech Limited. Nopart of this document may be copied or reproduced in any form or by any means, and the informationcontained within it is not to be communicated to a third party, without the prior written consent ofKongsberg Mesotech Limited.

WarningThe equipment to which this manual applies must only be used for the purpose for which it wasdesigned. Improper use or maintenance may cause damage to the equipment and/or injury to personnel.You must be familiar with the contents of the appropriate manuals before attempting to operateor work on the equipment.

Kongsberg Mesotech disclaims any responsibility for damage or injury caused by improper installation,use or maintenance of the equipment.

DisclaimerKongsberg Mesotech Limited endeavours to ensure that all information in this document is correct andfairly stated, but does not accept liability for any errors or omissions.

Support informationIf you require maintenance or repair, contact your local dealer. You can contact us by phone at+1 604 464 8144, or by email at: [email protected]. If you need informationabout our other products, visit http://www.km.kongsberg.com/mesotech. On our website you will also finda list of our dealers and distributors.

Page 5: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 3

Table of contents

ABOUT THIS MANUAL.............................................................. 5M3 SONAR PHS........................................................................ 6System description .............................................................................................................7System diagram..................................................................................................................8System units .......................................................................................................................9

Sonar Processor ......................................................................................................10M3 Sonar Interface Unit.........................................................................................10Seapath 130 sensor unit ..........................................................................................10Sonar Head .............................................................................................................11Motion Reference Unit ...........................................................................................11Sound speed sensor ................................................................................................11Pole Mount .............................................................................................................12

Scope of supply................................................................................................................13Basic items provided with a standard delivery.......................................................13Additional required items.......................................................................................15

General safety rules..........................................................................................................15Installation requirements..................................................................................................16

Supply power requirements....................................................................................16Uninterruptible Power Supply (UPS) requirements ...............................................16

Support information .........................................................................................................16PREPARATIONS..................................................................... 17Installation summary........................................................................................................18Tools and equipment required for M3 Sonar PHS installation ........................................19ATTACHING THE SENSORS TO THE POLE MOUNT................... 20INSTALLING THE SEAPATH 130 SENSOR UNIT ...................... 26INSTALLING THE SONAR PROCESSOR ................................... 31CABLE LAYOUT AND INTERCONNECTIONS............................. 34Read this first ...................................................................................................................35Cable plan ........................................................................................................................36List of M3 Sonar PHS cables...........................................................................................37Installing the M3 Sonar PHS cables ................................................................................38

Connecting the Seapath 130 sensor unit to the Interface Unit ...............................38Connecting the underwater sensors to the Interface Unit.......................................39Connecting the Sonar Processor and power supply to the Interface Unit ..............42

Cable drawings and specifications ...................................................................................44

Installation Manual

Page 6: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

4 922-00037011/1.2

Sonar Head - SEA CON MINK-10-CCPL:Power, Ethernet, 1PPS, andSync ...................................................................................................................45

Motion Reference Unit - Seatex with 10m subsea bottle: Connector A................45SETTING TO WORK................................................................ 46Setting to work summary .................................................................................................47Verifying that the M3 Sonar PHS is ready for operational use........................................48Turning on the M3 Sonar PHS for the first time..............................................................49Configuring the M3 Sonar PHS for normal operation .....................................................51

Setting the Sonar Processor to High Performance .................................................52Defining the IP address on the Sonar Processor network adapter ..........................52Installing the M3 software......................................................................................53Configuring the M3 software .................................................................................54

Creating a backup with the M3 configuration and software installation .........................60Turning off the M3 Sonar PHS ........................................................................................61DRAWING FILE...................................................................... 62About the drawings in the drawing file............................................................................62Seapath 130 sensor unit outline dimensions ....................................................................63Motion Reference Unit outline dimensions .....................................................................64500 m Sonar Head outline dimensions ............................................................................65Sonar Head with integrated sound speed sensor outline dimensions ..............................68Sound speed sensor outline dimensions...........................................................................70M3 Sonar Interface Unit outline dimensions ...................................................................71MRU flange outline dimensions ......................................................................................72M3 Sonar flange outline dimensions ...............................................................................74Seapath sensor flange outline dimensions........................................................................75TECHNICAL SPECIFICATIONS................................................ 76Introduction to technical specifications ...........................................................................77Performance specifications ..............................................................................................77Mechanical specifications ................................................................................................79Power requirements .........................................................................................................80Environmental requirements............................................................................................81

M3 Sonar PHS

Page 7: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 5

About this manual

The purpose of this manual is to provide the information, procedures and basic drawingsrequired for the physical installation of the M3 Sonar PHS.

Target audience

The manual is intended for technical personnel. You are expected to have basicmechanical skills and familiarity with handling of sensitive electronic equipment. Youmust also be familiar with computer hardware, interface technology and installation ofelectronic and mechanical products.

We assume that you are familiar with the basic acoustic principles of sound in water.Familiarity with multibeam echo sounder and survey techniques are also recommended.

License information

The M3 software is included with the M3 Sonar PHS. Updates are available free ofcharge and can be downloaded from: http://www.km.kongsberg.com/mesotechsoftware.

Software version

This M3 Sonar PHS Installation Manual complies with M3 software version 2.3.

Registered trademarks

Observe the registered trademarks that apply.

Windows® is a registered trademark of Microsoft Corporation in the United States andother countries.

M3 Sonar® is a registered trademark of Kongsberg Mesotech Limited in the UnitedStates and other countries.

We want your feedback

We want to improve M3 Sonar PHS continuously. We also want our end-userdocumentation to be comprehensive and relevant. You can help. Please providecomments, suggestions or constructive criticism to our support office. You can contact usby phone at +1 604 464 8144, or by email at: [email protected].

About this manual

Page 8: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

6 922-00037011/1.2

M3 Sonar PHS

TopicsSystem description, page 7

System diagram, page 8

System units, page 9

Scope of supply, page 13

General safety rules, page 15

Installation requirements, page 16

Support information, page 16

M3 Sonar PHS Installation Manual

Page 9: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 7

System descriptionThe M3 Sonar PHS is a compact Portable Hydrographic System (PHS) for shallow-watersurvey.

System components:• Laptop computer• M3 Sonar Head• Seapath 130 sensor and Motion Reference

Unit (MRU)• Sound speed sensor• M3 Sonar Interface Unit• Pole Mount and mounting brackets

Key features• Frequency: 500 kHz• CW/LFM pulse• ZDA/1PPS time synchronization• Integrated GNSS signal and inertial

measurement• Real-time sound speed measurement at

transducer• IP56-rated splash-proof interface unit• Repeatable deployment pole mount with

safety breakaway

M3 Sonar PHS

Page 10: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

8 922-00037011/1.2

System diagramThe system diagram identifies the main components of the M3 Sonar PHS.

A Seapath 130 sensor unitB DGNSS Correction sourceC M3 Sonar Interface UnitD Motion Reference Unit (MRU)E Sound speed sensorF M3 Sonar HeadG M3 Sonar Processor to run M3 software and third-party acquisition softwareH Breakout box for power and Ethernet telemetryI Power supply

M3 Sonar PHS Installation Manual

Page 11: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 9

System units

TopicsSonar Processor, page 10

M3 Sonar Interface Unit, page 10

Seapath 130 sensor unit, page 10

Sonar Head, page 11

Motion Reference Unit, page 11

Sound speed sensor, page 11

Pole Mount, page 12

M3 Sonar PHS

Page 12: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

10 922-00037011/1.2

Sonar ProcessorThe Sonar Processor is the computer that controls the M3 Sonar PHS. It is a vital part ofthe M3 Sonar PHS Portable Hydrographic System (PHS).

In this publication, the computer is referred to as theSonar Processor.

The Sonar Processor runs the M3 software that managescommunication with the Sonar Head, performs allbeamforming and image processing and presents thesonar imagery. The Sonar Processor communicateswith the sonar through a standard Ethernet cable.

M3 Sonar Interface UnitThe M3 Sonar Interface Unit is a telemetry junction box which also provides powerto all the sensors.

The Seapath 130 sensor unit, Motion Reference Unit(MRU), Sound speed sensor, M3 Sonar Head, andSonar Processor all connect to the M3 Sonar InterfaceUnit. The connection ports are all located on the frontpanel.

An external power supply connects to the M3 SonarInterface Unit, providing power to all system units.

Seapath 130 sensor unitThe sensor unit runs the navigation software. This software combines the GNSS signaland the inertial measurements to determine accurate position, heading, attitude andheave signal. This software uses Kongsberg Seatex AS advanced true multi-referencealgorithms for real-time parallel processing of all available correction signals.

The sensor unit includesthe following.• Two GNSS receivers

and antennas• Cable that connects to the M3 Sonar Interface Unit• Mounting bracket

M3 Sonar PHS Installation Manual

Page 13: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 11

Sonar HeadThe Sonar Head includes transmit and receive transducers and the electronics to generatethe transmit pulse and digitize the received signal.

Two Sonar Head models are available for use with the M3 SonarPHS: model number 922-20220000 (Ethernet with Sync and1PPS), and model number 922-20240000 (with an integratedsound speed sensor). In the M3 Sonar PHS, the Sonar Headis attached to the bottom of the Pole Mount. The Sonar Headconnects to the M3 Sonar Interface Unit through a head cablewith 100Mbps Ethernet and 1PPS time synchronization.

Note

The M3 Sonar Head’s black polyurethane transducer is delicate.Always keep the Guard Ring and protective cover over thetransducer during installation and storage.

Motion Reference UnitThe Motion Reference Unit (MRU) is specially designed for high precision motionmeasurements in marine applications.

The MRU is mounted in a lightweight subsea bottle, rated 10 metres.The MRU cable connects to the M3 Sonar Interface Unit to integrate withSeapath 130 GNSS sensor.

The Motion Reference Unit is very sensitive to impacts. Be careful notto drop the MRU. The electronics inside will be damaged and need to bereturned to the manufacturer for repair.

Sound speed sensorIn order to ensure accurate measurements, a dedicated sound speed sensor is positionedclose to the Sonar Head.

The sound speed sensor cable connects to the M3 Sonar InterfaceUnit to output the real-time sound speed to the M3 software. If thesound speed sensor is integrated into the Sonar Head, a dedicatedcable connected to the M3 Sonar Interface Unit is not required.

M3 Sonar PHS

Page 14: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

12 922-00037011/1.2

Pole MountThe M3 Sonar PHS Pole Mount provides precise and easy bolt on/off of flanges forall the sensors.

Key features:• Adjustable and repeatable with no need to re-calibrate• Quick to set up and easy to use• Safe and audible release of sensor during collision or snag with submerged hazard• Adjustable heading and depth with indexing

The Pole Mount parts include the following.• The GPS Mast for mounting the Seapath 130 sensor unit.• The Compact Mount for attaching to your gunwale.• The Z Pole, MRU flange, and M3 Sonar flange for mounting the Sonar Head, Motion

Reference Unit, and sound speed sensor.• The X Pole for connecting the Z Pole to the Compact Mount.

M3 Sonar PHS Installation Manual

Page 15: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 13

Scope of supply

TopicsBasic items provided with a standard delivery, page 13

Additional required items, page 15

Basic items provided with a standard deliveryTo assemble a complete M3 Sonar® Portable Hydrographic System (PHS), you will needa set of system units. The main units required are provided with the standard delivery.Other required units may be purchased from Kongsberg Mesotech or obtained locally.Some units are optional.

When you unpack the parts provided with the M3 Sonar PHS delivery, make sure thatthe following items are included.

M3 Sonar PHS

Page 16: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

14 922-00037011/1.2

Item Part number In the box

Pole Mount 803-01620000 Compact MountX Pole, Z Pole, and GPS MastShear BlockX-Pole WrenchAdditional kits and clamp

Sonar Head 922-20220000 M3 Sonar HeadAccessory kitDocumentationCable (for use with the M3 Sonar InterfaceUnit)

Sonar Head with integratedsound speed sensor

922-20240000 M3 Sonar HeadAccessory kitDocumentationCable (for use with the M3 Sonar InterfaceUnit)AML SVT Xchange sound speed sensor

M3 Sonar Interface Unit 922-60090001 Interface UnitAccessory kit

Seapath 130 sensor unit withMRU-3

803-10670000

Seapath 130 sensor unit withMRU-H

803-10680000

Seapath 130 sensor unitMounting bracketSpider cableMotion Reference Unit in subsea bottleDummy plugUSB with software and documentationCables (for use with the M3 Sonar InterfaceUnit)

Sonar Processor laptop 922-10010000 LaptopPower cords and supplyMouseUSB flash drive with software anddocumentation

Third-party acquisition software 804-00250000 HYPACK Survey & HYSWEEP

Sound speed sensor 803-10760000 Valeport miniSVSPigtail interface leadCable (for use with the M3 Sonar InterfaceUnit)Operating manual

Note

When you order the M3 Sonar PHS, several choices are available. For example, for theMotion Reference Unit, you can choose either an MRU-3 or MRU-H. For the SonarHead, you can choose a model with an integrated sound speed sensor or a Sonar headplus an external sound speed sensor. The exact items and parts you receive will dependon your order.

Operational software

Operational software is provided on a suitable media. The operational software isinstalled on the Sonar Processor, and ready for use.

M3 Sonar PHS Installation Manual

Page 17: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 15

End user documentation

End-user documentation is provided on paper and/or digital formats.

Additional required itemsAdditional items are available for the M3 Sonar PHS. Some are required for M3 SonarPHS operation. These items must be added to the M3 Sonar PHS for full operationalfunctionality. The additional items can be provided by Kongsberg Mesotech. You canorder them with the other basic M3 Sonar PHS items.You can also purchase these itemsfrom your dealer, agent or local supplier.

Sound velocity profiler

A sound velocity profiler must be used to measure the in-water sound speed profile of thewater column to correct for ray bending during data post-processing.

General safety rulesThe following safety precautions must be followed at all times during installation andmaintenance work.

WARNING

The voltages used to power this equipment are potentially lethal. You must neverwork alone on high-voltage equipment!

• You must always switch off all power before installation or maintenance work onthe M3 Sonar PHS.Use the main circuit breaker, and label the breaker with a warning sign that informsothers that maintenance or installation work is in progress on the system.

• For safety reasons, two persons must always be present during troubleshooting withpower ON.

• Read and understand the applicable first aid instructions related to electric shock.• Whenever maintenance is in progress, it is essential that a first aid kit is available, and

that all personnel are familiar with the first aid instructions for electrical shock.

M3 Sonar PHS

Page 18: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

16 922-00037011/1.2

Installation requirements

TopicsSupply power requirements, page 16

Uninterruptible Power Supply (UPS) requirements, page 16

Supply power requirementsObserve the general requirements related to the supply power.The supply voltage to the equipment must kept within ±10% of the installation’s nominalvoltage. Maximum transient voltage variations on the main switchboard’s bus-bars arenot to exceed -15% to +20% of the nominal voltage (except under fault conditions).

Uninterruptible Power Supply (UPS) requirementsObserve these requirements related to the Uninterruptible Power Supply (UPS).

The Uninterruptible Power Supply (UPS) must have the capacity to independentlymaintain power to the M3 Sonar PHS for a minimum of 10 minutes.

This ensures that the M3 Sonar PHS can be turned off in a controlled manner in theevent of a power failure.

Support informationIf you need technical support for your M3 Sonar PHS you must contact your local dealer,or our support department.

If you require maintenance or repair, contact your local dealer. You can contact us byphone at +1 604 464 8144, or by email at: [email protected] you need information about our other products, visit http://www.km.kongs-berg.com/mesotech. On our website you will also find a list of our dealers anddistributors.

M3 Sonar PHS Installation Manual

Page 19: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 17

Preparations

TopicsInstallation summary, page 18

Tools and equipment required for M3 Sonar PHS installation, page 19

Preparations

Page 20: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

18 922-00037011/1.2

Installation summaryInstallation of the M3 Sonar PHS requires a number of specific procedures and softwaresettings. Two people are required for this installation.

Context

An overall installation procedure is provided.

Note

In order to obtain maximum safety and M3 Sonar PHS performance, it is very importantthat the installation procedures in this manual are complied to. You must do the tasksin the order they are described.

Procedure1 Unpack all the system units.2 Install the Pole Mount on the vessel according to the USM Pole Mount manual

(included on the USB flash drive).3 Mount the Motion Reference Unit onto the MRU flange.4 Mount the Sonar Head and sound speed sensor onto the M3 Sonar flange.

Note

The MRU flange and M3 Sonar flange are custom mounting brackets designed toattach your sensors onto the Pole Mount.

5 Mount the Seapath 130 GNSS sensor onto the Seapath sensor flange on top ofthe Pole Mount mast.

6 Install the M3 Sonar Interface Unit and make all cable connections.7 Install the Sonar Processor.8 Lower the pole with the underwater sensors into the water.9 Perform initial power on and system check.

M3 Sonar PHS Installation Manual

Page 21: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 19

Tools and equipment required for M3 SonarPHS installationAll necessary tools, instruments and consumables must be ready at hand prior tocommencing M3 Sonar PHS installation.

You must be equipped with a standard set of tools. This tool set must comprise thenormal tools for electronic and electromechanical tasks. This includes differentscrewdriver types, pliers, spanners, a cable stripper, a soldering iron, etc. Each toolmust be provided in various sizes. We recommend that all tools are demagnetized toprotect your equipment.

Specific fasteners and consumables you will need for the M3 Sonar PHS installation areincluded in the supplied accessory kits.

The following tools and items are required for the M3 Sonar PHS installation and are notincluded in the standard delivery. You must purchase these items locally.• Allen keys, wrenches and screwdrivers — both metric and imperial.• A short length of garden hose to protect the cables from chafing• Silicone-based o-ring lubricant, such as Dow Corning DC4 (MS4) or equivalent• Marine-grade anti-seize product, such as Never Seez or equivalent.• A silicone spray or lubricant that does not make plastic swell, such as Boeshield

T-9 or equivalent.• Velcro wraps or electrical tape• A utility knife• A recovery rope

Preparations

Page 22: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

20 922-00037011/1.2

Attaching the sensors to thePole Mount

The M3 Sonar PHS Pole Mount comes with two custom mounting brackets for theunderwater sensors — the MRU flange and the M3 Sonar flange. The Motion ReferenceUnit is mounted on the MRU flange. The Sonar Head and sound speed sensor aremounted on the M3 Sonar flange.

Prerequisites• To install the M3 Sonar PHS, you must have basic mechanical skills. At least two

people must do the installation together.• Install the Pole Mount on the vessel according to the USM Pole Mount manual

(included on the USB flash drive).

Procedure1 For easier installation of the sensors, use the Pole Mount’s hinge function.

a Make sure the hinge bracket (A) is installed so that the Pole Mount is tilted 90degrees up and positioned above the gunnel.

b Using a socket wrench, turn the bolt (B) counterclockwise to disengage theshear block so that you can freely move the Z-pole.

c Pivot the bottom of the Z-pole towards the deck so that you can access itcomfortably.

M3 Sonar PHS Installation Manual

Page 23: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 21

2 If required, assemble the MRU flange using the provided fasteners.

3 Attach the MRU flange to the Z-pole with the three provided fasteners (!).The provided fasteners include two small screws and one large locking screw.

Attaching the sensors to the Pole Mount

Page 24: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

22 922-00037011/1.2

4 Attach the Motion Reference Unit to the MRU flange with the four providedfasteners, including two washers for each fastener.

Important

Make sure that the MRU is oriented according to the mounting angles configuredin the Seapath operator software. Use the X and Y arrow indications etched ontothe MRU housing to correctly orient the device. In the default configuration, whendeployed, X points toward the direction of the vessel’s movement (usually thebow) and Y points starboard.

5 Attach the M3 Sonar flange to the Z-pole with the four flat-head metric fasteners.a If you are going to install a sound speed sensor onto the M3 Sonar flange,

attach the sound speed sensor clamp onto the flange with two fasteners (!).

Orient the M3 Sonar flange so that the sound speed sensor will face awayfrom the vessel hull.

M3 Sonar PHS Installation Manual

Page 25: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 23

b If you are using a Sonar Head with an integrated sound speed sensor, attach theM3 Sonar flange without the sound speed sensor clamp.

6 Attach the Sonar Head to the M3 Sonar flange with the four provided fasteners,including two washers for each fastener.

Caution

Be aware the Motion Reference Unit and the M3 Sonar Head are easily damagedthrough mishandling – in particular the polyurethane face of the Sonar Headtransducer.

a Make sure that the Sonar Head connector points toward the stern of the vessel(when deployed).

Attaching the sensors to the Pole Mount

Page 26: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

24 922-00037011/1.2

b If you are using a Sonar Head with an integrated sound speed sensor,underwater sensor installation is complete.

7 If you are using a standalone Sonar Head (without an integrated sound speedsensor), attach the sound speed sensor to the M3 Sonar flange with four fasteners.

Result

The Sonar Head, Motion Reference Unit, and sound speed sensor are attached to thePole Mount.

Tip

As an extra precaution, tie a recovery rope to the bottom of the Pole Mount. It is safe totie the rope to the MRU flange.

Further requirements

You are now ready to install the Seapath 130 sensor unit.

M3 Sonar PHS Installation Manual

Page 27: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 25

Related topicsMRU flange outline dimensions, page 72M3 Sonar flange outline dimensions, page 74

Attaching the sensors to the Pole Mount

Page 28: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

26 922-00037011/1.2

Installing the Seapath 130sensor unit

The M3 Sonar PHS Pole Mount comes with a custom mounting bracket for the Seapath130 sensor unit, called the Seapath sensor flange. The Seapath 130 sensor unit ismounted onto this flange, which is attached to the top of the GPS Mast.

Prerequisites

Make sure that the Pole Mount is installed and that the Sonar Head, Motion ReferenceUnit, and sound speed sensor are attached to the Pole Mount

M3 Sonar PHS Installation Manual

Page 29: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 27

Procedure1 Lower the Pole Mount into a deployment position.

a Stabilize the Z-pole with a block and tackle set or by employing multiplepeople to hold the pole in place.

b Remove the hinge bracket (A) by unfastening the two long bolts and two shortbolts securing the bracket in place.

c Using a socket wrench, turn the bolt (B) clockwise to engage the shear blockso that the Z-pole is locked in place.

d Use a block and tackle set or multiple people to safely pivot the Z-pole downinto position so that the Compact Mount is aligned with its base plate.

e Secure the Compact Mount to the base plate using the four long bolts supplied.

Installing the Seapath 130 sensor unit

Page 30: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

28 922-00037011/1.2

2 Attach the Seapath sensor flange (A) onto the GPS Mast (B) with the four providedfasteners (1/2"-13 screws).

3 Attach the GPS Mast to the Seapath 130 sensor unit.a Place the Seapath 130 sensor unit upside down on the deck.b Remove the mounting bracket from the Seapath 130 sensor unit by unfastening

the four bolts (!) attaching the bracket to the sensor unit.

M3 Sonar PHS Installation Manual

Page 31: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 29

c Attach the Seapath sensor mounting bracket (A) to the Seapath sensor flange(B) using the four provided fasteners (5/16"-18 screws with washers).

d Flip the GPS Mast assembly upside down and attach itonto the Seapath 130 sensor unit.

Re-fasten the four bolts (!) attaching the mountingbracket to the sensor unit.

4 Install the GPS Mast and Seapath 130 sensor unit onto theCompact Mount.a Align the Seapath 130 sensor unit so that the unit is

oriented alongships (parallel with the vessel’s heading).b Make sure the cable exiting the Seapath 130 sensor unit

faces aft (back toward the stern).c Attach the GPS Mast to the Compact Mount with the

provided fasteners (3/8"-16 screws with washers).

Installing the Seapath 130 sensor unit

Page 32: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

30 922-00037011/1.2

Result

The underwater sensors and Seapath 130 sensor unit have been installed on the PoleMount.

Related topicsSeapath sensor flange outline dimensions, page 75

M3 Sonar PHS Installation Manual

Page 33: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 31

Installing the SonarProcessor

The Sonar Processor is the computer that controls the M3 Sonar PHS. It is a vital part ofthe M3 Portable Hydrographic System (PHS).

Prerequisites

A suitable location for the computer must be defined prior to installation. This computeris intended to be installed inside in an area suitable for extended human habitation.Choose a position to fit the available cable lengths between the computer and the otherunits it connects to.

Caution

Ensure electronic components are free from condensation before turning on.Condensation can occur when transitioning from a cool air-conditioned environment to ahot and humid environment – such as outside on an open boat. These parts shouldalso be protected from coming into contact with water, sea-spray, etc. Failure to do socould result in component failure.

Context

The Sonar Processor uses a high-quality commercial-off-the-shelf laptop computerworkstation. Contact your Kongsberg Mesotech representative for information about thecurrent model that is delivered with your M3 Sonar PHS.

Installing the Sonar Processor

Page 34: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

32 922-00037011/1.2

A Power cord for EuropeB Power cord for the UKC Power supply and North American power cordD Sonar Processor laptopE MouseF Software and documentation on a USB flash drive

For installation of a commercial computer, refer to the manual supplied by themanufacturer.

Note

Make sure that the chosen computer meets the M3 Sonar PHS requirements. The designand construction must allow for marine use, and the computer must be able to withstandthe movements and vibrations normally experienced on a vessel. Verify that you haveeasy access to cables and connectors, and that the computer can be installed in a safeand secure way.

Standard office computers may not be well fitted for maritime use. The motions andvibrations experienced on a vessel may reduce the computer lifetime considerably. Whileinstalling a commercial computer, use your common sense to improve the installationmethod suggested by the manufacturer.

M3 Sonar PHS Installation Manual

Page 35: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 33

Procedure1 Set up the Sonar Processor in the location available for the operator workstation.

Tip

Covering the laptop computer from direct sunlight with a sunshade will make thedisplay easier to see.

a Make sure that adequate ventilation is available to avoid overheating.b Make sure that enough space is made available for maintenance purposes.c Make sure that the installation method allows for the physical vibration,

movements and forces normally experienced on a vessel.2 Select the power cord with the appropriate local plug and connect it to the AC

to DC Sonar Processor power supply.3 Connect the AC to DC power supply to the Sonar Processor.4 Connect the mouse to a USB port on the Sonar Processor.

Note

When you connect the cables, make sure that they are all properly secured, and ableto withstand the vibration and movements of the vessel.

Result

The M3 Sonar Processor is set up in a suitable location with the power supply andmouse connected.

Installing the Sonar Processor

Page 36: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

34 922-00037011/1.2

Cable layout andinterconnections

TopicsRead this first, page 35

Cable plan, page 36

List of M3 Sonar PHS cables, page 37

Installing the M3 Sonar PHS cables, page 38

Cable drawings and specifications, page 44

M3 Sonar PHS Installation Manual

Page 37: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 35

Read this firstDetailed information about cable specifications, termination and connectors is provided.Unless otherwise specified, all cables are supplied by Kongsberg Mesotech as a partof the M3 Sonar PHS delivery.

Kongsberg Mesotech Limited accepts no responsibility for damage to the system, orreduced operational performance, when this is caused by improper wiring.

Note

Before you install or maintain the M3 Sonar PHS cables, make sure that the AC mainscircuit breaker for the system is switched off.

Cable layout and interconnections

Page 38: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

36 922-00037011/1.2

Cable plan

A Seapath 130 sensor unitB Motion Reference Unit (MRU)C M3 Sonar HeadD Sound speed sensorE Pole MountF M3 Sonar Interface UnitG M3 Sonar Processor to run M3 software and third-party acquisition softwareH Breakout box for power and Ethernet telemetryI Power supply

Related topicsList of M3 Sonar PHS cables, page 37

M3 Sonar PHS Installation Manual

Page 39: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 37

List of M3 Sonar PHS cablesA set of cables is required to connect the M3 Sonar PHS units to each other, and to therelevant power source(s).Cable Type From To

C1 Fixed-length cable Seapath 130 sensor unit M3 Sonar Interface Unit

C2 20-ft cable M3 Sonar Head M3 Sonar Interface Unit

C3 20-ft cable Sound speed sensor M3 Sonar Interface Unit

C4 Fixed-length cable Motion Reference Unit (MRU)(Connector A)

M3 Sonar Interface Unit

C5 50-ft Deck cable M3 Sonar Interface Unit Breakout box for power andEthernet telemetry

C6 Ethernet cable Breakout box for power andEthernet telemetry

M3 Sonar Processor

C7 AC power cable Breakout box for power andEthernet telemetry

Power supply

C2, C3, and C4 are threaded through the top cut-out in the trailing foil edge of the PoleMount’s Z-pole. If you have a Sonar Head with an integrated sound speed sensor, C3 isnot necessary.

Note

Make sure dummy plugs are installed on all open connectors. For example, Connector Bon the MRU.

Related topicsCable plan, page 36

Cable layout and interconnections

Page 40: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

38 922-00037011/1.2

Installing the M3 Sonar PHS cables

TopicsConnecting the Seapath 130 sensor unit to the Interface Unit, page 38

Connecting the underwater sensors to the Interface Unit, page 39

Connecting the Sonar Processor and power supply to the Interface Unit, page 42

Connecting the Seapath 130 sensor unit to the Interface UnitUse the six-metre (20-foot) cable included with the Seapath 130 sensor unit equipmentcase to connect it to the M3 Sonar Interface Unit.

Prerequisites• The Seapath 130 sensor unit must be mounted on the GPS Mast of the Pole Mount.• Cable ties or electrical tape

Procedure1 Connect the one-metre cable exiting the sensor unit with the supplied six-metre

cable by joining the two cable connectors (A).

M3 Sonar PHS Installation Manual

Page 41: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 39

2 Connect the six-metre cable to the port labelled Seapath Ant. on the InterfaceUnit (B).

Tip

Attach the cable to the GPS Mast with electrical tape or a cable tie.

Connecting the underwater sensors to the Interface UnitAll underwater sensors, including the M3 Sonar Head, Motion Reference Unit (MRU),and Sound speed sensor connect to the M3 Sonar Interface Unit. Refer to the cable plansand the list of cables. Detailed information about cable specifications, termination andconnectors are provided in the relevant cable drawings.

Prerequisites• Cable ties or electrical tape• Silicone-based o-ring lubricant, such as Dow Corning DC4 (MS4) or equivalent• A utility knife• A short length of garden hose to protect the cables from chafing• You will need the dummy plug from the MRU equipment case

Caution

• All cable connectors should be kept dry during assembly and mating.

• Ensure the cables are not damaged during installation and deployment. Bending thecables excessively may weaken or break them.

Procedure1 Locate and unroll the cables that attach to the MRU, Sonar Head, and sound speed

sensor.

Cable layout and interconnections

Page 42: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

40 922-00037011/1.2

Note

If you are using a Sonar Head with an integrated sound speed sensor, a cable forthe sound speed sensor is not necessary.

2 Feed the cables through the top cut-out in the trailing foil edge of the Pole Mount’sZ-pole.

3 Pull each cable out from the opening at the bottom of the trailing foil edge, oneat a time.

4 If necessary, connect the sound speed sensor cable (!).5 Connect the 8-pin cable to the connector labelled Connector A on the MRU (A).

a Before mating, make sure that the MRU and MRU cable connector are clean.If not, clean the connector with compressed air, a lint-free cloth, or swab.

b Apply a small amount of o-ring grease to the rubber on the Motion ReferenceUnit’s cable connector before mating.

Important

To ensure the connectors remain water resistant, use a silicone-based o-ringgrease — do not use a petroleum-based lubricant.

c Mate and fully secure the locking ring so that it is hand tight.

Hold the cable connector while tightening the engaging nut. Over-tighteningmay damage the connector.

d Install the dummy plug into the other connector on the MRU.

M3 Sonar PHS Installation Manual

Page 43: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 41

Caution

The Motion Reference Unit can be damaged if it is turned on without thedummy plug installed.

6 Connect the 10-pin cable connector to the Sonar Head (B).a Before mating, inspect the cable connector and the Sonar Head connector.

Make sure that the connectors are clean and that the pins are not bent, broken,or corroded. Make sure that an o-ring is properly installed in the cableconnector.

b Mate and fully secure the locking ring so that it is hand tight.

Rotate the connector to align the key when mating. Hold the cable connectorwhile tightening the engaging nut. When the connector is tight, there should beno gap between the engaging nut and the Sonar Head connector.

7 Connect the underwater sensor cables to the Interface Unit.a If necessary, connect the sound speed sensor cable to the port labelled SVS (A).b Connect the MRU cable to the port labelled Seapath MRU (B).c Connect the Sonar Head cable to the port labelled Sonar (C).

8 Attach anti-chafing protection to the cables to prevent damage during use.a Using the utility knife, cut a slit down one side of a short section of garden hose.b Tape the garden hose to the cables near the top cutout in the trailing foil edge

of the Pole Mount’s Z-pole.c You may also wish to tape down the cables at the bottom of the Pole Mount to

minimize cable movement during the survey.

Cable layout and interconnections

Page 44: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

42 922-00037011/1.2

Connecting the Sonar Processor and power supply to theInterface UnitThe Sonar Processor and power supply connect to a breakout box. The breakout boxconnects to the M3 Sonar Interface Unit with a 50-foot deck cable.

Prerequisites• The Sonar Processor, breakout box, and power supply are designed for indoor use and

should be installed at the operator station (wheelhouse).• Make sure that the Pole Mount’s Z-pole is oriented vertically with the main system

units deployed underwater.

Caution

Do not turn on the system if the Z-pole is oriented horizontally with the main systemunits out of the water.

Procedure1 Locate the 50-foot deck cable.2 Connect the deck cable to the port labelled Deck Cable on the Interface Unit (!).

3 Unroll the cable into the operator station and connect the other end to the side ofthe breakout box.

Tip

Route the deck cable out of the way so that it is not a tripping hazard. If possible,tape down or cover the cable.

M3 Sonar PHS Installation Manual

Page 45: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 43

4 Connect the Ethernet cable to the Ethernet port (A) on the breakout box.5 Connect the other end of the Ethernet cable to the RJ45 network socket on your

Sonar Processor.6 Connect the power supply cable to the port on the right side (B) of the breakout box.

Note

The port on the left side of the breakout box is reserved for other use.

Result

Hardware installation and cable interconnections are complete.

Cable layout and interconnections

Page 46: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

44 922-00037011/1.2

Cable drawings and specifications

TopicsSonar Head - SEA CON MINK-10-CCPL:Power, Ethernet, 1PPS, and Sync, page 45

Motion Reference Unit - Seatex with 10m subsea bottle: Connector A, page 45

M3 Sonar PHS Installation Manual

Page 47: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 45

Sonar Head - SEA CON MINK-10-CCPL:Power, Ethernet, 1PPS, and SyncThis rugged cable is intended for underwater use and includes both power and Ethernettelemetry connections for the Sonar Head. The underwater connector is a dry-mate styleand must be mated or unmated at the surface.Pin Functions• Pin 1: +V (20 AWG)• Pin 2: TX+ (white/orange)• Pin 3: 1PPS (white/blue)• Pin 4: TX- (white)• Pin 5: RX+ (white/green)• Pin 6: 1PPS GND (white)• Pin 7: SYNC (white/brown)• Pin 8: RX- (white)• Pin 9: SYNC GND (white)• Pin 10: -V (20 AWG)

Motion Reference Unit - Seatex with 10m subsea bottle:Connector A

Pin Signal (Seapath compatible)• Pin 1: POWER -• Pin 2: POWER +• Pin 3: COM1_IN_A -• Pin 4: COM1_IN_B +• Pin 5: COM1_OUT_B +• Pin 6: COM1_OUT_A -• Pin 7: CGND (ground ref for XIN)• Pin 8: XIN (Seapath 1PPS)

Cable layout and interconnections

Page 48: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

46 922-00037011/1.2

Setting to work

TopicsSetting to work summary, page 47

Verifying that the M3 Sonar PHS is ready for operational use, page 48

Turning on the M3 Sonar PHS for the first time, page 49

Configuring the M3 Sonar PHS for normal operation, page 51

Creating a backup with the M3 configuration and software installation, page 60

Turning off the M3 Sonar PHS, page 61

M3 Sonar PHS Installation Manual

Page 49: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 47

Setting to work summaryOnce all the hardware units have been installed, and all the cables have been connected,the M3 Sonar PHS can be turned on for the first time, and set to work.

Prerequisites• All M3 Sonar PHS hardware units have been installed according to the relevant

instructions..• All system cables have been installed.• All connections have been made.• All operating power is available.• All peripheral devices that shall communicate with the M3 Sonar PHS are available

and operational.• All relevant personnel and tools are available.

Procedure1 Verify that the M3 Sonar PHS is ready for operational use.

a Verify that all hardware have been installed correctly.b Verify that all cables have been connected correctly.

2 Turn on the M3 Sonar PHS for the first time.3 Configure the M3 Sonar PHS for operational use.

a If required, configure the network adapter.b Set the mounting offsets according to the number of poles you are using.c Set the sound speed.

4 Make sure that the M3 Sonar PHS is fully operational

To make sure that the M3 Sonar PHS fulfils all operational and functionalrequirements, specific tests are provided.

5 Create a backup with the M3 Sonar PHS configuration and software installation.

Once all M3 Sonar PHS configuration and testing have been finalized, it is goodpractice to back up the configuration data and software installation.

Setting to work

Page 50: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

48 922-00037011/1.2

Verifying that the M3 Sonar PHS is ready foroperational useThe M3 Sonar PHS relies on communication between each system unit, and between theM3 Sonar PHS and external devices. It is very important that the hardware, cables, andsoftware are properly installed.

Prerequisites• All M3 Sonar PHS hardware units have been

installed according to the relevant instructions.• All cables have been connected.• All operating power is available.

Procedure1 Make sure that the operating power is

correct.

The system operates on 24 VDC power (anAC to DC power adapter is provided).

2 Make sure that the Pole Mount is orientedin a vertical position.

Caution

Do not turn on the system if the Z-pole isoriented horizontally with the main systemunits out of the water.

3 For each cable that is in used on the M3Sonar PHS, make sure of the following.a The cable has been installed.b The connections made at each end of

the cable are correct.c The cables are secured and do not

represent a trip hazard.4 Make sure that the Motion Reference Unit

(MRU) cable is connected to Connector Aand a dummy plug is installed on Connector B on the MRU.

5 Remove the protective cover from the Sonar Head before sonar operation.6 Make sure that the Sonar Processor has been set up in the correct location.

M3 Sonar PHS Installation Manual

Page 51: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 49

Note

The Sonar Processor, breakout box, and power supply are designed for indoor useand should be installed at the operator station (wheelhouse).

7 Make sure that the required software packages have been installed on your SonarProcessor, including the Seapath Operator Software, M3 software, and third-partyacquisition software.

Further requirements

You are now ready to turn on the M3 Sonar PHS for the first time.

Turning on the M3 Sonar PHS for the firsttimeTurn on the M3 Sonar PHS using the power switch on the M3 Sonar Interface Unit.

Prerequisites

• The M3 Sonar PHS units have all been installed according to the instructions providedin the M3 Sonar PHS Installation Manual.

• All power and interface cables and connections have been connected and verified.

• All system units have been inspected.

Caution

Do not turn on the system if the Z-pole is oriented horizontally with the main systemunits out of the water.

Context

The M3 Sonar Interface Unit provides power to the following units.• Seapath 130 sensor and Motion Reference Unit (MRU)• M3 Sonar Head• Sound speed sensor

The Sonar Processor has its own power adapter.

Setting to work

Page 52: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

50 922-00037011/1.2

Note

It is impossible to control the weather. However, if the vessel has high dynamics duringstart-up (for example, as a result of rough seas), the Motion Reference Unit (MRU) mayrun into problems. High dynamics during start-up means that the MRU has moved upto ±10 degrees on all the orientation axes. At worst, the alignment must be redoneby restarting the MRU.

Procedure1 Turn on the Sonar Processor.

Wait while the operating system loads.2 Log in to Windows.3 Turn on the M3 Sonar Interface Unit to provide power to most of the system units.

Note

After the system is turned on, it will take up to 30 minutes for the MRU and theGPS to achieve full accuracy.

Further requirements

You are now ready to configure the M3 Sonar PHS for operational use.

M3 Sonar PHS Installation Manual

Page 53: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 51

Configuring the M3 Sonar PHS for normaloperation

TopicsSetting the Sonar Processor to High Performance, page 52

Defining the IP address on the Sonar Processor network adapter, page 52

Installing the M3 software, page 53

Configuring the M3 software, page 54

Setting to work

Page 54: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

52 922-00037011/1.2

Setting the Sonar Processor to High PerformanceTo avoid slowdowns or disruptions while running the sonar, ensure your Sonar Processoris using all of its processing power and does not go to sleep.

Prerequisites

This procedure is made for the Microsoft® 64-bit Windows 10 operating system.

Procedure1 In the bottom-left corner of your desktop, select the Windows® Start button.2 On the menu, select Settings.

Observe that the Settings window opens.3 Select System.4 In the menu on the left, select Power & sleep.5 Make sure that the Sonar Processor will never go to sleep when plugged in.

a Click the Additional power settings link on the right side of the window.Observe that the Power Options dialog box opens.

b In the menu on the left, select Create a power plan.c Select the High performance radio button.d Give your new custom plan a name, then click Next.e Select Never for both Turn off the display and Put the computer to sleep when

plugged in.f Click Create.

Tip

Once you have created a custom plan, you can adjust some more advanced settings.You may, for example, wish to keep any secondary displays on when the laptop lidis closed. Click Change plan settings next to your custom plan. Click the Changeadvanced power settings link. Observe that the Power Options dialog box opens.Click the “+” to expand the submenus, then select the desired options from thedrop-down lists. At the bottom of the dialog box, select Apply to save your settings.

Defining the IP address on the Sonar Processor networkadapterThe communication between the Sonar Processor and the other system units is madethrough a single Ethernet connection.

Prerequisites

This procedure is made for the Microsoft® 64-bit Windows 10 operating system.

M3 Sonar PHS Installation Manual

Page 55: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 53

ContextIf purchased from Kongsberg Mesotech, the M3 Sonar PHS Sonar Processor isconfigured at the factory prior to delivery. If you are using your own computer, youwill only need to do this procedure once.

Procedure1 On the Sonar Processor, close the M3 software.2 Open the Network Connections dialog box.

a In the bottom-left corner of your desktop, select the Windows® Start button.b On the menu, select Settings.c Observe that the Settings dialog box opens.d Select Network and Internet.e At the bottom of the dialog box, select Change adapter options.f Select the network adapter you are going to use; then right-click and select

Properties on the short-cut menu.g On the list of connections, select Internet Protocol 4 (TCP/IPv4), and then

Properties.3 Select Use the following IP address, and type the IP address and network mask.

IP Address: 192.168.1.N ("N" can be any number from 1 to 254, except 234 (SonarHead default), 10 (Seapath 130 default), or 254 (sound speed sensor default).)Subnet mask: 255.255.255.0You can leave Default Gateway blank.

4 Click OK to save the settings, then close all the dialog boxes.

Installing the M3 softwareIf your system is provided with a Sonar Processor, the M3 software has already beeninstalled. If you intend to use your own computer, you must install the software yourself.We recommended installing the latest M3 software on your Sonar Processor.

Prerequisites• You will need the Kongsberg USB drive included with the system or download the

latest M3 software release from: http://www.km.kongsberg.com/mesotechsoftware.• If you are installing a new software version, uninstall the previous version of the

M3 software before proceeding.

Note

When running the M3 software for the first time, a Windows Firewall dialog box mayappear. Allow access for all networks.

Setting to work

Page 56: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

54 922-00037011/1.2

Procedure1 Launch the installerM3_V0230 Setup.exe.2 Follow the installation wizard’s instructions and select Standard Installation.

Note

Use the Dual-M3 on Same PC option only if you are using two M3 Sonars. Selectingthis option will install two separate copies of the software, with each copy havingits own settings. You can identify which copy you are using by observing the topheader of the software presentation. The header will read either “M3 - MasterHead” or “M3 - Slave Head”.

3 Use the default folder location and check Create a desktop icon, then click Next.4 Click Yes to install the KML USB Converter when prompted and follow the

instructions to finish the installation process.5 Pin the M3 software icon to the Windows Taskbar.

a Right click on the M3 software icon.b Click Pin to taskbar.

6 Test the M3 software startup.a Double click the M3 icon on the desktop to run the M3 software.b Confirm the software finishes launching without any error windows appearing.

Configuring the M3 softwareIf purchased from Kongsberg Mesotech, the M3 Sonar PHS Sonar Processor isconfigured at the factory prior to delivery. If you are using your own computer, youwill only need to do this procedure once.

Prerequisites

The M3 software must be installed on your Sonar Processor.

Context

The M3 software controls the Sonar Head, acquires sounding data, and exports thesounding data to third-party software using the “.all” format. Third-party softwarereceives the sounding data from the M3 software through UDP with the KongsbergMesotech M3 driver. The M3 software can also receive and log the sensor data locally.

Procedure1 Double click the M3 icon on the desktop to run the M3 software.2 Configure the profiling settings.

a Select Sonar Apps→Profiling - Bathy.

M3 Sonar PHS Installation Manual

Page 57: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 55

b If the profiling settings are not visible, click Display→Profiling Settings toopen the Profiling Settings dialog box.

c Select Image and Profile in the Profiling Settings dialog box.

d Set the Algorithm to Split Beam.e Set the Point Selection to Strongest.f Check the Depth Tracking box to automatically adjust the range according

to the current depth.3 Set the exporting format.

a Click File→Exporting Format.b Select Profile Point (.all).

4 Configure the UDP Data Export settings.a Click Setup→Preferences.b Enter the following values in the UDP Data Export section.

Port for .ALL format: 20002This UDP port must match the port set inthe Hypack software.

Remote IP Address: 127.0.0.1127.0.0.1 is a loopback address (localhost).The Remote IP Address shown hereassumes Hypack is running on the samecomputer as the M3 software.

c Click Close.5 Set up the sonar.

a Click Setup→System Configuration→Devices→Sonar Setup.b Click Discover Sonar Heads to search for the sonar on the network.

Setting to work

Page 58: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

56 922-00037011/1.2

c If the M3 Sonar Head is found, select it, then click Use Discovered Head.

A discovered Sonar Head appears in the Online Sonar Heads list. If the SonarHead does not appear, the Ethernet connection between the Sonar Processorand Sonar Head has not been established.

d In the Device Properties table, select 1PPS from the Time Sync Mode drop-downlist.

Note

To use 1PPS, you must send NMEA ZDA to the M3 Sonar on UDP port 31100at 1Hz.

e Click Close.6 Configure the sensor inputs.

a Click Setup→System Configuration→Devices→Sensors Setup.

b Click Add Device, then set the Protocol GGA (GPS position) for the Seapath130 sensor unit with the following device properties.Name: Seapath PositionProtocol: GGAPort Location: PC UDPPort#: 31098

M3 Sonar PHS Installation Manual

Page 59: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 57

c Click Add Device, then set the Protocol HDT (vessel heading) for the Seapath130 sensor unit with the following device properties.Name: Seapath HeadingProtocol: HDTPort Location: PC UDPPort#: 31098

d Click Add Device, then set the Protocol VTG (course and speed) for the Seapath130 sensor unit with the following device properties.Name: Seapath SpeedProtocol: VTGPort Location: PC UDPPort#: 31098

e Click Add Device, then set the Protocol TSS (heave, roll, and pitch) for theMotion Reference Unit (MRU) with the following device properties.Name: MRUProtocol: TSSPort Location: PC UDPPort#: 31301

f If you have a standalone sound speed sensor, click Add Device, then set theProtocol Valeport MiniSVS for the sound speed sensor with the followingdevice properties.

Note

If you are using a Sonar Head with an integrated sound speed sensor, you canskip this step. You do not need to add the sound speed sensor as a separatedevice.

Name: Sound Speed SensorProtocol: Valeport MiniSVSPort Location: PC UDPPort#: 4001

g Select each sensor device and click the Test Device button.h Make sure that the sensor string is being displayed in the Port Monitor box.

Note

The sound speed sensor string is only visible if the sensor is in the water.

i Click Stop Test when done.

Setting to work

Page 60: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

58 922-00037011/1.2

7 Configure your deployment.a Click Setup→System Configuration→Deployment→Master Reference.

b Select Seapath Position from the Position drop-down list.c Leave Depth as Fixed.d Select Seapath Heading from the Heading drop-down list.e Select MRU from the Pitch/Roll and Heave drop-down lists.f If you have a standalone sound speed sensor, select Sound Speed Sensor

from the Sound Speed drop-down list. If you are using a Sonar Head with anintegrated sound speed sensor, select IntegratedSVS from the Sound Speeddrop-down list.

g Click Setup→System Configuration→Deployment→Mounting Offsets.h Make sure that the X, Y, and Z offsets are all zero.

M3 Sonar PHS Installation Manual

Page 61: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 59

Note

In the M3 Sonar PHS, the X (Starboard), Y (Forward), and Z (Vertical) offsetsare entered into the Hypack software.

i Select Downward for the Orientation parameter.

8 Rotate the sonar view.a Click Display→Sector Orientation.b Select 180.

Setting to work

Page 62: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

60 922-00037011/1.2

Creating a backup with the M3 configurationand software installationAs the M3 software is pre-configured at the factory, you will lose all the M3 Sonar PHSsettings if you re-install the software. We recommend creating a backup in case youneed to restore your settings at a later time.

Prerequisites

When restoring a backup, make sure that you are restoring the same software version.

Note

Attempting to restore a backup folder from an older version of the M3 software maynot work, as backwards compatibility will vary between software releases. However,you can safely restore some user settings from an older version of software by clickingFile→Load User Settings, then browsing for a “UsersInfo.xml” file in the folderC:\KML\M3_V0230\bin\Settings.

Procedure1 Once the system has been configured and tested, copy the folder

C:\KML\M3_V0230 to an external drive as a backup of the configuration.2 To restore the M3 software settings, copy the backup folder into C:\KML.3 As a secondary measure, run windows backup to create a restore point on the M3

Sonar Processor.

M3 Sonar PHS Installation Manual

Page 63: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 61

Turning off the M3 Sonar PHSTurn off the M3 Sonar PHS using the power switch on the M3 Sonar Interface Unit.

Context

When you do not use the M3 Sonar PHS, turn off the entire system.

Procedure1 If you are running the sonar, click Setup→Disconnect in the M3 software.2 Turn off the Sonar Processor.

a Save your settings, then close the M3 software and any third-party software.b Shut down Windows.

3 Disconnect the power cord leading to the Sonar Processor power adapter.4 Turn off the M3 Sonar Interface Unit.5 Disconnect the power cord leading to the Interface Unit 24-VDC power adapter.6 Turn off any additional items, such as a display.

If required, refer to the instructions provided by the product’s manufacturer.

Setting to work

Page 64: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

62 922-00037011/1.2

Drawing file

About the drawings in the drawing fileRelevant drawings related to the installation and/or maintenance of the M3 Sonar PHSare provided for information purposes only.

The drawings are not to scale. Unless otherwise specified, all measurements are ininches. The original installation drawings are available by request in PDF and/orSolidWorks format.

M3 Sonar PHS Installation Manual

Page 65: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 63

Seapath 130 sensor unit outline dimensions

Drawing file

Page 66: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

64 922-00037011/1.2

Motion Reference Unit outline dimensions

M3 Sonar PHS Installation Manual

Page 67: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 65

500 m Sonar Head outline dimensions

Drawing file

Page 68: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

66 922-00037011/1.2

M3 Sonar PHS Installation Manual

Page 69: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 67

Drawing file

Page 70: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

68 922-00037011/1.2

Sonar Head with integrated sound speedsensor outline dimensions

M3 Sonar PHS Installation Manual

Page 71: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 69

Drawing file

Page 72: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

70 922-00037011/1.2

Sound speed sensor outline dimensions

M3 Sonar PHS Installation Manual

Page 73: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 71

M3 Sonar Interface Unit outline dimensions

Drawing file

Page 74: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

72 922-00037011/1.2

MRU flange outline dimensions

M3 Sonar PHS Installation Manual

Page 75: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 73

Related topicsAttaching the sensors to the Pole Mount, page 20

Drawing file

Page 76: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

74 922-00037011/1.2

M3 Sonar flange outline dimensions

Related topicsAttaching the sensors to the Pole Mount, page 20

M3 Sonar PHS Installation Manual

Page 77: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 75

Seapath sensor flange outline dimensions

Related topicsInstalling the Seapath 130 sensor unit, page 26

Drawing file

Page 78: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

76 922-00037011/1.2

Technical specifications

TopicsIntroduction to technical specifications, page 77

Performance specifications, page 77

Mechanical specifications, page 79

Power requirements, page 80

Environmental requirements, page 81

M3 Sonar PHS Installation Manual

Page 79: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 77

Introduction to technical specificationsThese technical specifications summarize the main functional and operationalcharacteristics of the M3 Sonar PHS Portable Hydrographic System (PHS). Italso provides information related to power requirements, physical properties andenvironmental conditions.

Note

At Kongsberg Mesotech, we are continuously working to improve the quality andperformance of our products. The technical specifications may be changed withoutprior notice.

Performance specificationsThese performance specifications summarize the main functional and operationalcharacteristics of the M3 Sonar PHS.

M3 Sonar Interface Unit• One RJ-45 Ethernet port (at the breakout box) to provide sensor and sonar data output,

sensor control, and sonar control communication.• One RJ-45 RS-232 serial port for DGNSS correction input with a 9600 bps baud rate.• One spare RJ-45 Ethernet port for other sensor use.

M3 Sonar Head• Depth: 0.2 to 50 m• Coverage: 3.5 x Depth / 120°• Range resolution: 1 cm• Frequency: 500 kHz• Pulse forms: CW, LFM• Across track beam width: 1.6°• Along track beam width: 3°• Number of beams: up to 256• Update rate: up to 40 Hz

Technical specifications

Page 80: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

78 922-00037011/1.2

Position, Heading, and Motion Sensor• Seapath 130-3 with MRU 3 Roll and pitch accuracy for ±5° amplitude: 0.08° RMS• Seapath 130-H with MRU H Roll and pitch accuracy for ±5° amplitude: 0.03° RMS• Heading accuracy: 0.2° RMS• Heave accuracy (real-time output): 5 cm or 5 % whichever is highest• Seapath 130-3 with MRU 3 heave motion periods (real-time output): 0 to 18 seconds• Seapath 130-H with MRU H heave motion periods (real-time output): 0 to 25 seconds• Seapath 130-3 with MRU 3 heave accuracy (delayed signal, PFreeHeave®): 4 cm or 5

% whichever is highest• Seapath 130-H with MRU H heave accuracy (delayed signal, PFreeHeave®): 2 cm or 2

% whichever is highest• Heave motion periods (delayed signal, PFreeHeave®): 0 to 50 seconds• Position accuracy with DGPS/DGLONASS: 0.5 m RMS or 1 m 95 % CEP• Position accuracy with SBAS: 0.5 m RMS or 1 m 95 % CEP• Position accuracy with Fugro SeaSTAR XP2/G2: 0.1 m RMS or 0.2 m 95 % CEP• Position accuracy with VERIPOS Ultra/Ultra: 0.1 m RMS or 0.2 m 95 % CEP• Position accuracy with RTK (x and y): 1 cm + 1 ppm RMS• Position accuracy with RTK (z): 2 cm + 1 ppm RMS• Velocity accuracy: 0.03 m/s RMS or 0.07 m/s 95 % CEP

Valeport miniSVS sound speed sensor• Range: 1375 - 1900 m/s• Resolution: 0.001 m/s• Accuracy:: Total max theoretical error ±0.019 m/s• Acoustic Frequency: 2.5 MHz

AML SVT Xchange sound speed sensor

A Sonar Head with an integrated AML sound speed sensor is available from KongsbergMesotech.• Range: 1375 - 1625 m/s• Resolution: 0.001 m/s• Accuracy: 0.025 m/s• Response time: 20 ms• Precision: 0.006 m/s

M3 Sonar PHS Installation Manual

Page 81: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 79

Mechanical specificationsThese mechanical specifications summarize the physical properties of the M3 Sonar PHS.

Note

For more detailed information about the physical dimensions, see the Drawing file.

Sonar Processor

The Sonar Processor uses a high-quality commercial-off-the-shelf laptop computerworkstation. The weight and dimensions of the model may vary. Contact yourKongsberg Mesotech representative for information about the current model that isdelivered with your M3 Sonar PHS.

M3 Sonar Interface Unit• Dimensions

– Width: 338.5 mm (13.33”)– Height: 118.5 mm (4.67”)– Depth: 221.2 mm (8.71”)

• Weight: 3.3 kg (7.3 lb)• Materials: Aluminium

Sonar Head• Depth rating: 500 m• Dimensions

– Diameter: 185 mm (7.28”)– Depth: 126 mm (4.95”)

• Weight: 4.4 kg (air), 1.8 kg (water)• Materials: Anodized Aluminium, Stainless Steel 316, Elastomeric Polyurethane• Connector type: SEA CON®

• Connector model: MINK-10-FCRL (Ethernet & Power)

Seatex Motion Reference Unit in 10m subsea bottle• Depth rating: 10 m• Dimensions

– Height: 209 mm, 240.5 mm incl. connectors– Diameter: 120 mm

• Weight: 3.7 kg (air), 1.3 kg (water)

Technical specifications

Page 82: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

80 922-00037011/1.2

• Material: Anodised aluminium• Connectors: 2, 8-pin SEA CON®

Seapath 130 sensor unit• Length: 1210 mm• Width: 210 mm• Height: 94 mm• Weight: 6.8 kg

Valeport miniSVS sound speed sensor• Depth Rating: 500 m• Weight: 1 kg• Housing & Bulkhead: Acetal• Transducer Window: Polycarbonate• Sensor Legs: Carbon Composite• Reflector Plate: Titanium

AML SVT Xchange sound speed sensor

A Sonar Head with an integrated AML sound speed sensor is available from KongsbergMesotech.• Depth rating: 11000 m• Weight: 120 g• Material: Titanium

Power requirementsAn external power supply connects to the M3 Sonar Interface Unit, providing powerto all system units.

M3 Sonar Interface Unit• Input voltage: 20-30 VDC• Input power: 150 W

M3 Sonar PHS Installation Manual

Page 83: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 81

Environmental requirementsThese specifications summarize the temperature requirements and other environmentalstandards for the M3 Sonar PHS.

M3 Sonar Interface Unit• Ingress protection (IP) rating: IP 56• Operating temperature range: 0°C to +40°C• Storage temperature range: 0°C to +50°C• Operating humidity (max): 95%• Standards: CE Mark (EMI standard and RoHS compliancy)

Seapath 130 sensor unit• Enclosure material: Aluminium bottom part and polyurethane cover• Operating temperature range: -40°C to +70°C• Storage temperature range: -40°C to +70°C• Operating humidity (max): Sealed, no limit• Storage humidity: Sealed, no limit• Ingress protection (IP) rating: IP 56• Electromagnetic compatibility (immunity/emission): IEC 60945/EN 60945• Vibration: IEC 60945/EN 60945

Sonar Head• Temperature: -2° to + 38°C (operation), -40 to +55°C (storage)• Shock qualified: +/-50gs, 3 Axes, 6 shocks per axis• Vibration qualified: 4g, 30Hz 3 Axes, 2 hours per axis. No resonance below 800Hz

Motion Reference Unit• Temperature: -5° to +55°C (operation), -25° to +70°C (storage)• Mean time between failures (MTBF): 50,000 hours• Standards: IEC 60945• Max shock non-operational (10ms peak): 1000 m/s2 (Seatex MRU)

Valeport miniSVS sound speed sensor• Sensor spacer rods: Resistant to corrosion; virtually zero coefficient of thermal

expansion

Technical specifications

Page 84: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

82 922-00037011/1.2

AML SVT Xchange sound speed sensor

A Sonar Head with an integrated AML sound speed sensor is available from KongsbergMesotech.• Storage temperature: -20 to 60 °C• Operating temperature: -5 to 45 °C

M3 Sonar PHS Installation Manual

Page 85: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 83

Index

Aaboutcomments .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5constructive criticism... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5feedback... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5installation drawings .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62purpose of this manual .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5registered trademarks.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5software license .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5software version.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5suggestions .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5target audience .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

additional required itemsnot provided with the delivery .. . . . . . . . . . . . . . . . . . . . . . . . 15

audiencethis manual.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Bbacking upsoftware .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

basic itemsprovided with the delivery.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

blockdiagram... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

bookpurpose .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5target audience .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Ccable drawingSeacon MINK-10-CCPL... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

cable plan .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36cableslist of system interconnection cables .. . . . . . . . . . . . . . . . . 37procedures .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38–39, 42read this first . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

characteristicsmechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79performance .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

commentssend us.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

configuringsoftware .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54Sonar Processor .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

constructive criticismsend us.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Ddescriptionsystem ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

dimensionsabout .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Interface Unit outline dimensions drawing... . . . . . . . . 71M3 Sonar flange outline dimensions drawing ... . . . . . 74Motion Reference Unit (MRU) outlinedimensions drawing... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64MRU flange outline dimensions drawing... . . . . . . . . . . 72

Seapath 130 sensor unit outline dimensionsdrawing ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63Seapath sensor flange outline dimensionsdrawing ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75Sonar Head outline dimensionsdrawing ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65, 68sound speed sensor outline dimensionsdrawing ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

drawingInterface Unit outline dimensions .. . . . . . . . . . . . . . . . . . . . 71M3 Sonar flange outline dimensions .. . . . . . . . . . . . . . . . . 74Motion Reference Unit (MRU) outlinedimensions .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64MRU flange outline dimensions .. . . . . . . . . . . . . . . . . . . . . . 72Seapath 130 sensor unit outline dimensions .. . . . . . . . 63Seapath sensor flange outline dimensions .. . . . . . . . . . . 75Sonar Head outline dimensions .. . . . . . . . . . . . . . . . . . 65, 68sound speed sensor outline dimensions .. . . . . . . . . . . . . . 70system diagram... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

drawingsabout .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

Eenvironmentalrequirements .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

Ethernet interfacenetwork adapter .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Ffeatureskey ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

feedbacksend us.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

functionaldiagram... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Ggeneral requirementsuninterruptible power supply.. . . . . . . . . . . . . . . . . . . . . . . . . . 16

general safety rules .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Hhigh voltagesafety rules.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

how toback up the software.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60configure the software.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54configure the Sonar Processor.. . . . . . . . . . . . . . . . . . . . . . . . . 52install the Motion Reference Unit (MRU)... . . . . . . . . . 20install the operational software .. . . . . . . . . . . . . . . . . . . . . . . 53install the Seapath 130 sensor unit . . . . . . . . . . . . . . . . . . . . 26install the Sonar Head ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20install the Sonar Processor.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31install the sound speed sensor .. . . . . . . . . . . . . . . . . . . . . . . . . 20set to work .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47turn off .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Index

Page 86: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

84 922-00037011/1.2

turn on ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49verify the M3 Sonar PHS is ready for use .. . . . . . . . . . . 48

humidityrequirements .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

Iinformationhigh voltage.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

installationoverview ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18software .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53summary ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18tasks .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

installation drawingsabout .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

installation requirementsenvironmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81humidity.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81temperature .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

installingMotion Reference Unit (MRU) ... . . . . . . . . . . . . . . . . . . . . . 20Seapath 130 sensor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Sonar Head ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Sonar Processor .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31sound speed sensor .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

interconnectionprocedures .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38–39, 42

interconnection cableslist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Interface Unitintroduction .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10outline dimensions drawing ... . . . . . . . . . . . . . . . . . . . . . . . . . 71overview ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10purpose .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

introductionInterface Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Motion Reference Unit (MRU) ... . . . . . . . . . . . . . . . . . . . . . 11Pole Mount .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Seapath 130 sensor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Sonar Head ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Sonar Processor .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10sound speed sensor .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

IP addressnetwork adapter .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

IP Addressnetwork adapter .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Kkey featuressystem ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Kongsberg Mesotechsupport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Llicensesoftware .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

listsystem interconnection cables.. . . . . . . . . . . . . . . . . . . . . . . . . 37

MM3 Sonar flangeoutline dimensions drawing ... . . . . . . . . . . . . . . . . . . . . . . . . . 74

main itemsprovided with the delivery.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

mains powerrequirements .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

manualpurpose .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5target audience .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

mechanicalspecifications .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

mechanical drawingsabout .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

Motion Reference Unit (MRU)installing .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20introduction .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11outline dimensions drawing ... . . . . . . . . . . . . . . . . . . . . . . . . . 64overview ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11purpose .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

MRUinstalling .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20introduction .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11outline dimensions drawing ... . . . . . . . . . . . . . . . . . . . . . . . . . 64overview ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11purpose .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

MRU flangeoutline dimensions drawing ... . . . . . . . . . . . . . . . . . . . . . . . . . 72

Nnetwork adapterIP Address .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52IP address for transceiver communication.. . . . . . . . . . . 52Subnet mask ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Ooffturn.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

officesupport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

onturn.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

operational softwareinstallation .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

outline dimensionsabout .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

outline dimensions drawingInterface Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71M3 Sonar flange.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74Motion Reference Unit (MRU) ... . . . . . . . . . . . . . . . . . . . . . 64MRU flange... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72Seapath 130 sensor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63Seapath sensor flange.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75Sonar Head ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65, 68sound speed sensor .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

overviewinstallation tasks .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Interface Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Motion Reference Unit (MRU) ... . . . . . . . . . . . . . . . . . . . . . 11Pole Mount .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Seapath 130 sensor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Sonar Head ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

M3 Sonar PHS Installation Manual

Page 87: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

922-00037011/1.2 85

Sonar Processor .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10sound speed sensor .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Pperformancespecifications .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

Pole Mountintroduction .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12overview ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12purpose .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

powerrequirements .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80specifications .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

procedurebacking up software .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60configuring the software .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54configuring the Sonar Processor .. . . . . . . . . . . . . . . . . . . . . . 52installing the Motion Reference Unit (MRU) ... . . . . . 20installing the operational software.. . . . . . . . . . . . . . . . . . . . 53installing the Seapath 130 sensor unit. . . . . . . . . . . . . . . . . 26installing the Sonar Head ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20installing the Sonar Processor.. . . . . . . . . . . . . . . . . . . . . . . . . 31installing the sound speed sensor .. . . . . . . . . . . . . . . . . . . . . 20setting to work .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47turning off.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61turning on ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49verifying the M3 Sonar PHS is ready for use .. . . . . . . 48

procedurescables .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38–39, 42wiring.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38–39, 42

publicationpurpose .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5target audience .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

purposeInterface Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Motion Reference Unit (MRU) ... . . . . . . . . . . . . . . . . . . . . . 11Pole Mount .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Seapath 130 sensor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Sonar Head ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Sonar Processor .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10sound speed sensor .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11this manual.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Rreaderthis manual.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

registered trademarks.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5required itemsnot provided with the delivery .. . . . . . . . . . . . . . . . . . . . . . . . 15

requirementsenvironmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81humidity.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81mains power .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80power .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80supply power .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80temperature .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81uninterruptible power supply.. . . . . . . . . . . . . . . . . . . . . . . . . . 16

rulessafety .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Ssafety rules.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

scope of supplybasic items ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13required items not provided with the delivery .. . . . . . . 15

Seapath 130 sensor unitinstalling .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26introduction .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10outline dimensions drawing ... . . . . . . . . . . . . . . . . . . . . . . . . . 63overview ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10purpose .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Seapath sensor flangeoutline dimensions drawing ... . . . . . . . . . . . . . . . . . . . . . . . . . 75

setting to workprocedures .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

softwarebackup ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60configuring.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54installation .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53license .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5version.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Sonar Headinstalling .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20introduction .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11outline dimensions drawing ... . . . . . . . . . . . . . . . . . . . . 65, 68overview ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11purpose .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Sonar Processorconfiguring.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52installing .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31introduction .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10overview ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10purpose .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

sound speed sensorinstalling .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20introduction .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11outline dimensions drawing ... . . . . . . . . . . . . . . . . . . . . . . . . . 70overview ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11purpose .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

specificationsmechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79performance .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77power .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80Seacon MINK-10-CCPL... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45Seatex Motion Reference Unit connector .. . . . . . . . . . . 45technical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

standard itemsprovided with the delivery.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

standard toolsinstallation of system units .. . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Subnet masknetwork adapter .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

suggestionssend us.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

summaryinstallation .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

supply powerrequirements .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

support information.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16switchoff .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61on ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

systemdescription .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7diagram... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8key features .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7standard tools for installation .. . . . . . . . . . . . . . . . . . . . . . . . . 19

Index

Page 88: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

86 922-00037011/1.2

system cablesdescription .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

system softwareinstallation .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Ttarget audiencethis manual.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

technicalspecifications .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

temperaturerequirements .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

this manualpurpose .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5target audience .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

toolsinstallation of system units .. . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

trademarksregistered.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

turnoff .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61on ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

Uuninterruptible power supplygeneral requirements .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

unitsstandard tools for installation .. . . . . . . . . . . . . . . . . . . . . . . . . 19

UPSgeneral requirements .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

VverifyingM3 Sonar PHS is ready for use .. . . . . . . . . . . . . . . . . . . . . . . 48

versionsoftware .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Wwiringlist of system interconnection cables .. . . . . . . . . . . . . . . . . 37procedures .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38–39, 42

M3 Sonar PHS Installation Manual

Page 89: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2
Page 90: M3 Sonar PHS Installation Manual - mesotech.online · 922-00037011/1.2 January2019©KongsbergMesotechLimited M3SonarPHS PortableHydrographicSystem(PHS) InstallationManual Release1.2

©2019 Kongsberg Mesotech