    Datapoints Configuration

    PCLPCLPCLPCL

    PACiSPACiSPACiSPACiS TechnicalTechnicalTechnicalTechnical TrainingTrainingTrainingTraining LevelLevelLevelLevel 2 22 2

    CS&PCS&PCS&PCS&P – –– – Support Team Support Team Support Team Support Team

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    2/43

    Schneider Electric 2- CS&P – Datapoints Configuration – E01

    • Content

    SPS, DPS, MPS

    MV, TPI, Counters

    SPC, DPC, SetPoints

    Datapoints Quality

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    3/43

    Schneider Electric 3- CS&P – Datapoints Configuration – E01

    • Content

    SPS, DPS, MPS

    MV, TPI, Counters

    SPC, DPC, SetPoints

    Datapoints Quality

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    4/43

    Schneider Electric 4- CS&P – Datapoints Configuration – E01

    TYPED DIGITAL INFORMATION

    It is an information which is representing a special input regarding theMiCOM C264 inner automations.

    Examples : 

    - Switchgear Position DPS, Locking device status SPS, BayLocal/Remote DPS 

    • Typed / Generic xPS

    GENERIC INFORMATION

    It is a standard information which can be configured at any level.

    Examples : 

    - Module xPS, Bay xPS, VoltageLevel xPS, Substation xPS (x=S,D,M)

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    5/43

    Schneider Electric 5- CS&P – Datapoints Configuration – E01

    Mapping SPS

    It is an input which is produced by mapping to another DP. Each state ofthis DP is mapped and corresponds to a state of the mapping SPS.

    • Typed / Generic xPS

    Day cyclic SPSDay cyclic SPSDay cyclic SPSDay cyclic SPS

    It is a transient SPS which is triggered every day at fixed time. (accuracy of+/- 1 minute)(8 max per C264).

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    6/43

    Schneider Electric 6- CS&P – Datapoints Configuration – E01

    • Add / Configure a SPS (1)1) SPS can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy. Some SPS are System Info .

    Short Name :SCE Key + appears in C264 local SOE

    Detection Mode :permanent : DI remains ON as far as signal is ON 

    Time tagging :done at starting/end of signal filtering 

    2) SPS attributes

    Long Name :appears in viewers + printers

    Persistence filtering :SPS should remain valid “Set” or “Reset” duringthe configured timer 

    Forcing Management :

    if FSS enabled, auto/manual force 

    LHMI display :yes = SPS in state list (MSC) 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    7/43

    Schneider Electric 7- CS&P – Datapoints Configuration – E01

    • Add / Configure a SPS (2)3) SPS can be acquired by DIU/CCU board , IED . Some SPS are computed by

    C264 application (C264 automation, …)=> Relations under a SPS

    Has for IED address :SPS acquired by IED 

    Wired on : DI Channel

    SPS acquired by DIU/CCU board 

     V4.7 V4.7 V4.7 V4.7

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    8/43

    Schneider Electric 8- CS&P – Datapoints Configuration – E01

    1) DPS can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy. Some DPS are System Info .

    Short Name :SCE Key + appears in C264 local SOE

    Time tagging :done at starting/end of motion 

    2) DPS attributes

    Long Name :appears in viewers + printers

    Motion & Persistence filtering :Motion : eliminate transients 00 and/or 11 motion

    states Persistence : DPS should remain valid “Open” or“Closed” during the configured timer 

    Forcing Management :

    if FSS enabled, auto/manual force 

    LHMI display :yes = DPS in state list (MSC) 

    • Add / Configure a DPS (1)

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    9/43

    Schneider Electric 9- CS&P – Datapoints Configuration – E01

    • Add / Configure a DPS (2)3) DPS can be acquired by DIU/CCU board , IED . Some DPS are computed by

    C264 application (C264 automation, …)=> Relations under a DPS

    Has for IED address :DPS acquired by IED 

    Wired on :DPS acquired by 2 channels (“open” and“closed”) on DIU/CCU board 

    DPS computed from 2 SPS :DPS acquired using 2 SPS, 1 for “open” and 1 for“closed” 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    10/43

    Schneider Electric 10- CS&P – Datapoints Configuration – E01

    1) MPS can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy. Some MPS are System Info .A MPS can have a maximum 16 valid states.

    Short Name :SCE Key + appears in C264 local SOE

    2) MPS attributes

    Long Name :appears in viewers + printers

    Motion & Persistence filtering :Motion : inhibition (cf. next slide) Persistence : MPS should remain in one validstate during the configured timer 

    Forcing Management :if FSS enabled, auto/manual force 

    LHMI display :yes = MPS in state list (MSC) 

    • Add / Configure a MPS (1)

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    11/43

    Schneider Electric 11- CS&P – Datapoints Configuration – E01

    Example : Change State with Filtering “all DI =0 “

    During change all DI =0

    End of change state

    Before change state 0 1  

     0 2  

     0  3  

     0 4  

     0  5  

     0  6  

     0 7  

     0  8  

     0  9  

    1  0  

    1 1  

    1 2  

    1  3  

    1 4  

    1  5  

    1  6 

     0  

     0  

     0  

     0  

     0  

     0  

     0  

    1  

     0  

     0  

     0  

     0  

     0  

     0  

     0  

     0 

    During change all DI =1

    Example : Change State with Filtering “all DI =1 “

     0 1  

     0 2  

     0  3  

     0 4  

     0  5  

     0  6  

     0 7  

     0  8  

     0  9  

    1  0  

    1 1  

    1 2  

    1  3  

    1 4  

    1  5  

    1  6 

     0  

     0  

     0  

     0  

     0  

     0  

     0  

     0  

     0  

     0  

     0  

     0  

     0  

     0  

     0  

     0 

     0 1  

     0 2  

     0  3  

     0 4  

     0  5  

     0  6  

     0 7  

     0  8  

     0  9  

    1  0  

    1 1  

    1 2  

    1  3  

    1 4  

    1  5  

    1  6 

     0  

     0  

     0  

     0  

     0  

     0  

     0  

     0  

    1  

     0  

     0  

     0  

     0  

     0  

     0  

     0 

     0 1 

     

     0 2 

     

     0  3 

     

     0 4 

     

     0  5 

     

     0  6 

     

     0 7 

     

     0  8 

     

     0  9 

     

    1  0 

     

    1 1 

     

    1 2 

     

    1  3 

     

    1 4 

     

    1  5 

     

    1  6 

     0  

     0  

     0  

     0  

     0  

     0  

     0  

    1  

    1  

     0  

     0  

     0  

     0  

     0  

     0  

     0 

    • Add / Configure a MPS (2)

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    12/43

    Schneider Electric 12- CS&P – Datapoints Configuration – E01

    • Add / Configure a MPS (3)3) MPS can be acquired by DIU/CCU board , IED . Some MPS are computed by

    C264 application (C264 automation, …)=> Relations under a MPS

    Has for IED address :

    MPS acquired by IED 

    Wired on :MPS acquired by a maximum of 16 channels onDIU/CCU boards 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    13/43

    Schneider Electric 13- CS&P – Datapoints Configuration – E01

    • Content

    SPS, DPS, MPS

    MV, TPI, Counters

    SPC, DPC, SetPoints

    Datapoints Quality

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    14/43

    Schneider Electric 14- CS&P – Datapoints Configuration – E01

    • Add / Configure a MV (1)1) MV can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy. Some MV are System Info .

    Short Name :SCE Key + appears in C264 local SOE

    2) MV attributes in General Tab

    Long Name :appears in viewers + printers

    Analogue Type :Analogue (AI,CT/VT,IED) 

    or Digital Measurement 

    Forcing Management :

    if FSS enabled, automatic force to a given value 

    LHMI display :yes = MV in measurementslist (MSC) 

    MV transmission :SBUS, LHMI 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    15/43

    Schneider Electric 15- CS&P – Datapoints Configuration – E01

    • Add / Configure a MV (2)

    Minimum / Maximum Value :scaled values for SCADA and OI display + FullScale definition

    3) MV attributes in Value Features Tab

    Thresholds definition :scaled values for LLL, LL, L, H, HH, HHHthresholds + hysteresis 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    16/43

    Schneider Electric 16- CS&P – Datapoints Configuration – E01

    • Add / Configure a MV (3)

    Scaling Low :Linear / Quadratic 

    4) MV attributes in Scaling Tab

    Minimum / Maximum acquisition values :- if transducer 0/10 mA : 

    min=0, max=10 * - if transducer 4/20 mA : min=0, max=16 * 

    - if voltage of CT/VT with nominal ph-N = 57.7 V min=0, max=57.7 * 

    - if IED (T103 : min=0, max=1; Modbus : cf. IED

    documentation) …* schedule a max value = 120% of expected max max=12, max=20, max=70 ... (transducers canmeasure more and display overflow and

    undershoot measurements).

    Scaling coefficients :scaled value = A1 x acq. Value + B1

    Up to 20 segments

    Additional segments :

    A2, B2 - A3, B3 - ...

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    17/43

    Schneider Electric 17- CS&P – Datapoints Configuration – E01

    • Add / Configure a MV (4)5) MV can be acquired by AIU/TMU/DIU/CCU board , IED . Some MV arecomputed by C264 application (C264 automation, …)=> Relations under a MV

    Has for IED address :

    MV acquired by IED 

    Wired on DI Channels :Digital Measurements acquired by a maximum of64 channels on DIU/CCU boards 

    Wired on AI Channel :Channel to be configured (cf. next slide) 

    Computed by CT/VT board :relation to be configured 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    18/43

    Schneider Electric 18- CS&P – Datapoints Configuration – E01

    • Add / Configure a MV (5)6) AI Board channel configuration

    Transducer range :

    Scanning acquisition period :cf. C264 configuration, Measurements tab 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    19/43

    Schneider Electric 19- CS&P – Datapoints Configuration – E01

    • Add / Configure a TPI (1)1) TPI can ONLY be added under a Tap Changer object belonging to aTransformer module.=> Add / Configure a Tap Changer object :

    Built-in function :Tap Changer 

    Min TAP, Max TAP

    Execution timeout :Time allowed for Tap Changing 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    20/43

    Schneider Electric 20- CS&P – Datapoints Configuration – E01

    • Add / Configure a TPI (2)2) TPI attributes :2.1) General Tab

    TPI type :- Analogue Tap Position acquired byAIU or IED,- Coded Digital Measurement (1/N,

    decimal, gray, BCD) acquired by DIU 

    Note : Tabs are not the same - Value Features is common to Analogue and Digital TPI - Scaling & Tap Position for Analogue 

    - Tap Position for Digital 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    21/43

    Schneider Electric 21- CS&P – Datapoints Configuration – E01

    • Add / Configure a TPI (3)2) TPI attributes :2.2) Value Features Tab

    Minimum / Maximum Value :Should comply with Tap Changer objectconfiguration

    Thresholds definition :scaled values for LLL, LL, L, H, HH, HHHthresholds 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    22/43

    Schneider Electric 22- CS&P – Datapoints Configuration – E01

    • Add / Configure a TPI (4)2) TPI attributes :2.3) Scaling Tab (for Analogue TPI only)

    Minimum / Maximum Acquisition Value :

    Same as for a MV 

    2.4) Tap Position Tab

    For Analogue TPI :

    filtering => transient “intertap” filtering current valid range => gives validity DC inputrange for each tap 

    For Digital TPI :filtering => signal validation inhibition => transient “intertap” filtering 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    23/43

    Schneider Electric 23- CS&P – Datapoints Configuration – E01

    • Add / Configure a TPI (5)3) TPI can be acquired by AIU/DIU/CCU board , IED .=> Relations under a TPI

    Has for IED address :TPI acquired by IED 

    Wired on DI Channels :Digital TPI acquired by a maximum of 64 channelson DIU/CCU boards 

    Wired on AI Channel :Channel to be configured 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    24/43

    Schneider Electric 24- CS&P – Datapoints Configuration – E01

    • Add / Configure a Counter (1)1) Counter can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy.

    Short Name :SCE Key + appears in C264 local SOE

    2) Counter attributes in General Tab

    Long Name :appears in viewers + printers

    Counter Type :Standard (standard DI counting) 

    Energy import / Energy export 

    Counter Acquisition :

    validation => min pulse length to be counted invalidity => for double, non complementarity 

    LHMI display :yes = Counter inmeasurements list (MSC) 

    Counter Management :cf. next slide 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    25/43

    Schneider Electric 25- CS&P – Datapoints Configuration – E01

    • Add / Configure a Counter (2)2) Counter attributes in General Tab

    Counter cumulative period :- configure a period at the end of which the counter value is transmitted (SBUS,LHMI) - possible values : 10mn, 15mn, 30mn, 1h, 2h, 3h, … 24h -at the end of this period, counter value can be reset (C264 re-start counting from

    0) 

    Counter Total for IED counters :Yes => IED is sending real counter

    value No => IED is sending non-scaledvalue 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    26/43

    Schneider Electric 26- CS&P – Datapoints Configuration – E01

    • Add / Configure a Counter (3)3) Counter can be acquired by DIU/CCU board , IED . Some Counters arecomputed by C264 application (C264 automation, …)=> Relations under a Counter

    Has for IED address :

    Counter acquired by IED 

    Wired on :Single counter => 1 DI Channel Double counter => 2 DI Channels 

    integrate :Counter computed by MV integration (example : P) Counter type is not “Standard” but “Energy import” or “Energy export” 

    Integration of P or Q :In case the scale and unit is to big ( In case the scale and unit is to big ( In case the scale and unit is to big ( In case the scale and unit is to big (MVarh MVarh MVarh MVarh for ex.), iffor ex.), iffor ex.), iffor ex.), ifenergy is changing of less than 1MVarh in 10 minutes,energy is changing of less than 1MVarh in 10 minutes,energy is changing of less than 1MVarh in 10 minutes,energy is changing of less than 1MVarh in 10 minutes,the value is not sent (counter is integer so 0.2 value isthe value is not sent (counter is integer so 0.2 value isthe value is not sent (counter is integer so 0.2 value isthe value is not sent (counter is integer so 0.2 value isequal to 0).equal to 0).equal to 0).equal to 0).

    !

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    27/43

    Schneider Electric 27- CS&P – Datapoints Configuration – E01

    • Content

    SPS, DPS, MPS

    MV, TPI, CountersSPC, DPC, SetPoints

    Datapoints Quality

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    28/43

    Schneider Electric 28- CS&P – Datapoints Configuration – E01

    TYPED CONTROL

    It is an information which is representing a special functionality regardingthe MiCOM C264 inner automations.

    Examples : 

    - Switch Ctrl DPC, Locking device status SPC, Bay Local/Remote DPC,Sync CB Close 

    • Typed / Generic xPC

    GENERIC CONTROL

    It is a standard control which can be configured at any level.

    Examples : 

    - Module xPC, Bay xPC, VoltageLevel xPC, Substation xPC (x=S,D)

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    29/43

    Schneider Electric 29- CS&P – Datapoints Configuration – E01

    • Add / Configure a SPC (1)1) SPC can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy. Some SPC are System Info .

    Short Name :SCE Key + appears in C264 local SOE

    Activation Mode :- transient => configure pulse duration - permanent 

    - permanent until feedback 

    2) SPC attributes General Tab

    Long Name :appears in viewers + printers

    LHMI display :yes = SPC in control list

    (MSC) 

    Inter Control timeout :no possibility to execute 2 consecutive ordersduring this timer 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    30/43

    Schneider Electric 30- CS&P – Datapoints Configuration – E01

    • Add / Configure a SPC (2)3) SPC execution may be dependant on Local/Remote status ofSubstation/Bay, on SBMC and/or on control uniqueness=> SPC attributes Dependencies tab

    Substation Local/Remote :

    SS Local => control from OI allowed,from SCADA forbidden 

    Control Uniqueness

    Bay Local/Remote :

    Bay Local => control from LHMIallowed, from OI & SCADA notallowed 

    SBMC :advised not to use SBMC (put No) 

    if needed, local transfer when SS is inRemote 

    Note : This is internal automation existing and configurable for all xPC.

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    31/43

    Schneider Electric 31- CS&P – Datapoints Configuration – E01

    • Add / Configure a SPC (3)4) SPC can be executed on DOU/CCU board , IED . Some SPC are computedby C264 application (C264 automation, …)=> Relations under a SPC

    Has for IED address :

    SPC executed by IED 

    Wired on : DO ChannelSPC executed on DOU/CCU board 

    Interlock SPS :holds a logic allowing/blocking the control 

    Associated DO channel status SPS :for hardwired SPC only 

    Auto/Manu dependency :

    blocks the operator control if an automation is inprogress => connect to SPS/DPS givingautomation status 

    Feedback definition :for C264 acknowledgement cf. slide “§3.4” 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    32/43

    Schneider Electric 32- CS&P – Datapoints Configuration – E01

    • Add / Configure a DPC (1)1) DPC can be added at Substation , Voltage Level , Bay , Module , ISaGRAF automation level in Electric hierarchy. Some DPC are System Info .

    Short Name :SCE Key + appears in C264 local SOE

    Activation Mode :- transient => configure pulse duration (2channels “open” / “close”) 

    - permanent - permanent until feedback 

    2) DPC attributes

    Long Name :appears in viewers + printers

    LHMI display :yes = DPC in control list

    (MSC) 

    Inter Control timeout :no possibility to execute 2 consecutive ordersduring this timer 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    33/43

    Schneider Electric 33- CS&P – Datapoints Configuration – E01

    • Add / Configure a DPC (2)3) DPC execution is dependant on one hand from Local/Remote status ofSubstation/Bay and on the other hand from control uniqueness=> DPC attributes Dependencies tab

    Substation Local/Remote :

    SS Local => control from OI allowed,from SCADA forbidden 

    Control Uniqueness

    Bay Local/Remote :

    Bay Local => control from LHMIallowed, from OI & SCADA notallowed 

    SBMC :advised not to use SBMC (put No) 

    if needed, local transfer when SS is inRemote 

    Note : This is internal automation existing and configurable for all xPC.

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    34/43

    Schneider Electric 34- CS&P – Datapoints Configuration – E01

    • Add / Configure a DPC (2)4) DPC can be executed on DOU/CCU board , IED . Some DPC are computedby C264 application (C264 automation, …)=> Relations under a DPC

    Has for IED address :

    DPC executed by IED 

    Wired on : DO ChannelDPC executed on DOU/CCU board 

    2 Interlock SPS (open/close):holds a logic allowing/blocking the controls 

    2 Associated DO channel status SPS :for hardwired DPC only 

    Auto/Manu dependency :

    blocks the operator control if an automation is inprogress => connect to SPS/DPS givingautomation status 

    Feedback definition :for C264 acknowledgement cf. slide “§3.4” 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    35/43

    Schneider Electric 35- CS&P – Datapoints Configuration – E01

    • Configure a xPC feedback1) SPC/DPC can have for feedback a SPS/DPS=> C264 checks if control success (ex: CB control, feedback CB position)=> Example given for DPC with DPS feedback

    Relation “has for feedback”with 2 attributes :- execution timeout : maximumtime allowed to get feedback - status check : C264 will checkstatus before performing control 

    DPC

    DPS

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    36/43

    Schneider Electric 36- CS&P – Datapoints Configuration – E01

    • Add / Configure a SetPoint (1)1) SetPoints can be added at Substation , Voltage Level , Bay , Module ,ISaGRAF automation level in Electric hierarchy.

    Short Name :SCE Key + appears in C264 local SOE

    SetPoint type :

    2) SetPoint attributes

    Long Name :appears in viewers + printers

    LHMI display :yes = SetPoint in control list(MSC) 

    Minimum / Maximum value :

    raw values for SetPoint validity 

    For Digital SetPoint :increment value pulse duration 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    37/43

    Schneider Electric 37- CS&P – Datapoints Configuration – E01

    • Add / Configure a SetPoint (2)3) SetPoint execution is dependant on one hand from Local/Remote status ofSubstation/Bay and on the other hand from control uniqueness=> SetPoint attributes Dependencies tab

    Substation Local/Remote :

    SS Local => control from OI allowed,from SCADA forbidden 

    Control Uniqueness

    Bay Local/Remote :

    Bay Local => control from LHMIallowed, from OI & SCADA notallowed 

    SBMC :advised not to use SBMC (put No) 

    if needed, local transfer when SS is inRemote 

    Note : This is internal automation existing and configurable for allSetpoints.

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    38/43

    Schneider Electric 38- CS&P – Datapoints Configuration – E01

    • Add / Configure a SetPoint (3)4) SetPoints can be executed on DOU/CCU board , IED . Some SetPoints arecomputed by C264 application (C264 automation, …)=> Relations under a SetPoints

    Has for IED address :SP executed by IED 

    DO Channels :

    C264 will close DO channels using configuredcode (BCD, binary, …) 

    Auto/Manu dependency :blocks the operator control if an automation is in

    progress => connect to SPS/DPS givingautomation status 

    AO Channels :C264 will set AO channel 

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    39/43

    Schneider Electric 39- CS&P – Datapoints Configuration – E01

    • Content

    SPS, DPS, MPS

    MV, TPI, CountersSPC, DPC, SetPoints

    Datapoints Quality

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    40/43

    Schneider Electric 40- CS&P – Datapoints Configuration – E01

    • SPS Status

    SPS STATUS

    RESET

    SET

    SELF CHECK FAULTY

    MEANING

    Electric status 0

    Electric status 1

    Faulty DI Channel on board

    TOGGLING Toggling filtering has detected behaviour

    UNKNOWN IED acquiring DP is disconnected from C264

    FORCED SET * SPS is Forced Set by C264 (FSS enable)

    SUBSTITUTED SET * SPS is Substituted Set by Oper. (FSS enable)

    SUPPRESSED SPS is Suppressed by Oper. (FSS enable)

    * => Same for RESET

    Quality => gives the nature of invalidity

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    41/43

    Schneider Electric 41- CS&P – Datapoints Configuration – E01

    • DPS Status

    DPS STATUS

    OPEN

    CLOSED

    SELF CHECK FAULTY

    MEANING

    Electric status 01

    Electric status 10

    Faulty DI Channel on board

    TOGGLING Toggling filtering has detected behaviour

    UNKNOWN IED acquiring DP is disconnected from C264

    FORCED OPEN * DPS is Forced Open by C264 (FSS enable)

    SUBSTITUTED OPEN * DPS is Substituted Open by Op. (FSS enable)

    SUPPRESSED DPS is Suppressed by Oper. (FSS enable)

    * => Same for CLOSED

    Quality => gives the nature of invalidity

    JAMMED Electric status 00

    UNDEFINED Electric status 11

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    42/43

    Schneider Electric 42- CS&P – Datapoints Configuration – E01

    • MPS Status

    MPS STATUS

    STATE 1 -> STATE 16

    SELF CHECK FAULTY

    MEANING

    Only one channel activated

    Faulty DI Channel on board

    TOGGLING Toggling filtering has detected behaviour

    UNKNOWN IED acquiring DP is disconnected from C264

    FORCED STATE N * MPS is Forced St. N by C264 (FSS enable)

    SUBSTITUTED STATE N * MPS is Substituted St. N by Op. (FSS enable)

    SUPPRESSED MPS is Suppressed by Oper. (FSS enable)

    Quality => gives the nature of invalidity

    UNDEFINED No channel or more than one activated

  • 8/20/2019 L2 V4 02 Datapoints Configuration E 01

    43/43

    Schneider Electric 43- CS&P – Datapoints Configuration – E01

    • MV Status

    MV STATUS

    VALID

    SELF CHECK FAULTY

    MEANING

    MV in between min/MAX and/or L/H threshold

    Faulty DI/AI Channel on board

    TOGGLING Toggling filtering has detected behaviour

    UNKNOWN IED acquiring DP is disconnected from C264

    FORCED MV is Forced C264 (FSS enable)

    SUBSTITUTED STATE N * MV is Substituted by Op. (FSS enable)

    SUPPRESSED MV is Suppressed by Oper. (FSS enable)

    Quality => gives the nature of invalidity

    UNDEFINED No DI channel or more than one activated DM

    OVERRANGE Acquisition out of range

    OPEN CIRCUIT No current on AI channel (mA)

    OVERSHOOT [1,2,3] Over H, HH, HHH Threshold

    UNDERSHOOT [1,2,3] Under L, LL, LLL Threshold