Basic Modules
Configuration
PCLPCLPCLPCL
PACiSPACiSPACiSPACiS TechnicalTechnicalTechnicalTechnical TrainingTrainingTrainingTraining LevelLevelLevelLevel 2 22 2
CS&PCS&PCS&PCS&P – –– – Support Team Support Team Support Team Support Team
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
2/17
Schneider Electric 2- CS&P – Basic Modules Configuration – E01
• Content
Circuit Breaker
Disconnector Switch
Transformer
Generic Module
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
3/17
Schneider Electric 3- CS&P – Basic Modules Configuration – E01
• Content
Circuit Breaker
Disconnector Switch
Transformer
Generic Module
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
4/17
Schneider Electric 4- CS&P – Basic Modules Configuration – E01
• Add / Configure a CB1) Circuit Breaker can be added at Bay level in Electric hierarchy.
CB 3 phases (1 DPS for global position) / CB 1 phase (single phase acq.)
Short Name :SCE Key + appears in viewers + printers
CB Type :3-ph, 1-ph, other
2) CB attributes
Nodes definition :AVR
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
5/17
Schneider Electric 5- CS&P – Basic Modules Configuration – E01
• CB-1ph Configuration (1)1) CB 1 phase basic configuration
1.1) Type 1
Typed Switch Ctrl DPC :DPC Open/Close
Typed CB Computed Position DPS :- Global CB Position, computed by C264
- is feedback of DPC command - is animated on PACiS OI / C264 LCD
Typed Switchgear ph A,B,C DPS :
CB single phase position, acquired by C264(DI/CCU or IED)
1.2) Type 2
Position can be computed by :
- typed Switch ph A DPS- typed Phases Not Together SPS
Note : Positions can be SPS
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
6/17
Schneider Electric 6- CS&P – Basic Modules Configuration – E01
• CB-1ph Configuration (2)2) CB enhanced configuration => possible sons
Typed Lock Control SPC :Operator lock
Typed Selection SPC :when SBO, activated at selection
Typed Sync CB Close :Synchrocheck
Typed Lock SPS :Lock status
Typed Phase Not Together SPS :- Indicates if all phases are in same position
- holds a timer for CB trip
Typed withdrawn SPS :brushable devices
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
7/17
Schneider Electric 7- CS&P – Basic Modules Configuration – E01
• CB-3ph Configuration1) CB 3 phases basic configuration
1.1) Type 1
Typed Switch Ctrl DPC :DPC Open/Close
Typed CB Computed Position DPS :- Global CB Position, computed by C264 - is feedback of DPC command
- is animated on PACiS OI / C264 LCD
Typed Switchgear position DPS :CB Position, acquired by C264 (DI/CCU or IED)
1.2) Type 2
Typed Switch Ctrl DPC can be replaced by :
- typed Switch Ctrl SPC for CLOSE- typed Switch ph A SPC for OPEN
Note : Positions can be SPS
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
8/17
Schneider Electric 8- CS&P – Basic Modules Configuration – E01
• Content
Circuit Breaker
Disconnector Switch
Transformer
Generic Module
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
9/17
Schneider Electric 9- CS&P – Basic Modules Configuration – E01
• Add / Configure a Disconnector Switch1) Disconnector switch is a Switchgear , it can be added at Bay level in
Electric hierarchy.
Short Name :SCE Key + appears in viewers + printers
2) DS attributes
Nodes definition :AVR
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
10/17
Schneider Electric 10- CS&P – Basic Modules Configuration – E01
• Switchgear Configuration (1)1) Switchgear basic configuration
Typed Switch Ctrl DPC :DPC Open/Close
Typed Switchgear position DPS :Switchgear Position, acquired by C264 (DI/CCUor IED)
Note : Position can be SPS
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
11/17
Schneider Electric 11- CS&P – Basic Modules Configuration – E01
• Switchgear Configuration (2)2) Switchgear enhanced configuration => possible sons
Typed Lock Control SPC :Operator lock
Typed Selection SPC :when SBO, activated at selection
Typed Lock SPS :Lock status
Typed withdrawn SPS :brushable devices
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
12/17
Schneider Electric 12- CS&P – Basic Modules Configuration – E01
• Content
Circuit Breaker
Disconnector Switch
Transformer
Generic Module
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
13/17
Schneider Electric 13- CS&P – Basic Modules Configuration – E01
• Add / Configure a Transformer1) Transformer module can be added at Transformer or Generic Bay level inElectric hierarchy.
Short Name :SCE Key + appears in viewers + printers
Transformer Type :- Auto wound : no galvanic isolation between HVand LV sides, tap changer acts simultaneously inprimary and secondary : TAP RAISE = LV LOWER - Double wound : galvanic isolation between HVand LV sides, tap changer acts in primary : TAPRAISE = LV RAISE
2) Transformer attributes
Nodes definition :AVR
Power value / impedance :AVR
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
14/17
Schneider Electric 14- CS&P – Basic Modules Configuration – E01
• Transformer Configuration (1)1) Transformer basic configuration
Tap Changer built-in function:cf. DATAPOINTS CONFIGURATION course
Typed Raise/Lower DPC :Tap Change control
Typed TPI MV :cf. DATAPOINTS CONFIGURATION course
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
15/17
Schneider Electric 15- CS&P – Basic Modules Configuration – E01
• Transformer Configuration (2)2) Transformer enhanced configuration => possible sons
Typed Goto min/max DPC :DPC doing raise until max tap / lower until mintap
Typed MCB Open SPC :- AVR
- In case of invalid tap changing, it will stopsupplying tap changer (power cutting)
Typed Higher Position / Lower Position SPS :
- SET when max tap and min tap are reached
Typed TAP Select SPC :when SBO, activated at selection
Typed Tap in progress SPS :- physically acquired by C264 - impact on control sequence
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
16/17
Schneider Electric 16- CS&P – Basic Modules Configuration – E01
• Content
Circuit Breaker
Disconnector SwitchTransformer
Generic Module
-
8/20/2019 L2 V4 04 Basic Modules Configuration E 01
17/17
Schneider Electric 17- CS&P – Basic Modules Configuration – E01
• Features1) Generic Modules are :- non typed modules- contains generic datapoints - huge range of use => non particular context
- ADVISE : DON’T USE GENERIC MODULES for CB and disconnector if youhave :
- Built-in automation (AVR, Synchrocheck, Autorecloser)
- lock, hardware selection, withdrawn
Example for switching device