Job Name: System Reference: Date: Indoor Unit: PKA-A12HA7 Outdoor Unit: PUY-A12NKA7 PUY-A12NKA7-BS INDOOR UNIT FEATURES Sleek, compact design Simple installation Vane setting for air flow direction control Auto fan speed mode Ideal for spaces such as server rooms, daycare centers, classrooms, churches, small offices, and more OUTDOOR UNIT FEATURES Variable speed INVERTER-driven compressor Suction accumulator pre-charged with refrigerant volume for piping length up to 100 ft (70 ft. for A12/18/24/30) Low ambient cooling down to -20ºF providing 100% capacity (only for PUY models with wind baffles installed) 24-hour continuous operation (cooling mode) High pressure protection Fast restart due to bypass valve make it ideal for equipment cooling applications, such as data centers Superior energy and operational efficiency SUBMITTAL DATA: PKA-A12HA7 & PUY-A12NKA7(-BS) 12,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEM Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc. P-SERIES

Transcript of Job Name: PUY-A12NKA7-BS -...

Job Name:

System Reference: Date:

Indoor Unit:PKA-A12HA7

Outdoor Unit:□ PUY-A12NKA7□ PUY-A12NKA7-BS

INDOOR UNIT FEATURES• Sleek, compact design• Simple installation• Vane setting for air flow direction control• Auto fan speed mode• Ideal for spaces such as server rooms, daycare centers, classrooms, churches, small offices, and more

OUTDOOR UNIT FEATURES• Variable speed INVERTER-driven compressor• Suction accumulator pre-charged with refrigerant volume for piping length up to 100 ft (70 ft. for A12/18/24/30)• Low ambient cooling down to -20ºF providing 100% capacity (only for PUY models with wind baffles installed)• 24-hour continuous operation (cooling mode)• High pressure protection• Fast restart due to bypass valve make it ideal for equipment cooling applications, such as data centers• Superior energy and operational efficiency

SUBMITTAL DATA: PKA-A12HA7 & PUY-A12NKA7(-BS)12,000 BTU/H WALL-MOUNTED AIR-CONDITIONING SYSTEM

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

P-SERIES

Model Number

Indoor Unit PKA-A12HA7

Outdoor UnitPUY-A12NKA7

PUY-A12NKA7-BS

Cooling*1

Maximum Capacity Btu/h 12,000

Rated Capacity Btu/h 12,000

Minimum Capacity Btu/h 5,800

Maximum Power Input W 1,000

Rated Power Input W 1,000

Moisture Removal Pints/h 2.0

Sensible Heat Factor 0.81

Power Factor % 94.5

EfficiencySEER 20.8

EER *1 12.0

Electrical

Voltage, Phase, Frequency 208 / 230V, 1-phase, 60 Hz

Guaranteed Voltage Range V AC 198 – 253

Voltage: Indoor - Outdoor, S1-S2 V AC 208 / 230

Voltage: Indoor - Outdoor, S2-S3 V DC 24

Voltage: Indoor - Remote controller V DC 12

Recommended Fuse/Breaker Size A 15

Recommended Wire Size (Indoor - Outdoor) AWG 14

Indoor Unit

MCA A 1

Fan Motor Full Load Amperage A 0.33

Fan Motor Output W 30

Airflow Rate, Dry CFM 320-370-425

Airflow Rate, Wet CFM 290-335-380

External Static Pressure in.WG n/a

Sound Pressure Level dB(A) 36-40-43

Drain Pipe Size In. (mm) 5/8 (16)

Condensate Lift Mechanism, Max. Distance In. (mm) n/a

Heat Exchanger Type Plate fin coil

External Finish Color White Munsell 1.0Y 9.2/0.2

Unit DimensionsW: In. (mm) 35-3/8 (898)

D: In. (mm) 9-13/16 (249)

SPECIFICATIONS: PKA-A12HA7 & PUY-A12NKA7(-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Model Number

Indoor Unit PKA-A12HA7

Outdoor UnitPUY-A12NKA7

PUY-A12NKA7-BS

H: In. (mm) 11-5/8 (295)

Package Dimensions

W: In. 39-6/16

D: In. 15-12/16

H: In. 13-6/16

Unit Weight Lbs. (kg) 29 (13)

Package Weight Lbs. 33

Indoor UnitOperatingTemperature range

Cooling Intake Air Temp (Maximum / Minimum) °F 90 DB, 73 WB / 66 DB, 59 WB

Outdoor Unit

MCA A 11

MOCP A 28

Fan Motor Full Load Amperage A 0.50

Fan Motor Output W 46

Airflow Rate CFM 1,590

Refrigerant Control Electronic Expansion Valve

Heat Exchanger Type Cross fin

Sound Pressure Level, Cooling*1 dB(A) 44

Sound Pressure Level, Heating*2 dB(A) 46

Compressor Type INVERTER-driven twin rotary

Compressor Model SNB092FNCM

Compressor Rated Load Amps A 7

Compressor Locked Rotor Amps A 12

Compressor Oil Type // Charge oz. FV50S // 12

External Finish Color Ivory Munsell 3Y 7.8/1.1

Base Pan Heater n/a

Unit Dimensions

W: In. (mm) 31-13/16 + 7/16 (809+62)

D: In. (mm) 11-3/16 (300)

H: In. (mm) 24-13/16 (630)

Package Dimensions

W: In. 37-1/16

D: In. 16-3/16

H: In. 27-7/16

SPECIFICATIONS: PKA-A12HA7 & PUY-A12NKA7(-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Model Number

Indoor Unit PKA-A12HA7

Outdoor UnitPUY-A12NKA7

PUY-A12NKA7-BS

Unit Weight Lbs. (kg) 92 (41)

Package Weight Lbs. (kg) 104 (47)

Outdoor UnitOperatingTemperatureRange

Cooling Intake Air Temp (Maximum / Minimum) °F 115 DB / -20* DB

RefrigerantType R410A

Charge Lbs, oz 4 lbs, 7 oz

Piping

Gas Pipe Size O.D. (Flared) In.(mm) 1/2 (12.7)

Liquid Pipe Size O.D. (Flared) In.(mm) 1/4 (6.35)

Maximum Piping Length Ft. (m) 165 (50)

Maximum Height Difference Ft. (m) 100 (30)

Maximum Number of Bends 15

AHRI Rated Conditions (Rateddata is determined at a fixedcompressor speed)

*1 Cooling (Indoor // Outdoor) °F 80°F DB, 67°F WB // 95°F DB, 75°F WB

Notes*Wind baffles required to operate below 23°F DB in cooling mode. PUY with wind baffle: -20°F - 115°F. Refer to windbaffle documentation for further information.**System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures

SEACOAST PROTECTION• External Outer Panel: Phosphate coating + Acrylic-Enamel coating• Fan Motor Support: Epoxy resin coating (at edge face)• Separator Assembly; Valve Bed: Epoxy resin coating (at edge face)• “Blue Fin” treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airborne

contaminants.

Notes:

SPECIFICATIONS: PKA-A12HA7 & PUY-A12NKA7(-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

3-Pole Disconnect Switch (30A/600V/UL) [fits 2" X 4" utility box] □ TAZ-MS303

Drain Pan Level Sensor (Control for indoor unit shut off to prevent drain pan overflow) □ DPLS2

MaxiBlue Advanced Blue Diamond Mini-Condensation pump w/ Reservoir & Sensor (110V)up to 48,000 Btu/h [recommended]

□ X87-711 - 110

MaxiBlue Advanced Blue Diamond Mini-Condensation pump w/ Reservoir & Sensor(208/230V) up to 48,000 Btu/h [recommended]

□ X87-721 - 208/230

MicroBlue Blue Diamond Mini Condensate Pump (110/208/230V) □ XA5-003

Fascia Kit for MicroBlue Pump – mounts beneath pump □ T18-016

Extension Cord for Blue Diamond Pump □ C13-103

Sauermann Mini-Condensation pump (115V) □ SI30-115

Sauermann Mini-Condensation pump (230V) □ SI30-230

MegaBlue Blue Diamond Condensate Pump (110-230V) □ X87-835

Remote Sensor (extensible) □ PAC-SE41TS-E

Connector for CN32 (remote ON/OFF) □ PAC-SE55RA-E

Connector for CN152 (Back up heating) □ PAC-SE59RA-E

External fan / Heater control relay adapter □ CN24RELAY-KIT-CM3

Backlit, wall-mounted, wireless □ MHK1

Wireless Remote Controller □ MRCH1

Wireless Receiver □ MFH1

Portable Central Controller □ MCCH1

Outside Air Sensor □ MOS1

Wireless adapter □ PAC-USWHS002-WF-1

BACnet® and Modbus Interface □ PAC-UKPRC001-CN-1

Wall-mounted, Wired □ PAC-YT53CRAU-J

Wired Remote Controller □ PAR-33MAA-J

T-STAT Interface □ PAC-US444CN-1

Simple remote controller □ PAC-YT53CRAU

Wireless Remote Controller □ PAR-FL32MA-E

Wire for Remote ON/OFF with CN32 connector □ PAC-715AD

Lockdown Bracket for wireless, hand-held, remote controllers □ RCMKP1CB

ACCESSORIES: PKA-A12HA7

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

Air Outlet Guide □ PAC-SJ07SG-E

Front Wind Baffle □ WB-PA4

Side Advanced Wind Baffle □ WB-SD4

Rear Advanced Wind Baffle □ WB-RE4

Hail Guard □ HG-A5

Drain Socket □ PAC-SJ08DS-E

Centralized Drain Pan □ PAC-SG63DP-E

Control/Service Tool □ PAC-SK52ST

Wall Mounting Bracket (Powder-coated Steel) □ QCWB2000M-1

Wall Mounting Bracket (316 Series Stainless Steel) □ QSWBSS

M-NET Control Adapter for Building Management System □ PAC-SJ19MA-E

Outdoor Unit Mounting Pad 16" x 36" x 3" □ ULTRILITE1

Outdoor Unit 3-1/4 inch Mounting Base - Pair (Plastic) □ DSD-400N

MiniSplit Mounting Stand-Single Fan Models - 12" □ QSMS1201M

MiniSplit Mounting Stand-Single Fan Models - 18" □ QSMS1801M

MiniSplit Mounting Stand-Single Fan Models - 24" □ QSMS2401M

1/4 x 1/2 x 15' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-15

1/4 x 1/2 x 30' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-30

1/4 x 1/2 x 50' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-50

1/4 x 1/2 x 65' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-65

1/4 x 1/2 x 100' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-100

ACCESSORIES: PUY-A12NKA7(-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

PKA-A12HA7

13

OUTLINES AND DIMENSIONS6

Unit: inch (mm)

1/2F ([12.7)

1/4F ([6.35)RefrigerantPiping

Drain hose

Gas pipe

Liquid pipe

[2-1/2~[3-1/8 ([65~[80)

[2-1/2~[3-1/8 ([65~[80)

Through holeSleeve(purchased locally)

Center measurement hole [3/32([2.5)

5/32

(3.8

)

2-1/

4(58

)

0

Wall hole forleft rear piping

Knock out hole forleft rear piping2-3/4×12-3/16(70×310) Wall hole for

right rear piping

77-[3/16([5.1)Tappingscrew hole

4-[5/16([9)Bolt hole Mount board

Indoor unit outline

05/8(16)

9-15/16(253.5)9-1/8(232.5)

1-1/16(28.5)1-9/16(41)

3-1/16(78.5)

4-1/16(103.5)4-9/16(116)6-1/2(166)

7(178.5)8(203.5)

3-9/16(91)

13/16(21.8)

9-1/16(231.5)

10-3/4(273.2)

0

1-1/4(32.7)

2-9/16(66)2-1/16(53.5)

5(128.5)6(153.5)

3/4(20)

9/16

(15)

14-5

/8(3

72.3

)14

(356

.3)

12-7

/8(2

37.5

)

11-7

/16(

291.

5)10

-3/8

(265

)9-

5/16

(238

)8-

13/1

6(22

5)7-

13/1

6(20

0)

4-7/

8(12

5)

2-3/

4(70

)

9/16

(15)

14-5

/8(3

72.3

)14

(356

.3)

12-7

/8(3

27.5

)

10-3

/8(2

65)

11-7

/16(

291.

5)

7-13

/16(

200)

8-13

/16(

225)

4-7/

8(12

5)

2-3/

4(70

)

0

17-5

/8(4

49)

7-9/

16(1

93.5

)7-

1/16

(180

.3)

6-9/

16(1

67)

5-1/

2(14

0)4-

1/2(

115)

6-13

/16(

174)

8-3/

8(21

3)9-

5/16

(238

)10

-15/

16(2

78.3

)

15-1

/2(3

94)

11-1

/16(

281)

17-5

/8(44

9)0

Emergency operation switch(cooling/heating)

Terminal block for MA-remote controller

Terminal block for power supply (option)

Front side(Grille open)

Terminal block for indoor/outdoorconnecting line

17-15/16(457)Gas pipe21-3/16(539)Liquid pipe

6-5/8(169)6-3/16(158)Drain hose

7-3/16(184)

250m

m,9

-13/

16in

ch o

r gre

ater

with

op

tiona

l dra

in p

ump

inst

alla

tion.

Required space(Indoor unit)(mm)

Air inlet

Air inlet

Air outlet

Min

.1-3

1/32

(50)

Min

.9-1

3/16

(250

)

Min.5-7/8(150)Min.8-5/8(220)

Min.1-31/32(50)

Min

.1/4

(7)

Knock out hole for piping

D

2-3/

16(5

6)

2-11

/16(

69)

3/16

(6)

1-11/16(43)

C2-3/16(56)7/16(12.5)

1-11

/16(

43)

B1-3/4(46)

2-5/16(60)

2-5/

16(5

9)

1-11

/16(

43)

A

1-11/16(43)

1-3/

4(46

)2-

3/16

(56)

3/16

(6)

A

Knock out holefor right piping

Right side

Mount board

3/16(5)9-13/16(249)

Top side15-3/16(387) 7-1/2(192)

7-3/

4(19

7)

23-9/16(599)

C B

Operation lamp DEFROST/STAND BY lamp

ReceiverLouver(manual)

Vane(auto)

Knock out holefor lower piping

Knock out holefor lower piping

Under side

5/16

(8) 24-1/16(612)

DKnock out holefor left piping

Left side

Front side

6-1/16(155)2-1/8(55)

27-1/16(688)

11-5

/8(2

95)

35-3/8(898)

[5/8 ([16) O.DEffective length: 15-3/4 (400)

DIMENSIONS: PKA-A12HA7 & PUY-A12NKA7 (-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.

PUY-A12NKA7(-BS)

14

PUZ-A12NKA7 PUZ-A18NKA7 PUY-A12NKA7 PUY-A18NKA7PUZ-A12NKA7-BS PUZ-A18NKA7-BS PUY-A12NKA7-BS PUY-A18NKA7-BS

6 OUTLINES AND DIMENSIONS

1/2 conduit hole

144<5-21/32>

2-{22.2<7/8>

22<7/8>

38<1

-1/2

>24

1<9-

1/2>

Min.100mm<3-15/16>

Piping and wiring connection canbe made from the rear direction only.

*1 In the place where short cycle tends to occur, cooling and heating capacity and power consumption might get lowered 10%. Air outlet guide (optional PAC-SG58SG-E) will help them improve. *2 If air discharges to the wall, the surface might get stained.

2 sides should be open inthe right, left and rear side.

Min.100mm<3-15/16> as long as no obstacle is placed on therear and light-and-left sidesof the unit

*1*2 *1

Air intake

Air discharge4-oval hole

Air intake

Service panel

Connection for liquid pipe

Service panel for charge plug

Service port

Connection for gas pipe

Min.100mm<3-15/16>

Min.500mm<19-11/16>

Min.350mm<13-25/32>

Basi

cally

open

Max

.

<Foundation bolt height>

FOUNDATION

Please secure the unit firmlywith 4 foundation M10<W3/8> bolts.(Bolts, washers and nut must be purchased locally.)

18m

m<2

3/32

>

{33<1-5/16> drain hole

43.6

<1-2

3/32

>15

2<6>

155

400<15-25/32>

347.5<13-11/16>

45.4<1-25/32>

365<

14-3

/8>

330<

13>

300<

11-1

3/16

>

40<1-9/16>

Handle

600<

23-5

/8>

10<3

/8>

300<

11-1

3/16

>

150<5-29/32>287.5<11-11/32>

500<19-11/16>

800<31-1/2>

69<2-23/32>

183<7-7/32>

90<3

-17/

32>

155<

6-3/

32>

23<29/32>

32.5

<1-9

/32>

18<23/32>

FLARE {12.7<1/2>

FLARE {6.35<1/4>

Installation bolt pitch

PIPING-WIRING DIRECTION

Minimum installation space for outdoor unit

Free space around the outdoor unit(basic example)

FOUNDATION BOLTS

Unit: mm<in>

Air discharge

Air intake

Air intake

oval hole2-10×21

drain holeø 42 2-U Shaped notched holes

(Foundation Bolt M10<W 3/8>)

(Foundation Bolt M10<W 3/8>)

330<

13>

300<

11-1

3/16

>

40 <1-19/32>

404.5<15-15/16>

48<1

-29/

32>

360<

14-3

/16>

32.5

<1-9

/32>

500<19-11/16>

Min.500mm<19-11/16>

Min.100mm <3-15/16>

Service portFLARE 12.7 (1/2F)

Connection forgas pipe

FLARE ø

ø

6.35 (1/4F)Connection forliquid pipe

Service panelfor charge plug

Service panelEarth terminal

Terminal connectionLeft ... Power supply wiringRight ... Indoor/Outdoor wiring

23.2<15/16>

99.5

<3-1

5/16

>16

4.5<

6-1/

2>49

2<19

-3/8

>

185.5 <7-5/16>43 °

35 °

2-ø22.2<7/8>1/2 conduit hole

Installation bolt pitch

Handle for moving

22 <7/8>

320<

12-5

/8>

809 <31-7/8> 62 <2-15/32>

154.5 <6-3/32>

310 <12-7/32>

8.5<

11/3

2>

22.3 <29/32>

630

<24-

13/1

6>

Min.100mm<3-15/16>

Basic

ally

open

Min.350mm <13-25/32>

Max.

<Foundation bolt height>

18m

m<2

3/32

>

Free space around the outdoor unit(basic example)

100mm<3-15/16> or more as long asno obstacle is placed on therear and right-and-left sidesof the unit

2 sides should be open in the right, left and rear side.

Please secure the unit firmlywith 4 foundation (M10<W3/8>) bolts.(Bolts, washers and nut must be purchased locally).

FOUNDATION BOLTS

Piping and wiring connection canbe made from the rear direction only.

PIPING-WIRING DIRECTION

FOUNDATION

OCH636

FORM# PKA-A12HA7 / PUY-A12NKA7(-BS) - 201709

1340 Satellite Boulevard, Suwanee, GA 30024Toll Free: 800-433-4822 www.mehvac.com

DIMENSIONS: PKA-A12HA7 & PUY-A12NKA7 (-BS)

Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.