LAB6
-
Upload
helena-francis -
Category
Documents
-
view
212 -
download
0
description
Transcript of LAB6
-
EP 314LAB 6 Closed Loop and Controller Design
Block Diagram & Controller Design
-
EP314 Lab Timeline
LAB 1 & 2 -Introduction to MATLAB
Interface, code, function, graph, Simulink, etc.
LAB 3, 4 & 5 - Modelling of Chemical Process
ODE, Transfer Function, Open Loop Analysis, Sensitivity analysis, etc.
LAB 6 ,7,8 & 9 - Closed Loop and Controller Design
Block diagram, controller design, Performance Analysis, Criteria of Good controller, Stability Analysis, etc.
NO LAB
LAB 10 - Advanced Control System
Feedforward, Cascade and Ratio controls.
we
ek
NO LAB
2 3 4 5 6 7 8 9 10 11 12
-
Construct a Simulink block diagram for the control system shownbelow. Design the P controller which gives the offset less than20% of unit step R.
Exercise 1: Design Conventional P Controller
Note: Observe what happen when the value is increased
-
Exercise 1 : Solution1. Create Control system as below
2. Change value until you reach offset < 20% of R
-
Develop PID controller block
1. Start Simulink
2. Formulate PID equation into Simulink block diagram
() = +1
0
+
Required block diagram:
-
Construct a Simulink block diagram for the control system shown below.
Exercise 2: Design Conventional Controller
()
Compare the performance of conventional controller underZN tuning method.
-
Ziegler-Nichols (Z-N) Rulesclosed-loop tuning method
Target : and Steps:
1. Remove the integral and derivative modes of the controller, leaving onlyproportional control.
2. Select a value of proportional gain , disturb the system, and observethe transient response.
Continue increasing the gain in small steps until the response first exhibits asustained oscillation.The value that correspond to the sustained oscillation are the ultimate gain and the ultimate period .
-
Step 1: Apply P Controller, Kc
= 2 = 4 = 8 = 10
Exercise 2 : Solution
At = 10,Control system produce sustain oscillation response.
-
SaveAs: LAB6_ex2.mdl
Step 2: Find Ku and Pu
Exercise 2 : Solution
= = 10
=9.445 1.845
4= 1.9
Hint: Use Data Cursor & hold Alt for multiple point
-
Step 3: Apply Z-N Controller Setting
------------- Z-N Controller Setting --------------Controller Kc TauI TauDP controller: 5 inf 0PI controller: 4.5 1.5833 0PID controller: 6 0.95 0.2375
Answer
Exercise 2 : Solution
-
Exercise 2 : Answer
-
Challenge
Design conventional controller to meet the control system requirement as below:
Zero offset with settling time less than 6s and maximum overshoot of 20%.
-
Challenge : solutionControl System Performance: Zero offset with settling time less than 6s and overshoot of 20%.