LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF...

45
LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering of Lehigh University as partial fulfillment for the Departmental Honors Program. Department of Civil Engineering Lehigh University Bethlehem, Pennsylvania May 1968 Fritz Engineering Laboratory Report Nummber 338.5

Transcript of LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF...

Page 1: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

LOCAL BUCKLING OF COMPOSITE BEAMS

David Geoffrey Miller

A THESIS

Presented to the Department of CivilEngineering of Lehigh University aspartial fulfillment for the DepartmentalHonors Program.

Department of Civil Engineering

Lehigh University

Bethlehem, Pennsylvania

May 1968

Fritz Engineering Laboratory Report Nummber 338.5

Page 2: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering
Page 3: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

1. INTRODUCTION

While existing specifications1 allow plastic design

methods to be employed for one and two story steel building

frames, adequate information is presently available for the

extension of plastic design methods to multi-story frames.

The desirability of plastic design concepts lies in the more

efficient use of steel and the relative simplicity of design

over traditional allowable stress design methods. 2

Since unbraced multi-story frames require adequate

lateral as well as vertical strength, composite steel-concrete

construction with its inherent increased stiffness of the floor

system should provide a more economical solution for unbraced

multi-story frames than pure steel construction. Specifications

of the American Institute of Steel Construction currently rec­

ognizes the use of composite beams, but only on an allowable

stress basis. 1

Recent research has been aimed at an extension of

simple plastic theory to continuous composite steel-concrete

beams. 3 ,sSuch an extension would require simple rules for the

determination of the ultimate moment and rotation capacities of

composite cross-sections in both the positive and negative moment

regions.

Page 4: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

It has been shown experimentally that in the positive

moment regions the ultimate moment capacity is determined by

plastification of the steel beam or crushing of the concrete

slab. 10 In the negative moment regions the ultimate moment

capacity is determined by plastification of the steel beam and

the longitudinal reinforcing steel. It has also been shown

experimentally that large rotation capacities are available at

plastic hinge locations providing that secondary failures, such

as local buckling of the flange and web of the steel beam, can

be prevented. 3,4 While the results of previous investigations

may be used for the design of composite beams in both braced

and unbraced multi-story frames subjected only to gravity loads,

they may not be considered to be generally applicable for the

design of unbraced frames which are subjected to combined grav­

ity and lateral 10ads. 5

Figure 1 represents a distribution of bending moments

in one story of an unbraced multi-story frame which is subjected

to combined gravity and lateral wind loads. In the case con­

sidered it has been assumed that the lateral wind load is suffi­

ciently large so that positive bending moments will develop in

the beam at the leeward side of the joint, while the negative

bending moments will remain, as in the case of only gravity loads,

-2-

Page 5: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

on the windward side of the joint. Such a distribution of bend-

ing moments will determine four main regions which must be con-

sidered in an investigation of the ultimate strength behavior of

composite beams under combined wind and gravity loads. These

regions are shown in Fig. 2 and may be defined as follows:

Region 1:

Region 2:

Region 3:

The interior region in which cross-sections are

subjected to positive bending moments and com-

pressive forces act over the full effective slab

width at the ultimate moment capacity. The lee-

ward boundary of this section is determined by

the inflection point.

The positive moment region between Region 1 and

the cross-section adjacent to the leeward side

of the joint, where compressive forces act on a

reduced slab width. Adjacent to the column com-

pressive forces will be developed only between the

column face and the concrete slab, which is assumed

to be in contact with the column.

The negative moment region situated between Region

1 and the cross-section adjacent to the windward

side of the interior joint.

-3-

Page 6: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

Region 4: The negative moment region situated between Region I

and the cross-section adjacent to the windward

side of the leeward exterior joint.

Regions I and 3 do not differ appreciably from similar

regions of composite beams subjected only to gravity loads. It

is anticipated that the results of previous investigations3 could

be used to predict the ultimate moment capacity of cross-sections

within these two regions. However, since these previous inves­

tigations do not provide sufficient information on the expected

capacities of Regions 2 and 4, a pilot study was undertaken to

provide preliminary experimental data on the behavior of com­

posite beams within these two regions, as well as confirmation

of the behavior in Region 3.

This report will be concerned only with the behavior

of Regions 3 and 4. The purpose of this report is to summarize

the experimental program and to suggest suitable criteria which

will assure the attainment of the negative moment capacity of

a composite cross-section in these two regions prior to the onset

of local buckling of the steel beam. A report of the experimental

results obtained from Region 2 will be presented in Reference 6.

-~

Page 7: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

Since in composite construction one flange of the

steel beam is connected to the concrete slab at close intervals

by means of shear connectors, there is assumed to be no local

buckling of the connected flange. Furthermore, since the beam

in the negative moment region is usually subjected to a steep

moment gradient and restrained by the concrete slab, it is as­

sumed that no lateral-torsional buckling of the cross-section

will occur.

-5-

Page 8: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

2. EXPERIMENTAL INVESTIGATION

2.1 Description of Test Specimens and Design Criteria

The experimental phases of this investigation consisted

of testing two test specimens, Jl and J2, under the applied loads

shown in Figures 3 and 4. Since the objective was to investigate

local buckling in Regions 2 and 4 (See Introduction) two speci­

mens were tested. Each test specimen consisted of two composite

steel-concrete beams rigidly connected to a steel column as

shown in the figures. Shear loading was applied to the columns

in order to simulate the column shears due to wind loads acting

on a real frame. No gravity loads were applied to the columns

or the beams.

In order to duplicate conditions found in a real frame,

a 16-in. wide spreader plate was welded to both column flanges

in each test specimen at the elevation of the concrete slab.

The spreader plates are shown in Figure 5. The use of the

spreader plates enabled a smaller column to be used in each test

specimen while maintaining an effective column flange width of

16-in. Figure 5 also shows that the column section at the joint

was stiffened substantially to insure negligible joint deformation,

thus eliminating this variable from consideration.

-6-

Page 9: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

Test specimen Jl was constructed so that the concrete

slab was discontinuous at the column (See Figure 4). In this

way, the negative moment region would simulate the windward side

of an exterior joint, previously designated as Region 4. Specimen

J2 was constructed with a continuous concrete slab through the

joint so that the negative moment region would simulate the

conditions present at the windward side of an interior joint,

previously designated as Region 3.

Two rows of 1/2 in. diameter by 2-in. high headed steel

studs were welded to the top flanges of the steel beams as shown

in Figure 6. Since a real multi-story frame could be loaded

laterally in either direction, the pattern of shear connectors

provided was symetrical about the column. They were spaced uni­

formly at 5-in. throughout most of the length of each beam in

order to duplicate practical spacings found in real frames. The

spacing was reduced near the exterior end of each beam in order

to simulate the boundary conditions in an actual structure and to

assure adequate capacity of the shear connection.

The two specimens were designed according to ultimate

strength theory. The negative moment region of specimen Jl was

proportioned based only on the plastic strength of the steel

beam. Since the slab and the longitudinal reinforcing bars in

-7-

Page 10: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

specimen Jl were not made continuous they could not sustain a

tensile force at the joint. In specimen J2 the negative moment

region wps designed based on the strength of both the pteel

beam and the steel reinforcing bars. The reinforcing bars

situated directly over the upper flanges of the steel beams

were not considered since these bars were not continuous in

either specimen. In both Jl and J2 the concrete in the negative

moment region was assumed to be fully cracked. Since there are

no existing recommendations for the effective width of concrete

slabs in composite beams which are designed on an ultimate

strength basis a slab width of 72 inches was used in order to

approximately conform with the maximum effective width require­

ments of the AISC Specifications.

2.2 Construction and Fabrication of Specimens

The steel fabrication for each test specimen was

identical, and details of the specimens are shown in Figure 6.

The two steel beams for each specimen were cut from the same

36 foot length of 16 WF 40 ASTM A36 steel beam. The original

beam was sectioned into thirds with the mid-section being used

for the control tests discussed in Section 2.4. The beams were

welded and fitted to the column flanges in the shop using full

penetration butt welds. Likewise, the bearing stiffners and

loading plates were welded and fitted in the shop.

-8-

Page 11: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

The stud shear connectors were also shop welded and

conform to the l~ecommendations for Material and for Welding

Steel Channel Spiral and Stud Shear Connectors" suggested by

the ASCE-ACI Joint Committee July 1964. All other welding was

performed in accordance with the AISC specifications - "Structural

Steel for Buildings".

Figures 7 and 8 show the formwork and the reinforcing

bar layouts. The slab, which was 4 inches thick to conform with

practical slab thicknesses, was reinforced with intermediate

grade reinforcing bars~ The corners of the slab were cut off

in order to accommodate the test specimens in the load frame.

The reinforcement provided was made as nearly identical to that

which would exist near the joint in a real frame.

Both slabs were formed simultaneously with plywood

forms being constructed to support the slabs. A timber bulk­

head was used to separate the slabs of the two specimens as

well as to form the discontinuity for specimen Jl. Figure 8

shows the two specimens as they were formed together but with

the plywood forms removed. The concrete for the slabs was transit

mixed and was proportioned for a 28 day compressive strength of

4000 psi. Consolidation was performed by internal vibration

along the slab as placement progressed. The final finish was

applied by hand trowelling. Four test cylinders were poured

during the casting of the slabs.

-9-

Page 12: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

The concrete in the slabs was moist-cured for 7 days.

The surface was covered with wet burlap and a polyethylene sheet.

The form was removed after 14 days; after which Jl was moved to

the testing bed.

2.3 Instrumentation

Figures 9 and 10 show the locations of the several

types of gages employed in the experimental phases of the

investigations. Four different types of instruments were used:

electrical resistance strain gages, dial deflection gages, level

bar rotation gages and slide bar extensometers. As shown in

Fig. 9, strains were measured on both sides of the web of the

steel beam at three levels, using SR-4 electrical resistance gages

as well as mechanical gage points with a 3 inch gage length

located symetrically about the electrical gages. A slide bar

extensometer, with a O.OOOl-in. dial gage, was used to measure

the elongation between the mechanical gage points. These mea­

surements were most accurate for determining the larger values

of strain. The electrical resistance gages were accurate until

plastification of the steel beam in the region of a gage occurred.

Figure 9 shows the location of the SR-4 electrical resistance

gages on the top of the concrete slab. No mechanical gage read­

ings were taken at these locations.

-10-

Page 13: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

Figure 10 shows the locations of the remaining

instrumentation for measuring slip, rotation and the onset

of local buckling. The amount of slip between the steel-con­

crete interface was measured by O.OOl-in. dial deflection gages.

The rotation of the joint was measured with a level bar gage

located at the center of the joint. Two O.OOOl-in. dial de­

flection gages were located on each side of the web and gave

an indication of the occurrence of local buckling in the neg­

ative moment region. These gages were placed between the upper

and lower flanges and they measured the relative deflection of

the two flanges.

2.4 Control Test Program

A test program was conducted to determine the mech­

anical properties of the materials used in the composite test

specimens. The physical dimensions were also obtained in order

to determine the section properties of the beams.

Table 1 presents the mechanical properties of the

16 WF 40 that were determined from tests of tensile specimens

which were cut from a 2-ft. length of the center 12-ft. length

of beam which remained after fabrication of the two composite

specimens. Three web and four flange tensile specimens were

tested using a 120 kip mechanical testing machine.

-11-

Page 14: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

The 4 standard 6-in. by 12-in. concrete cylinders,

which were cast during the fabrication of the slab, were tested

to determine the mechanical properties of the concrete. Table 2

tabulates the compressive strengths and moduli of elasticity

ascertained from these cylinder tests.

The remaining 10-ft. length of the 16 WF 40 steel beam

was tested as schematically shown in Figure 11. The purpose of

the control test was to determine the moment-curvature behavior

of the steel beam under a steep moment gradient, similar to that

which would occur in test specimens Jl and J2. This moment cur­

vature curve could then be compared with that obtained during the

testing of specimens Jl and J2. The load was applied to the con­

trol test beam by a 300 kip hydraulic testing machine, and the

instrumentation was similar to that used for specimens Jl and J2.

2.5 Load Program

Load was applied to the ends of the column in each

test specimen by means of hydraulic tension jacks as shown in

Figure 12. This load was measured using calibrated tension rods

placed between the tension jacks and the loading frame. These

rods are also shown in Figure 12.

A calibrated compression dynamometer was used to mea­

sure the beam reaction in the positive moment region as shown in

-12-

Page 15: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

Figure 12. The beam reaction in the negative moment region

however, was taken directly by the loading frame.

Load was applied to each test specimen in increments

which varied from approximately zero to 5 kips. Initially strain

controlled and thus the increments of load were fairly uniform.

However, as plastification of the beam occurred, the tension

jacks maintained a nearly constant load up to the development

of the moment plateau. The test specimens were unloaded and re­

loaded at various stages of testing due to problems resulting

from the test frame. Figure 4 shows a picture of the testing

set-up prior to testing beam Jl.

Due to the fact that the negative moment region had a

lower theoretical moment capacity than the positive moment region,

it was necessary to brace the former area in order to develop

plastification in the positive moment region. Figures 4 and 13

clearly show the purpose of this brace.

-13-

Page 16: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

3. TEST RESULTS AND ANALYSIS

Plastification of one cross-section does not necessarily

signify the limit of usefulness of a structure. The limit of

usefulness is considered to have been reached, in plastic design,

with the formation of a collapse mechanism. Thus, the sequence

of formation of the plastic hinges and the associated rotation

capacity requirement at each plastic hinge location is signif­

icant.

Figure 14 shows typical non-dimensionalized moment

curvature curves which represent the behavior in both the positive

and negative moment regions of a two span composite beam. Since

it is evident that the plastic hinge in the negative moment

region will form first, adequate rotation capacity must be pro­

vided at this hinge location in order to ensure the formation of

the positive plastic hinges and thus a mechanism. Hence, more

severe restrictions must be considered for the local buckling

characteristics of the plate elements at the negative plastic

hinge locations. They must be able to undergo large deformations

during plastification without experiencing a loss in load ca­

pacity.

-14-

Page 17: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

Existing criteria for predicting local buckling in

steel wide-flange beams subjected to combined bending moments

and axial load was developed by Geerhard Haaijer. 7 ,e Dr. Haaijer

used the incremental stress theory to solve the equilibrium

condition for an orthotropic differential plate element. Solving

this problem for an axially loaded plate also subjected to bend­

ing in the plane of the plate yielded criteria for predicting web

local buckling.

Figure 15 is a replot of Haaijer Figure 6.116 where

three curves are plotted for various ratios of maximum strain

to yield strain. Note that as the ratio of the maximum strain

to yield strain increases, the allowable web depth to thickness

ratio decreases. Thus, the greater the rotation capacity re­

quirement the more crit±cal local buckling becomes.

Figure 16 shows the theoretical curve developed by

Haaijer as well as his design approximation. The design approx­

mation shows that for the case of a bending member subjected to

zero axial load, the allowable depth to thickness ratio is

limited to 70. At the other extreme, Haajard chose a limiting

value of 43 on the basis that the web, under uniform compression,

does not have to go beyond the yield strain value. He pointed

out that to reach strain-hardening strain a lower value of 31

would have to be used.

-15-

Page 18: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

Haaijer, in deriving his design approximation, made

the following assumptions:

(1)

( 2)

( 3)

( 4)

d/df

= 1. 05

A/A = 2.0w

A7 Steel

emf = 4.0eo

Assumption number four is the crucial one. In order to make

this assumption, Haaijer had to do much experimental work.

Assumption number four says that for any wide-flange member, no

matter what the load condition is, if the width to thickness

ratios are such that the cross-section can undergo maximum

straining to four times the yield strain value the plastic hinge

can be formed. This is a very important criteria for it is the

key to developing a theory for predicting the occurrence of

local buckling. Note, however, that when shear connectors are

omitted in continuous beams, the anchorage of the slab subjects

the beam to axial force. In that case, the design approximation

in Figure 16 may. be used.

For composite members, however, the case is not quite

so simple for in any given structure the negative plastic moment

is not likely to equal the positive plastic moment. The key to

applying Haaijers theory to composite beams rests with determining

-16-

Page 19: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

some particular ratio of maximum to yield strain which will in­

sure adequate rotation for all cases to form a failure mechanism.

Analyzing some theoretical moment curvature curves

for varying wide flange members, it appears as though Haaijer

considered a plastic hinge to have formed if the section was

capable of reaching 98% of its theoretical plastic moment.

In other words, when a wide-flange reaches a maximum strain of

4 times its yield strain the associated moment with that par­

ticular curvature will, on the average, be approximately .98 M •P

Figure 17 summarizes the results of test specimens Jl

and J2 in the form of moment versus curvature plots. The curve

for the plain rolled of control beam was also included in order

to have a basis of comparison.

Specimen Jl behaved somewhere in between that of the

plain rolled beam and that of the composite beam J2. Since Jl

had discontinuity in reinforcing from the positive to the negative

moment region, it was predicted that it would not be able to

develop the full moment capacity for the composite section. While

Jl did exceed the moment capacity of the plain member, it was

only possible after very large deformations.

Figures 18 and 19 clearly show that local buckling did

occur in the negative moment region for both Jl and J2. While all

-17-

Page 20: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

three beams yielded at approximately the same moment, J2 did begin

to yield at a slightly higher moment due to the position of its

neutral axis. However, specimen J2 was not able to develop the

theoretical plastic moment based on the steel beam plus the

reinforcement, due to the occurrence of local buckling. If

stiffners had been provided, as was the case in beams CC-3F and

CC-4F of Ref. 4, it is probable that the plastic moment capacity

would have been attained.

-18-

Page 21: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

4. SU~Y

Thus in conclusion, from all available information at

present it appears as though local buckling in composite members

can be predicted by depth to thickness ratios for the web.

Specifically, if a composite section can develop enough curvature

to reach .98 M local buckling will not have prevented thep

formation of a hinge. Naturally the ratio of the maximum to

yield strain ascertained from the composite beam in order to

develop 98% of M could be very much larger than the value ofp

4 assumed to be correct for wide-flange members; however, Figure

15 indicates that even with an extremely large jump in maximum

strain ratios, the curve will not vary much. Thus, if a con-

servative theory was developed based on a maximum strain ratio

of infinity our criteria would not be very much different from

that for a ratio of 12 or 20 or even 50.

-19-

Page 22: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

ACKNOWLEDGMENTS

The author wishes to acknowledge the special advice

and guidance that he received from his advisors Professors John

w. Fisher and J. Hartley Daniels.

The work described in this thesis was conducted as

part of a general investigation into the plastic design of

multi-story frames at Fritz Engineering Laboratory, Department

of Civil Engineering, Lehigh University. The experimental

investigation upon which this study was based was sponsored by

the American Iron and Steel Institute and Lehigh University.

This study was supported by loads provided by the National

Science Foundation for under graduate research.

The manuscript was typed by Mrs. Shirley Labert.

-20-

Page 23: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

5. TABLES AND FIGURES

-21-

Page 24: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

Property

TABLE 1

Mechanical Properties of 16 \'W 40

Flange Web

Yield Stress 36.4 l~si .40.0 ksi

. Modulus of Elasticity 29266.6 ksi 29900.0 ksi

Strain Hardening Strain .02520 in/in .02394 info~n

Strain Hardening Modulus 466 ksi 492 ksi

TABLE 2.

Mechanical Properties of Concrete

Compressive Strength 4110 ksi

Tangent r>lodulus 2480 ksi

(

, -22-

,.,

.'

Page 25: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

'.J

. .

-23-

\.:, ...,I illi!

. I

TI-~

;I--,

I

1 7,7 7/7 7t(

-=t6A~\-~~~~s-~--....D~~~c:.~\l

- '~~YU'L\'\'- C;"'T~"y .~RA.\~.E..

----~ ... __ . -

- ----_.--- \ - - \ ~'~'- \

~ \:..~\)\N(-:;· MO'M-e~\~

1>.:;e. "0

Page 26: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

.. -.- .-':

-.

-_. N <:>"\ ~.';

-:t: N."i= \... 'E.'-\"-\c. N. ~.

SU.~~~\""-'::>~~G.\r::>~s

f7\ .- -h\ -- - ---o tlo.""C ~

-=t:::>""E-~V\~-':"~'" .-'\"\C;~\~-~\~ ~\)t. ~C> - c.~\'<\~\\'\c\;)

-. -~i:-C::-T C;~~~ --_..-Coi·<~i.-=-~_·._ ..

Ii'.)

-l">I

--~ '.'

._._..1-._.._\._~ ._ .. __2- _

Page 27: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

-25-

,_......-._-

..

T -3---------·,----. " \~.

Page 28: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

Testing Set-Up for Specim n Jl

Figure 4

-26-

Page 29: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

-27-- ....."

~7'~7; 0 f-..

~ QJ.0.1

V_":! j'

~!A.

:1,

.\ ilt T

4-" C.o""-\c:.. 'S \....J:,.'h .

-

I -S-o~~y S.~.lli'~K£.\:o.-:'

~ -=.\'<>~ 40

II po..-:.lO

IJ I· . 'P Iir~« $"-=:-%:_------ .""'"" I " .,:

f-o".-------~ ..!;>..:.~ ....... 16' Ij I

=:1--.r

.J d.- 'I~

.;".

, I.

~-.q

\<;,.1/')<. c:. '\... \ .,

'S, '\".~\!:.l:.\>.....~t. '?'-A.\-~ ~~ "i'r-.1' ,I, ~-

.1

l\ <:>0<:> ~~\ ~~\"".

4" c...::.~c.... ":;;"'A£>.

r ~'-O"T;----------f:ir-----------..

(

"t""--- .._..~_.. \ \ ~.

Page 30: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

=-

-28-

.~ rr \C~ ~

Page 31: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

-29-

I

~I--rI

- -

- ----

I- J

---III

I

tI,

I I II T

I 0I II

( II

II- I

I I I I r! I I

II

Page 32: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

Figure 8

-30-

Page 33: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

-31-

I

TI1

I

-,-IiII

II;

TiI

I!I

II

-I

II\

I\

I--1_

Page 34: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

·"':.:-,,,-\

.l~ "-' .)

~\~ \0I

VJrvI

Page 35: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

'S-\~s \_·~c\:>

""''t:..;.::s;.\""~"\,>

coI"IIIl::

IV-JV-JI

Page 36: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

"

\ Y_ II ,l l ' \ \- '1 - \~ \'-' . - Co el\ ..... '!>\\ ....d.

II __

~\~. \2-

'.

IW~I

Page 37: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

Figure 13

-35-

Page 38: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

.. .

IINmI

\0

)

-------e-\----

t> ~

t . 1~:;-S·.-·--:J~-·-;1\ ~

~~ ~~ \ ~~

\c:.. ~=. "C..,

'-

-~----f

Page 39: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

\.CO+

-37-

Page 40: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

-38-

\

~'''''~....~~

-+I-----------~·-::'0 '-to So Gl::l 10

I~,l

Page 41: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

- 5000

I • • ! • .. . .

_ \.\C>OO.

-\000

I\00

ISec

@- "ib.\~\-\\,,\",,,\~~ c:;;;.\~~~ 0',-: L.o,-~L.

~u c:.'(..\- \N~

,'""-

1\ ..--,\ I

ILNillI

Page 42: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

, , . ,

.o~---­

I~oI

-L~ c... '" '-~'-J:::...~\.-. \ 'No.~ .

\~

-:s- \

\0

'\J,r:.\~\.\'M\("""c;.t&'t./. ~,

----:o:-:c:;-----·------~------------.. ~---·---~~. ~ P Ll; .~ ,0'2.. ,0\ .0\ ,OG.

D~'-'\..-c..c:...~,I ~ (\~~

\B

Page 43: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

.. ------- ,. ;'--'- , (

'. I ,

=,--- .:.JL.:--=--------~-----------.------ ...----. -- -'-----

7..0

~ut..'t..,\..\\-\Gt

~",,~~0

.o~ ,0<;

( \"-\~\-\'C~

.0, ,°60 I.j::>I-'I

\~

Page 44: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

6. REFERENCES

1. American Institute of Steel ConstructionMANUAL OF STEEL CONSTRUCTION, AISC, New York 1963

2. Beedle, L. S.PLASTIC DESIGN OF STEEL FRAMES, John Wiley and SonsNew York 1958

3. Daniels, J. H. and Fisher, J. W.STATIC BEHAVIOR OF CONTINUOUS COMPOSITE BEAMS, FritzEngineering Laboratory Report No. 324.2, Lehigh University,March 1966

4. Daniels, J. H.COMBINED LOAD ANALYSIS OF UNBRACED FRAMES, FritzEngineering Laboratory Report No. 338.2, Lehigh University,March 1966

5. Fritz Laboratory StaffPLASTIC DESIGN OF MULTI-STORY FRAMES-LECTURE NOTES,Fritz Engineering Laboratory Report No. 273.20, LehighUniversity, August 1965

6. Kroll, G. D.THE DEGREE OF COMPOSITE ACTION AT BEAM TO COLUMN JOINTS(Honors Thesis) Fritz Engineering Laboratory Report No.338.4, Lehigh University, April 1968

7. American Society of Civil EngineersCOMMENTARY ON PLASTIC DESIGN IN STEEL, Welding ResearchCouncil and the ASCE, 1961

8. Haaijer, GeerhardTRANSACTIONS OF THE AMERICAN SOCIETY OF THE CIVIL ENGINEERS,"Buckling", New York, Vol. 125, 1960

9. Yam, Lloyd, C. P. and Chapman, J. C.THE INELASTIC BEHAVIOR OF SIMPLY SUPPORTED COMPOSITEBEAMS OF STEEL AND CONCRETE, London, October 1967

10. Slutter, Roger G. and Driscoll, George C. Jr.FLEXURAL STRENGTH OF STEEL CONCRETE BEAMS, Journal ofthe Structural Division, ASCE, Vol. 91, No. ST2, 1965

- 42-

Page 45: LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller · 2012-08-01 · LOCAL BUCKLING OF COMPOSITE BEAMS David Geoffrey Miller A THESIS Presented to the Department of Civil Engineering

" TABLE OF CONTENTS

Page

1. INTRODUCTION 1

2. EXPERIMENTAL INVESTIGATION 6

2.1 Description of Test Specimens and 6Design Criteria

2.2 Construction and Fabrication of 8Specimens

2.3 Instrumentation· 10

2.4 Control Test Program 11

2.5 Load Program 12

3. TEST RESULTS AND ANALYSIS 14

4. SUMMARY 19

5. TABLES· .AND FIGURES 21

6. REFERENCES 42