LDM Series Lamp Driver Modules - Fire Alarm Resources...The LDM Series Lamp Driver Modules, which...
Transcript of LDM Series Lamp Driver Modules - Fire Alarm Resources...The LDM Series Lamp Driver Modules, which...
Document 1588510/29/97 Rev: F
P/N 15885:F2 ECN 97-407
12 Clintonville RoadNorthford, CT 06472(203) 484-7161FAX: (203) 484-7118
LDM SeriesLamp Driver Modules
For Graphic Annunciation and Control
Used with the System 500, System 5000,AM2020/AFP1010 and AFP-200
Fire Alarm Control Panels
www.PDF-Zoo.com
215885 Rev. F1 8/2/95 P/N 15885:F1
INSTALLATION WARNING
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F13
Table of ContentsSection One: Introduction to the LDM Series 5
Section Two: LDM Features 62.1 The LDM-32 6
Figure 2-1: LDM-32 62.2 The LDM-E32 7
Figure 2-2: LDM-E32 72.3 Connectors on the LDM-32 and LDM-E32 82.4 Switches 92.5 Terminal Blocks 92.6 Cables 102.7 The LDM-R32 11
Figure 2-3: LDM-R32 11
Section Three: Installation 123.1 External Cabinets 123.2 CHS-4L Chassis 12
Figure 3-1: CHS-4L Mounting 12Figure 3-2: Installing LDM Modules in CHS-4L 13Figure 3-3: LDMs Mounted in UL Listed Cab 13Figure 3-4: Mounting Optional LDM-R32 Relay Mod. 14
Section Four: Wiring Considerations 154.1 Limits 154.2 Wire Runs 15
Figure 4-1: EIA-485 Communications 154.3 Wiring Specifications 15
Figure 4-2: Wiring the Enclosure 164.4 EIA-485 Shield in Conduit 16
Figure 4-3: Terminating the Shield - Conduit 164.5 EIA-485 Shield Not in Conduit 16
Figure 4-4: Terminating the Shield - No Conduit 164.6 EIA-485, Power and Relay Wiring 17
Figure 4-5: Wiring Multiple LDMs (6000 ft. max..) 17Figure 4-6: Wiring Supervision Terminals 17UL Power Limited Wiring Requirements 18
4.7 Remote Power Supply Connector 19Figure 4-7: Remote Power Supply Connections 19
4.8 Lamp/LED Wiring 20Figure 4-8: Typical LDM-to-Graphics @ 5 VDC 20Figure 4-9: Typical LDM-to-Graphics @ 24 VDC 20
4.9 Control Switch Wiring 21Figure 4-10: Optional Zone/Pt. Control Switch Wire 21
Section Five: Summary - Installing the Lamp Driver Module 22
Section Six: Operating the Lamp Driver Module 246.1 Lamp Test/Acknowledge 246.2 On Line LED 246.3 Graphic Annunciator Lamp/LED 24
www.PDF-Zoo.com
415885 Rev. F1 8/2/95 P/N 15885:F1
Section Seven: LDM Communications 25Figure 7-1: LDM-32 Supervision 25
Section Eight: LDM Electrical Ratings & Current Calculations 26
Appendix A: LDM and the System 5000 29Table A-1: Annunciator Point Assignments 30AIM-200 Point Assignments 31Table A-2: LDM Switch Control Functions 32Figure A-1: Alarm Only Operation w/o 8-Point Shift 33Figure A-2: Alarm Only Operation with 8-Point Shift 34Figure A-3: Alarm/Trouble Op. w/o 8-Point Shift 35Figure A-4: Alarm/Trouble Op. with 8-Point Shift 36Figure A-5: Alarm Relays with LDM-R32 37Figure A-6: Alarm Relays with 8-Point Shift 38Figure A-7: Alarm & Trbl Relays with LDM-R32 39Figure A-8: Alarm & Trbl Relays with 8-Point Shift 40
Appendix B: LDM and the AM2020/AFP1010 41Figure B-1: The EIA-485 Loop 42Table B-1: Lamp Driver Point Functions 43Figure B-2: Lamp Driver Alarm Points 45Figure B-3: Alarm and Trouble Points 46Figure B-4: Alarm-Only Relay Operation 47Figure B-5: Alarm & Trbl Relay Operation 48
Appendix C: LDM and the System 500 49Figure C-1: Connecting the EIA-485 Loop 49Table C-1: Annunciator Point Assignments 51Table C-2: LDM Switch Control Functions 52Figure C-2: Alarm Points Only Operation 52Figure C-3: Alarm Only Operation with CPU Shift 53Figure C-4: Alarm and Trouble Points Operation 53Figure C-5: Alarm/Trouble Operation with 8-Pt Shift 54Figure C-6: Alarm Relays with LDM-R32 54Figure C-7: Alarm Relays with 8-Point Shift 55Figure C-8: Alarm and Trouble Relay with LDM-R32 56Figure C-9: Alarm & Trbl Relays with 8-Point Shift 57
Appendix D: LDM and the AFP-200 58Table D-1: LDM Switch Control Functions 60Figure D-1: Display Active Status of Software Zones 61Figure D-2: Active Status of Zones with 8-Pt Shft 62Figure D-3: Activation and Trbl Status Annunciation 63Figure D-4: Activation Operation with 8-Pt Shift 64
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F15
Section One: Introduction to the LDM Series
The LDM Series Lamp Driver Modules, which consist of the LDM-32 master and LDM-E32expander modules, are used to provide an interface to a custom graphic annunciator. Themaster module provides power and control for a maximum of three expander modules.The LDM-32 and LDM-E32 have output connectors which are used to drive lamps or LEDsand input connectors which are used for remote switch functions.
The LDM Series Lamp Driver Modules may be connected to fire alarm control panels(FACP) to provide remote annunciation of the following:
• General system status:ü General Alarmü General Troubleü General supervisoryü Notification Appliance Circuit (NAC) output statusü Municipal tie statusü System silenceü Alarm relay status
• Alarm and trouble status of zones or individual points• Alarm only status of zones or individual points
The LDM Series Modules also interface to remote control switches which may be used toprovide:
• System reset• System silence• System acknowledge• Temporary activation of NAC outputs• Alarm relay activation• Other control functions
The LDM Series Modules interface to the host fire alarm control panel via an EIA-485communications bus circuit. A maximum of 32 LDM-32s may be connected to the power-limited EIA-485 bus, but if other types of devices are also connected to the EIA-485 bus,the maximum number of LDM-32s must be reduced by the total of such devices. The EIA-485 wiring distance must not exceed 6,000 feet and cannot be T-tapped. Multiple LDM-32s may be used to annunciate duplicate information.
Power to the LDM-32s is typically provided by the host FACP and must be power-limitedregulated 24 VDC. External UL listed battery backed power supplies may also be used.Careful consideration must be given to system battery calculations when power for theLDM modules and lamps or LEDs is provided by the host FACP. Refer to the specificationsin the appropriate FACP technical manual when making these calculations.
www.PDF-Zoo.com
615885 Rev. F1 8/2/95 P/N 15885:F1
Section Two: LDM Features
2.1 The LDM-32The Lamp Driver Module LDM-32 has 32 alarm lamp/LED driver outputs which sink currentto system common (-) on activation. A single positive (+) voltage is required to supply totaloperating power for all lamps or LEDs when all drivers are activated. The LDM-32 providesa separate driver for system trouble and inputs for a local lamp test switch. A maximum of16 external control switches may be wired to the LDM-32. DIP switch SW3 is used to enableor disable the onboard piezo, enable remote switch functions, select a flashing LED functionfor new alarms and troubles, and other functions. Switch SW4 is used to configure themodule to annunciate 32 alarms or 16 troubles. A green ON LINE LED flashes to indicateongoing communications with the host FACP. One LDM-32 supports up to 3 LDM-E32modules. The LDM-32 is supplied with 4 standoffs and screws for mounting to a CHS-4Lchassis or custom backbox.
Figure 2-1: LDM-32
Lamp Power (+24 VDC)System Trouble
Ribbon CableConnection toLDM-E32
Output Connectorsfor Wiring to LEDs
Security KeySwitch Terminal
Terminal for max.of 16 externalcontrol switches
AddressSwitches
LDM ProgramSwitch
Indicates EIA-485Communication Active
Alarm orAlarm/Trbl
EIA-485 In (-)EIA-485 Out (-)EIA-485 Out (+)EIA-485 In (+)
SupervisionInputs (NC)
Common In (-)Common Out (-)
Power In +24 VDCPower Out +24 VDC
Earth Ground
Power-limited
Relay Power RibbonCable Connection
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F17
2.2 The LDM-E32Each LDM-E32 expander module provides 32 additional lamp/LED driver outputs from J5,J6, J7 and J8. The expander module has a slide switch SW4 for selecting alarm or alarmand trouble annunciation and an input for a local lamp test switch. In alarm mode, use onlyone LDM-32 and one LDM-E32 for a maximum of 56 alarm indicators and 8 system statusindicators. In alarm/trouble mode, use one LDM-32 and three LDM-E32s for a maximum of56 alarm indicators, 56 trouble indicators, 16 status indicators and 64 optional control switchinputs. Multiple sets of LDM-32s with LDM-E32 expanders increase the system annunciationcapabilities beyond 56 zones or points. This is possible by various settings of addressswitches SW1 and SW2 on the LDM-32 (refer to Appendices). Each LDM-E32 is suppliedwith a 26 conductor expander ribbon cable, 4 standoffs and 4 screws.
Figure 2-2: LDM-E32
Ribbon CableConnections toNext LDM-E32
Ribbon CableConnection FromPrevious LDM-32 orLDM-E32
Output Connectorsfor Wiring to LEDs
Security KeySwitch Terminal
Terminal For max.of 16 ExternalControl Switches
Alarm Only orAlarm/TroubleSelect Switch
Relay Power RibbonCable Connection
www.PDF-Zoo.com
815885 Rev. F1 8/2/95 P/N 15885:F1
2.3 Connectors on the LDM-32 and LDM-E32
J1 - Switch MatrixUp to 16 optional external control switches and a local lamp test switch may be attachedto the LDM-32 and LDM-E32 via J1 as shown in Figure 4-10. To determine which switchfunction each point will perform in a System 5000, refer to Appendix table A-1 (System5000). Switch functions on an AM2020/AFP1010 are completely programmable.
J2 - Ribbon Cable Connection Between Master and Expander Modules to J3A single 26 conductor ribbon cable may be connected from J2 on the LDM-32 or LDM-E32 (see Figure 3-3) to J3 on adjacent LDM-E32s. The ribbon cable carries power,ground and signaling from the LDM-32 to up to three LDM-E32s. The preformed cablesare supplied in fixed lengths of 24 and 48 inches.
J3 - Ribbon Cable Connection From J2This connector supports a single 26 conductor ribbon cable from J2 of the previousLDM-32 or LDM-E32. Refer to Figure 3-3.
J4 - Keyswitch InputThis two pin connector is provided as an input on LDM-32 and LDM-E32 modules for anexternal security keyswitch. Keyswitch contacts must be Normally Closed. The keyswitchprevents unauthorized use of remote control switches wired to J1.
J5, J6, J7 and J8 - Lamp/LED Driver OutputsEach connector provides 8 driver outputs for a total of 32 drivers on each LDM-32 andLDM-E32. Each driver is rated for a maximum of 30 volts and a current of 100 mA. Eachbipolar Darlington open collector driver output must be current limited by an externalresistor. 8-Point Shift and Flash functions are selectable by DIP switch SW3 (refer toSection 2.4). Lamp/LEDs may function in 'alarm only mode' or 'alarm/trouble mode' asselected by switch SW4. Use the charts and examples shown in Appendices A and B foradditional information.
J9 - Lamp Power/System TroubleConnector J9 is located only on the LDM-32. J9 pin 1 provides 24 volts regulated powerto all lamps/LEDs used in a custom graphic annunciator. The current limit of J9 pin 1 isdependent upon the current limits of the external power source being used. J9 pin 3 isa driver output for system trouble indication only. J9 pin 2 connects to system common.
J10 - Relay ExpanderCables to the optional LDM-R32 Relay Expander Module which can be used to provideup to 32 dry Form-A (normally open) contacts.
J11 - 5 VDC PowerThis connector is located only on the LDM-32. J11 pin 1 provides 5 volts regulatedpower to all lamps/LEDs used in a custom graphic annunciator. The maximum currentavailable from this output is 300 mA. This current is sufficient to power the maximumnumber of LEDs available with one LDM-32 and three LDM-E32s (from J5, J6, J7, J8and one system trouble LED) provided the current rating per LED is 2 mA.
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F19
2.4 Switches
SW1 and SW2 - Address SwitchesTwo rotary BCD switches, located only on the LDM-32, are used to set the LDM Seriessystem address. Switch SW1 represents the 'ones' position and switch SW2 representsthe 'tens' position of the address setting. In system configurations of 56 zones or less,the switches must be set to address 01 for all LDMs in the system. For configurationslarger than 56 zones, multiple sets of LDMs are required with sequential addresses, thefirst LDM starting at address 01. Each incremental setting adds 64 zones/points to thesystem.
SW3 - Function DIP SwitchSW3, which is located only on the LDM-32, is used to set the annunciator functions.Function settings include:
• Number of expanders connected• 8-Point Shift enabled• Receive Only communications to host FACP (no system control switches or
loss of supervision)• Receive/Transmit communications to host FACP (system control switches plus
supervision)• Control Switch Disable• Piezo disable• Flash Inhibit
Refer to Appendices A and B for additional information.
SW4 - Alarm/Trouble Mode SwitchThe Alarm/Trouble mode switch is installed on the LDM-32 and LDM-E32. The switchsetting on each expander module must match the switch setting of the associated LDM-32. 'Alarm Only' mode causes the driver outputs to turn on only for alarm conditions perassociated zone or point at the host FACP. Alarm/Trouble mode causes the driver outputsto turn on for both alarm and trouble conditions per associated zone or point at the hostFACP. Since this switch affects the assignments of connectors J5, J6, J7 and J8, makecertain to review the appendices in this manual for additional information on wiring to thelamp/LED drivers.
TB1 - Power, Earth Ground and SupervisionRemovable terminal block TB1 appears only on the LDM-32. 24 volts power-limited,regulated, non-resettable power from the host FACP or a compatible UL listed batterybacked power supply must be connected to TB1-3 (+) and TB1-5 (-). Terminals TB1-2(+) and TB1-4 (-) may be used to daisy chain the 24 volts to other LDMs or devices.Earth ground must be connected to TB1-1. Terminals TB1-6 and TB1-7 provide asupervised input which may be used to supervise local power sources or other devices.A trouble signal is transmitted to the host FACP upon an open circuit across theseterminals. The input must be power-limited. If these terminals are not used, a jumpermust be installed.
TB2- In/OutRemovable terminal block TB2 appears only on the LDM-32. All LDM-32s must connectto the EIA-485 communications bus circuit for proper operation. The EIA-485 bus carriescommands and data sent between the host FACP and the LDMs. The input must bepower-limited.
2.5 Terminal Blocks
www.PDF-Zoo.com
1015885 Rev. F1 8/2/95 P/N 15885:F1
2.6 CablesExpander Ribbon Cable (75120)The Expander Ribbon Cable is supplied with the LDM-E32 to allowfor connection to the LDM-32 master module. The cable connectsbetween J2 of the LDM-32 or LDM-E32 and J3 of the next LDM-E32.
The LDM-CBL24 and LDM-CBL48Cable sets for connecting LDM-32 and LDM-E32 connectors tolamps/LEDs, switches, etc., are provided through the optional LDM-CBL24 (24" long) and LDM-CBL48 (48" long) cabling kits. Eachcable has a plug on one end for connection to the LDM modules.
• Each LDM-CBL24 cable kit includes:
(4) P/N 75116, 24" cable consisting of 8 stranded,multicolored conductors. Cables connect to J5, J6, J7 andJ8.
(1) P/N 75122, 24" cable consisting of 10 stranded,multicolored conductors. Connects to J1, optional controlswitches.
(1) P/N 75117, 24" cable consisting of 2 stranded, singlecolor conductors. Connects to J1, Lamp Test Switch.
(1) P/N 75118, 24" cable consisting of 3 stranded,multicolored conductors. Connects to J9 or J11, LampPower.
• Each LDM-CBL48 cable kit includes:
(4) P/N 75147, 48" cable consisting of 8 stranded,multicolored conductors. Cables connect to J5, J6, J7 andJ8.
(1) P/N 75150, 48" cable consisting of 10 stranded,multicolored conductors. Connects to J1, optional controlswitches.
(1) P/N 75148, 48" cable consisting of 2 stranded, singlecolor conductors. Connects to J1, Lamp Test Switch.
(1) P/N 75149, 48" cable consisting of 3 stranded,multicolored conductors. Connects to J9 or J11, LampPower.
• Keylock Control Switch Security:A UL listed key-lock switch wired to J4 on the LDM-32 shouldbe used to provide access security for all control switches wiredto that set of LDM modules. Control switches will not functionwhen the key-lock switch is in its closed position.
KEYSWITCH LDM-32
J4
21
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F111
2.7 The LDM-R32The LDM-R32 Relay Expander Module provides the LDM-32 or LDM-E32 with 32 dry Form-A (normally open) contacts. The relay module serves as a slave to the particular lamp driverannunciator it is connected to - instead of driving lamps or LEDs, the alarm and/or troublesignals from the LDM-32 and LDM-E32 modules are used to activate the relays on the LDM-R32. A maximum of two of these relay modules can be supported by an LDM-32/LDM-E32operating in alarm-only mode, providing a maximum of 64 alarm relays. In alarm/troublemode, one, two or four LDM-R32 modules may be connected to LDM-32/LDM-E32s, providinga maximum of 64 alarm and 64 trouble relays. Includes mounting hardware, one RelayPower Cable and four Relay Expander Ribbon cables for connection to the master LDM-32/LDM-E32 module.
Figure 2-3: LDM-R32
www.PDF-Zoo.com
1215885 Rev. F1 8/2/95 P/N 15885:F1
Section Three: Installation
This section discusses basic requirements and CHS-4L mounting instructions.
3.1 External CabinetsThe CAB-3A and the CAB-3B are UL listed cabinets suitable for use in graphic annunciatorapplications. For size and dimensions, refer to the CAB-3 Series Installation Document .Other cabinets such as those provided by custom graphic annunciator manufacturers maybe used provided they meet UL requirements as UL listed secured enclosures. Select anappropriate knockout on the enclosure. Mount the cabinet and ground it to a solid metallicearth ground.
3.2 CHS-4L ChassisThe CHS-4L chassis will support one LDM-32 module and up to three LDM-E32 expandermodules. The CHS-4L chassis may be mounted inside the CAB-3A and the CAB-3Benclosures. Note that a solid earth ground connection is required for proper operation aswell as to aid in transient protection. Two female-to-female standoffs must be installed to thechassis to secure the LDMs in place. (See Figure 3-1).
Figure 3-1: CHS-4L Mounting
Mount the CHS-4L Chassis to a cabinet andsecure with the hardware provided. A GroundingCable Assembly must be connected to the chassismounting stud for connection to the annunciator'sEarth Ground terminal. For each LDM module tobe installed on the chassis, connect two female-to-female standoffs (provided) to the uppermounting studs on the chassis.
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F113
Figure 3-3: LDMs Mounted in UL Listed Cabinet
Slip the bottom edge of the LDM board into theslot on the CHS-4L chassis and move the moduletoward the standoffs. Secure the LDM to thestandoffs with the screws provided. Repeat forinstallation of additional LDM modules.
Figure 3-2: Installing LDM Modules in CHS-4L
Connect an expander ribbon cable (P/N 75120) from the LDM-32 connector J2 to J3 of thefirst LDM-E32 expander module. If multiple LDM-E32 modules are to be used, connectadditional cables from J2 to J3 as shown in Figure 3-3. Note: One LDM-32 may support amaximum of three LDM-E32 modules.
www.PDF-Zoo.com
1415885 Rev. F1 8/2/95 P/N 15885:F1
Figure 3-4: Mounting Optional LDM-R32 Relay ModulesSecure the LDM-R32 to the LDM-32 with the standoffs provided(see below). Attach ribbon cables between the LDM-32 and theLDM-R32 for each group of relays needed (connector J5 to J5, J6 toJ6, etc.) as illustrated at right. Note: The relay module can also beconnected to an LDM-E32.
Connect the Relay Power Ribbon Cable between J10 on the LDM-R32 and J10 on the LDM-32. this connection supplies the power needed to energize the LDM-R32's relay coils duringactivation.
LDM-R32Chassis LDM-32(or LDM-E32)
LDM-R32LDM-32
StandoffStandoff
LDM-32(or LDM-E32)
LDM-R32
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F115
Section Four: Wiring Considerations4.1 LimitsA maximum of 32 LDM-32s may be connected to the EIA-485 bus, but if other types ofdevices are also connected to the EIA-485 bus, the maximum number of LDM-32s must bereduced by the total of such devices. Total annunciation and switch capability dependsupon the number of LDM-E32 expander modules used.
4.2 Wire RunsCommunications between the Fire Alarm Control Panel and the LDM is accomplished overa two-wire EIA-485 serial communications bus which must be power-limited. Communicationsbetween the host FACP and LDMs is supervised by the fire alarm control panel. Powersupplied by the host control panel or external power supply must be power-limited. It isinherently supervised (loss of power also results in a communication failure at the controlpanel). Refer to appropriate control panel manual for UL Power-limited Wiring Requirements.
Figure 4-1: EIA-485 Communications
4.3 Wiring SpecificationsThe EIA-485 circuit cannot be T-tapped; it must be wired in a continuous fashion from thecontrol panel to the LDMs. The maximum wiring distance between the panel and LDMs is6000 feet. The wiring must be a 18 AWG to 14 AWGtwisted shielded pair cable having a characteristicimpedance of 120 ohms, +/- 20%. Limit the total wireresistance to 100 ohms on the EIA-485 circuit, and 10ohms on the LDM power circuit. Do not run cableadjacent to, or in the same conduit as, 120 volts ACservice, noisy electrical circuits that are powering mechanical bells or horns, audio circuitsabove 25 V
RMS, motor control circuits, or SCR power circuits.
Note: All enclosures, including the FACP backbox, must be connected to earth ground!Never use the shield for grounding purposes. Terminate the EIA-485 shield at the FireAlarm Control Panel only.
Fire Alarm Control Panel
STANDARD ANNEALED COPPER WIRE
Wire SizeA.W.G.
Diameterin Mils
Cross Section Ohms per 1000 feet Poundsper 1000 ft.Circ. Mils Sq. Inch @ 77 F. @ 149 F.
14 64 4110 0.00323 2.58 2.97 12.4
16 51 2580 0.00203 4.09 4.73 7.82
18 40 1620 0.00128 6.51 7.51 4.92
Lamp Driver
Two-wire EIA-485 Circuit(Maximum 6000 ft.)
Power for LDM(18 to 14 AWG)
www.PDF-Zoo.com
1615885 Rev. F1 8/2/95 P/N 15885:F1
4.4 EIA-485 Shield in ConduitWhen the EIA-485 wiring is in conduit, connect the shield to system common. The shieldcan enter the cabinet, but must be insulated from the cabinet (no electrical contact). BetweenLDMs, wire-nut multiple shields together (which can be inside of the respective LDM enclosurebut ensure that the shield does not contact earth ground).
Figure 4-4: Terminating the Shield - No Conduit
Mount cabinet or backbox and draw all wiring into enclosure.
Figure 4-2: Wiring the Enclosure
Annunciator
Enclosure
4.5 EIA-485 Shield Not in ConduitWhen the EIA-485 wiring is not in conduit, terminate the shield at the outside of the FACPcabinet. Do not allow the shield to enter or even touch the cabinet housing the LDMs.Between LDMs, wire-nut multiple shields together outside of the respective enclosures.Ensure that the shield does not touch earth ground at any junction points.
Annunciator
Figure 4-3: Terminating the Shield - Conduit
Enclosure
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F117
SupervisionInput
SupervisionInput
5 VDC @ 0.5 mA
When not using the Supervisioninput, jumper terminals 7 and 6together.
Device to be supervised
Figure 4-6: Wiring Supervision Terminals
Supervision Input - TB1, Terminals 6 & 7The Supervision Input, which requires a normally-closed condition, can be used forsupervising power sources or other devices. It must be power-limited. If employed, a changein status will be transmitted to the host control panel in the event of device failure or restoral.If not used, a jumper must be installed across these terminals on TB1. A trouble signal willbe registered by the control panel if a short circuit does not exist across terminals 6 & 7.
Figure 4-5: Wiring Multiple LDMs (6,000 ft. max run)
Host FACP First LDM
4.6 EIA-485, Power and Relay Wiring
EIA-485 - TB2, Terminals 1 to 4• Do not T-tap the EIA-485 circuit. It will not functionproperly. Wire as shown below. Must be power-limited.• Leave a 120 ohm resistor installed across the EIA-485Out terminals at the last LDM on the circuit (see below).All other LDMs should not have a resistor installed.
Power, Earth Grnd and Relay - TB1, Terminals 1 to 7• Connect Earth Ground (TB1-1) to a mounting screw onthe backbox or cabinet.
• 24 VDC Power supplied to the LDM must be power-limited but it need not be supervised by an end-of-linepower supervision relay. This power is inherentlysupervised (the control panel registers a loss ofcommunications during loss of power to the LDM).
Last LDM
120ΩΩΩΩΩ ELRPart #71244
EIA-485 Out (+)
EIA-485 Out (-)
EIA-485 In (-)
EIA-485 In (+)
N.C. Supervision
Inputs
Common In (-)
Common Out (-)
Power In (+24 VDC)
Power Out (+24 VDC)
Earth Ground
Normally ClosedTrouble Contacts
www.PDF-Zoo.com
1815885 Rev. F1 8/2/95 P/N 15885:F1
UL Power Limited Wiring RequirementsPower limited and nonpower limited circuit wiring must remain separated in the cabinet. Allpower limited circuit wiring must remain at least 0.25" away from any nonpower limitedcircuit wiring. Furthermore, all power limited circuit wiring and nonpower limited circuit wiringmust enter and exit the cabinet through different knockouts and/or conduits. A typical wiringdiagram for the LDM-R32 is shown below. If this module is used to drive both power limitedand nonpower limited circuits, connect relays 1 to 16 to power limited circuits and connectrelays 17 to 32 to nonpower limited circuits or vice versa. Use an appropriate power limitedpower supply which is UL listed for fire alarm systems to provide power for the power limitedcircuits.
MPS-24ATB3 Terminal 3 = +24 VDCTB3 Terminal 4 = Common
MPS-24BTB2 Terminal 3 = +24 VDCTB2 Terminal 4 = CommonCAUTION: The +24 VDC provided on TB2 Terminal 3 is power-limited only when used withthe minus return on TB2 Terminal 4. Do not use the minus return on TB2 Terminal 2 with the+24 VDC power on TB2 Terminal 3.
Note: Refer to Figure 4-7 for additional information on these power supplies.
LDM-R32
Non-PowerLimitedCircuits
PowerLimitedCircuits
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F119
4.7 Remote Power Supply ConnectionsThe LDMs may be powered by an MPS-24A or an MPS-24B. The power run to the LDMsneed not contain a Power Supervision Relay since loss of power is inherently supervised.
MPS-24A Main Power SupplyConnect the power run for the LDMs to MPS-24A TB3, Terminals 1 (+) and 2 (-). Maximumcurrent is 1 amp.
MPS-24A
Common (-)to LDM-32 TB1-5
24 VDC Power (+)to LDM-32 TB1-3
MPS-24B
Figure 4-7: Remote Power Supply Connections
MPS-24B Main Power Supply:Connect the power run for the LDMs to MPS-24B, TB2, Terminals 1 (+) and 2 (-). No morethan 200 mA current can be drawn from these terminals in standby or alarm.
System 5000
Common (-)to LDM-32 TB1-5
24 VDC Power (+)to LDM-32 TB1-3
www.PDF-Zoo.com
2015885 Rev. F1 8/2/95 P/N 15885:F1
4.8 Lamp/LED WiringFigure 4-8 illustrates LEDs being powered by the 5 volt output from LDM-32, J11 pin 1.Figure 4-9 illustrates LEDs being powered by the 24 volt output from LDM-32, J9 pin 3.
Note: Use cable kits for wiring from connectors on LDM.
Figure 4-8: Typical LDM-to-Graphics DisplayConnection @ 5VDC
Figure 4-9: Typical LDM-to-Graphics DisplayConnection @ 24 VDC
Note: Use cable kits for wiring from connectors to LDM.
Wiring is notsupervised
SystemTrouble LED:
(Yellow)
CustomGraphicDisplay
SystemTrouble LED:
(Yellow)
Wiring is notsupervised
CustomGraphicDisplay
Point Status LEDs:Use red for alarm points,yellow for trouble pointsand green for output points
Point Status LEDs:Use red for alarm points,yellow for trouble pointsand green for output points
Note: All LEDs must be located in thesame room as the LDM modules.
Use 680 ohm, 1/4-watt resistors foreach point if using 2 mA LEDs
Note: All LEDs must be located in thesame room as the LDM modules.
Use 10K ohm, 1/4-watt resistors foreach point if using 2 mA LEDs
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F121
Each LDM must be set for Alarm/Trouble Mode by positioning slide switch SW4 to the right,for the optional control switches to function (the Acknowledge/Lamp Test switch will work ineither mode). In this configuration, each LDM-32 and LDM-E32 provides 16 alarm drivers,16 trouble drivers and 16 control switches. The alarm and trouble drivers are assigned tohost FACP zones/points via user setup/installation. See Tables in Appendices A and B foradditional information. Not all switches must be used - switches can be wired only fordesired functions. To determine the function of each switch and driver in a System 5000,refer to Table A-1 and the System 5000 Manual. For AM2020/AFP1010 applications, referto Table B-1 and the AM2020/AFP1010 Technical Manual.
1Switches must be UL listed to switch 5 volts DC @ 0.5mA. Switches must be key-locktype, secured in a locked enclosure or a security key switch must be installed to controlaccess. All switches must be installed in the same room as, and no more than 20 feetfrom, the LDM enclosure. Switch wiring must be in conduit.
4.9 Control Switch WiringOptional zone/point control switches must be momentary type. Wiring from the LDM to thecontrol switches must be in conduit and in the same room as the LDM since the wires arenot supervised. Use the cables supplied in the cable kits to wire the control switches.1
Switch #16
Switch #15
Switch #10
Switch #14
Switch #13
Switch #12
Switch #11
Switch #9
Switch #8
Switch #7
Switch #6
Switch #5
Switch #4
Switch #3
Switch #2
Switch #1
Figure 4-10: Optional Zone/Point-Control Switch Wiring
Acknowledge/ Lamp TestSwitch (momentary)
www.PDF-Zoo.com
2215885 Rev. F1 8/2/95 P/N 15885:F1
Section Five: SummaryInstalling the Lamp Driver
Note for the System 5000: The LDM begins annunciation of circuits on the module installeddirectly after the CPU-5000. To ensure full employment of LDM points, mount the modules thatneed lamp driver annunciation in the CPU row first, then in the second row, etc. Modules withcircuits that are not to be annunciated by the LDM-32 should be installed further down in thecabinet.
• Mounting the cabinet or backboxSelect an appropriate knockout on the enclosure. Mount the cabinet or backboxenclosure. Ground the enclosure to a solid metallic earth ground.
• Wiring the LDM-32Pull all annunciator wiring into the enclosure. Terminate the shield as shown in Figure4-3 or 4-4. Connect annunciator wiring to the removable terminal blocks as shown inFigures 4-5 and 4-6. Maintain 0.25" spacing between power-limited and nonpower-limited wiring which must also enter/exit the enclosure through separate knockouts.
Note: A 120 ohm End-of-Line impedance-matching resistor (P/N 71244 supplied with the lampdriver) must be installed at the last annunciator on the EIA-485 circuit. Remove the ELRs installedon all LDMs except the last.
• Mounting hardwareIf a CHS-4L is to be used in mounting the LDM, connect the chassis to the cabinet asillustrated in Figure 3-1. Secure standoffs (supplied) to the chassis or enclosures asshown in Figure 3-1.
• Mounting the modulesMount all LDM modules to the chassis or enclosure as shown in Figure 3-2. One orthree expanders can be installed when the LDM is configured for Alarm/Trouble operation.
• Connecting expander modules (optional)Connect an Expander Ribbon Cable from the LDM-32 (connector J2) to the LDM-E32(connector J3) as illustrated in Figure 3-3.
• Lamp Driver PowerLDM outputs can be powered from 24 VDC or 5 VDC, depending on the loading required.Figures 4-8 and 4-9 illustrate connection of the desired voltage, as well as the SystemTrouble LED. Connection of LDM operating power from a Main Power Supply is illustratedin Figure 4-7. The LDM annunciator can be powered by either the MPS-24A or MPS-24B.
• Control Switches (optional)If normally-open switches are to be installed on the LDM to permit the execution ofsystem control functions and point-control, refer to Figure 4-10.
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F123
In the Appendices:
The following steps are covered in panel-specific appendices. For the System 5000, refer toAppendix A. For the AM2020/AFP1010, refer to Appendix B. For the System 500, refer toAppendix C. For the AFP-200, refer to Appendix D.
• Wiring the Point LEDsVarious point wiring schemes based on LDM configuration are illustrated in the particularappendix for the control panel employed.
Note: All LEDs/lamps being driven by the LDM series must be located in the sameroom as the modules.
• Connect the EIA-485 circuit to the CPU.
• Configure the LDM-32Set the address and DIP switches on the LDM-32 annunciator.
• Programming and testing the LDM-32After complete installation, the Lamp Driver must be programmed into the control panel.Program the LDM as if it were an annunciator. After programming the fire alarm controlpanel to accept the annunciators, fully test the LDMs by ensuring that each switch andLED performs its intended function, and that the annunciators can perform the functionsoutlined in the section, 'Operating the Lamp Driver Module.'
www.PDF-Zoo.com
2415885 Rev. F1 8/2/95 P/N 15885:F1
Section Six:Operating the Lamp Driver Module
6.1 LAMP TEST/ACKNOWLEDGEA separate, dedicated lamp test switch is required for each LDM-32 and LDM-E32. A switchinstalled for LAMP TEST/ACKNOWLEDGE performs two functions:
1) When pressed, it will light all LEDs wired to the specific LDM module (except the OnLine LED) and will sound the integral piezo (if enabled) for as long as the switch is helddown. The Lamp Test switch will light only the LEDs on the module to which it is wired.
2) The switch connected to the LDM-32, when pressed, acknowledges all status changes(for both the LDM-32 and any LDM-E32 expanders). Flashing LEDs will latch on solidand the piezo will be silenced.
6.2 On Line LEDThis green LED, located on the LDM-32 module (lower right corner), flashesduring communication with the host control panel.
6.3 Graphic Annunciator Lamps/LEDsTo adhere to standard fire alarm control panel convention and remainconsistent with other products that may exist in the system, the followingcolor convention is employed:
Red Alarm LEDsTo indicate an alarm condition for an Initiating Device Circuit, softwarezone or addressable initiating device.
Yellow Trouble LEDsTo indicate a trouble condition exists on an initiating or indicating device circuit or zone.Yellow trouble LEDs also are used to indicate general system trouble conditions suchas low battery, earth fault, general system trouble, etc.
Green Controlled Output LEDsIndicates that power is applied or that the controlled output circuit or device has beenactivated. Applicable to notification appliance, relay, speaker, telephone, and time controlcircuits.
The graphic annunciator may contain a yellow System Trouble LED and a red SystemAlarm LED which will light for all trouble or alarm conditions (respectively) in the system(not just for those points of zones mapped to the LDM annunciator/expanders).
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F125
Section Seven: LDM Communications
Receive Only LDM-32sFor duplicate annunciation of system points, LDMs can be configured for Receive Onlyannunciation. Receive Only LDMs must be set to the same address as the LDM they duplicate,but are not fully supervisable. Receive Only LDMs intercept information being transmittedto a Receive/Transmit LDM so that this information can be duplicated at an intermediatedisplay location. When configured for Receive Only operation, LDMs cannot transmitinformation to the host control panel. Remote Acknowledge, Silence, or Reset cannot beperformed. Control switches on Receive Only LDMs are for local lamp test only. If a Receive/Transmit LDM is located at the end of the EIA-485 bus, it will provide supervision of ReceiveOnly LDMs located on the EIA-485 bus between the Receive/Transmit LDM and the FACP.See Figure 7-1.
Receive/Transmit LDM-32LDMs that are configured to serve as full-function annunciators can both receive statusinformation for annunciation as well as transmit commands to the control panel throughcustom-wired point control switches. This allows the LDM to initiate control panel switchfunctions from a remote location in addition to displaying the status of the system.
Figure 7-1: LDM-32 Supervision
Fire AlarmControl Panel
Receive Only LDM-32 setto Address X
Full-Function Receive/TransmitLDM-32 set to Address X
Two-wire EIA-485 Circuit*
LDM-32 LDM-E32
LDM-32 LDM-E32
* EIA-485 circuit is supervised andpower-limited with a characteristicimpedance of 120 ohms.
www.PDF-Zoo.com
2615885 Rev. F1 8/2/95 P/N 15885:F1
Section Eight: LDM Electrical Ratings andCurrent Calculations
Lamp Driver Electrical RatingsLDM modules may use either 24 VDC (regulated) or internal 5 VDC for powering connectedLEDs. 5 volt usage conserves power but is limited in the current available to drive the LEDs.Refer to Section Four, Figures 4-8 and 4-9 for connection illustrations.
Maximum Current per Driver: 100 mA (external circuit must limit current)Maximum Voltage rating per output driver: 30 VDCSupervised circuit (typical rating): 5 volts DC @ 0.5 mABipolar Darlington Open Collector NPN Transistor
Supervision of LDM pointsAny LEDs or lamps connected to the LDM-32 or LDM-E32 are not supervised for failure.Therefore, all LEDs or lamps, must be located in the same room as the LDM modules.
Note: The LDM-32 drives 32 LEDs and each LDM-E32 drives 32more LEDs. An LDM system configured for Alarm and TroubleDisplay Mode and employing three expanders could have as manyas 128 LEDs, all of which are activated during Lamp Test.
5-volt LED Power Limitations
LED currentdesired (mA)
Max # ofLEDs
Number of ModulesLDM-32 LDM-E32
2 130 1 3
5 66 1 1
10 34 1 0
20 17 1/2 0
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F127
Calculating LDM Series Standby and Alarm Currents
Notes:1The 0.040 amps can be reduced to 0.030 for modules with Piezo disable orFlash Inhibit selected.
2Use this line for calculations if LEDs are powered from 24 VDC source.3Use this line for calculations if LEDs are powered from the 5 VDC source fromJ1 on the LDM-32.
The LDM series annunciators draw their power from the Fire Alarm Control Panel andmust be considered when calculating primary and secondary power requirements. Referto the installation manual for the particular control panel employed for the calculation ofpower requirements for the entire system.
1) Enter Standby Total obtained here into the standby calculation tables.2) Enter Alarm Current obtained here into the alarm calculation tables.
[ ] # of LDM-32 Modules X 40 mA =
[ ] # of LDM-E32 Modules X 2 mA =
Standby Total =
Standby Current:
Current Draw for LED Power @ 24 VDC
1
24 VDC
[ ] # of LDM-32 Modules X 56 mA =
[ ] # of LDM-E32 Modules X 18 mA =
[ ] # of LDM-R32 Modules X 288 mA =
[ ] # of LEDs X [ ] mA per LED =
[ ] # of LEDs X [( ) mA/3] =
Alarm Total =
2
3
Alarm Current:
24 VDC
www.PDF-Zoo.com
2815885 Rev. F1 8/2/95 P/N 15885:F1
Appendix A: LDM and the System 5000
CapabilitiesWhen installed with a System 5000, the LDM Series modules can annunciate the status ofinitiating and notification circuits, relays, and several system control functions. Each lampdriver output is automatically assigned to one and only one system I/O point:
Optional System 5000 plug in ModulesIZM-8 - Initiating Device Circuits (alarm and trouble)AIM-200 Zones (alarm and trouble)ICM-4/ICE-4 - Notification Appliance Circuits (trouble)CRM-4/CRE-4 - Control Relay ModulesTCM-2/TCM-4 - Time Control ModulesVCM-4/VCE-4DCM-4
System Contr ol Switc hesAcknowledgeSignal SilenceSystem ResetActivate selected system outputs (notification circuits, relays)
Trouble IndicationCommunication between the CPU and the LDMs is accomplished over a two-wire EIA-485serial communication bus. The EIA-485 bus is supervised by the System 5000. Loss ofcommunication results in System Trouble and Module Failure indications at the CPU.
Lamp/LED Driver OperationLamp Driver outputs do not latch - they track or follow the status of each zone/point that theyare assigned to annunciate. Table A-1 defines the ON status of each Lamp Driver output.
Software RequiredFor the LDM to function properly, the CPU must be operating under ROM1-5000 Part Number73085 (or higher).
Programming for Remote AnnunciationAfter complete installation, the LDM must be programmed into the System 5000 before it willfunction. Program the LDM as if it were an annunciator. Refer to the System 5000 InstallationManual, Document 15584.
Installation RequirementsThe EIA-485 circuit that communicates with the LDM must be connected to the CPU asillustrated below. The CPU must be Revision D or greater. The revision level of the CPU ismarked on a label affixed to the upper board.
System 5000 CPU
(+) EIA-485to LDM TB2 Terminal #1
EIA-485 (-)to LDM TB2 Terminal #4
Supervised andPower-Limited
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F129
Configuration for the LDM-32 and System 5000
Lamp Driver Mode Switch
Ones
Tens
Lamp Driver Address Set in the range 01-04*
DIP Switch (SW3) (see settings below)
LDM-32
Switch set toOFF position
ALARM ONLY mode (SW4 set to left side)
LDM-32 DIP Switch (SW3) settings (for System 5000):
1. Relay Control: Future Use - this switch must be set OFF on the System 5000.
None One Two Three
2. Number of LDM-E32 Expanders Installed: OFF ON OFF ON
3. Number of LDM-E32 Expanders Installed: OFF OFF ON ON
4. 8-Point Shift: Set switch ON to shift CPU-5000 LED function annunciation from the first eightannunciator positions on the LDM-32 to the third LDM-E32 expander positions 57 - 64. This shift canonly be set on an LDM-32 set for address 1.
5. Receive Only: Set this switch ON for each LDM series that will provide the same information asanother LDM series in a different physical location (when two or more sets of LDM series have thesame address, all but one must be configured as Receive Only.)
6. Piezo Disable: Set this switch ON to disable the piezo from sounding for any event.
7. Switch Inhibit: To disable the point I/O control switches on the LDMs from functioning, set thisswitch ON. When inhibited, the local Lamp Test switch continues to function. In addition, theAcknowledge/Lamp Test switch will function only in a local capacity, unrecognized by the hostSystem 5000.
8. Flash Inhibit: Set this switch ON to disable the flashing of LEDs associated with unacknowledgedevents. Flash Inhibit also disables the piezo from sounding. Flash Inhibit must be ON when usingthe relay expander module (LDM-R32).
*The lamp driver can be set for addresses 1, 2, 3 or 4. The actual mapping arrangement for arespective module and its expanders depends on System 5000 annunciator programming. Refer toDocument 15584 for details.
SW4
SW4
Switch set toON position
ALARM/TROUBLE mode (SW4 set to right side)
www.PDF-Zoo.com
3015885 Rev. F1 8/2/95 P/N 15885:F1
Notes:1) Control Switches marked 'not used' will still function as local LAMP TEST or local
ACKNOWLEDGE switches for their respective points.2) If Alarm Only Mode is selected, column labeled Yellow LED is not applicable and control
switches do not function.
1If the 8-Point Shift (DIP switch #4 of SW3) is set ON, the eight System 5000 CPU functions (ACK,SIL, RESET, LAMP TEST, NAC1, NAC2, MUNTIE, RELAY) will be shifted from annunciator points 1through 8 (as shown above) to points 57 through 64 (provided those points exist in the system andthe LDM-32 is set to address 01).
2Optional control switches are active only if all of these conditions are met:a) '8-Point Shift' (DIP switch #4) is set to OFF.b) Receive Only (DIP Switch #5) is set to OFF.c) Switch Inhibit (DIP Switch #7) is set to OFF.
3These Status LEDs are active only when the System 5000 is programmed for Output Status.
4Use green LEDs to indicate activation on controlled output circuits.
5These control switches require that the System 5000 be programmed for Output Control.
Table A-1A: System 5000 CPU Annunciator Point Assignments to LDMs
System 5000CPU Points
LDM Alarm LEDRed
LDM Trouble/Supv LEDYellow
LDM Control Switches
Annunciator Point #1 Indicates System Alarm Indicates System TroubleFunctions as an
ACKNOWLEDGE
Annunciator Point #2 not usedIndicates that signals have
been silencedFunctions as a SIGNAL
SILENCE
Annunciator Point #3 not used not usedFunctions as a SYSTEM
RESET
Annunciator Point #4 not usedIndicates Supervisory
conditionnot used
Annunciator Point #5Indicates that Notification
Circuit 1 has been activatedIndicates trouble status of
circuitControls Notification
Circuit 1
Annunciator Point #6Indicates that Notification
Circuit 2 has been activatedIndicates trouble status of
circuitControls Notification
Circuit 2
Annunciator Point #7Indicates that the Remote
Signaling Municipal Tie hasbeen activated
Indicates trouble status ofcircuit
Controls RemoteSignaling Municipal Tie
Annunciator Point #8Indicates that the Alarm Relay
has been activated
Indicates Module Trouble,Power Failure or Disabled
Circuit(s)Controls Alarm Relay
Table A-1B: System 5000 Option Modules Annunciator Point Assignments to LDMs
System 5000Option Modules
LDM Alarm LEDRed
LDM Trouble/Supv LEDYellow
LDM Control Switches
IZM-8 Alarm Status per Circuit Trouble Status per Circuit not used
ICM-4/ICE-4 Indicates ActivationIndicates Trouble per
CircuitControls Notification Circuit
CRM-4/CRE-4 Indicates ActivationIndicates Trouble per
CircuitControls Relays
TCM-2/TCM-4 Indicates ActivationIndicates Trouble per
CircuitRemote Switch Functions
AIM-200Indicates Alarm Status of
eight software ZonesIndicates Trouble Status of
eight software Zonesnot used
4
4
4
4
3, 4
3, 4
3, 4
5
5
5
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F131
AIM-200 Point AnnunciationThe CPU-5000 can be programmed for an alternate method of annunciating the AIM-200.Up to 192 intelligent devices can be annunciated on a single AIM-200 with LDM seriesannunciators. The System 5000 annunciates the AIM-200 installed directly to the right ofthe CPU-5000. Note that an annunciator cannot be used to execute manual ON/OFF controlof intelligent AIM-200 points only standard System 5000 zones. The option providesannunciation of up to 256 points for the System 5000, broken down as follows:
Annunciator Address 1:
8 CPU points (CPU point shift not an option).
8 unusable points (redundant AIM-200 points).
48 points mapped to the next six modules installed in the System 5000 (which can alsobe AIM-200s for annunciation of their 8 software zones.)
Annunciator Address 2:
Intelligent Detectors, addressed 1-64, on the AIM-200 installed next to the CPU-5000.
Annunciator Address 3:
Addressable Modules, addressed 1-64, on the AIM-200 installed next to the CPU-5000.
Annunciator Address 4:
Intelligent Detectors, addressed 65-96, followed by Addressable Modules, addressed65-96, on the AIM-200 installed next to the CPU-5000.
The System 5000 Programming Manual, Document 15584, provides programminginstructions for this option. Refer to program choice 'AIM(256).'
Note: AIM-200 detector and module addresses 97, 98 and 99 may be used, but cannot bepoint-annunciated.
8 CPUpoints
8 unusableAIM-200points
48 points mapped to thenext six modules installed.
www.PDF-Zoo.com
3215885 Rev. F1 8/2/95 P/N 15885:F1
Notes:1) Circuit corresponds to a specific I/O module installed in user configured System 5000.2) Without 8-Point Shift, the first 8 optional control switches correspond to CPU switch functions:ACK, RES, NAC 1, NAC 2, MUN TIE, RELAY.
Notes:1) It is assumed that systems with 8-Point Shift selected will be 56 zones/points or less.2) Circuit corresponds to a specific I/O module installed in user configured System 5000.3) With 8-Point Shift, the first 8 optional control switches move to the 3rd LDM-E32. The 8CPU switch functions are assigned to Circuits 57 through 64 as shown in the table above.
Table A-2A: LDM Series Switch Control FunctionsAlarm and Trouble Mode Without 8-Point Shift
LDM Switch Position LDM-32 1st LDM-E32 2nd LDM-E32 3rd LDM-E32
1 ACK Circuit 9 Circuit 25 Circuit 41
2 SIG.SIL. Circuit 10 Circuit 26 Circuit 42
3 RESET Circuit 11 Circuit 27 Circuit 43
4 not used Circuit 12 Circuit 28 Circuit 44
5 NAC 1 Circuit 13 Circuit 29 Circuit 45
6 NAC 2 Circuit 14 Circuit 30 Circuit 46
7 MUN TIE Circuit 15 Circuit 31 Circuit 47
8 Alarm Relay Circuit 16 Circuit 32 Circuit 48
9 Circuit 1 Circuit 17 Circuit 33 Circuit 49
10 Circuit 2 Circuit 18 Circuit 34 Circuit 50
11 Circuit 3 Circuit 19 Circuit 35 Circuit 51
12 Circuit 4 Circuit 20 Circuit 36 Circuit 52
13 Circuit 5 Circuit 21 Circuit 37 Circuit 53
14 Circuit 6 Circuit 22 Circuit 38 Circuit 54
15 Circuit 7 Circuit 23 Circuit 39 Circuit 55
16 Circuit 8 Circuit 24 Circuit 40 Circuit 56
Table A-2B: LDM Series Switch Control FunctionsAlarm and Trouble Mode With 8-Point Shift
LDM Switch Position LDM-32 1st LDM-E32 2nd LDM-E32 3rd LDM-E32
1 Circuit 1 Circuit 17 Circuit 33 Circuit 49
2 Circuit 2 Circuit 18 Circuit 34 Circuit 50
3 Circuit 3 Circuit 19 Circuit 35 Circuit 51
4 Circuit 4 Circuit 20 Circuit 36 Circuit 52
5 Circuit 5 Circuit 21 Circuit 37 Circuit 53
6 Circuit 6 Circuit 22 Circuit 38 Circuit 54
7 Circuit 7 Circuit 23 Circuit 39 Circuit 55
8 Circuit 8 Circuit 24 Circuit 40 Circuit 56
9 Circuit 9 Circuit 25 Circuit 41 ACK
10 Circuit 10 Circuit 26 Circuit 42 SIG.SIL.
11 Circuit 11 Circuit 27 Circuit 43 RESET
12 Circuit 12 Circuit 28 Circuit 44 not used
13 Circuit 13 Circuit 29 Circuit 45 NAC 1
14 Circuit 14 Circuit 30 Circuit 46 NAC 2
15 Circuit 15 Circuit 31 Circuit 47 MUN TIE
16 Circuit 16 Circuit 32 Circuit 48 Alarm Relay
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F133
Address #2 1
LDM-32 57 - 64 65 - 72 73 - 80 81 - 88LDM-E32 89 - 96 97 - 104 105 - 112 113 - 120
view of LDM-32
wire toLEDs
Notification Circuit #2 ON (Green LED)
Municipal Tie ON (Red LED)
Alarm Relay ON (Red LED)not used
* System Status Indicators
Figure A-1: Alarm Only Operation Without 8-Point Shift
This figure illustrates the configuration of LDMs to annunciate alarms for up to 120 zones(no zone troubles) with the first eight points (P1 through P8) dedicated to the System 5000functions listed below. (Control switches do not function in Alarm Only configuration).
1It is assumed this module/expander annunciates points (circuits) 65-128 and is not functioning as aReceive Only annunciator.
System Alarm (Red LED)
Notification Circuit #1 ON (Green LED)
Address #1LDM-32 System Functions* 1 - 8 9 - 16 17 - 24LDM-E32 25 - 32 33 - 40 41 - 48 49 - 56
www.PDF-Zoo.com
3415885 Rev. F1 8/2/95 P/N 15885:F1
Address #1LDM-32 1 - 8 9 - 16 17 - 24 25 - 32LDM-E32 33 - 40 41 - 48 49 - 56 System Functions*
wire toLEDs
view of LDM-32
Notification Circuit #2 ON (Green LED)
Municipal Tie ON (Red LED)
Alarm Relay ON (Red LED)not used
1It is assumed that the '8-Point Shift' will be selected only on systems containing less than 56zones/points or a total of 64 annunciator points or less.
* System Status Indicators
1
Figure A-2: Alarm Only Operation with 8-Point Shift
This figure illustrates the configuration of LDMs to annunciate alarms for up to 56 zones (nozone troubles) with the last eight points (P57 through P64) dedicated to the System 5000function annunciations listed below. (Control Switches do not function in Alarm Only mode).
Notification Circuit #1 ON (Green LED)
System Alarm (Red LED)
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F135
Figure A-3: Alarm/Trouble Operation Without 8-Point Shift
This figure illustrates the configuration of LDMs to annunciate alarms and troubles for up to120 zones with the first eight points - 16 LEDs (J5: P1 through P8 and J6: P1 through P8)dedicated to System 5000 system status annunciation.
not used
not used
Supervisory (Yellow LED)
Signals Silenced (Yellow LED)
System Trouble (Yellow LED)
Alarm Relay Trbl (Yellow LED)Municipal Tie Trbl (Yellow LED)
NAC Ckt #2 Trbl (Yellow LED)NAC Ckt #1 Trbl (Yellow LED)
Municipal Tie ON (Red LED)
Alarm Relay ON (Red LED)
NAC Ckt #2 ON (Green LED)
NAC Ckt #1 ON (Green LED)
System Alarm (Red LED)
1It is assumed this module/expander annunciates points (circuits) 64-128.
Address #1
LDM-32 System Status Indicators * 1 - 4 5 - 8
1st LDM-E32 9 - 12 13 - 16 17 - 20 21 - 24
2nd LDM-E32 25 - 28 29 - 32 33 - 36 37 - 40
3rd LDM-E32 41 - 44 45 - 48 49 - 52 53 - 56
Address #2 1
LDM-32 57 - 60 61 - 64 65 - 68 69 - 72
1st LDM-E32 73 - 76 77 - 80 81 - 84 85 - 88
2nd LDM-E32 89 - 92 93 - 96 97 - 100 101 - 104
3rd LDM-E32 105 - 108 109 - 112 113 - 116 117 - 120
view of LDM-32
* System Status Indicators
www.PDF-Zoo.com
3615885 Rev. F1 8/2/95 P/N 15885:F1
not used
not used
Supervisory (Yellow LED)
Signals Silenced (Yellow LED)
System Trouble (Yellow LED)
* System Status Indicators
Alarm Relay Trbl (Yellow LED)Municipal Tie Trbl (Yellow LED)
NAC Ckt #2 Trbl (Yellow LED)NAC Ckt #1 Trbl (Yellow LED)
Municipal Tie ON (Red LED)
Alarm Relay ON (Red LED)
NAC Ckt #2 ON (Green LED)
NAC Ckt #1 ON (Green LED)
1It is assumed that the '8-Point Shift' will be selected only on systems containing lessthan 56 zones/points.
view of LDM-32
System Alarm (Red LED)
Address #1
LDM-32 1 - 4 5 - 8 9 - 12 13 - 16
1st LDM-E32 17 - 20 21 - 24 25 - 28 29 - 32
2nd LDM-E32 33 - 36 37 - 40 41 - 44 45 - 48
3rd LDM-E32 49 - 52 53 - 56 System Status Indicators *
1
Figure A-4: Alarm/Trouble Operation with 8-Point Shift
This figure illustrates the configuration of LDMs to annunciate alarms and troubles for up to56 zones with the last eight points (16 LEDs) dedicated to the CPU functions listed below.
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F137
Address #2 1
LDM-32 57 - 64 65 - 72 73 - 80 81 - 88LDM-E32 89 - 96 97 - 104 105 - 112 113 - 120
Figure A-5: Alarm Relays with LDM-R32
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarmrelays for up to 56 zones with the first eight relays dedicated to the System 5000 functionslisted below.
* System Functions
System Alarmnot usednot usednot used
NAC Circuit #1 ONNAC Circuit #2 ON
N.O. contacts
N.O. contactsN.O. contacts
N.O. contacts
Common for TB1
Common for TB2
Common for TB3Common for TB4
LDM-R32 Lamp Driver Relay Module
1It is assumed this module/expander annunciates points 65-128.
Municipal Tie ONAlarm Relay ON
Address #1LDM-32 System Functions* 1 - 8 9 - 16 17 - 24LDM-E32 25 - 32 33 - 40 41 - 48 49 - 56
www.PDF-Zoo.com
3815885 Rev. F1 8/2/95 P/N 15885:F1
Figure A-6: Alarm Relays with 8-Point Shift
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarmrelays for up to 56 zones with the last eight relays dedicated to the System 5000 functionslisted below.
Address #1LDM-32 1 - 8 9 - 16 17 - 24 25 - 32LDM-E32 33 - 40 41 - 48 49 - 56 System Functions*
1
N.O. contacts
N.O. contactsN.O. contacts
N.O. contacts
Common for TB1
Common for TB2
Common for TB4
LDM-R32 Lamp Driver Relay Module
Common for TB3
System Alarmnot usednot usednot usedNAC Circuit #1 ON
Alarm Relay ON
NAC Circuit #2 ONMunicipal Tie ON
* System Functions
1It is assumed that the '8-Point Shift' will be selected only on systems containing less than 56circuits.
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F139
Figure A-7: Alarm and Trouble Relays with LDM-R32
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarmand trouble relays for up to 120 zones with the first eight relays dedicated to the System5000 functions listed below.
Address #1
LDM-32 System Status Indicators * 1 - 4 5 - 8
1st LDM-E32 9 - 12 13 - 16 17 - 20 21 - 24
2nd LDM-E32 25 - 28 29 - 32 33 - 36 37 - 40
3rd LDM-E32 41 - 44 45 - 48 49 - 52 53 - 56
Address #2
LDM-32 57 - 60 61 - 64 65 - 68 69 - 72
1st LDM-E32 73 - 76 77 - 80 81 - 84 85 - 88
2nd LDM-E32 89 - 92 93 - 96 97 - 100 101 - 104
3rd LDM-E32 105 - 108 109 - 112 113 - 116 117 - 120
Common for TB1
Common for TB2
LDM-R32 Lamp Driver Relay Module
Common for TB4Common for TB3
* System Functions
Municipal Tie Trouble
NAC Circuit # 1 ONNAC Circuit #2 ONMunicipal Tie ONAlarm Relay ONNAC Circuit #1 TroubleNAC Circuit #2 Trouble
Alarm Relay Troublenot used
not usednot usednot usedSystem TroubleSignal Silenced
Supervisory
System Alarm
N.O. contactsN.O. contactsAlarm
N.O.contacts
N.O.contacts
Alarm
Trouble
Alarm
Trouble
Alarm
Trouble
Trouble
www.PDF-Zoo.com
4015885 Rev. F1 8/2/95 P/N 15885:F1
* System Functions
Municipal Tie Trouble
Municipal Tie ONAlarm Relay ONNAC Circuit #1 TroubleNAC Circuit #2 Trouble
Alarm Relay Troublenot used
not usednot usednot usedSystem TroubleSignal Silenced
1It is assumed that the '8-Point Shift' will be selected only on systems containing less than 56 circuits.
Address #1
LDM-32 1 - 4 5 - 8 9 - 12 13 - 16
1st LDM-E32 17 - 20 21 - 24 25 - 28 29 - 32
2nd LDM-E32 33 - 36 37 - 40 41 - 44 45 - 48
3rd LDM-E32 49 - 52 53 - 56 System Status Indicators *
1
Common for TB1
Common for TB2
LDM-R32 Lamp Driver Relay Module
Common for TB4Common for TB3
N.O. contactsN.O. contactsAlarm
N.O.contacts
N.O.contacts
Alarm
Trouble
Alarm
Trouble
Alarm
Trouble
Trouble
Supervisory
System Alarm NAC Circuit # 1 ONNAC Circuit #2 ON
Figure A-8: Alarm and Trouble Relays with 8-Point Shift
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarmsand troubles for up to 56 zones with the last eight relays dedicated to the CPU functionslisted below.
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F141
Appendix B: LDM and the AM2020/AFP1010
CapabilitiesWhen installed with an AM2020/AFP1010, the LDM Series modules can annunciate thestatus of addressable devices, software zones, XP Series Transponder points and severalsystem control functions:
DevicesIntelligent DetectorsMMX Monitor Modules and CMX Control ModulesBGX Addressable Manual Pull Stations, security devices & all other addressabledevices.
Software ZonesAll software zones can be annunciated provided that each zone is mapped toan annunciator point.
System Contr olsAcknowledge/Step (the ACK/STEP key)Signal SilenceSystem ResetLamp Test (test LEDs, printer & CRT terminal output on AM2020/AFP1010only)
XP Series Transponder SystemPower and Audio Supply Supervision PointXPP-1 Form-C Alarm and Trouble Relay PointsXPC Control, XPM Monitor and XPR Relay Module Circuit Points
Software RequiredThe AM2020/AFP1010 is fully compatible with LDM Series modules. The AM2020/AFP1010must be operating with software of the following part numbers (or greater):
AM2020/AFP1010 Board ROM Part NumberCentral Processing Unit (CPU-2020) 73123Display Interface Assembly (DIA-1) 73132Loop Interface Board (LIB-200) 73117 (for each LIB-200)
Warning: Each software ROM installed in the AM2020/AFP1010 must be part of the samesoftware combination. For a list of valid software combination numbers, contact the NotifierTechnical Services Department.
www.PDF-Zoo.com
4215885 Rev. F1 8/2/95 P/N 15885:F1
Hardware RequiredThe AM2020/AFP1010 must include an intelligent Serial Interface Board (SIB-2048). TheEIA-485 circuit must be connected to the SIB-2048 as illustrated below.
P5EIA-485 CommonEarth Ground (chassis)
EIA-485 Loop 1 (+)EIA-485 Loop 1 (-)EIA-485 Loop 2 (+)EIA-485 Loop 2 (-) SIB-2048
The SIB-2048 can support one EIA-485 circuit, capable of spanning 12,000 feet (12 AWG),as illustrated below, provided that the SIB-2048 is located in the center of the span illustratedbelow. A 120 ohm terminating resistor is required at each end of the twisted pair.
LDM-32LDM-32
Control Panel
24 V Power24 V Power
For programming the Lamp Driver Series into AM2020/AFP1010 memory, and for mappingsystem points and software zones to annunciator points, refer to the AM2020/AFP1010Programming Guide, Document 15334.
LDM 'Alarm'/Trouble Mode:
LDM 'Alarm" Only Mode:
First Second ThirdLDM-32 LDM-E32 LDM-E32 LDM-E32points 1-16 points 17-32 points 33-48 points 49-64
LDM-32 LDM-E32points 1-32 points 33-64
Programming for Remote AnnunciationLDM points must be programmed from the AM2020/AFP1010 before the LDM will function.The AM2020/AFP1010 employs the following format for annunciator points:
A(xx) P(yy)
LDM (Annunciator) addressIn the range of 1-32, as set on the
annunciator's rotary decimal switches. LDM (Annunciator) point
EIA-485 Loop(6,000 feet Max)
EIA-485 Loop(6,000 feet Max)
Figure B-1:The EIA-485 Loop
Supervised and Power-Limited
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F143
OperationLDM points 'track' or follow those system points they are programmed to annunciate; thepoints do not latch unless latched by the panel. Table B-1 is a list of how the LDM-32annunciates various AM2020/AFP1010 devices and functions. Note: Control Switchesmarked 'not used' will still function as local LAMP TEST switches for their respective LEDs.
Table B-1: Lamp Driver Point Functions
Point Type
Alarm and Trouble Mode
Alarm Mode Only
Red LED Yellow LED Control Switch
Control ModuleXPC CircuitXPR Circuit
Indicates on/off statusof module or circuit
Indicates trouble/supervisory status of
module or circuit
Turn moduleon/off
Monitor ModuleXPM Circuit
Indicates active statusof module or circuit
Indicates trouble/supervisory status of
module or circuit
not used
Intelligent Detector Indicates fire alarmstatus of detector
Indicates trouble statusof detector
not used
Software Zone Indicates active statusof software zone
Indicates trouble/supervisory status of
software zone
not used
ACK/STEP key Indicates Fire Alarm Indicated SystemTrouble
Functions as anACK/STEP key
SIGNAL SILENCEkey
not used Indicates SignalsSilenced
Functions as aSIGNAL SILENCE
key
SYSTEM RESETkey
Indicates Fire Alarm Indicates SystemTrouble
Functions as aSYSTEM RESET
key
LAMP TEST key not used not used Functions as aLAMP TEST key
www.PDF-Zoo.com
4415885 Rev. F1 8/2/95 P/N 15885:F1
Configuration for the LDM-32 and the AM2020/AFP1010
Lamp Driver Mode Switch
Ones
Tens
Lamp Driver Address Set in the range 01-32*
DIP Switch (SW3) (see settings below)
LDM-32
Switch set toON position
Switch set toOFF position
ALARM ONLY mode (SW4 set to left side)
LDM-32 DIP Switch (SW3) settings (for AM2020/AFP1010):
1. Relay Control: Set to ON when the lamp driver is used to control relays or to provide fanshutdown (see the Annunciator Control System manual, Document 15842 for more details).
None One Two Three
2. Number of LDM-E32 Expanders Installed: OFF ON OFF ON
3. Number of LDM-E32 Expanders Installed: OFF OFF ON ON
4. 8-Point Shift: This switch must always be set OFF on the AM2020 or AFP1010.
5. Receive Only: Set this switch ON for each LDM series that will provide the same information asanother LDM series in a different physical location (when two or more sets of LDM series have thesame address, all but one must be configured as Receive Only.)
6. Piezo Disable: Set this switch ON to disable the piezo from sounding for any event.
7. Switch Inhibit: Set this switch OFF to enable any control switches wired to the Lamp Driver. Ifset ON, switches wired to the Lamp Driver will not execute their intended functions, but will serveonly as a local Lamp Test for their respective points.
8. Flash Inhibit: Set this switch ON to disable the flashing of LEDs associated with unacknowledgedevents. Flash Inhibit also disables the piezo from sounding. Flash Inhibit must be ON when usingthe relay expander module (LDM-R32).
SW4
SW4
ALARM/TROUBLE mode (SW4 set to right side)
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F145
Wiring the LDM for the AM2020/AFP1010
Figure B-2: Lamp Driver Alarm Points
The LDM-32 and one expander can be configured for up to64 alarm points by setting Switch SW4 to the 'ALARM ONLY'position.
SW4
P(1) - P(8) P(9) - P(16) P(17) - P(24)P(25) - P(32)
Points Points Points Points
P(33) - P(40) P(41) - P(48) P(49) - P(56) P(57) - P(64)
Points Points Points Points
LDM-E32 Expander
LDM-32 Lamp Driver
www.PDF-Zoo.com
4615885 Rev. F1 8/2/95 P/N 15885:F1
Figure B-3: Alarm and Trouble Points
Points Points Points Points
The LDM-32 and up to three expanders can be configuredfor up to 64 alarm points and trouble points by setting SwitchSW4 to the 'ALARM/TROUBLE' position.
SW4
LDM-32 Lamp Driver
Alarm Trouble1 - 4 1 - 4
Alarm Trouble5 - 8 5 - 8
Alarm Trouble9 - 12 9 - 12
Alarm Trouble13 - 16 13 - 16
Points Points Points PointsAlarm Trouble17 - 20 17 - 20
Alarm Trouble21 - 24 21 - 24
Alarm Trouble25 - 28 25 - 28
Alarm Trouble29 - 32 29 - 32
FirstLDM-E32 Expander
Points Points Points PointsAlarm Trouble33 - 36 33 - 36
Alarm Trouble37 - 40 37 - 40
Alarm Trouble41 - 44 41 - 44
Alarm Trouble45 - 48 45 - 48
SecondLDM-E32 Expander
ThirdLDM-E32 Expander
Points Points Points PointsAlarm Trouble49 - 52 49 - 52
Alarm Trouble53 - 56 53 - 56
Alarm Trouble57 - 60 57 - 60
Alarm Trouble61 - 64 61 - 64
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F147
Figure B-4: Alarm-Only Relay Operation
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarmrelays for up to 64 AM2020 or AFP1010 points.
N.O. contacts
N.O. contactsN.O. contacts
N.O. contacts
Common for TB1
Common for TB2
Common for TB4
LDM-R32 Lamp Driver Relay Module
Common for TB3
LDM-32 1 - 8 9 - 16 17 - 24 25 - 32LDM-E32 33 - 40 41 - 48 49 - 56 57 - 64
www.PDF-Zoo.com
4815885 Rev. F1 8/2/95 P/N 15885:F1
Figure B-5: Alarm and Trouble Relay Operation
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarmand trouble relays for up to 64 AM2020 or AFP1010 points.
LDM-32 1 - 4 5 - 8 9 - 12 13 - 16
1st LDM-E32 17 - 20 21 - 24 25 - 28 29 - 32
2nd LDM-E32 33 - 36 37 - 40 41 - 44 45 - 48
3rd LDM-E32 49 - 52 53 - 56 57 - 58 59 - 60
Common for TB1
Common for TB2
LDM-R32 Lamp Driver Relay Module
Common for TB4Common for TB3
N.O. contactsN.O. contactsAlarm
N.O.contacts
N.O.contacts
Alarm
Trouble
Alarm
Trouble
Alarm
Trouble
Trouble
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F149
Appendix C: LDM and the System 500
CapabilitiesWhen installed with a System 500, the LDM Series modules can annunciate the status ofinitiating and notification circuits, relays, and several system control functions. Each lampdriver output is automatically assigned to one and only one system I/O point:
Optional System 500 plug in ModulesIZ-4/IZ-4A/IZ-8 - Initiating Device Circuits (alarm and trouble)IC-4/ICE-4/ICR-4L - Notification Appliance Circuits (activation and trouble)CR-4/CRE-4/CR-4L - Control Relay Modules (activation and trouble)TC-2/TC-4 - Time Control Modules (activation and trouble)
System Contr ol Switc hesAcknowledgeSignal SilenceSystem ResetActivate Notification Circuits 1 and 2, the Remote SignalingMunicipal Tie circuit and the Alarm Relay
System 500 Trouble IndicationCommunication between the CPU and the LDMs is accomplished over a two-wire EIA-485serial communication bus. The EIA-485 bus is supervised by the System 500. Loss ofcommunication results in System Trouble and Module Failure indications at the CPU.
Note: 'System Trouble' and 'Module Failure' will also occur if the normally closedsupervisory path between TB1 Terminals 6 and 7 on the annunciator is opened (or thejumper has not been installed).
Installation RequirementsThe EIA-485 circuit that communicates with the LDM must be connected to the CPU asillustrated below.
Figure C-1: Connecting the EIA-485 Loop to the CPU-500
EIA-485 (-)to LDM TB2 Terminal #4
(+) EIA-485to LDM TB2 Terminal #1
Supervised and Power-Limited
www.PDF-Zoo.com
5015885 Rev. F1 8/2/95 P/N 15885:F1
Configuration for the LDM-32 and System 500
Lamp Driver Mode Switch
Ones
Tens
Lamp Driver Address Set in the range 01-04
DIP Switch (SW3) (see settings below)
LDM-32
Switch set toON position
Switch set toOFF position
ALARM ONLY mode (SW4 set to left side)
LDM-32 DIP Switch (SW3) settings (for System 500):
1. Relay Control: Future Use - this switch must be set OFF on the System 500.
None One
2. Number of LDM-E32 Expanders Installed: OFF ON
3. Number of LDM-E32 Expanders Installed: OFF OFF
4. 8-Point Shift: Set switch ON to shift CPU-500 LED function annunciation out of the first eightannunciator positions on the LDM-32 . This switch is intended for systems between 9 and 16 circuitsand employing one LDM-32 module (with no expander) where annunciation of all circuits is desired.
5. Receive Only: Set this switch ON for each LDM series that will provide the same information asanother LDM series in a different physical location (when two or more sets of LDM series have thesame address, all but one must be configured as Receive Only.)
6. Piezo Disable: Set this switch ON to disable the piezo from sounding for any event.
7. Switch Inhibit: To disable the point I/O control switches on the LDMs from functioning, set thisswitch ON. When inhibited, the local Lamp Test switch continues to function. In addition, theAcknowledge/Lamp Test switch will function only in a local capacity, unrecognized by the hostSystem 500.
8. Flash Inhibit: Set this switch ON to disable the flashing of LEDs associated with unacknowledgedevents. Flash Inhibit also disables the piezo from sounding. Flash Inhibit must be ON when usingthe relay expander module (LDM-R32).
SW4
SW4
ALARM/TROUBLE mode (SW4 set to right side)
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F151
Annunciator OperationAnnunciator points 'track' or follow those System 500 points they are programmed toannunciate; they do not latch. Table C-1 outlines the annunciation of various System 500circuits and functions. Note: Control Switches marked 'not used' will still function as localLAMP TEST or local ACKNOWLEDGE switches for their respective points.
1If the 8-Point Shift (DIP switch #4 of SW3) is set ON, the eight functions (ACK, SIL, RESET, LAMPTEST, NAC1, NAC2, MUNTIE, RELAY) will be shifted out of annunciator points 1 through 8. Theseeight points would then annunciate the status of the first eight zones.
2Optional control switches are active only if all of these conditions are met:a) Receive Only (DIP Switch #5) is set to OFF.b) Switch Inhibit (DIP Switch #7) is set to OFF.
3If an IZ-4, IZ-4A or IZ-8 circuit is programmed on the System 500 as a supervisory point, both the redand yellow LEDs will be illuminated for a supervisory condition. Illumination of the yellow LED aloneindicates a trouble condition (open circuit) on the IZ supervisory circuit.
Table C-1A: System 500 CPU Annunciator Point Assignments to LDMs
System 5000CPU Points
LDM Alarm LEDRed
LDM Trouble/Supv LEDYellow
LDM Control Switches
Annunciator Point #1 Indicates System Alarm Indicates System TroubleFunctions as anACKNOWLEDGE
Annunciator Point #2 not usedIndicates that signals have
been silencedFunctions as a SIGNAL
SILENCE
Annunciator Point #3 not used not usedFunctions as a SYSTEM
RESET
Annunciator Point #4 not usedIndicates Supervisory
conditionnot used
Annunciator Point #5Indicates that Notification
Circuit 1 has been activatedIndicates trouble status of
circuitControls Notification
Circuit 1
Annunciator Point #6Indicates that Notification
Circuit 2 has been activatedIndicates trouble status of
circuitControls Notification
Circuit 2
Annunciator Point #7Indicates that the Remote
Signaling Municipal Tie hasbeen activated
Indicates trouble status ofcircuit
Controls RemoteSignaling Municipal Tie
Annunciator Point #8Indicates that the Alarm Relay
has been activated
Indicates Module Trouble,Power Failure or Disabled
Circuit(s)Controls Alarm Relay
1
Table C-1B: System 500 Option Modules Annunciator Point Assignments to LDMs
System 500Option Modules
LDM Alarm LEDRed
LDM Trouble/Supv LEDYellow
LDM Control Switches
IZ-4, IZ-4A, IZ-8 Alarm Status per Circuit Trouble Status per Circuit not used
IC-4/ICE-4/ICR-4L Indicates ActivationIndicates Trouble per
CircuitControls Notification Circuit
CR-4/CRE-4CR-4L Indicates ActivationIndicates Trouble per
CircuitControls Relays
TC-2/TC-4 Indicates ActivationIndicates Trouble per
CircuitRemote Switch Functions
3
2
www.PDF-Zoo.com
5215885 Rev. F1 8/2/95 P/N 15885:F1
Table C-2A: LDM Series Switch Control FunctionsAlarm and Trouble Mode Without 8-Point Shift
LDM Switch Position LDM-32 1st LDM-E32
1 ACK Circuit 9
2 SIG.SIL. Circuit 10
3 RESET Circuit 11
4 not used Circuit 12
5 NAC 1 Circuit 13
6 NAC 2 Circuit 14
7 MUN TIE Circuit 15
8 Alarm Relay Circuit 16
9 Circuit 1 Circuit 17
10 Circuit 2 Circuit 18
11 Circuit 3 Circuit 19
12 Circuit 4 Circuit 20
13 Circuit 5 Circuit 21
14 Circuit 6 Circuit 22
15 Circuit 7 Circuit 23
16 Circuit 8 Circuit 24
Table C-2B:LDM Series Switch Control FunctionsAlarm and Trouble Mode With 8-Point
Shift
LDM Switch Position LDM-32
1 Circuit 1
2 Circuit 2
3 Circuit 3
4 Circuit 4
5 Circuit 5
6 Circuit 6
7 Circuit 7
8 Circuit 8
9 Circuit 9
10 Circuit 10
11 Circuit 11
12 Circuit 12
13 Circuit 13
14 Circuit 14
15 Circuit 15
16 Circuit 16
Figure C-2: Alarm Points Only Operation
This figure illustrates the configuration of LDMs to annunciate alarms for up to 24 zones (nozone troubles) with the first eight points (P1 through P8) dedicated to the System 500 functionannunciations listed below. No expander is needed in this mode.
Address #1LDM-32 System Functions* 1 - 8 9 - 16 17 - 24
wire toLEDs
view of LDM-32
Notification Circuit #2 ON (Green LED)
Municipal Tie ON (Red LED)
Alarm Relay ON (Red LED)not used
* System Status Indicators
Notification Circuit #1 ON (Green LED)
System Alarm (Red LED)
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F153
Figure C-3: Alarm Only Operation with CPU shift
This figure illustrates the configuration of LDMs to annunciate alarms for up to 24 zones (nozone troubles).
Address #1LDM-32 1 - 8 9 - 16 17 - 24 not applicable
wire toLEDs
view of LDM-32
Figure C-4: Alarm and Trouble Points Operation
This figure illustrates the configuration of LDMs to annunciate alarms and troubles for up to24 zones with the first eight points (J5: P1 through P8 and J6: P1 through P8) dedicated toSystem 500 functions.
Address #1
LDM-32 System Status Indicators * 1 - 4 5 - 8
1st LDM-E32 9 - 12 13 - 16 17 - 20 21 - 24
not used
not used
Supervisory (Yellow LED)
Signals Silenced (Yellow LED)
System Trouble (Yellow LED)
Alarm Relay Trbl (Yellow LED)Municipal Tie Trbl (Yellow LED)
NAC Ckt #2 Trbl (Yellow LED)NAC Ckt #1 Trbl (Yellow LED)
Municipal Tie ON (Red LED)
Alarm Relay ON (Red LED)
NAC Ckt #2 ON (Green LED)
NAC Ckt #1 ON (Green LED)
System Alarm (Red LED)
* System Status Indicators
view of LDM-32
www.PDF-Zoo.com
5415885 Rev. F1 8/2/95 P/N 15885:F1
Figure C-5: Alarm/Trouble Operation with 8-Point Shift
This figure illustrates the configuration of LDMs to annunciate alarms and troubles for up to24 zones.
Address #1
LDM-32 1 - 4 5 - 8 9 - 12 13 - 16
1st LDM-E32 17 - 20 21 - 24 not used
view of LDM-32
Figure C-6: Alarm Relays with LDM-R32
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate relays forup to 24 zones with the first eight relays dedicated to the System 500 functions listed below.
Address #1LDM-32 System Functions* 1 - 8 9 - 16 17 - 24
N.O. contactsN.O. contacts
N.O. contacts
Common for TB1
Common for TB2
Common for TB3Common for TB4
LDM-R32 Lamp Driver Relay Module
not usedNAC Circuit #1 ONNAC Circuit #2 ONMunicipal Tie ONAlarm Relay ON
not usednot usedSystem Alarm
N.O.contacts
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F155
Figure C-7: Alarm Relays with 8-Point Shift
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate relays forup to 24 zones.
Address #1LDM-32 1 - 8 9 - 16 17 - 24 not used
N.O. contactsN.O. contacts
N.O. contacts
Common for TB1
Common for TB2
Common for TB3Common for TB4
LDM-R32 Lamp Driver Relay Module
N.O. contacts
www.PDF-Zoo.com
5615885 Rev. F1 8/2/95 P/N 15885:F1
Figure C-8: Alarm and Trouble Relays with LDM-R32
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarmand trouble relays for up to 24 zones with the first eight relays dedicated to the System 500functions listed below..
Address #1
LDM-32 System Status Indicators * 1 - 4 5 - 8
1st LDM-E32 9 - 12 13 - 16 17 - 20 21 - 24
Common for TB1
Common for TB2
LDM-R32 Lamp Driver Relay Module
Common for TB4Common for TB3
N.O. contactsN.O. contactsAlarm
N.O.contacts
N.O.contacts
Alarm
Trouble
Alarm
Trouble
Alarm
Trouble
Trouble
* System Functions
Municipal Tie Trouble
NAC Circuit # 1 ONNAC Circuit #2 ONMunicipal Tie ONAlarm Relay ONNAC Circuit #1 TroubleNAC Circuit #2 Trouble
Alarm Relay Troublenot used
not usednot usednot usedSystem TroubleSignal Silenced
Supervisory
System Alarm
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F157
Figure C-9: Alarm and Trouble Relays with 8-Point Shift
This figure illustrates the configuration of the LDM-R32 to activate alarm and trouble relaysfor up to 24 zones.
Address #1
LDM-32 1 - 4 5 - 8 9 - 12 13 - 16
1st LDM-E32 17 - 20 21 - 24 not used
Common for TB1
Common for TB2
LDM-R32 Lamp Driver Relay Module
Common for TB4Common for TB3
N.O. contactsN.O. contactsAlarm
N.O.contacts
N.O.contacts
Alarm
Trouble
Alarm
Trouble
Alarm
Trouble
Trouble
www.PDF-Zoo.com
5815885 Rev. F1 8/2/95 P/N 15885:F1
Appendix D: LDM and the AFP-200
CapabilitiesWhen installed with an AFP-200, LDM Series modules can annunciate the status of 99software zones and several system control functions. Each lamp driver output is automaticallyassigned to one and only one system I/O point:
Software Intelligent DetectorsZones: MMX Monitor Modules
CMX Control ModulesBGX Addressable Manual Pull Stations
SystemControlSwitches: Acknowledge
Signal SilenceSystem ResetDrill
Trouble IndicationCommunication between the AFP-200 and the LDMs is accomplished over a two-wireEIA-485 serial communication bus. The EIA-485 is supervised by the AFP-200. Loss ofcommunication results in System Trouble and Annunciator 1 (2) No Answer message on thepanel's 80 character LCD display.
Lamp/LED Driver OperationLamp Driver outputs do not latch - they track or follow the status of those point they areprogrammed to annunciate. Table D-1 outlines the annunciation of the various zones andfunctions.
Programming for Remote AnnunciationAfter complete installation, the LDM must be programmed into the AFP-200 before it willfunction. Program the LDM as if it were an ACS annunciator. Refer to the AFP-200Programming Manual, Document 15511.
Installation RequirementsRegulated power (24 VDC) and the EIA-485 circuit that communicates with the LDMs mustbe connected to the AFP-200 as illustrated below.
AFP-200 Main Circuit Board (Top edge)
To LDM TB1-5
To LDM TB1-3
To LDM TB2-1
To LDM TB2-4
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F159
Configuration for the LDM-32 and the AFP-200
Lamp Driver Mode Switch
Ones
Tens
Lamp Driver Address Set in the range of 01 or 02
DIP Switch (SW3) (see settings below)
LDM-32
Switch set toON position
Switch set toOFF position
ALARM ONLY mode (SW4 set to left side)
LDM-32 DIP Switch (SW3) settings (for AFP-200):
1. Relay Control: Future Use - this switch must be set OFF on the AFP-200.
None One Two Three
2. Number of LDM-E32 Expanders Installed: OFF ON OFF ON
3. Number of LDM-E32 Expanders Installed: OFF OFF ON ON
4. 8-Point Shift: Set switch ON to shift AFP-200 LED function annunciation from the first eightannunciator positions on the LDM-32 to the third LDM-E32 expander positions 57 - 64. This shift canonly be set on an LDM-32 set for address 1 (system using less than 56 software zones).
5. Receive Only: Set this switch ON for each LDM series that will provide the same information asanother LDM series in a different physical location (when two or more sets of LDM series have thesame address, all but one must be configured as Receive Only.)
6. Piezo Disable: Set this switch ON to disable the piezo from sounding for any event.
7. Switch Inhibit: To disable the point I/O control switches on the LDMs from functioning, set thisswitch ON. When inhibited, the switches will serve as local Lamp Test switches only. In addition, theAcknowledge/Lamp Test switch will function only in a local capacity, unrecognized by the hostAFP-200.
8. Flash Inhibit: Set this switch ON to disable the flashing of LEDs associated with unacknowledgedevents. Flash Inhibit also disables the piezo from sounding.. Flash inhibit must be ON when usingthe relay expander module (LDM_R32).
SW4
SW4
ALARM/TROUBLE mode (SW4 set to right side)
www.PDF-Zoo.com
6015885 Rev. F1 8/2/95 P/N 15885:F1
A second LDM-32 set to address 02 with expanders would not support control switches.
It is assumed that systems with 8-Point Shift selected will be 56 zones or less.
Table D-1A: LDM Series Switch Control FunctionsAlarm and Trouble Mode Without 8-Point Shift
LDM Switch Position LDM-32F 1st LDM-E32F 2nd LDM-E32F 3rd LDM-E32F
1 ACK not used not used not used
2 SIG.SIL. not used not used not used
3 RESET not used not used not used
4 DRILL not used not used not used
5 not used not used not used not used
6 not used not used not used not used
7 not used not used not used not used
8 not used not used not used not used
9 not used not used not used not used
10 not used not used not used not used
11 not used not used not used not used
12 not used not used not used not used
13 not used not used not used not used
14 not used not used not used not used
15 not used not used not used not used
16 not used not used not used not used
Table D-1B: LDM Series Switch Control FunctionsAlarm and Trouble Mode With 8-Point Shift
LDM Switch Position LDM-32F 1st LDM-E32F 2nd LDM-E32F 3rd LDM-E32F
1 not used not used not used not used
2 not used not used not used not used
3 not used not used not used not used
4 not used not used not used not used
5 not used not used not used not used
6 not used not used not used not used
7 not used not used not used not used
8 not used not used not used not used
9 not used not used not used ACK
10 not used not used not used SIG.SIL.
11 not used not used not used RESET
12 not used not used not used DRILL
13 not used not used not used not used
14 not used not used not used not used
15 not used not used not used not used
16 not used not used not used not used
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F161
wire toLEDs
view of LDM-32
System Alarm
not used
* System Status Indicators
It is assumed this module/expander annunciates zones 65-99 and is not functioning as a 'ReceiveOnly' annunciator.
Figure D-1: Display Active Status of Software Zones Only
This figure illustrates configuration of the LDM to annunciate the Active state of all 99 softwarezones (no zone troubles) with the first eight points (P1 through P8) dedicated to the AFP-200 system function LEDs listed below.
Address #2 1
LDM-32 57 - 64 65 - 72 73 - 80 81 - 88LDM-E32 89 - 96 97 - 99
Address #1LDM-32 System Functions* 1 - 8 9 - 16 17 - 24LDM-E32 25 - 32 33 - 40 41 - 48 49 - 56
www.PDF-Zoo.com
6215885 Rev. F1 8/2/95 P/N 15885:F1
Figure D-2: Active Status of Software Zones with 8-Point Shift
This figure illustrates configuration of the LDM to annunciate the Active state for up to 56zones (no zone troubles) with the last eight points (P57 through P64) dedicated to the AFP-200 system function LEDs listed below.
Address #1LDM-32 1 - 8 9 - 16 17 - 24 25 - 32LDM-E32 33 - 40 41 - 48 49 - 56 System Functions*
view of LDM-32
1
wire toLEDs
System Alarm
not used
* System Status Indicators
1It is assumed that the '8-Point Shift' will be selected only on systems containing less than 56software zones or a total of 64 annunciator points or less.
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F163
Figure D-3: Activation and Trouble Status Annunciation
This figure illustrates wiring the LDM to annunciate the active and trouble states for all 99zones with the first eight points (J5: P1 through P8 and J6: P1 through P8) dedicated toAFP-200 functions listed below.
Address #1
LDM-32 System Status Indicators * 1 - 4 5 - 8
1st LDM-E32 9 - 12 13 - 16 17 - 20 21 - 24
2nd LDM-E32 25 - 28 29 - 32 33 - 36 37 - 40
3rd LDM-E32 41 - 44 45 - 48 49 - 52 53 - 56
Address #2
LDM-32 57 - 60 61 - 64 65 - 68 69 - 72
1st LDM-E32 73 - 76 77 - 80 81 - 84 85 - 88
2nd LDM-E32 89 - 92* 93 - 99*
view of LDM-32
not used
not used
Signals Silenced (Yellow LED)
System Trouble (Yellow LED)
Supervisory (Yellow LED)
not used
not used
not used
not used
not used
* System Status Indicators
System Alarm (Red LED)
1It is assumed that this module/expander annunciates points 64-99.
Zones 90-99 are special functions:
Z90 Presignal Time Run Z94 Time Started/Release Z98 TornadoZ91 Time Started/Release Z95 Time Ctl Active Z99 PrealarmZ92 Time Started/Release Z96 Time Ctl ActiveZ93 Time Started/Release Z97 Holiday Active
AC Fail (Yellow LED)Panel Trouble
Pre-Alarm
www.PDF-Zoo.com
6415885 Rev. F1 8/2/95 P/N 15885:F1
Figure D-4: Activation/Trouble Operation With 8-Point Shift
This figure illustrates configuration for the LDM to annunciate active and trouble states forthe first 56 software zones with the last eight points (16 LEDs) dedicated to the AFP-200functions listed below.
* System Status Indicators
not used
not used
Signals Silenced (Yellow LED)
System Trouble (Yellow LED)
not used
not used
not used
not used
not used
Supervisory (Yellow LED)
System Alarm (Red LED)
view of LDM-32
Address #1
LDM-32 1 - 4 5 - 8 9 - 12 13 - 16
1st LDM-E32 17 - 20 21 - 24 25 - 28 29 - 32
2nd LDM-E32 33 - 36 37 - 40 41 - 44 45 - 48
3rd LDM-E32 49 - 52 53 - 56 System Status Indicators *
1
Pre-AlarmAC Fail (Yellow LED)Panel Trouble
1It is assumed that the '8-Point Shift' will be selected only on systems containing less than 56circuits.
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F165
www.PDF-Zoo.com
6615885 Rev. F1 8/2/95 P/N 15885:F1
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F167
www.PDF-Zoo.com
6815885 Rev. F1 8/2/95 P/N 15885:F1
LIMITED WARRANTY
www.PDF-Zoo.com