Liquid Chillers Rev

download Liquid Chillers Rev

of 136

Transcript of Liquid Chillers Rev

  • 8/14/2019 Liquid Chillers Rev

    1/136

    J.ILANGUMARANJ.ILANGUMARAN

  • 8/14/2019 Liquid Chillers Rev

    2/136

    Liquid Chilling SystemLiquid Chilling System

    A liquid chilling system cools water, brine,A liquid chilling system cools water, brine,or other secondary coolant for airor other secondary coolant for airconditioning or refrigeration.conditioning or refrigeration.

    The system may be either factory assembledThe system may be either factory assembledand wired or shipped in sections forand wired or shipped in sections forerection in the fielderection in the field

  • 8/14/2019 Liquid Chillers Rev

    3/136

    Components of chillers (vapor compressionComponents of chillers (vapor compressionsystem)system)

  • 8/14/2019 Liquid Chillers Rev

    4/136

    Chilled Water SystemChilled Water System

    Air Handling unit Circulating Pumps

    Condenser

    Chiller - Pump Evaporator

    Chiller

    Chilled Water Headers

  • 8/14/2019 Liquid Chillers Rev

    5/136

    Components of vapor compression systemComponents of vapor compression system

  • 8/14/2019 Liquid Chillers Rev

    6/136

    Chilled Water SystemChilled Water SystemChilled Water SystemChilled Water SystemChilled Water SystemChilled Water SystemChilled Water SystemChilled Water System

    Chiller Yard Pump

    Room

    HT

    OT

    PD

    To Hotel Tower 450Dia

    To Office Tower 400Dia

    To Podium 250Dia

  • 8/14/2019 Liquid Chillers Rev

    7/136

    Chiller YardChiller YardChiller YardChiller Yard

  • 8/14/2019 Liquid Chillers Rev

    8/136

    Multiple Chiller SystemMultiple Chiller System

    Parallel chilled water flowParallel chilled water flow

    arrangementarrangement

    Series water flow arrangementSeries water flow arrangement

  • 8/14/2019 Liquid Chillers Rev

    9/136

    Parallel chilled water flow arrangement

  • 8/14/2019 Liquid Chillers Rev

    10/136

    Series water flow arrangement

  • 8/14/2019 Liquid Chillers Rev

    11/136

    Type Of ChillersType Of Chillers

    Based OnBased On

    Condensing MediaCondensing Media

    Air cooledAir cooled

    Water cooledWater cooled

    Based onBased on

    CompressorCompressor

    ReciprocatingReciprocating

    CompressorCompressor

    Screw CompressorScrew Compressor

    CentrifugalCentrifugal

    CompressorCompressor

  • 8/14/2019 Liquid Chillers Rev

    12/136

    Chiller packageChiller package

    Hermetically sealed Compressor & Motor,Hermetically sealed Compressor & Motor,

    Condenser, Expansion device & Evaporator, interCondenser, Expansion device & Evaporator, inter--connected to form refrigeration cycle withconnected to form refrigeration cycle with

    Fully charged refrigerant.Fully charged refrigerant.

    Safety & operational controls.Safety & operational controls.

    Lubrication system.Lubrication system.

    Operation monitoring devices.Operation monitoring devices.

    Control panel duly wired.Control panel duly wired.

    Starter with Disconnect switch duly wiredStarter with Disconnect switch duly wired

  • 8/14/2019 Liquid Chillers Rev

    13/136

    ChillersChillers

    AirAir--cooled Reciprocating Chiller ORcooled Reciprocating Chiller OR

    Water cooled Reciprocating ChillerWater cooled Reciprocating Chiller

    AirAir--cooled Screw Chiller OR Watercooled Screw Chiller OR Water

    cooled Screw Chillercooled Screw ChillerAirAir--cooled Centrifugal Chiller ORcooled Centrifugal Chiller OR

    Water cooled Centrifugal ChillerWater cooled Centrifugal Chiller

  • 8/14/2019 Liquid Chillers Rev

    14/136

    Chiller with Reciprocating CompressorChiller with Reciprocating Compressor

    1.1. Semi Hermetic Reciprocating compressorSemi Hermetic Reciprocating compressor

    2.2. MufflerMuffler3.3. Fan & condenser coilFan & condenser coil

    4.4. Filter drierFilter drier

    5.5. Liquid Line sight glassLiquid Line sight glass

    6.6. Moisture indicatorMoisture indicator7.7. Expansion valveExpansion valve

    8.8. DxDx--EvaporatorEvaporator

    9.9. Control PanelControl Panel

    10.10. StarterStarter

    11.11. ControlsControls

  • 8/14/2019 Liquid Chillers Rev

    15/136

    Chiller with CentrifugalChiller with Centrifugal

    CompressorCompressorSemi Hermetic Centrifugal compressorSemi Hermetic Centrifugal compressor

    Fan & condenser coilFan & condenser coilLiq. Line sight glassLiq. Line sight glass

    Moisture indicatorMoisture indicator

    Fixed orifice assemblyFixed orifice assembly

    Flooded EvaporatorFlooded Evaporator

    External Lubrication systemExternal Lubrication system

    External Capacity control systemExternal Capacity control system

    Motor cooling systemMotor cooling system

    Control PanelControl Panel

    StarterStarter

    ControlsControls

  • 8/14/2019 Liquid Chillers Rev

    16/136

    Chiller with ScrewChiller with Screw

    CompressorsCompressorsSemi Hermetic Screw compressorSemi Hermetic Screw compressor

    Oil SeparatorOil SeparatorFan & condenser coilFan & condenser coil

    Receiver/SubReceiver/Sub--cooling coilscooling coils

    Filter drierFilter drier

    Liq. Line sight glassLiq. Line sight glass

    Moisture indicatorMoisture indicator

    Expansion valveExpansion valve

    DxDx--EvaporatorEvaporator

    Lubrication systemLubrication system

    Control PanelControl Panel

    StarterStarter

    ControlsControls

  • 8/14/2019 Liquid Chillers Rev

    17/136

    Basis of DesignBasis of Design

    The Chilled Water System has beenThe Chilled Water System has been

    designed to produce the chilled waterdesigned to produce the chilled water

    at following so as to achieve theat following so as to achieve the

    comfort conditionscomfort conditionsby Air conditioningby Air conditioning

    system at floors.system at floors.

    Entering Chilled Water Temp. : 55Entering Chilled Water Temp. : 55FF

    Leaving Chilled Water Temp.Leaving Chilled Water Temp. : 45: 45FF

  • 8/14/2019 Liquid Chillers Rev

    18/136

    Variable Speed DriveVariable Speed Drive

    All the chilled water pumps areAll the chilled water pumps are

    provided with a microprocessor based,provided with a microprocessor based,

    pulse width modulated, adjustablepulse width modulated, adjustable

    frequency AC drive.frequency AC drive.

    The drive controls AC motor.The drive controls AC motor.

  • 8/14/2019 Liquid Chillers Rev

    19/136

    Chilled Water systemChilled Water system

    OperationOperation-- LogicLogic

    The whole system is automatic thruThe whole system is automatic thru

    Building Management System to achieveBuilding Management System to achievethe specified conditions at floors.the specified conditions at floors.

    Once temperature is achieved in conditionOnce temperature is achieved in condition

    space the motorized 2space the motorized 2--way valve closesway valve closeswhich in turn increases the difference inwhich in turn increases the difference in

    pressure between supply & Return pipes.pressure between supply & Return pipes.

    Reduction in speed reduces the chilledReduction in speed reduces the chilled

    water flow in the system and save thewater flow in the system and save the

    energy.energy.

  • 8/14/2019 Liquid Chillers Rev

    20/136

    Chilled Water system OperationChilled Water system Operation--

    LogicLogic

    Once load in condition space increases,Once load in condition space increases,two way valves opens thus reduces thetwo way valves opens thus reduces the

    pressure difference between supply &pressure difference between supply &

    return pipes.return pipes.

    Increase in speed, increases the ChilledIncrease in speed, increases the Chilled

    flow to meet the requirement of conditionflow to meet the requirement of condition

    spacespace..

  • 8/14/2019 Liquid Chillers Rev

    21/136

    PumpsPumps-- Automatic ShutdownAutomatic Shutdown

    The VFD shuts down the pump shouldThe VFD shuts down the pump shouldany of the following happens:any of the following happens:

    Over TemperatureOver Temperature

    Motor OverloadMotor Overload

    High Motor CurrentHigh Motor Current

    Motor GroundMotor Ground

  • 8/14/2019 Liquid Chillers Rev

    22/136

    Chiller principleChiller principle

  • 8/14/2019 Liquid Chillers Rev

    23/136

    Reciprocating ChillersReciprocating Chillers

  • 8/14/2019 Liquid Chillers Rev

    24/136

    Refrigeration cycleRefrigeration cycle

  • 8/14/2019 Liquid Chillers Rev

    25/136

    Refrigeration cycleRefrigeration cycle

  • 8/14/2019 Liquid Chillers Rev

    26/136

    RefrigerationCycleRefrigerationCycle

    Motor Compressor

    MeteringDevice

    Condenser

    T

    0C

    on

    ditio

    ne

    dS

    pace

    Retu

    rnair

  • 8/14/2019 Liquid Chillers Rev

    27/136

    Reciprocating compressors

  • 8/14/2019 Liquid Chillers Rev

    28/136

    Reciprocating CompressorReciprocating Compressor

  • 8/14/2019 Liquid Chillers Rev

    29/136

    Semihermetic reciprocating compressorsSemihermetic reciprocating compressors

  • 8/14/2019 Liquid Chillers Rev

    30/136

    Semihermetic reciprocating compressorsSemihermetic reciprocating compressors

  • 8/14/2019 Liquid Chillers Rev

    31/136

    Thermostatic expansion valveThermostatic expansion valve

  • 8/14/2019 Liquid Chillers Rev

    32/136

    Thermostatic expansion valveThermostatic expansion valve

  • 8/14/2019 Liquid Chillers Rev

    33/136

  • 8/14/2019 Liquid Chillers Rev

    34/136

    Returning discharge to suction

  • 8/14/2019 Liquid Chillers Rev

    35/136

    Capacity controlCapacity control Controlling suction pressure by throttling;Controlling suction pressure by throttling;

    Controlling discharge pressure;Controlling discharge pressure;

    Returning discharge gas to suction;Returning discharge gas to suction;

    Adding reexpansion volume;Adding reexpansion volume;

    Changing the stroke;Changing the stroke;

    Opening a cylinder discharge port to suction whileOpening a cylinder discharge port to suction whileclosing the port to discharge manifold;closing the port to discharge manifold;

    Changing compressor speed;Changing compressor speed;

    Closing off cylinder inlet, andClosing off cylinder inlet, and

    Holding the suction valve openHolding the suction valve open

  • 8/14/2019 Liquid Chillers Rev

    36/136

    Factors Affecting the performance ofFactors Affecting the performance of

    Refrigeration unitRefrigeration unit

    Discharge pressureDischarge pressure

    Out door air temperatureOut door air temperature

    Air circulation thruAir circulation thru

    condensercondenser

    Condenser fins & tubeCondenser fins & tubeconditioncondition

    Space between chillersSpace between chillers

    Condenser fansCondenser fans

    Excess refrigerantExcess refrigerant Evaporator pressureEvaporator pressure

    Lack of refrigerantLack of refrigerant

    Less water flowLess water flow

    Erratic operation ofErratic operation of

    Lubrication systemLubrication system

    Low oil pressureLow oil pressure

    Oil filter chokeOil filter choke

    Quality & Accuracy ofQuality & Accuracy of

    controls and Sensorscontrols and Sensors Calibration & settingCalibration & setting

    Proper installationProper installation

    Routine & preventiveRoutine & preventive

    maintenancemaintenance

    TimelyTimely

    ProperlyProperly

  • 8/14/2019 Liquid Chillers Rev

    37/136

    Factors Affecting theFactors Affecting the

    performance ofperformance ofAir & water side systemAir & water side system

    Air balancingAir balancing

    Supply air flowSupply air flow

    Return air flowReturn air flow

    Grills and damperGrills and damper

    adjustmentadjustment Fresh air flowFresh air flow

    Dampers adjustmentDampers adjustment

    AHU performanceAHU performance

    Filters conditionFilters condition

    Cooling coilCooling coil

    Belts & pulleysBelts & pulleys

    DampersDampers

    Quality,Accuracy andQuality,Accuracy and

    setting of Thermostats,setting of Thermostats,Humidistat and SensorsHumidistat and Sensors

    Chilled water distributionChilled water distribution

    StrainersStrainers

    Flow control ValvesFlow control Valves

    Pump performancePump performance

    Chiller performanceChiller performance

    Routine & preventiveRoutine & preventivemaintenancemaintenance

  • 8/14/2019 Liquid Chillers Rev

    38/136

    Air Cooled CondenserAir Cooled Condenser

  • 8/14/2019 Liquid Chillers Rev

    39/136

    E F

  • 8/14/2019 Liquid Chillers Rev

    40/136

    DxDx EvaporatorEvaporator --Coil & FinsCoil & Fins

    TypeType

    DX E tDX E t Sh ll &T bSh ll &T b

  • 8/14/2019 Liquid Chillers Rev

    41/136

    DX EvaporatorDX Evaporator--Shell &TubeShell &Tube

    typetypeWater flow thru the shell.

    Refrigerant is in tubes.

    DX E aporatorDX Evaporator Shell &TubeShell &Tube

  • 8/14/2019 Liquid Chillers Rev

    42/136

    DX EvaporatorDX Evaporator-- Shell &TubeShell &Tube

    typetypeWater flow thru the shell

    Refrigerant is in tubes

    C i i lC iti l F t

  • 8/14/2019 Liquid Chillers Rev

    43/136

    Critical FactorsCritical Factors

    Shell & Tube EvaporatorsShell & Tube EvaporatorsQuality of watersQuality of waters

    CleanedCleaned

    Chemically treatedChemically treated

    Velocity of water should not be higherVelocity of water should not be higher

    than recommendedthan recommended Proper setting of Expansion valveProper setting of Expansion valve

    Adequate water flowAdequate water flow

    Proper installation of Sensors /ThermistorProper installation of Sensors /Thermistor

  • 8/14/2019 Liquid Chillers Rev

    44/136

    Flooded EvaporatorsFlooded EvaporatorsIn flooded type evaporator aIn flooded type evaporator a

    constant Refrigerant liquid level isconstant Refrigerant liquid level ismaintained.maintained.

    A float valve / Level switches areA float valve / Level switches are

    used as metering device to maintainused as metering device to maintainthe constant level.the constant level.

    TypesTypes

    Coil & Fins typeCoil & Fins typeShell & Tube typeShell & Tube type

    Fl d d E tFlooded E aporator

  • 8/14/2019 Liquid Chillers Rev

    45/136

    Flooded EvaporatorFlooded Evaporator

    Coil & Fins typeCoil & Fins type

    Fl d d E tFl d d E t

  • 8/14/2019 Liquid Chillers Rev

    46/136

    Flooded EvaporatorFlooded Evaporator

    Shell & Tube TypeShell & Tube Type

    Orifice Assembly

    Distributor

    Tubes

    From CondenserTo Compressor

  • 8/14/2019 Liquid Chillers Rev

    47/136

    Metering DevicesMetering DevicesCapillary tubeCapillary tube

    Fixed orifice typeFixed orifice type

    Float valveFloat valve

    Automatic expansion valveAutomatic expansion valveThermostatic expansion valveThermostatic expansion valve

    Electronic expansion valveElectronic expansion valve

  • 8/14/2019 Liquid Chillers Rev

    48/136

    Automatic expansion valveAutomatic expansion valveAutomatic expansion valveAutomatic expansion valveAutomatic expansion valveAutomatic expansion valveAutomatic expansion valveAutomatic expansion valve

    It allows the flow ofIt allows the flow of

    refrigerant torefrigerant tomaintain the constantmaintain the constant

    pressure inpressure in

    evaporator.evaporator.

    It does not allow theIt does not allow therefrigerant flow torefrigerant flow to

    maintain the Suctionmaintain the Suction

    superheat.superheat.

    Thermostatic ExpansionThermostatic Expansion

  • 8/14/2019 Liquid Chillers Rev

    49/136

    Thermostatic ExpansionThermostatic Expansion

    valvevalve

  • 8/14/2019 Liquid Chillers Rev

    50/136

    Thermostatic Expansion valveThermostatic Expansion valve

  • 8/14/2019 Liquid Chillers Rev

    51/136

    Electronic Expansion ValveElectronic Expansion Valve

  • 8/14/2019 Liquid Chillers Rev

    52/136

    Sensing Bulb FixingSensing Bulb Fixing

    Smaller diameter 1Smaller diameter 1Inch and belowInch and belowsuction linesuction line

    Sensing bulb shouldSensing bulb should

    be on topbe on topAbove 1 Inch dia,Above 1 Inch dia,

    4 O4 O Clock Position.Clock Position.

    Sensing Bulb shouldSensing Bulb shouldbe fully covered bybe fully covered byinsulating materialinsulating material..

    dP i d i

  • 8/14/2019 Liquid Chillers Rev

    53/136

    Protective devicesProtective devices

    A highA high--pressure cutout.pressure cutout.HighHigh--temperature control devices to protect againsttemperature control devices to protect against

    overheating and oil breakdown.overheating and oil breakdown.

    Motor over temperature protective devicesMotor over temperature protective devices LowLow--pressure protection may be provided forpressure protection may be provided for

    Suction gas and compressorSuction gas and compressor

    Time delay, or lockouts with manual resets,Time delay, or lockouts with manual resets,prevents damage to both compressor motor andprevents damage to both compressor motor andcontactors from repetitive rapidcontactors from repetitive rapid--starting cyclesstarting cycles

    Low voltage and phase loss or reversal protectionLow voltage and phase loss or reversal protection

    is used on some systems. Phase reversalis used on some systems. Phase reversalprotection is used with multiprotection is used with multi--phase devices tophase devices toensure the proper direction of rotation.ensure the proper direction of rotation.

    Suction line strainer.Suction line strainer.

    Testing of Positive Displacement Refrigerant CompressorsTesting of Positive Displacement Refrigerant Compressors..

  • 8/14/2019 Liquid Chillers Rev

    54/136

    g f p f g pg f p f g p

    Compressor tests are of two types: the firstCompressor tests are of two types: the firstdetermines capacity, efficiency, sound level, motordetermines capacity, efficiency, sound level, motor

    temperatures, etc.; the second predicts thetemperatures, etc.; the second predicts thereliability of the machine.reliability of the machine.

    Standard rating conditions, which are usuallyStandard rating conditions, which are usuallyspecified by compressor manufacturers, includespecified by compressor manufacturers, includethe maximum possible compression ratio, thethe maximum possible compression ratio, themaximum operating pressure differential, themaximum operating pressure differential, themaximum permissible discharge pressure, and themaximum permissible discharge pressure, and the

    maximum inlet and discharge temperaturemaximum inlet and discharge temperature Lubrication requirementsLubrication requirements

    Power requirements for compressor startingPower requirements for compressor starting

    Reciprocating ChillersReciprocating Chillers ControlsControls

  • 8/14/2019 Liquid Chillers Rev

    55/136

    Reciprocating ChillersReciprocating Chillers ControlsControls

    Discharge Pressure Control (High Pressure Control)Discharge Pressure Control (High Pressure Control)

    Its function is to switch off the compressor, Once dischargeIts function is to switch off the compressor, Once dischargepressure exceeds the prepressure exceeds the pre--determineddetermined set pressureset pressure..

    Set PointSet Point Cut outCut out -- 425 (+ or425 (+ or 6 ) Psig with R6 ) Psig with R--22 Refrigerant22 Refrigerant

    Cut InCut In -- 320 (+ or320 (+ or 20) Psig20) Psig

    Low Pressure Control (Depends upon Manufacturer)Low Pressure Control (Depends upon Manufacturer) Its function is to unload the compressor, once Suction /Its function is to unload the compressor, once Suction /

    Evaporator pressure decreases to pre set pressure. Some timeEvaporator pressure decreases to pre set pressure. Some timeused to switch off the compressor.used to switch off the compressor.

    Set PointSet Point Cut out 30 (+ orCut out 30 (+ or -- 5) Psig with R5) Psig with R--22 refrigerant.22 refrigerant.

    Cut In 45 (+ orCut In 45 (+ or 5) Psig.5) Psig.

    Reciprocating ChillersReciprocating Chillers ControlsControls

  • 8/14/2019 Liquid Chillers Rev

    56/136

    Reciprocating ChillersReciprocating Chillers ControlsControls

    Low Water Temperature ControlLow Water Temperature Control

    Its function is to stop the refrigeration by stopping the compreIts function is to stop the refrigeration by stopping the compressor, oncessor, onceevaporator water temperature goes down below Set point so as toevaporator water temperature goes down below Set point so as to avoidavoidfreezing of water in the evaporator of chiller. Some time, it isfreezing of water in the evaporator of chiller. Some time, it is called ascalled as

    AntiAnti--Freeze.Freeze.

    Set Point 34 to 36Set Point 34 to 36 oo FF

    Low Refrigerant Temperature ControlLow Refrigerant Temperature Control

    It is used for not allowing the refrigerant temperature to go bIt is used for not allowing the refrigerant temperature to go below Setelow Setpoint, so as to avoid freezing of water and as well as loosing tpoint, so as to avoid freezing of water and as well as loosing theheefficiency of chiller.efficiency of chiller.

    Flow ControlFlow Control

    Its function is to ensure the adequate water flow through evapoIts function is to ensure the adequate water flow through evaporator.rator.Once flow decreases below set point, The switch will actuate andOnce flow decreases below set point, The switch will actuate and givegivealarm / stop signal to control panel, to avoid lower water tempealarm / stop signal to control panel, to avoid lower water temperature orrature orfreezing of water in evaporatorfreezing of water in evaporator

    Reciprocating ChillersReciprocating Chillers ControlsControls

  • 8/14/2019 Liquid Chillers Rev

    57/136

    Oil pressure differential switchOil pressure differential switch

    It is used to ensure proper lubrication of bearingsIt is used to ensure proper lubrication of bearingsand other moving parts of compressor. To ensureand other moving parts of compressor. To ensureproper lubrication, a pressure difference is to beproper lubrication, a pressure difference is to bemaintained between oil pump pressure and crankmaintained between oil pump pressure and crankcase pressure. Once Differential pressure is lowercase pressure. Once Differential pressure is lower

    than the preset differential pressure, It will actuatethan the preset differential pressure, It will actuateand alarm /stop the compressor operation.and alarm /stop the compressor operation.

    Set pointSet point 6 to 10 Psig6 to 10 Psig-- DifferentialDifferential

    Ground Current SafetyGround Current Safety

    It opens on sensing a current to ground inIt opens on sensing a current to ground incompressor winding exceeds the 2.5 Amps.compressor winding exceeds the 2.5 Amps.

    Reciprocating ChillersReciprocating Chillers ControlsControls

  • 8/14/2019 Liquid Chillers Rev

    58/136

    In Adequate air flow thru condenserIn Adequate air flow thru condenser

    Condensing Pressure will increase.Condensing Pressure will increase.

    Load on compressor increases.Load on compressor increases.

    Power consumption will increase.Power consumption will increase. Cooling capacity will reduce.Cooling capacity will reduce.

    Leaving chilled water temperature will remain high.Leaving chilled water temperature will remain high.

    Inadequate chilled water flow through evaporatorInadequate chilled water flow through evaporator Low suction pressure & Low evaporating temperature.Low suction pressure & Low evaporating temperature.

    Liquid floodLiquid flood--back to compressor and may damageback to compressor and may damagecompressor discharge reeds (In Reciprocating compressor).compressor discharge reeds (In Reciprocating compressor).

    May damage the Helical of screw compressor.May damage the Helical of screw compressor. Ice formation may occur and burst the evaporator.Ice formation may occur and burst the evaporator.

    Cut out 30 (+ orCut out 30 (+ or -- 5) Psig with R5) Psig with R--22 refrigerant.22 refrigerant.

    Cut In 45 (+ orCut In 45 (+ or 5) Psig.5) Psig.

    Reciprocating ChillersReciprocating Chillers ControlsControls

  • 8/14/2019 Liquid Chillers Rev

    59/136

    p gp g

    NonNon-- Condensable gases in the systemCondensable gases in the system

    Condensing Pressure will be high.Condensing Pressure will be high.

    Load on compressor increases and compressorLoad on compressor increases and compressorwill be very hot.will be very hot.

    Power consumption will be high.Power consumption will be high.

    Cooling capacity will reduce.Cooling capacity will reduce.

    Leaving chilled water temperature will remainLeaving chilled water temperature will remainhigh.high.

    Poor cooling in conditioned space.Poor cooling in conditioned space.

    Refrigerant ChargeRefrigerant Charge

  • 8/14/2019 Liquid Chillers Rev

    60/136

    g gg g

    Less chargeLess charge Compressor suction pressure will be low.Compressor suction pressure will be low.

    Evaporator pressure and temperature will be low.Evaporator pressure and temperature will be low.

    Heavy flashing and ice formation will occur at expansionHeavy flashing and ice formation will occur at expansionvalve, as a result lesser liquid refrigerant shall be availablevalve, as a result lesser liquid refrigerant shall be available

    for actual refrigeration.for actual refrigeration.

    BeingBeing low evaporator pressure & temperature, Any moisturelow evaporator pressure & temperature, Any moisture

    present in refrigerant will freeze expansion valve orifice andpresent in refrigerant will freeze expansion valve orifice andrestrict the refrigerant flow.restrict the refrigerant flow.

    Lower cooling capacity.Lower cooling capacity.

    Over chargeOver charge

    Higher head pressure and higher suction pressure.Higher head pressure and higher suction pressure. Load on compressor, will draw more current andLoad on compressor, will draw more current and

    unnecessary High power consumption.unnecessary High power consumption.

    Liquid flood back to compressor and can damage dischargeLiquid flood back to compressor and can damage dischargereeds.reeds.

  • 8/14/2019 Liquid Chillers Rev

    61/136

    Centrifugal ChillersCentrifugal Chillers

  • 8/14/2019 Liquid Chillers Rev

    62/136

    Working Of centrifugal Chiller

  • 8/14/2019 Liquid Chillers Rev

    63/136

    Refrigeration cycleRefrigeration cycle

  • 8/14/2019 Liquid Chillers Rev

    64/136

    Refrigeration cycleRefrigeration cycle

    (With Centrifugal Compressor(With Centrifugal Compressor))

    Centrifugal ChillerCentrifugal ChillerCentrifugal ChillerCentrifugal ChillerCentrifugal ChillerCentrifugal ChillerCentrifugal ChillerCentrifugal Chiller

  • 8/14/2019 Liquid Chillers Rev

    65/136

    Centrifugal ChillerCentrifugal ChillerCentrifugal ChillerCentrifugal ChillerCentrifugal ChillerCentrifugal ChillerCentrifugal ChillerCentrifugal Chiller

    (Water Cooled)(Water Cooled)(Water Cooled)(Water Cooled)(Water Cooled)(Water Cooled)(Water Cooled)(Water Cooled)

    Centrifugal CompressorCentrifugal Compressor

    CondenserCondenser

    --Shell & TubeShell & Tube

    Orifice AssemblyOrifice Assembly--11

    EconomizerEconomizer

    Orifice AssemblyOrifice Assembly--22 Flooded EvaporatorFlooded Evaporator

    Lubrication SystemLubrication System

    Motor Cooling SystemMotor Cooling System Control PanelControl Panel

    StarterStarter

    ControlsControls

  • 8/14/2019 Liquid Chillers Rev

    66/136

    CompressorCompressorCompressorCompressorCompressorCompressorCompressorCompressor

  • 8/14/2019 Liquid Chillers Rev

    67/136

    CompressorCompressorCompressorCompressoreeee

    Compressor &Compressor &

    Motor casing.Motor casing. IIstst stage impellerstage impeller

    IIIIndnd stage impellerstage impeller

    Volute casingsVolute casings

    Thrust bearingThrust bearing

    Journal bearingsJournal bearings

    High speed gearsHigh speed gearsassembly Inner oilassembly Inner oil

    guardsguards

    Gear spray nozzlesGear spray nozzles Motor stator & rotorMotor stator & rotor

    Suction inlet guideSuction inlet guide

    vane & actuatorvane & actuator

    Orifice AssemblyOrifice AssemblyOrifice AssemblyOrifice AssemblyOrifice AssemblyOrifice AssemblyOrifice AssemblyOrifice Assembly

  • 8/14/2019 Liquid Chillers Rev

    68/136

    Orifice AssemblyOrifice AssemblyOrifice AssemblyOrifice AssemblyOrifice AssemblyOrifice AssemblyOrifice AssemblyOrifice Assembly

    It is a assembly of twoIt is a assembly of twoplates having nos. ofplates having nos. of

    orificesorifices

    Liquid refrigerantLiquid refrigerant

    pressure reduces whilepressure reduces while

    passing thru it.passing thru it.

    Refrigerant flowRefrigerant flow

    controlled based oncontrolled based ondifferential pressuredifferential pressure..

    Orifice

    From Condenser To Evaporator

  • 8/14/2019 Liquid Chillers Rev

    69/136

    EconomizerEconomizer

    This is a intermediate pressure chamber in whichThis is a intermediate pressure chamber in which

    a intermediate pressure (Second stage suctiona intermediate pressure (Second stage suction

    pressure) is maintained.pressure) is maintained.

    The high pressure liquid refrigerant enters intoThe high pressure liquid refrigerant enters into

    economizer through orifice plate assembly.Whileeconomizer through orifice plate assembly.While

    liquid passing thru orifice assembly,a portion of itliquid passing thru orifice assembly,a portion of it

    evaporates (flashes) by absorbing heat fromevaporates (flashes) by absorbing heat from

    remaining liquid refrigerant and thus remainingremaining liquid refrigerant and thus remaining

    liquid gets cooled.liquid gets cooled.

    Evaporated refrigerant goes directly to 2nd stageEvaporated refrigerant goes directly to 2nd stage

    impeller for recycling.impeller for recycling.

  • 8/14/2019 Liquid Chillers Rev

    70/136

    Lubrication SystemLubrication System

  • 8/14/2019 Liquid Chillers Rev

    71/136

    Lubrication SystemLubrication System

    Oil SumpOil Sump

    Oil HeaterOil Heater

    Sight glassSight glass

    ThermometerThermometer

    Submersible OilSubmersible OilPumpPump

    Oil PressureOil Pressure

    regulatorregulator

    Oil cooling coilOil cooling coil

    Oil Filter & IsolatingOil Filter & Isolatingvalvevalve

    Oil by pass valvesOil by pass valves

    Oil pipingOil piping

    TemperatureTemperature

    sensorssensors

    Motor Cooling SystemMotor Cooling SystemMotor Cooling SystemMotor Cooling SystemMotor Cooling SystemMotor Cooling SystemMotor Cooling SystemMotor Cooling System

  • 8/14/2019 Liquid Chillers Rev

    72/136

    Motor Cooling SystemMotor Cooling SystemMotor Cooling SystemMotor Cooling SystemMotor Cooling SystemMotor Cooling SystemMotor Cooling SystemMotor Cooling System

    The hermetic motor are cooled by liquidThe hermetic motor are cooled by liquid

    refrigerant.refrigerant.Liquid refrigerant enters the motor housing thruLiquid refrigerant enters the motor housing thru

    an orifice and flows into a chamber surroundingan orifice and flows into a chamber surrounding

    the stator.the stator.The refrigerant flows from this chamber thru theThe refrigerant flows from this chamber thru the

    motor stator,thus cooling the stator and rotor.motor stator,thus cooling the stator and rotor.

    Liquid refrigerant evaporates by absorbing heatLiquid refrigerant evaporates by absorbing heatfrom stator and rotor.from stator and rotor.

    Finally Liquid & vapor mixture drain back toFinally Liquid & vapor mixture drain back to

    evaporator thru bottom pipes.evaporator thru bottom pipes.

    Electrical SystemElectrical SystemElectrical SystemElectrical SystemElectrical SystemElectrical SystemElectrical SystemElectrical System

  • 8/14/2019 Liquid Chillers Rev

    73/136

    Starter panelStarter panel

    SwitchesSwitches FusesFuses

    TransformerTransformer

    StarStar--Delta starter forDelta starter forcompressor motorcompressor motor

    DOL / StarDOL / Star--DeltaDelta

    starter for fansstarter for fansOverload relaysOverload relays

    TimersTimers

    ContractorsContractors

    Control panelControl panel

    Control switchControl switch Control TransformerControl Transformer

    FusesFuses

    RelaysRelays

    Microprocessor modulesMicroprocessor modules

    Unit control modulesUnit control modules

    TimersTimers

    AntiAnti--Recycle TimerRecycle Timer

    Coast down TimerCoast down Timer

    Safety switches (Outside)Safety switches (Outside)

  • 8/14/2019 Liquid Chillers Rev

    74/136

    Flow SwitchesFlow SwitchesFlow SwitchesFlow SwitchesFlow SwitchesFlow SwitchesFlow SwitchesFlow Switches

    It is a combination of Microprocessor andIt is a combination of Microprocessor and

    Flow sensor.Flow sensor.Function is to give alarm or stop signal toFunction is to give alarm or stop signal to

    chiller once flow reduces below set point.chiller once flow reduces below set point.

    Setting in % (Minimum 50 %).Setting in % (Minimum 50 %).Shall give alarm signal to BMS at alarmShall give alarm signal to BMS at alarm

    setting.setting.

    Shall stop the chiller at stop setting.Shall stop the chiller at stop setting.Modulate Chiller capacity suit toModulate Chiller capacity suit to

    temperature outlet.temperature outlet.

  • 8/14/2019 Liquid Chillers Rev

    75/136

    Low Pressure cut out SwitchLow Pressure cut out SwitchLow Pressure cut out SwitchLow Pressure cut out SwitchLow Pressure cut out SwitchLow Pressure cut out SwitchLow Pressure cut out SwitchLow Pressure cut out Switch

  • 8/14/2019 Liquid Chillers Rev

    76/136

    Low Pressure cut out SwitchLow Pressure cut out SwitchLow Pressure cut out SwitchLow Pressure cut out SwitchLo essu e cu ou S cLow Pressure cut out SwitchLow Pressure cut out SwitchLo essu e cu ou S c

    It is a combination ofIt is a combination of

    microprocessor and sensor.microprocessor and sensor.Some times it is a pressure switch.Some times it is a pressure switch.

    The function is to give alarm / stopThe function is to give alarm / stop

    signal to compressor once thesignal to compressor once theevaporator pressure reduces below theevaporator pressure reduces below theset point.set point.

    Set pointSet pointCut out 2.0 bar (RCut out 2.0 bar (R--12 & R12 & R--134a)134a)

    Cut in 2.3 to 2.4 barCut in 2.3 to 2.4 bar

    Winding Temperature SensorsWinding Temperature SensorsWinding Temperature SensorsWinding Temperature SensorsWinding Temperature SensorsWinding Temperature SensorsWinding Temperature SensorsWinding Temperature Sensors

  • 8/14/2019 Liquid Chillers Rev

    77/136

    It is a combination of microprocessor andIt is a combination of microprocessor andsensor.sensor.

    A sensor sense the temperature and giveA sensor sense the temperature and givesignal to microprocessor.signal to microprocessor.

    Microprocessor compares this signal withMicroprocessor compares this signal withset point and give out put command toset point and give out put command tostop the compressor if temperature isstop the compressor if temperature ishigher than set point.higher than set point.

    Set point 265 deg F.Set point 265 deg F. Will Stop Motor once motor temperatureWill Stop Motor once motor temperature

    rises to set point and will give alarm signalrises to set point and will give alarm signal

    to BMS.to BMS.

    Current LimiterCurrent LimiterCurrent LimiterCurrent LimiterCurrent LimiterCurrent LimiterCurrent LimiterCurrent Limiter

  • 8/14/2019 Liquid Chillers Rev

    78/136

    e L ee L ee L ee L e

    Its function is to limit the currentIts function is to limit the current

    drawn by motor within set point.drawn by motor within set point. Set point 85Set point 85--95 % of full load95 % of full load

    amperes.amperes.

    It will unload the compressor byIt will unload the compressor byclosing the suction vane damper andclosing the suction vane damper andover ride all inputs / feed back for:over ride all inputs / feed back for:

    Opening the vane dampers .Opening the vane dampers .

    Increasing the load on compressorIncreasing the load on compressor

    Critical FactorsCritical FactorsCritical FactorsCritical FactorsCritical FactorsCritical FactorsCritical FactorsCritical Factors(Evaporator)(Evaporator)(Evaporator)(Evaporator)(Evaporator)(Evaporator)(Evaporator)(Evaporator)

  • 8/14/2019 Liquid Chillers Rev

    79/136

    Soft & Clean water.Soft & Clean water.

    Cleaned tubes.Cleaned tubes.

    Adequate chilled water flow.Adequate chilled water flow.

    Adequate refrigerant flow.Adequate refrigerant flow.

    Sensors are fitted properly.Sensors are fitted properly.

    Application of Silicon grease orApplication of Silicon grease or

    alternative heat transfer paste.alternative heat transfer paste.Chilled water temperatures as designed.Chilled water temperatures as designed.

    Critical FactorsCritical FactorsCritical FactorsCritical FactorsCritical FactorsCritical FactorsCritical FactorsCritical Factors

  • 8/14/2019 Liquid Chillers Rev

    80/136

    (Motor Cooling System)(Motor Cooling System)(Motor Cooling System)(Motor Cooling System)(Motor Cooling System)(Motor Cooling System)(Motor Cooling System)(Motor Cooling System)

    Adequate liquid refrigerant flowAdequate liquid refrigerant flow

    Strainer (Filter cum drier)Strainer (Filter cum drier) Adjustment of Service valvesAdjustment of Service valves

    Design condenser pressureDesign condenser pressure

    Design evaporator pressureDesign evaporator pressure

    ProblemProblemProblemProblemProblemProblemProblemProblem

    Higher motor temperatureHigher motor temperature

  • 8/14/2019 Liquid Chillers Rev

    81/136

  • 8/14/2019 Liquid Chillers Rev

    82/136

    System BalanceSystem Balance a)a)CompressorCompressor-- Able to pump refrigerant at same rate atAble to pump refrigerant at same rate atwhich liquid ref. vaporizes in evaporatorwhich liquid ref. vaporizes in evaporator

    b)Condenserb)Condenser-- Able to reject heat from ref.at same rate atAble to reject heat from ref.at same rate atwhich ii picks up heat in evaporator and compressorwhich ii picks up heat in evaporator and compressor

    c)Throttlingc)Throttlingdevicedevice-- Able to feed liquid ref.to evaporator atAble to feed liquid ref.to evaporator atsame rate at which the refrigerant is vaporized in thesame rate at which the refrigerant is vaporized in the

    evaporatorevaporator Interconnecting liquid, suction and suction linesInterconnecting liquid, suction and suction lines-- capablecapable

    of handling the same rate of flow of liquid ref, lowof handling the same rate of flow of liquid ref, low

    pressure vapor and high pressure vapour with a minimumpressure vapor and high pressure vapour with a minimumof pressure dropof pressure drop

    Capacity controlCapacity control

  • 8/14/2019 Liquid Chillers Rev

    83/136

    p y

    ReciprocatingReciprocating

    compressorcompressorVariable speed motorVariable speed motor

    Compressor cylinderCompressor cylinder

    unloadingunloadingHotgasHotgas bypassbypass

    Centrifugal compressorCentrifugal compressor

    Guide vanes (inlet ofGuide vanes (inlet ofimpeller )impeller )

    Screw compressorScrew compressor

    Slide valve methodSlide valve methodLift valve methodLift valve method

    LubricationLubrication

  • 8/14/2019 Liquid Chillers Rev

    84/136

    Adequate Oil ChargeAdequate Oil Charge Manufacturer recommended oil should be used.Manufacturer recommended oil should be used.

    Recommended quantity of oil should be charged.Recommended quantity of oil should be charged.

    Lubricating oil container should never be left open.Lubricating oil container should never be left open. Excess ChargeExcess Charge

    Can cause hydraulic knocking and damage the pistons.Can cause hydraulic knocking and damage the pistons.

    It will be difficult to monitor the lubrication system.It will be difficult to monitor the lubrication system. Under ChargeUnder Charge

    Oil pump will not be able to build up the pressure.Oil pump will not be able to build up the pressure.

    Poor lubrication will damage the moving parts ofPoor lubrication will damage the moving parts ofcompressor.compressor.

    Centrifugal ChillerCentrifugal ChillerControlsControls

    Flow switches / Flow Sensor & Microprocessor CombinationFlow switches / Flow Sensor & Microprocessor Combination

  • 8/14/2019 Liquid Chillers Rev

    85/136

    It is a combination of Microprocessor and Flow sensor.It is a combination of Microprocessor and Flow sensor. Function is to give alarm or stop signal to chiller once flow reFunction is to give alarm or stop signal to chiller once flow reducesduces

    below set point.below set point.

    Setting in % (Minimum 50 %).Setting in % (Minimum 50 %).

    Shall give alarm signal to BMS at alarm setting.Shall give alarm signal to BMS at alarm setting.

    Shall stop the chiller at stop setting.Shall stop the chiller at stop setting.

    Modulate Chiller capacity suit to temperature outlet.Modulate Chiller capacity suit to temperature outlet.

    Oil Differential Pressure SwitchOil Differential Pressure Switch

    Its function is to stop chiller once differential pressure betweIts function is to stop chiller once differential pressure between oilen oilsupply and compressor casing reduces below the differential setsupply and compressor casing reduces below the differential set point.point.

    Normally set at 1.0 bar to 1.5 bar differential.Normally set at 1.0 bar to 1.5 bar differential.

    Shall give Alarm signal to BMS at Alarm setting.Shall give Alarm signal to BMS at Alarm setting.

    Will stop Chiller if differential pressure below set poinWill stop Chiller if differential pressure below set pointt

    Centrifugal ChillerCentrifugal ChillerControlsControls

  • 8/14/2019 Liquid Chillers Rev

    86/136

    High Oil Temperature SensorHigh Oil Temperature Sensor It is a combination of microprocessor and sensor or some time itIt is a combination of microprocessor and sensor or some time it is ais a

    Temperature switch.Temperature switch.

    The function is to give alarm / stop signal to compressor once oThe function is to give alarm / stop signal to compressor once oilil

    temperature increases above set point.temperature increases above set point. Set point 180Set point 18000 F.F.

    Will give alarm signal to BMS on rising oil temperature above seWill give alarm signal to BMS on rising oil temperature above settpoint.point.

    May stop compressor if control circuit is made accordingly.May stop compressor if control circuit is made accordingly. High Pressure ControlHigh Pressure Control

    t is a combination of microprocessor and pressure sensor.t is a combination of microprocessor and pressure sensor.

    In some Chillers, it is a Pressure switch.In some Chillers, it is a Pressure switch.

    The function is to give alarm / stop signal to compressor onceThe function is to give alarm / stop signal to compressor once thethedischarge pressure increases to set point.discharge pressure increases to set point.

    Set point 12.0 to 12.5 (RSet point 12.0 to 12.5 (R--12) and 15.0 (R12) and 15.0 (R--134a).134a).

  • 8/14/2019 Liquid Chillers Rev

    87/136

    Centrifugal ChillerCentrifugal ChillerControlsControls

  • 8/14/2019 Liquid Chillers Rev

    88/136

    Chilled Water Temperature ControlChilled Water Temperature Control

    It is a combination of Microprocessor and Temperature Sensor.It is a combination of Microprocessor and Temperature Sensor.

    A sensor (installed in the outlet pipe of Evaporator) senses theA sensor (installed in the outlet pipe of Evaporator) senses the leaving chilledleaving chilled

    water temperature and gives temperature signal to microprocessorwater temperature and gives temperature signal to microprocessor..

    The Microprocessor compares this temperature signal with set temThe Microprocessor compares this temperature signal with set temperature.perature. According to difference, Microprocessor give output command to vAccording to difference, Microprocessor give output command to vane controlane control

    modulating motor, either for closing or opening the vane to modmodulating motor, either for closing or opening the vane to modulate the flowulate the flowof refrigerant. Thus by it controls the capacity of Chiller.of refrigerant. Thus by it controls the capacity of Chiller.

    Set Temperature generally 41 to 46Set Temperature generally 41 to 46

    oo

    FF Motor Winding Temperature SensorsMotor Winding Temperature Sensors

    It is a combination of microprocessor and sensor.It is a combination of microprocessor and sensor.

    A sensor sense the temperature and give signal to microprocessoA sensor sense the temperature and give signal to microprocessor.r.

    Microprocessor compares this signal with set point and give outMicroprocessor compares this signal with set point and give out put commandput command

    to stop the compressor if temperature is higher than set point.to stop the compressor if temperature is higher than set point.

    Set point 265 deg F.Set point 265 deg F.

    Will Stop Motor once motor temperature rises to set point andWill Stop Motor once motor temperature rises to set point and will give alarmwill give alarm

    signal to BMSsignal to BMS

    Centrifugal ChillerCentrifugal ChillerControlsControls

    M t O L d P t tiM t O L d P t ti

  • 8/14/2019 Liquid Chillers Rev

    89/136

    Motor Over Load ProtectionMotor Over Load Protection Its function is to protect compressor motor againstIts function is to protect compressor motor against

    overloading.overloading.

    Set point 95Set point 95--100 % full load Amperes.100 % full load Amperes.

    It will stop compressor motor, once current drawn byIt will stop compressor motor, once current drawn bymotor increases to set point and remain for more than 30motor increases to set point and remain for more than 30--40 second.40 second.

    Alarm signal will be given to BMS once it actuates.Alarm signal will be given to BMS once it actuates.

    Current LimiterCurrent Limiter Its function is to limit the current drawn by motorIts function is to limit the current drawn by motorwithin set point.within set point.

    Set point 80Set point 80--90 % of full load current.90 % of full load current.

    It will unload the compressor by closing the suctionIt will unload the compressor by closing the suctionvane damper, and over ride all inputs for opening thevane damper, and over ride all inputs for opening thevane dampers for increasing the load on compressorvane dampers for increasing the load on compressor..

    Centrifugal ChillerCentrifugal ChillerControlsControls

    A ti RA ti R l Til Ti

  • 8/14/2019 Liquid Chillers Rev

    90/136

    Anti ReAnti Re--cycle Timercycle Timer Its function is to ensure that chiller reIts function is to ensure that chiller re--start is not taking place before thestart is not taking place before the

    Set time.Set time.

    Once chiller stops either from controls or manually, It should nOnce chiller stops either from controls or manually, It should not take reot take re--start before a time recommended by manufacturer for the safety ostart before a time recommended by manufacturer for the safety off

    Compressor & MotorCompressor & Motor.. Set time generally 15Set time generally 15 --20 Minutes.20 Minutes.

    Coast Down TimerCoast Down Timer

    Its function is to ensure that the Oil Pump is running for a cerIts function is to ensure that the Oil Pump is running for a certain periodtain period

    even after chiller is given stop command either by controls or Meven after chiller is given stop command either by controls or Manualanualstop.stop.

    As chiller has been given stop command either by controls or manAs chiller has been given stop command either by controls or manualualstop, The motor & impeller keeps rotating for some time due to istop, The motor & impeller keeps rotating for some time due to inertia.nertia.During this period, it is essential to provide lubrication to beDuring this period, it is essential to provide lubrication to bearing andaring and

    rotating parts of Compressor & Motor.rotating parts of Compressor & Motor. Set time generally 3 minutesSet time generally 3 minutes (It is the time, Motor / Impeller takes in(It is the time, Motor / Impeller takes in

    coming to idle condition after giving stop command).coming to idle condition after giving stop command).

    PrePre--start Checksstart Checks

    Check oil sump temperatureCheck oil sump temperature

    Should beShould be 6060oo 7070oo CC

    Start upStart up --ChillerChiller

    Place system switch inPlace system switch in OFFOFF

    positionposition Pl l h A O

  • 8/14/2019 Liquid Chillers Rev

    91/136

    Should beShould be 6060oo -- 7070oo C.C.

    Check oil levelCheck oil level

    Should be visible 1/ 4 to 3/4 inShould be visible 1/ 4 to 3/4 in

    lower glass.lower glass.

    Check system pressureCheck system pressure

    Should be below 8 Bar.Should be below 8 Bar.

    Physical checkPhysical check -- CondenserCondenser

    Check condenser fan and fanCheck condenser fan and fanbelts.belts.

    Check chilled water flowCheck chilled water flow

    Control panel reading (Control panel reading (

    Microprocessor & Flow Sensor)Microprocessor & Flow Sensor)

    Pressure drop methodPressure drop method

    position.position. Place oil pump switch inPlace oil pump switch in AUTOAUTO

    position.position.

    Close the main disconnect switchClose the main disconnect switch(Make(Make ONON).).

    Operate oil pump and fans onOperate oil pump and fans on

    ManualManual to check operation.to check operation. Set the current limiterSet the current limiter %%

    CurrentCurrent..

    Suggest to setSuggest to set 75 to 80 %75 to 80 % initiallyinitiallyoror MinimumMinimum..

    Set theSet the

    Control TemperatureControl Temperature

    atat

    desired temperature.desired temperature.

    Reset the safety controls or circuitReset the safety controls or circuitbreaker.breaker.

    Place thePlace the Vane PositionVane Position switchswitchinin AutoAuto position.position.

    Start Chiller by Putting the systemStart Chiller by Putting the systemswitch inswitch in ONON PositionPosition

    Daily Operation Checks (Log Recommended by Manufacturer)

    Parameter Normal operation Reading Actual Reading Actual reading

    Ambient Condition DB & WB

  • 8/14/2019 Liquid Chillers Rev

    92/136

    Chilled water Temperature Entering Leaving Temp Drop

    Chilled water pressure Entering Leaving Pressure drop

    Condenser Water Temperature Entering Leaving Temp. Rise

    Condenser Water Pressure Entering Leaving Pressure drop

    Evaporator Pressure

    Discharge Pressure

    oil pressureSupply to BearingsReturn from bearing

    oil TemperatureSupply to BearingsReturn From bearing

    Sump oil Temperature

    % Vane opening

    Amperes

    Abnormal Sound or Noise

    Maintenance (Weekly)Maintenance (Weekly)

    Check Sump oil levelCheck Sump oil level Maintenance (Monthly)Maintenance (Monthly)

    Perform weekly checksPerform weekly checks

  • 8/14/2019 Liquid Chillers Rev

    93/136

    Check Sump oil level.Check Sump oil level. Oil should be visible inOil should be visible in

    lower site glass.lower site glass.

    Check liquid line siteCheck liquid line site

    glasses.glasses. Check unit piping and coilsCheck unit piping and coils

    for visible signs of leaks.for visible signs of leaks.

    Listen and observe theListen and observe the

    operation of the chiller foroperation of the chiller forusual sounds.usual sounds.

    Check all operatingCheck all operatingpressure and temperaturepressure and temperature

    againstagainst normal operatingnormal operatingcondition.condition.

    Perform weekly checks.Perform weekly checks.

    Check fan belt tension andCheck fan belt tension andwear.wear.

    Check fan and fan motor forCheck fan and fan motor for

    lubrication.lubrication. Check condenser condition,Check condenser condition,

    If required clean the coil byIf required clean the coil by NUNU--coil/ calcoil/ cal--clean.clean.

    Or follow individualOr follow individualmanufacturer recommendation.manufacturer recommendation.

    Maintenance (Annual)Maintenance (Annual)

    MechanicalMechanical

    Perform weekly & monthlyPerform weekly & monthly ElectricalElectrical

    Check physical condition ofCheck physical condition of

  • 8/14/2019 Liquid Chillers Rev

    94/136

    Perform weekly & monthlyPerform weekly & monthlyinspection checks.inspection checks.

    Clean the condenser coil byClean the condenser coil byrecommended chemical.recommended chemical.

    Straighten the fins by NylonStraighten the fins by Nyloncomb.comb.

    Change oil by approved oilChange oil by approved oilonly.only.

    Be doubly sure about oilBe doubly sure about oil

    quality and storage time.quality and storage time. Change oil filter.Change oil filter.

    Check and change theCheck and change theliquid line filter of motorliquid line filter of motorcooling system.cooling system.

    Clean the chilled water inletClean the chilled water inletstrainerstrainer

    Check physical condition ofCheck physical condition ofthe components in starterthe components in starterpanel.panel.

    Check physical conditionCheck physical condition

    of all actuating components.of all actuating components. Terminal & Lugs condition.Terminal & Lugs condition.

    Clean the contactor byClean the contactor byCommercial carbon tetraCommercial carbon tetrachloridechloride (CCL 100)(CCL 100) oror

    equivalent.equivalent. Check for loose connection.Check for loose connection.

    Check sensors.Check sensors.

    Fill the conductive liquid inFill the conductive liquid in

    thermothermo --well, if required.well, if required.

    Periodic ChecksPeriodic Checks Leak checkLeak check

    Purge operationPurge operation

    System drynessSystem dryness L b i t l lL b i t l l

    Inspection of starter contacts andInspection of starter contacts and

    actionaction

  • 8/14/2019 Liquid Chillers Rev

    95/136

    System drynessSystem dryness Lubricant levelLubricant level

    Lubricant filter pressure dropLubricant filter pressure drop

    Refrigerant quantity or levelRefrigerant quantity or levelSystemSystem pressures andpressures and

    temperaturestemperatures Water flowsWater flows

    Expansion valves operationExpansion valves operation

    RegularlyRegularly Scheduled MaintenanceScheduled Maintenance

    CondenserCondenser and lubricant coolerand lubricant coolercleaningcleaning

    EvaporatorEvaporator cleaning on opencleaning on opensystemssystems

    CalibratingCalibrating pressure, temperature,pressure, temperature,and flow controlsand flow controls

    TighteningTightening wires and powerwires and power

    connectionsconnections

    actionaction Safety interlocksSafety interlocks Dielectric checking of hermetic andDielectric checking of hermetic and

    open motorsopen motors Tightness of hot gas valveTightness of hot gas valve Lubricant filter and drier changeLubricant filter and drier change

    AnalysisAnalysis of lubricant and refrigerantof lubricant and refrigerant Seal inspectionSeal inspection Partial or complete valve or bearingPartial or complete valve or bearing

    inspection, as per manufacturerinspection, as per manufacturerssrecommendationsrecommendations

    Vibration levelsVibration levels

    Extended Maintenance ChecksExtended Maintenance ChecksCompressorCompressor guide vanes and linkageguide vanes and linkage

    operation and wearoperation and wearEddyEddy current inspection of heatcurrent inspection of heat

    exchanger tubesexchanger tubesCompressorCompressor teardown andteardown and

    inspection of rotating componentsinspection of rotating components Other components asOther components as

    recommended by manufacturerecommended by manufacture

    Screw ChillersScrew Chillers

  • 8/14/2019 Liquid Chillers Rev

    96/136

    Screw ChillersLiquid Chilling SystemLiquid Chilling System

    A liquid chilling system cools water, brine,A liquid chilling system cools water, brine,or other secondary coolant for airor other secondary coolant for air

    conditioning or refrigerationconditioning or refrigeration..

    The system may be either factoryThe system may be either factoryassembled and wired or shipped inassembled and wired or shipped in

    sections for erection in the field.sections for erection in the field.

    Twin Screw Compressors

  • 8/14/2019 Liquid Chillers Rev

    97/136

    Twin Screw Compressors

    ComponentsComponents

    of chillersof chillers

  • 8/14/2019 Liquid Chillers Rev

    98/136

    Components of chillers Compressor (reciprocating, centrifugal orCompressor (reciprocating, centrifugal or

    rotary),rotary),

    Liquid cooler (evaporator),Liquid cooler (evaporator),

    Condenser, a compressor drive, a liquidCondenser, a compressor drive, a liquid

    refrigerant expansion or flowrefrigerant expansion or flow--controlcontroldevice, and a control center.device, and a control center.

  • 8/14/2019 Liquid Chillers Rev

    99/136

  • 8/14/2019 Liquid Chillers Rev

    100/136

    EconomizerEconomizer

  • 8/14/2019 Liquid Chillers Rev

    101/136

    EconomizerEconomizerEconomizer is a separate vesselEconomizer is a separate vessel

    containing the Electronic Expansioncontaining the Electronic Expansionvalve and a float valvevalve and a float valve

    PurposesPurposes

    It improves chiller capacity andIt improves chiller capacity andefficiencyefficiency

    It provides compressor motor coolingIt provides compressor motor cooling

  • 8/14/2019 Liquid Chillers Rev

    102/136

    Screw CompressorsScrew Compressors

  • 8/14/2019 Liquid Chillers Rev

    103/136

    Both are conventionally used with fluidBoth are conventionally used with fluid

    injection where sufficient fluid cools andinjection where sufficient fluid cools and

    seals the compressorseals the compressor..

    Screw compressors have the capability toScrew compressors have the capability to

    operate at pressure ratios above 20:1operate at pressure ratios above 20:1

    single stage.single stage.

    The capacity range currently available isThe capacity range currently available is

    from 20 to 1300 tonsfrom 20 to 1300 tons

  • 8/14/2019 Liquid Chillers Rev

    104/136

    Single Screw Compressor

  • 8/14/2019 Liquid Chillers Rev

    105/136

  • 8/14/2019 Liquid Chillers Rev

    106/136

    Sequence of CompressionSequence of Compression

  • 8/14/2019 Liquid Chillers Rev

    107/136

    SSuctionuction

    CompressionCompression

    DDischargeischarge

    Compressor rotationCompressor rotation

  • 8/14/2019 Liquid Chillers Rev

    108/136

    Compressor rotationCompressor rotationCompressor rotation in ScrewCompressor rotation in Screw

    compressor is extremely importantcompressor is extremely importantOperation in the opposite direction, evenOperation in the opposite direction, even

    momentarily, can cause serious rotormomentarily, can cause serious rotor

    damage and must be avoideddamage and must be avoided

    Mechanical FeaturesMechanical Features

  • 8/14/2019 Liquid Chillers Rev

    109/136

    RotorsRotors

    The screw rotor is normally made of castThe screw rotor is normally made of castironiron and the mating gate rotors are madeand the mating gate rotors are made

    from an engineered plastic.from an engineered plastic.

    The inherent lubricating quality of the plastic,The inherent lubricating quality of the plastic,as well as its compliant nature, allow theas well as its compliant nature, allow the

    singlesingle--screw compressor to achieve closescrew compressor to achieve close

    clearances with conventional manufacturingclearances with conventional manufacturing

    practice.practice.

    Mechanical FeaturesMechanical Features

  • 8/14/2019 Liquid Chillers Rev

    110/136

    RotorsRotors

    BearingsBearings EconomizersEconomizers

    Economizers

  • 8/14/2019 Liquid Chillers Rev

    111/136

    Hermetic CompressorsHermetic Compressors

  • 8/14/2019 Liquid Chillers Rev

    112/136

    Hermetic screw compressors areHermetic screw compressors arecommercially available through 200 tons ofcommercially available through 200 tons of

    refrigeration effect using Rrefrigeration effect using R--22. The hermetic22. The hermetic

    motors can operate under discharge, suction,motors can operate under discharge, suction,

    or intermediate pressure. Motor cooling canor intermediate pressure. Motor cooling canbe with gas, oil, and/or liquid refrigerant. Oilbe with gas, oil, and/or liquid refrigerant. Oil

    separation for these types of compressorsseparation for these types of compressors

    may be accomplished either with anmay be accomplished either with an

    integrated oil separator or with a separatelyintegrated oil separator or with a separatelymounted oil separator in the systemmounted oil separator in the system..

    Capacity ControlCapacity Control

  • 8/14/2019 Liquid Chillers Rev

    113/136

    All positiveAll positive--displacement compressors, bothdisplacement compressors, both

    speed modulation and suction throttling can bespeed modulation and suction throttling can be

    used. Ideal capacity modulation for anyused. Ideal capacity modulation for anycompressor includescompressor includes

    Continuous modulation from 100% to less thanContinuous modulation from 100% to less than

    10%,10%,

    Good partGood part--load efficiencyload efficiency

    Unloaded startingUnloaded starting

    Unchanged reliabilityUnchanged reliability

    TwinTwin--screw compressorsscrew compressors

  • 8/14/2019 Liquid Chillers Rev

    114/136

    Twin screw is the common designation forTwin screw is the common designation fordouble helical rotary screw compressors.double helical rotary screw compressors.

    A twinA twin--screw compressor consists of twoscrew compressor consists of twomating helically grooved rotorsmating helically grooved rotors--malemale(lobes) and female (flutes or gullies) in a(lobes) and female (flutes or gullies) in a

    stationary housing with inlet and outletstationary housing with inlet and outletgas ports.gas ports.

    The flow of gas in the rotors is mainly inThe flow of gas in the rotors is mainly inan axial directionan axial direction

    Sequence of Compression Process inSequence of Compression Process in

    Twin Screw CompressorTwin Screw Compressor

  • 8/14/2019 Liquid Chillers Rev

    115/136

    SuctionSuction

    CompressionCompression DischargeDischarge

    LubricantLubricant

    b i i l d b f h f ll i h d

  • 8/14/2019 Liquid Chillers Rev

    116/136

    Lubricant is cooled by one of the following methodsLubricant is cooled by one of the following methods

    WaterWater--cooled using condenser water, evaporative condensercooled using condenser water, evaporative condenser

    sump water, chilled water, or a separate watersump water, chilled water, or a separate water-- or glycolor glycol--toto--air cooling loopair cooling loop

    AirAir--cooled using a lubricantcooled using a lubricant--toto--air heat exchangerair heat exchanger

    RefrigerantRefrigerant--cooled (where lubricant cooling load is low)cooled (where lubricant cooling load is low)

    Liquid injection into the compressorLiquid injection into the compressor Condensed refrigerant liquid thermal recirculationCondensed refrigerant liquid thermal recirculation

    (thermosyphon), where appropriate, compressor head(thermosyphon), where appropriate, compressor head

    pressure is availablepressure is available

    Oil separatorsOil separators

  • 8/14/2019 Liquid Chillers Rev

    117/136

    Efficient lubricant separators areEfficient lubricant separators are

    required. The types and efficienciesrequired. The types and efficienciesof these separators vary according toof these separators vary according to

    refrigerant and application. Fieldrefrigerant and application. Field

    built systems requires better built systems requires betterseparation than complete factoryseparation than complete factory--

    built systemsbuilt systems

  • 8/14/2019 Liquid Chillers Rev

    118/136

    MotorComp

    Control

    Air cooled condenser

    SCREW.CH.FLOW CYCLE

  • 8/14/2019 Liquid Chillers Rev

    119/136

    Oil separator

    Oil cooler

    StrainerOil pump

    Control

    Evaporator

    Filter coreReceiver

    MotorComp

    control

  • 8/14/2019 Liquid Chillers Rev

    120/136

    Oil separator

    oil cooler

    strainer

    oil pump

    oil filtersGauge

    Gaugecontrol

    CAPACITY CONTROL

    LUBRICATION SYSTEM

    Capacities and Types AvailableCapacities and Types Available

    Screw compressor liquid chillers are available as factoryScrew compressor liquid chillers are available as factory

  • 8/14/2019 Liquid Chillers Rev

    121/136

    Screw compressor liquid chillers are available as factoryScrew compressor liquid chillers are available as factory--

    packaged units from about 30 to 1250 Tons.packaged units from about 30 to 1250 Tons.

    The following types of liquid chillers are generally used for aiThe following types of liquid chillers are generally used for airrconditioning:conditioning:

    Up to 25 tonsUp to 25 tons Reciprocating or scrollReciprocating or scroll

    25 to 80 tons25 to 80 tons Screw, reciprocating, or scrollScrew, reciprocating, or scroll

    80 to 450 tons80 to 450 tons Screw, reciprocating, or centrifugalScrew, reciprocating, or centrifugal 200 to 1000 tons200 to 1000 tons Screw or centrifugalScrew or centrifugal

    Above 1000 tonsAbove 1000 tons CentrifugalCentrifugal

    Safety controlsSafety controls

  • 8/14/2019 Liquid Chillers Rev

    122/136

    Lubricant failure switch,Lubricant failure switch, High discharge pressure cutout,High discharge pressure cutout,

    Low suction pressure switch,Low suction pressure switch,

    Cooler flow switch,Cooler flow switch,

    High lubricant and discharge temperature cutout,High lubricant and discharge temperature cutout,

    Hermetic motor inherent protection,Hermetic motor inherent protection,

    Lubricant pump and compressor motor overloads,Lubricant pump and compressor motor overloads,

    andand

    Low lubricant temperature (flood back/dilutionLow lubricant temperature (flood back/dilutionprotection).protection).

  • 8/14/2019 Liquid Chillers Rev

    123/136

    Starting of Screw compressorStarting of Screw compressor

    The current limit relay protects against motorThe current limit relay protects against motor

  • 8/14/2019 Liquid Chillers Rev

    124/136

    The current limit relay protects against motorThe current limit relay protects against motoroverload from higher than normal condensingoverload from higher than normal condensing

    temperatures or lowtemperatures or low--voltage and also allows avoltage and also allows ademand limit to be set, if desired. An antire cycledemand limit to be set, if desired. An antire cycletimer is used to prevent overly frequenttimer is used to prevent overly frequentrecycling. Lubricant sump heaters are energizedrecycling. Lubricant sump heaters are energizedduring the off cycle. A hot gas capacity control isduring the off cycle. A hot gas capacity control isoptionally available and prevents automaticoptionally available and prevents automaticrecycling at norecycling at no--load conditions such as is oftenload conditions such as is oftenrequired in process liquid chilling. A suction torequired in process liquid chilling. A suction todischarge starting bypass sometimes aids startingdischarge starting bypass sometimes aids starting

    and allows the use of standard starting torqueand allows the use of standard starting torquemotors.motors.

    Starting of Screw compressorStarting of Screw compressor

    Some units are equipped with electronicSome units are equipped with electronic

  • 8/14/2019 Liquid Chillers Rev

    125/136

    Some units are equipped with electronicSome units are equipped with electronicregulators specially developed for theregulators specially developed for the

    screw compressorscrew compressor These regulators include PI controlThese regulators include PI control

    (Proportional(Proportional--Integrating) of the leavingIntegrating) of the leaving

    brine temperature and such functions as brine temperature and such functions asautomatic/manual control, capacityautomatic/manual control, capacityindication, time circuits to preventindication, time circuits to preventfrequent recycling and to bypass thefrequent recycling and to bypass the

    lubricant pressure cutout during startup,lubricant pressure cutout during startup,switch for unloaded starting, etc.switch for unloaded starting, etc.

    Inspection or change outInspection or change out

    timetabletimetable

  • 8/14/2019 Liquid Chillers Rev

    126/136

    Shaft seals 1.5 to 4 yr InspectShaft seals 1.5 to 4 yr Inspect

    Hydraulic cylinder seals 1.5 to 4 yrHydraulic cylinder seals 1.5 to 4 yr

    ReplaceReplace

    Thrust bearings 4.0 to 6 yrThrust bearings 4.0 to 6 yr

    Shaft bearings 7 to 10 yr InspectShaft bearings 7 to 10 yr Inspect

    Check preload via shaft end play every 6Check preload via shaft end play every 6months and replace as requiredmonths and replace as required

    Capacity Slide ValveCapacity Slide Valve

  • 8/14/2019 Liquid Chillers Rev

    127/136

    A slide valve for capacity control is a valveA slide valve for capacity control is a valve

    with sliding action parallel to the rotorwith sliding action parallel to the rotor bores. They are placed within or close to bores. They are placed within or close to

    the highthe high--pressure cusp region, face one orpressure cusp region, face one or

    both rotor bores, and bypass a variable both rotor bores, and bypass a variableportion of the trapped gas charge back toportion of the trapped gas charge back to

    suction, depending on their positionsuction, depending on their position

    Capacity Lift ValveCapacity Lift Valve

    Capacity lift valves or plug valves areCapacity lift valves or plug valves are

  • 8/14/2019 Liquid Chillers Rev

    128/136

    Capacity lift valves or plug valves areCapacity lift valves or plug valves aremovable plugs in one or both rotormovable plugs in one or both rotor

    bores (with radial or axial lifting bores (with radial or axial liftingaction) that regulate the actual startaction) that regulate the actual startof compression. These valves controlof compression. These valves control

    capacity in a finite number of steps,capacity in a finite number of steps,rather than by the infinite control ofrather than by the infinite control ofa conventional slide valvea conventional slide valve

    Chiller NumberChiller Number

    NomenclatureNomenclature

  • 8/14/2019 Liquid Chillers Rev

    129/136

    ExampleExample

    0 6 N A 11 2 3 S 6 E A0 6 N A 11 2 3 S 6 E A

    First three digits are the basic modelFirst three digits are the basic model 06N06N

    Fourth digitFourth digit AA for Airfor Air--cooledcooledWW for Waterfor Water--cooledcooled

    Fifth digit Type of RefrigerantFifth digit Type of Refrigerant 11for refrigerant 134afor refrigerant 134a

    Sixth, Seventh and Eighth digits Compressor displacementSixth, Seventh and Eighth digits Compressor displacement

    Ninth digit Electrical characteristicsNinth digit Electrical characteristics

    Tenth digit Electrical FrequencyTenth digit Electrical Frequency

    Eleventh digit Type of motor coolingEleventh digit Type of motor cooling EE forfor

    economizedeconomized NN noneconomizednoneconomized

    Twelfth digit PackagingTwelfth digit Packaging AA standard packagingstandard packaging BB

    service packagingservice packaging

    HVAC controlsHVAC controls

    Automatic HVAC control systems are designed toAutomatic HVAC control systems are designed tomaintain temperature, humidity, pressure, flow,maintain temperature, humidity, pressure, flow,power lighting levels and safe levels of indoorpower lighting levels and safe levels of indoor

  • 8/14/2019 Liquid Chillers Rev

    130/136

    power, lighting levels, and safe levels of indoorpower, lighting levels, and safe levels of indoorcontaminantscontaminants

    Automatic control primarily modulates, stages, orAutomatic control primarily modulates, stages, orsequences mechanical and electrical equipmentsequences mechanical and electrical equipmentto meet load requirements and provide safeto meet load requirements and provide safe

    operation of the equipment.operation of the equipment. It can use digital, pneumatic, mechanical,It can use digital, pneumatic, mechanical,

    electrical, and electric control devises, andelectrical, and electric control devises, and

    implies that human intervention is limited inimplies that human intervention is limited instarting and stopping equipment and adjustingstarting and stopping equipment and adjustingcontrol set points.control set points.

    HVAC controlsHVAC controls

    The sensor measuresThe sensor measures A controller can be inA controller can be in

  • 8/14/2019 Liquid Chillers Rev

    131/136

    the controlled variablethe controlled variable

    and transmits values toand transmits values tothe controllerthe controller

    The controller comparesThe controller comparesthe value of thethe value of the

    controlled variable withcontrolled variable withthe set point andthe set point andgenerates a signal to thegenerates a signal to the

    controlled device forcontrolled device forcorrective action.corrective action.

    the form of hardwarethe form of hardware

    or software.or software.Thermostats,Thermostats,humidistat, andhumidistat, andpressure controls arepressure controls areexamples of hardwareexamples of hardwarecontrollers. Digitalcontrollers. Digitalalgorithms arealgorithms are

    examples of softwareexamples of softwarecontrollers.controllers.

    HVAC controlsHVAC controls

    The set point is the desiredThe set point is the desired

  • 8/14/2019 Liquid Chillers Rev

    132/136

    value of the controlledvalue of the controlled

    variable.variable. The controller seeks toThe controller seeks to

    maintain this set point.maintain this set point.

    The controlled device reactsThe controlled device reactsto signals received from theto signals received from thecontroller to vary the flow ofcontroller to vary the flow ofthe control agentthe control agent

    The controlledThe controlled

    device may be adevice may be avalve, damper,valve, damper,heating element, or aheating element, or a

    motor driving amotor driving apump or a fan.pump or a fan.

  • 8/14/2019 Liquid Chillers Rev

    133/136

    ValvesValvesValvesValves

    A singleA single--seated valve isseated valve isdesigned for tightdesigned for tight

    A threeA three--way mixingway mixingvalve has two inlet andvalve has two inlet and

  • 8/14/2019 Liquid Chillers Rev

    134/136

    designed for tightdesigned for tightshutoffshutoff

    A doubleA double--sealed orsealed orbalanced valve isbalanced valve is

    designed so that thedesigned so that the

    media pressure actingmedia pressure actingagainst the valve disc isagainst the valve disc isessentially balanced,essentially balanced,reducing the operatorreducing the operator

    force requiredforce required

    valve has two inlet andvalve has two inlet and

    one outlet connectionsone outlet connectionsand a doubleand a double--faced discfaced discoperating between twooperating between twoseatsseats

    A threeA three--way divertingway divertingvalve has one inlet andvalve has one inlet andtwo outlet connectionstwo outlet connections

    and two separate discsand two separate discsand seatsand seats

    HVAC controlsHVAC controls

    A thermistor is aA thermistor is ad hi d h

    Preprogrammed controlPreprogrammed controlti k fiti k fi

  • 8/14/2019 Liquid Chillers Rev

    135/136

    semiconductor thatsemiconductor that

    changes electricalchanges electricalresistance withresistance withtemperature. It has atemperature. It has anegative temperaturenegative temperature

    coefficient; i.e., thecoefficient; i.e., theresistance decreases as theresistance decreases as thetemperature increasestemperature increases

    routines, known as firmware,routines, known as firmware,are typically stored inare typically stored inpermanent memory such aspermanent memory such asEEPROM (electronicallyEEPROM (electronicallyerasable programmable readerasable programmable readonly memory). To preventonly memory). To preventunauthorized alteration, theunauthorized alteration, theoperator can modify parametersoperator can modify parameterssuch as set points, limits, andsuch as set points, limits, andminimum off times within theminimum off times within the

    control routines, but thecontrol routines, but theprogram logic cannot beprogram logic cannot bechanged without replacing thechanged without replacing thememory chips.memory chips.

    HVAC controlsHVAC controls

    DampersDampers Indoor Air QualityIndoor Air Quality

  • 8/14/2019 Liquid Chillers Rev

    136/136

    DampersDampers

    Humidity SensorsHumidity Sensors

    Pressure TransmittersPressure Transmitters andand

    transducerstransducers

    Flow Rate SensorsFlow Rate Sensors

    TransducersTransducers

    Indoor Air QualityIndoor Air Quality

    SensorsSensors Digital ControllersDigital Controllers

    ThermostatsThermostats

    PI ControllersPI Controllers