LOW VOLTAGE INSTRUMENT TRANSFORMERS SINGLE PHASE VOLTAGE TRANSFORMERS TPN SERIES Technical data Rated insulation 0.72/3 kV Primary voltage 10 to 400 V Secondary voltage 100 / √3 - 110 / √3 - 100 - 110 V Frequency 50 or 60 Hz Rated output 5 VA to 80 VA Accuracy class 0.2 - 0.5 - 1 - 3 - cl A Thermal power Up to 250 VA Voltage factor 1.2 Un permanent Insulation class E Live terminal Terminal blocks with screw connectors Earth terminal Terminal block with screw connectors Terminal protection IP40 with cover lid Rated output -25°C to + 40°C Norm IEC - IEEE - CSA - AS - BS Autres caractéristiques sur demande Rated insulation Up to 1.2/6 kV Primary voltage 10 to 1200 V Secondary voltage 10 to 1200 V Thermal power Up to 100VA Accuracy class 0.2 – 3P – 6P Rated output - 25°C to + 70°C Winding taps Up to 3 primary and/or secondary taps Separate secondary windings Up to 2 secondary windings Terminal protection cover lid + seal IP54 PAGE 1/2 ©RS ISOLSEC Accessories / Options Sealable terminal cover lid Primary/Secondary shield Protection of primary and secondary connection cables through cable glands Voltage transformers for the mea- surement of AC voltages up to 1200 V for industrial and marine applications. The terminals are protected to pre- vent accidental contact with live parts. Fixing holes incorporated to the transformer body allow its installa- tion in any position. contact: [email protected] - non-binding information - DATASHEET : M2JB/3 TPN96 TPN96 - open terminal lid • For indoor, outdoor and wet environments • Primary voltage up to 1200V • Measurement and protection • Tropicalized 14

Transcript of LOW VOLTAGE INSTRUMENT TRANSFORMERS SINGLE PHASE … · TPN SERIES Technical data Rated insulation...

Page 1: LOW VOLTAGE INSTRUMENT TRANSFORMERS SINGLE PHASE … · TPN SERIES Technical data Rated insulation 0.72/3 kV Primary voltage 10 to 400 V Secondary voltage 100 / √3 - 110 / √3

LOW VOLTAGE INSTRUMENT TRANSFORMERS

SINGLE PHASE VOLTAGE TRANSFORMERSTPN SERIES

Technical data

Rated insulation 0.72/3 kVPrimary voltage 10 to 400 VSecondary voltage 100 / √3 - 110 / √3 - 100 - 110 VFrequency 50 or 60 HzRated output 5 VA to 80 VAAccuracy class 0.2 - 0.5 - 1 - 3 - cl AThermal power Up to 250 VAVoltage factor 1.2 Un permanentInsulation class ELive terminal Terminal blocks with screw connectorsEarth terminal Terminal block with screw connectorsTerminal protection IP40 with cover lidRated output -25°C to + 40°C Norm IEC - IEEE - CSA - AS - BS

Autres caractéristiques sur demandeRated insulation Up to 1.2/6 kVPrimary voltage 10 to 1200 VSecondary voltage 10 to 1200 VThermal power Up to 100VAAccuracy class 0.2 – 3P – 6PRated output - 25°C to + 70°CWinding taps Up to 3 primary and/or secondary tapsSeparate secondary windings Up to 2 secondary windingsTerminal protection cover lid + seal IP54

PAGE 1/2©RS ISOLSEC

Accessories / OptionsSealable terminal cover lidPrimary/Secondary shieldProtection of primary and secondary connection cables through cable glands

Voltage transformers for the mea-surement of AC voltages up to 1200 V for industrial and marine applications.

The terminals are protected to pre-vent accidental contact with live parts.

Fixing holes incorporated to the transformer body allow its installa-tion in any position.

contact: [email protected] - non-binding information - DATASHEET : M2JB/3

TPN96 TPN96 - open terminal lid

• For indoor, outdoor and wet environments• Primary voltage up to 1200V• Measurement and protection• Tropicalized

14

Page 2: LOW VOLTAGE INSTRUMENT TRANSFORMERS SINGLE PHASE … · TPN SERIES Technical data Rated insulation 0.72/3 kV Primary voltage 10 to 400 V Secondary voltage 100 / √3 - 110 / √3

PAGE 2/2 contact: [email protected] - non-binding information - DATASHEET : M2JB/3©RS ISOLSEC

SINGLE PHASE VOLTAGE TRANSFORMERS - TPN SERIES

Selection table

TPN96 TPN120

Type Burden Thermal output Weight maximum in VA maximum in VA Approximate

cl 3 cl 1 cl 0.5 cl 0.2 cl ATPN96 60 20 15 5 75 4kg

TPN120 200 100 50 15 250 6kg

109,5

8531,5 O8

150

172

Raccordements primaire et secondairepar blocs de jonction à vis

Passe fil à membrane pour câble O extérieur max 9mm

172,8

5,5

4,5

115

89

138

64

23,5

24,25

132

InstallationConnections to terminal blocks with screw connectors :• Solid conductor min 0.2 mm2

• Solid conductor max 6 mm2

• Stranded conductor min 0.2 mm2

• Stranded conductor max: 6 mm2

• Conductor Stripping length : 8 mm• Thread of the terminal blocks clamping screw: M3• Torque: 0.6 to 0.8 Nm

Terminal blocks with screw connection

Membrane grommet for max 9mm outside dia cable

Marking :

Primary : A-B Phase - Phase A-N Phase - Ground

Secondary : a-b Phase- Phase a-n Phase - Ground da-dn Tertiary winding