Isolated Intrinsic Safety Barrier
Tosilon Automation - NewPwR
NPEXA
Your Professional Supplier for Hazardous-Area Application
•Thermocouple-Current input type
•Thermocouple Resistance - Current input type
•MV-Mill Volt input type
•Resistance-Resistance input type
•Current, 2-wire input type
•Current output type
•Switch active, switch passive input type
•Switch active, switch passive output type
•Proximity switch input type
•RS485\232\422 communication signal input type
•Frequency signal input type
•Eddy current, magnetic, magneto-resistive input type
•High impedance K Dual
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
About Tosilon - NewPwR
The factory located in Nanjing Luhe Economic and Technology Development Zone, covering an area of 20 acres, with more than 160 employees including about 50 R&D technical engineers, 2 committee
members of national standard committee. The company introduces advanced product line and advanced equipment from USA, Germany, England, etc. and has built a complete production management and quality control system.
Up till now, we gets Ex certification, ATEX certification, CE certification from EU, FCC certification from USA, CCS shipment certification from China, and complied with SIL functional safety certification.
Tosilon is tier one supplier of Sinopec, CNOOC, and designated supplier of China National Chemical Corporation. Meanwhile, we provide long-term supply for our country's major equipment such as
military, aerospace and so on. We have formed a huge sales network all over the country. The total sales in 2012 have exceeded 250,000 units and we have become one of the largest scale companies in the field of industrial instrument in China.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Qualification & Certificates - ATEX
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Qualification & Certificates - FCC
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Qualification & Certificates - CE
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview
Series Code Description
C1 Thermocouple Signal Input / Output Type
C2 RTD Signal Input / Output Type CM3 Current Signal Input / Output Type CM4 Voltage Signal Input / Output Type
C5 Switch Signal Input / Output Type C6 Frequency Signal Input / Output Type C7 Communication Signal Input / Output Type
C87 Eddy Current Signal Input / Output Type C89 Magnetic Resistance Signal Input / Output Type C88 Magneto-electronic Signal Input / Output Type
Outline Structure for Reference
Installation for Reference
115mm
100mm12.8mm17.8mm
PWR
ALM
1 2
3 4
109
7 8
5 6
PWR
ALM
1 2
3 4
109
7 8
5 665
87
9 10
43
21
ALM
PWR PWR
ALM
1 2
3 4
109
7 8
5 665
87
9 10
43
21
ALM
PWRPWR
ALMALM
PWR
4 5 6
321
13 14 15
987
10 11 12121110
7 8 9
151413
1 2 3
654
PWR
ALMALM
PWR
4 5 6
321
13 14 15
987
10 11 12121110
7 8 9
151413
1 2 3
654
PWR
ALM
1 2
3 4
109
7 8
5 6
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Thermocouple Signal Input / Output Type
Main Technical Parameters Explosive-proof grade: [Ex ia]IIC
Permissible input signal from hazardous area:
Thermo-couple:K, E, S, B, J, T, R, N
Signal type and range can be specified at your order and may also be programmed by user.
Output signal to safe area:
DC current:0~10 mA, 4~20 mA, 0~20 mA
DC voltage:0~5 V, 1~5 V, 0~10 V
Signal type and range can be specified at your order and may also be programmed by user.
Transmitting accuracy (at 25 oC±2 oC, without temperature compensation):
Influence of ambient temperature: < 30 ppm/ oC
Rise time: ≤ 2 s (bounce from 10%~90%)
Output load capacity:
DC current: 0~10mA: 0~700 Ω; 4~20mA: 0~350Ω
DC voltage: 0(1) ~ 5V: ≥ 1 MΩ; 0~10V: ≥ 2MΩ
Cold junction compensation range:-20 oC ~+60 oC
Cold junction compensation accuracy:
±1 oC (Preheated for 10 minutes).
Parameters certified by China National Quality Supervision and Test Centre for Explosion Protected Electrical Products
(CQST):
Um =250VAC/DC
Between terminal 1 & 2, 4 & 5:
Uo=6.5 V, Io=9.7 mA, Po=15.8 mW IIB: Co=399 μF, Lo=792 mH
IIC: Co=17.5 μF, Lo=264 mH IIA: Co=700 μF, Lo=1000 mH
NPEXA-C11
NPEXA-C111 NPEXA-CA11
Referenced Model
This type of isolated safety barrier transmits thermocouple
signals from hazardous area to safe area by isolating
transmitting current or voltage signals in a circuit or two
isolated circuits, the input, output, and power supply are
galvanically isolated from each other. Besides, it may also
be connected in a connection network in safe area via
communication ports. It is an intelligent product with
online self-diagnosis function. Customer may set the type
and the range of the input or output signals with a
handheld programmer we provide.
TC type Measurable range Accuracy
K/E/J/N etc. < 300
oC ±0.3
oC
≥ 300 o
C ±0.1% F∙S
S/B/T/R/WRe-series < 500
oC ±0.5
oC
≥ 500 o
C ±0.1% F∙S
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Thermocouple Signal Input / Output Type
Dielectric strength:
≥2500V AC (Input/Output/Power supply, 1 mA leakage current, 1 minute test time)
Insulation coordination:
≥100MΩ (Input/Output/Power supply)
Electromagnetic compatibility: IEC 61000-4
Power supply:
18~32V DC (Recommended voltage:24V DC)
Power consumption:
0.5W (24V power supply, 20mA single output)
0.7W (24V power supply, 20mA double output)
Panel Light Indication:
Light indicating: PWR (green) remains illuminated during normal operation;
Light indicating: ALM (red)glitters or remains illuminated when signal fault occurs.
Model Selection Code Lists:
Model Note
NPEXA-C1 x x x x Thermo-couple input isolated safety barrier
Input loop Single loop as default
D Double loop
1st output
1 4~20mA
2 1~5V
3 0~10mA
4 0~5V
5 0~10V
6 0~20mA
2nd output
None as default
1 4~20mA
2 1~5V
3 0~10mA
4 0~5V
5 0~10V
6 0~20mA
Communication / Alarm function
(not coexists with 2ndoutput)
None as default
T1 485 communication (single output only)
T2 232 communication (single output only)
A1 Single relay alarm output
A2 Double relay alarm output
Note:
Thermocouple input type and the corresponding output range need to be specified when placing order. If you needs to program by yourself, please operate with computer or a handheld programmer.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Thermocouple Signal Input / Output Type
Wiring Diagram
Instructions
9
10
7
8
6
5
1
2
-
+
TcInput
Power supply
+
-
+
-
-
+
Hazardous area Safe area
Output2
Output1
D
R
5
6
8
7
10
9
Output2
Power supply
B
A
+
-
-
+
1
2
-
+
TcInput
Hazardous area Safe area
Output1
14
15
12
9
10
11
7
8
-
+
-
+
1
2
-
+
Tc
Hazardous area Safe area
Input
4~20mA
output1
Relay
output1
Relay
output2
Power supply
7
9
12
10
15
14
8
11
-
+
-
+
24V
24V
+
-
+
-
-
+
1
2
-
+
Tc
4
5
-
+
Tc
Hazardous area Safe area
Input1
Input2
Output1
Output2
Power supply
For the thermocouple input barrier, the compensation wire
should be connected directly to the input terminals on the
barrier without other materials wire. Otherwise it will
cause measurement errors.
Dimension W×H×D (12.8×100×115)mm
W×H×D (17.8×100×115)mm
115mm
100mm12.8mm17.8mm
Ambient Conditions Operating temperature range: -20~+60 oC
Relative humidity: 10%~90%RH
Operating atmosphere pressure: 80~106kPa
Storage and delivery temperature: -40~+80 oC
Installation Method Standard 35mm DIN rail installation, attention that position shall
be stable and firm.
In order to facilitate the heat of the instrument, Please mounted
it vertically if possible.
Calibration The product is of intelligent digital design and accuracy can be
maintained within the range specified in this manual. If
calibration is required, it shall be realized by the handheld
programmer we provide.
Operation Conditions Installation position shall not be affected by strong mechanical
vibration, impact and electromagnetic induction from signal
terminal and power supply, should conformity with the
requirements on electromagnetic interference resistance of
products in Class 3 industrial field atmosphere stipulated in IEC
61000-4, and the atmosphere shall be free from gases that are
corrosive to metal and plastic components.
Supplementary Information If there is any content difference between the specification and
the website or sample, this specification shall prevail. We reserve
the rights to change or update the product information without
prior noticing the users.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - RTD Signal Input / Output Type
Main Technical Parameters
Explosive-proof grade: [Ex ia] IIC
Permissible input signal from hazardous area:
2/3-wire RTD resistance: Pt100, Cu100, Cu50, BA2, BA1 etc.
Linear resistance: 40~400Ω
Signal type and range can be specified at your order and may also be programmed by user.
Output signal to safe area:
DC current: 0~10mA, 4~20mA, 0~20mA DC voltage: 0~5V, 1~5V, 0~10V
1:1 resistance repeating
Signal type and range can be specified at your order and may also be programmed by user.
Transmitting accuracy for RTD (at 25 oC±2 oC, without temperature compensation):
If measurable range <100 oC: ±0.1 oC; If measurable range ≥100 oC: ±0.1%F∙S
For linear resistance:
Accuracy reduces in proportion to Im. e.g.:
1 mA ≤Im≤5 mA: Rm < 0.1 Ω
0.5mA ≤Im < 1 mA: Rm < 0.15 Ω
0.2mA ≤Im<0.5 mA: Rm < 0.45 Ω
Rise time: ≤ 2 s (bounce from 10%~90%)
Influence of ambient temperature: <30ppm/ oC
Lead resistance: ≤ 20 Ω per lead
Output load capacity:
DC current: 0~10mA: 0~700 Ω; 4~20mA: 0~350 Ω
DC voltage: 0(1) ~ 5V: ≥ 1 MΩ; 0~10V: ≥ 2 MΩ
Parameters certified by China National Quality Supervision and Test Centre for Explosion Protected Electrical Products
(CQST): Um=250 V AC/DC
Between terminal 1 & 2, 1 & 3; and terminal 4&5, 4&6:
Uo=6.5 V, Io=9.7 mA, Po=15.8 mW
IIC: Co=17.5 μF, Lo=264 mH
IIB: Co=399 μF, Lo=792 mH
IIA: Co=700 μF, Lo=1000 mH
NPEXA-C21
NPEXA-C211 NPEXA-CA21
Referenced Model
This type of isolated safety barrier transmits RTD resistance
signals from hazardous area to safe area by isolating
transmitting current or voltage or resistance signals in a
circuit or two isolated circuits, and it may also be connected
in a connection network in safe area via communication
ports. The input, output, and the power supply are
galvanically isolated from each other. It is an intelligent
product with online self-diagnosis function. Customer may
set the type and the range of the input or the output signals
with a specific handheld programmer we provide.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - RTD Signal Input / Output Type
Dielectric strength: ≥2500 V AC( Input /Output /Power supply, 1 mA leakage current, 1 minute test time)
Insulation coordination:
≥100MΩ (Input/Output/Power supply)
Electromagnetic compatibility: IEC 61000-4
Power supply:
18~32 V DC (Recommended voltage: 24 V DC)
Power consumption:
0.4W (24V power supply, 20mA single output)
0.6W (24V power supply, 20mA double output)
Panel Light Indication Light indicating: PWR (green) remains illuminated during normal operation;
Light indicating: ALM (red) glitters or remains illuminated when signal fault occurs.
Calibration The product is of intelligent digital design and the accuracy can be maintained within the range specified in this manual. If
calibration is required, it shall be realized by the handheld programmer we provide.
Model Selection Code Lists: Model Note
NPEXA-C2 x x x x Isolated safety barrier
Input loop Single loop as default D Double loop
1st output
1 4~20mA 2 1~5V 3 0~10mA 4 0~5V 5 0~10V 6 0~20mA 7 1:1 resistance repeating
2nd output
None as default 1 4~20mA 2 1~5V 3 0~10mA 4 0~5V 5 0~10V 6 0~20mA 7 1:1 resistance repeating
Communication / Alarm function (not coexists with 2ndoutput)
None as default T1 485 communication (single output only) T2 232 communication (single output only) A1 Single relay alarm output A2 Double relay alarm output
Note: Thermal resistance input type and the corresponding output range need to be specified when placing
order. If you need to program by yourself, please operate with computer or the handheld programmer we provide.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - RTD Signal Input / Output Type
Wiring Diagram
9
10
7
8
6
5
1
2
3
RTD
Input
Output1
Output2
Power supply
RTD
+
-
+
-
-
+
Hazardous area Safe area
2-wire
resistance
3-wire
resistance
D
R
5
6
8
7
10
9
B
A
+
-
-
+
1
2
3
RTD
Input
RTD
Output1
Output2
Power supply
Hazardous area Safe area
2-wire
resistance
3-wire
resistance
14
15
12
9
10
11
7
8
-
+
-
+
0~20mA
output1
Relay
output1
Relay
output2
Power supply
1
2
3
RTD
Input
RTD
Hazardous area Safe area
2-wire
resistance
3-wire
resistance
Power supply
1:1 resistance
output2
1:1 resistance
output1
11
8
14
15
10
12
9
7
-
-
+
-
+
-
-
+
1
2
3
RTD
Input
RTD
Hazardous area Safe area
2-wire
resistance
3-wire
resistance
7
9
11
10
15
14
81:1 resistance
output
Power supply
4~20mA
output2
+
-
-
+
-
+
-
1
2
3
RTD
Input
RTD
Hazardous area Safe area
2-wire
resistance
3-wire
resistance
7
9
12
10
15
14
8
11
-
+
-
+
24V
24V
+
-
+
-
-
+
1
2
3
RTD
Input1
RTD
4
5
6
RTD
Input2
RTD
Output1
Output2
Power supply
Hazardous area Safe area
2-wire
resistance
3-wire
resistance
2-wire
resistance
3-wire
resistance
Dimension W×H×D (12.8×100×115) mm
W×H×D (17.8×100×115)mm
115mm
100mm12.8mm17.8mm
Installation Method
Standard 35mm DIN rail installation, attention that position
shall be stable and firm.
In order to facilitate the heat of the instrument, Please
mounted it vertically if possible.
PWR
ALM
1 2
3 4
109
7 8
5 6
PWR
ALM
1 2
3 4
109
7 8
5 665
87
9 10
43
21
ALM
PWR PWR
ALM
1 2
3 4
109
7 8
5 665
87
9 10
43
21
ALM
PWRPWR
ALMALM
PWR
4 5 6
321
13 14 15
987
10 11 12121110
7 8 9
151413
1 2 3
654
PWR
ALMALM
PWR
4 5 6
321
13 14 15
987
10 11 12121110
7 8 9
151413
1 2 3
654
PWR
ALM
1 2
3 4
109
7 8
5 6
Operation Conditions Installation position shall not be affected by strong
mechanical vibration, impact and electromagnetic induction
from signal terminal and power supply, should conformity
with the requirements on electromagnetic interference
resistance of products in Class 3 industrial field atmosphere
stipulated in IEC 61000-4, and the atmosphere shall be free
from gases that are corrosive to metal and plastic
components.
Supplementary Information If there is any content difference between the specification
and the website or sample, this specification shall prevail. We
reserve the rights to change or update the product
information without prior noticing the users.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Current Signal Input Type
Main Technical Parameters
Explosive-proof grade: [Exia] IIC
Transmitting accuracy: ±0.1%F.S(25 oC±2 oC)
Influence of ambient temperature: <30ppm/ oC
Rise time: ≤0.2ms (bounce from 10%~90%)
Settling time: ≤2ms
Ripple: < 1mV
Permissible input signal from hazardous area:
DC: 4~20mA
Signal type and range can be specified at your order.
Output signal to safe area:
DC current: 0~10mA, 4~20mA, 0~20mA
Signal type and range can be specified at your order.
Output load capacity:
DC current: 0~10mA: ≤1.2KΩ; 0(4)~20mA:≤500Ω
Parameters certified by China National Quality Supervision and Test Centre for Explosion Protected Electrical Products
(CQST):
Um=250VAC/DC
Between terminal 1 & 2 and terminal 4 & 5:
Uo=25.2V, Io=85mA, Po=536mW
IIC: Co=0.074μF, Lo=3.4mH
IIB: Co=0.57μF, Lo=10.2mH
IIA: Co=2.03μF, Lo=27.2mH
Dielectric strength:
≥2500V AC(Input/Output/Power supply, 1 mA leakage current, 1 min test time)
Insulation coordination:
≥100MΩ (Input/Output/Power supply)
Electromagnetic compatibility: IEC 61000-4
Power supply:
18~32V DC (Recommended voltage:24V DC)
Power consumption:
0.8W (single input, 20mA single output)
1.3W (double input, 20mA double output)
NPEXA-CM31
NPEXA-CM311 NPEXA-CM31H
Referenced Model
This type of isolated safety barrier transmits current or
voltage signals from safe area to hazardous area by isolating
transmitting current signals in a circuit or two isolated
circuits. The step response for this series is very quick,
independent power supply is necessarily. The input, output,
and power supply are galvanically isolated from each other.
1 2
3 4
109
7 8
5 6
1 2
3 4
109
7 8
5 665
87
9 10
43
21 1 2
3 4
109
7 8
5 665
87
9 10
43
214 5 6
321
13 14 15
987
10 11 12121110
7 8 9
151413
1 2 3
6544 5 6
321
13 14 15
987
10 11 12121110
7 8 9
151413
1 2 3
6541 2
3 4
109
7 8
5 6
PWR PWR PWRPWR PWR PWRPWR PWR PWR PWR
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Current Signal Input Type
Panel light indication: Light indicating: PWR (green) remains shining during normal operation.
Model Indication
Model Note
NPEXB-CM3 x x x x Analog current output Isolated safety barrier
Input loop Single loop as default
D Double loop
Input
1 4~20mA
2 1~5V
3 0~10mA
4 0~5V
5 0~10V
6 0~20mA
1st output
1 4~20mA
3 0~10mA
6 0~20mA
2nd output
None as default
1 4~20mA
3 0~10mA
6 0~20mA
Wiring diagram:
1
2
PI
IP
5
4
14
15
10
11
8
7
mA
mA
-
+
+
-
+
-
+
-
-
+
Hazardous area Safe area
Output1
Output2
Input1
Input2
Power supply
IP
2
1
mA
5
6
10
9
+
-
+
-
-
+
4~20mA
output
Input
Power supply
Safe areaHazardous area
Dimension W×H×D (12.8×100×115) mm
W×H×D (17.8×100×115) mm
115mm
100mm12.8mm17.8mm
Ambient Conditions Ambient temperature range: −20 oC~+60 oC
Relative humidity: 10%RH~90%RH (40 oC)
Atmospheric pressure: 80kPa~106kPa
Storage and delivery temperature: −40 oC ~+80 oC
Installation method Standard 35mm DIN rail installation, attention that position
shall be stable and firm.
In order to facilitate the heat of the instrument, Please
mounted it vertically if possible.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Voltage Signal Input / Output Type
Main Technical Parameters
Explosion protection sign: [Exia] IIC
Transmitting accuracy: ±0.1%F.S (25 oC±2 oC).
Influence of ambient temperature: <30ppm/oC.
Rise time: ≤0.2ms (bounce from 10%~90%).
Settling time: ≤2ms.
Ripple: <1mV.
Frequency range: 0~300Hz.
Permissible input signal from hazardous area:
DC: 0~5V, 1~5V, 0~10V.
Signal type and range can be specified at your order and may also be programmed by user.
Input resistance: ≥1MΩ.
Available voltage: Not more than 24V for no-load, not less than 15.5V for full load.
Output signal to safe area:
DC current: 0~10mA, 4~20mA, 0~20mA. DC voltage: 0~5V, 1~5V, 0~10V.
Signal type and range can be specified at your order and may also be programmed by user.
Output load capacity:
DC current: 0(4)~20mA: ≤ 350Ω; 0~10mA:≤700Ω;
DC voltage: 0(1)~5V: ≥1MΩ; 0~10V: ≥2MΩ.
Parameters certified by China National Quality Supervision and Test Centre for Explosion Protected Electrical Products
(CQST): Um=250VAC/DC.
Between terminal 1 & 2 and terminal 4 & 5:
Uo=13.7V, Io=3mA, Po=10.3mW
IIC: Co=0.553μF, Lo=1000mH
IIB: Co=3.50μF, Lo=1000mH
IIA: Co=12.6μF, Lo=1000mH
Between terminal 1 & 3 and terminal 4 & 6:
Uo=21V, Io=125mA, Po=657mW
IIC: Co=0.13μF, Lo=1.59mH
IIB: Co=0.89μF, Lo=4.77mH
IIA: Co=3.34μF, Lo=12.72mH
Dielectric strength:
≥2500V AC(Input/Output/Power supply, 1 mA leakage current, 1 min test time).
NPEXA-CM41
NPEXA-CM411 NPEXA-CM4D11
Referenced Model
This type of isolated safety barrier transmits voltage signals
from hazardous area to safe area by isolating transmitting
current or voltage signals in a circuit or two isolated circuits,
and it may also provide power to transmitters. The step
response for this series is very quick, independent power
supply is necessarily. The input, output, and power supply
are galvanically isolated from each other.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Voltage Signal Input / Output Type
Insulation coordination:
≥100MΩ (Input/Output/Power supply).
Electromagnetic compatibility: IEC 61000-4.
Power supply:
18~32V DC (Recommended voltage: 24V DC).
Power consumption:
≤0.4W (single voltage input, 20mA single output)
≤0.6W (single voltage input, 20mA double output)
≤1.6W (double voltage input, 20mA double output)
Panel light indication: Light indicating: PWR (green) remains shining during normal operation.
Model Selection Code Lists: Model Note
NPEXA-CM4 x x x Analog voltage input Isolated safety barrier
Input loop Single loop as default
D Double loop
1st output
1 4~20mA
2 1~5V
3 0~10mA
4 0~5V
5 0~10V
6 0~20mA
2nd output
None as default
1 4~20mA
2 1~5V
3 0~10mA
4 0~5V
5 0~10V
6 0~20mA
Dimension: W×H×D (12.8×100×115) mm
W×H×D (17.8×100×115) mm
115mm
100mm12.8mm17.8mm
Installation method Standard 35mm DIN rail installation, attention that position shall
be stable and firm.
In order to facilitate the heat of the instrument, Please mounted
it vertically if possible.
1 2
3 4
109
7 8
5 6
1 2
3 4
109
7 8
5 665
87
9 10
43
21 1 2
3 4
109
7 8
5 665
87
9 10
43
214 5 6
321
13 14 15
987
10 11 12121110
7 8 9
151413
1 2 3
6544 5 6
321
13 14 15
987
10 11 12121110
7 8 9
151413
1 2 3
6541 2
3 4
109
7 8
5 6
PWR PWR PWRPWR PWR PWRPWR PWR PWR PWR
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Voltage Signal Input / Output Type
Wiring diagram:
Ambient conditions Operating temperature range: -20~+60 oC
Relative humidity: 10%~90%RH
Operating atmosphere pressure: 80~106kPa
Storage and delivery temperature: -40~+80 oC
9
10
6
5
1
2
V
3Distribution
Input
Power supply
-
+
+
+
-
-
+
Hazardousarea
Safe area
Output
9
10
7
8
6
5
1
2
V
3Distribution
Input
Output1
Output2
Power Supply
-
+
+
+
-
+
-
-
+
Safe area
24V DC,single input, single or double output
Hazardous
area
3
V
2
1
4
5
V
6
-
+
-
+
12
11
10
14
15
9
8
7
+
-
+
-
+
-
+
+
-
-
+
+
Hazardous
areaSafe area
Input1
Distribution
Input2
Distribution
Output1
Output2
Power supply
Operation conditions Installation position shall not be affected by strong mechanical
vibration, impact and electromagnetic induction from signal
terminal and power supply, should conformity with the
requirements on electromagnetic interference resistance of
products in Class 3 industrial field atmosphere stipulated in IEC
61000-4, and the atmosphere shall be free from gases that are
corrosive to metal and plastic components.
Supplementary information If there is any content difference between the specification and the
website or sample, this specification shall prevail. We reserve the
rights to change or update the product information without prior
noticing the users.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Switch Signal Input / Output Type
Main Technical Parameters
Explosive-proof grade:
[Ex ia] IIC
Permissible input signal from hazardous area:
Dry contact input;
Electrode input;
Logical input: “ON” signal: 5V~30V, providing power to field apparatus; “OFF” signal: 0V~1V, open input.
Output signal to non-hazardous area:
Solenoids or audible alarms driven by 35mA current output;
Maximum output voltage:
22V
Minimum output voltage:
12V
Output current limit:
35mA
Parameter certified by China National Quality Supervision and Test Centre for Explosion Protected Electrical Products
(CQST): Um=250V AC/DC
Between terminals 1 & 2, terminals 4 & 5:
Uo=25.2V, Io=85mA, Po=536mW
IIC: Co=0.074μF, Lo=3.4mH
IIB: Co=0.57μF, Lo=10.2mH
IIA: Co=2.03μF, Lo=27.2mH
Dielectric strength:
≥2500V AC (Input /Output /Power supply, 1mA leakage current, 1 minute test time)
Insulation coordination:
≥100MΩ (Input /Output /Power supply)
Electromagnetic compatibility: IEC 61000-4
Power supply: 18~32V DC (Recommended voltage: 24V DC)
Power consumption:
1.0W (single input, single output)
2.0W (double input, double output)
NPEXA-C511
NPEXA-C5111 NPEXA-C512
Referenced Model
This isolated barrier is used for intrinsic safety applications. It
supplies power from non-hazardous area to small power
consumption intrinsically safe apparatus in hazardous area by
dry contacts, electrode and logic level signal. They are
applicable to such intrinsically safe apparatus as solenoids,
LEDs, and audible alarms.
The input, output and the power supply ports are galvanically
isolated from each other.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Switch Signal Input / Output Type
Output equivalent circuit diagram
危险区信号输出等效电路
300 Ohm(max.)
22 V(min.)
35mA
Output signal characteristic diagram
I(mA)35
12
22
U(V)
危险区信号输出特性图
E
E:Curve angle point (UE, IE)
Wiring diagram
Single input & single output
Double input & double output
2
1
10
9
5
6
Input
Output
Power supply
+
-
-
+
+
-
Hazardous area Safe area
NPEXB-C511
15
14
8
7
10
11
Input 1
Input 2
Output 1
Output 2
Power Supply
-
+
-
+
+
-
2
1
+
-
5
4
+
-
Hazardous area Safe area
NPEXB-C5D11
Dimension W×H×D (12.8×100×115) mm
W×H×D (17.8×100×115) mm
115mm
100mm12.8mm17.8mm
Installation Method Standard 35mm DIN rail installation, attention that position
shall be stable and firm.
In order to facilitate the heat of the instrument, Please
mounted it vertically if possible.
PWR
1 2
3 4
109
7 8
5 6
PWR
1 2
3 4
109
7 8
5 665
87
9 10
43
21
PWR PWR
1 2
3 4
109
7 8
5 665
87
9 10
43
21
PWRPWR
1 2
3 4
109
7 8
5 6
CHCHCHCHCHCH
PWR
4 5 6
321
13 14 15
987
10 11 12121110
7 8 9
151413
1 2 3
654
PWRPWR
4 5 6
321
13 14 15
987
10 11 12121110
7 8 9
151413
1 2 3
654
PWR
CH2
CH1
CH2
CH1
CH2
CH1
CH2
CH1
Panel Light Indication Light indicating: Power indicator PWR (green). It remains
illuminated during normal operation;
Light indicating (single channel): output signal status indicator
CH (red). It remains illuminated when there is output signal.
Light indicating (double channel): output signal status
indicators CH1 and CH2 (red). The corresponding indicator
turn on when output signal.
Ambient Conditions Ambient temperature range: −20 oC~+60 oC
Relative humidity: 10%RH~90%RH(40 oC)
Atmospheric pressure: 80kPa~106kPa
Storage and delivery temperature: −40 oC~+80 oC Operation Conditions Installation position shall not be affected by strong mechanical vibration, impact and electromagnetic
induction from signal terminal and power supply, should conformity with the requirements on
electromagnetic interference resistance of products in Class 3 industrial field atmosphere stipulated in IEC
61000-4, and the atmosphere shall be free from gases that are corrosive to metal and plastic components.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Frequency Signal Input / Output Type
Main Technical Parameters
Explosive-proof grade: [Exia] IIC
Transmitting accuracy: ±0.1%F.S (25 oC±2 oC)
Influence of ambient temperature: <30ppm/ oC
Rise time: ≤0.5s (current or voltage output)
≤5μs (frequency output)
Permissible input signal from hazardous area:
Frequency: 0~50 kHz (for analogue output)
Frequency: 0~20 kHz (for frequency output)
Switching trigger point: Low level: 0~1V; High level: 4~30V;
Input resistance: ≥3kΩ
Distribution voltage: 24V
Distribution current: 24V, not less than 16V when loaded with 20mA.
Output signal to safe area:
DC current output: 0~10mA, 4~20mA, 0~20mA;
DC voltage output: 0~5V, 1~5V, 0~10V;
1:1 frequency output: open collector
emitter follower
logic level
Open collector: high level: Vcc(≤30V); low level: ≤2V; drive current: ≤10mA
Emitter follower: high level: Vcc-2V; low level: ≤0.5V; drive current: ≤10mA
Logic level: High level: 18V≤VH≤24V; low level: VL≤2V;
Load resistance: ≥2kΩ (24V system)
Output load capacity:
DC current: 0~10mA: ≤700Ω; 4~20mA: ≤350Ω;
DC voltage: 0(1)~5V: ≥1MΩ; 0~10V: ≥2MΩ.
Power supply:
18~32 V DC (Recommended voltage: 24 V DC)
NPEXA-C61
NPEXA-C611 NPEXA-CA61
Referenced Model
This type of product transmits 0~50KHz frequency signal from
hazardous area to safe area by isolating transmitting current,
voltage or frequency signals in a circuit or two isolated
circuits, and it may also provide power to apparatus in
hazardous area. The input, output and the power supply is
galvanically isolated from each other. Besides, it may be
connected in a connection network in safe area via
communication ports. As an intelligent product, it has an
online self-diagnosis function. Customer may set the type and
the range of the input or output signals with a specific
handheld programmer (display in Chinese) we provide.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Frequency Signal Input / Output Type
Power consumption:
≤0.8W (single voltage input, 20mA single output)
≤1.0W (single voltage input, 20mA double output)
Parameters certified by China National Quality Supervision and Test Centre for Explosion Protected Electrical Products
(CQST):
Um=250VAC/DC
Between terminal 1 & 2:
Uo=15.8V, Io=10.7mA, Po=43mW
IIC: Co=0.33μF, Lo=217mH
IIB: Co=2.01μF, Lo=651mH
IIA: Co=8.12μF, Lo=1000mH
Between terminal 1 & 3:
Uo=15.8V, Io=110mA, Po=435mW
IIC: Co=0.33μF, Lo=2mH
IIB: Co=2.01μF, Lo=6mH
IIA: Co=8.12μF, Lo=16mH
Dielectric strength:
≥ 2500 V AC (Input/Output/Power supply, 1 mA leakage current, 1 minute test time)
Insulation coordination:
≥ 100 MΩ (Input /Output /Power supply)
Electromagnetic compatibility:
IEC 61000-4
Model Selection Code Lists: Model Note
NPEXA-C6 × × × Frequency input isolated safety barrier
Input Single as default D Double loop
Output1
1 4~20mA 2 1~5V 3 0~10mA 4 0~5V 5 0~10V 6 0~20mA 7 1:1 frequency
Output2
None as default 1 4~20mA 2 1~5V 3 0~10mA 4 0~5V 5 0~10V 6 0`20mA 7 1:1 frequency
Note: 12 V or 24 V distribution voltage need to be specified at your order.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Frequency Signal Input / Output Type
Wiring Diagram
Dimensions W×H×D (12.8×100×115) mm
W×H×D (17.8×100×115) mm
Panel Lights Indication Light indicating: PWR (green) remains illuminated during normal operation;
Light indicating: ALM (red) glitters or remains illuminated when signal fault occurs.
Ambient Conditions Operating temperature range: -20 oC~+60 oC
Relative humidity: 10% RH ~90%RH
Operating atmosphere pressure: 80 kPa ~106kPa
Storage and delivery temperature: -40 oC ~+80 oC
5
9
6
7
10
8
+
+
-
+
-
-
3
2
1
+
+
-
Hazardous area
Safe area
Power supply
Output2
Output1
Input
Distribution
Frequency
10
9
5
6
8
7
3
2
1
+
+
-
-
+
-
-
+
+
Hazardous area
Safe area
InputFrequency
Distribution
1:1 frequency
output2
1:1 frequency
output1
Power supply
+
-
RL
Vcc
+
-
RL
+
-
RL
Vcc
115mm
100mm12.8mm17.8mm
Calibration The product is of intelligent digital design and accuracy can be
maintained within the range specified in this manual. If
calibration is required, it shall be realized by the handheld
programmer we provide.
Installation Method 35mm rail mounting: attention that position clamping is stable
and firm.
Vertical position shall be kept as possible to facilitate heat
dispersion.
1 2
3 443
211 2
3 4
1 2
3 4
109
7 8
5 665
87
9 10109
7 8
5 6
109
7 8
5 665
87
9 10
43
21
ALM
PWR
4 5 6
321
13 14 15
987
10 11 12 121110
7 8 9
151413
1 2 3
654
PWR
ALM ALM
PWR
4 5 6
321
13 14 15
987
10 11 12 121110
7 8 9
151413
1 2 3
654
PWR
ALMALM
PWR
ALM
PWR
ALM
PWR PWR
ALM ALM
PWR
Operation Conditions Installation area shall not be affected by strong mechanical
vibration, impact or electromagnetic induction, heavy current,
spark and the like from signal terminal and power supply, and
the atmosphere shall be free from gases that are corrosive to
metal and plastic components.
Supplementary Information If there is any content difference between the specification and
the website or sample, this specification shall prevail. We
reserve the rights to change or update the product information
without prior noticing the users.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Communication Signal Input / Output Type
Main Technical Parameters
Explosive-proof grade: [Ex ia] IIC
Permissible input signal from hazardous area: Communicational digital signal: RS-485 (HDX)
Input signal level rule: Standard differential RS-485 level
Available voltage: Open circuit voltage greater than 20V, & not less than 12V when loaded with 50mA
Output signal to safe area: Communicational digital signal: RS-485
Output signal level rule: Standard differential RS-485 level
Transmitting delay: ≤10μs
Transmitting rate:≤115.2 kbps
Control mode: Half-duplex
Safety parameter certified by China National Quality Supervision and Test Centre for Explosion Protected Electrical
Products (CQST): Um=250VAC/DC
Between terminals 1 & 2:
Uo=7.7V, Io=39mA, Po=75mW
IIC: Co=6.8μF, Lo=16.3mH
IIB: Co=101μF, Lo=48.9mH
IIA: Co=700μF, Lo=130.4mH
Between terminals 3 & 4:
Uo=23.1V, Io=149mA, Po=861mW
IIC: Co=0.1μF, Lo=1.1mH; IIB: Co=0.71μF, Lo=3.3mH; IIA: Co=2.57μF, Lo=8.8mH
Dielectric strength: ≥2500V AC (Input /Output /Power supply, 1 mA leakage current, 1 minute test time)
Insulation coordination: ≥100MΩ (Input /Output /Power supply)
Electromagnetic compatibility: IEC 61000-4
Power supply: 18~32V DC (Recommended voltage: 24V DC)
Power consumption: ≤1.5W
NPEXA-C711
Referenced Model
This type of isolated safety barrier can transmit communicational
digital signals (half duplex RS485) from hazardous area to safe
area. And it may also be connected in a connection network in
safe area via communication ports. Besides, it may also provide
power to the apparatus on the spot.
This product needs an independent power supply.
It is an excellent product with online self-diagnosis function. The
input, output, and power supply are galvanically isolated from
each other.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Communication Signal Input / Output Type
Wiring Diagram
Dimensions
W×H×D (12.8×100×115)mm
Panel light Indication Light indicating: PWR (green) remains illuminated during normal operation;
Light indicating: COM (red) glitters when the occurrence of data exchange, or else, It is out.
Ambient Conditions Operating temperature range: −20 oC~+60 oC
Relative humidity: 10% RH~90% RH (40 oC)
Operating atmospheric pressure: 80 kPa~106 kPa
Storage and delivery temperature: −40 oC~+80 oC
Supplementary Information If there is any content difference between the specification and the website or samples, this specification shall prevail. We
reserve the rights to change or update the product information without prior noticing the users.
4
3 9
10
RS485
output
5
6
R
D
RS485
input
1
2
R
D
Power Supply
A
B
A
B
Distribution
+
--
+
Hazardous
areaSafe area
Single RS485 input ,single RS485 output, HDX
17.8mm 100mm12.8mm
115mm
Installation Method Standard 35mm DIN rail installation, attention that position
shall be stable and firm.
In order to facilitate the heat of the instrument, Please
mounted it vertically if possible.
PWR
1 2
3 4
109
7 8
5 6
PWR
1 2
3 4
109
7 8
5 665
87
9 10
43
21
PWR
1 2
3 4
109
7 8
5 665
87
9 10
43
21
PWR
1 2
3 4
109
7 8
5 6
PWR PWR
COM COM COM COM COM COM
Operation Conditions Installation position shall not be affected by strong
mechanical vibration, impact and electromagnetic induction
from signal terminal and power supply, should conformity
with the requirements on electromagnetic interference
resistance of products in Class 3 industrial field atmosphere
stipulated in IEC 61000-4, and the atmosphere shall be free
from gases that are corrosive to metal and plastic
components.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Eddy Current Signal Input / Output Type
Main Technical Parameters
Explosive-proof grade: [Exia] IIC
Permissible input signal from hazardous area: -20~ -0.5V AC
Input impedance: ≥10kΩ
Output signal to safe area: -20~ -0.5V AC
Output resistance: <3Ω
DC transmitting accuracy: <±20mV
AC transmitting accuracy:
0 Hz~1 kHz: ±1%;
1 kHz~ 20 kHz: -2%~ +1%.
Temperature shift: <30ppm/ oC
Voltage stability bandwidth:
< -0.1dB (at 5 kHz)
< -3dB (at 50 kHz)
Phase response: <10μs, equivalent to:
-0.72º at 200 Hz; -2º at 600 Hz; -3.6º at 1 kHz; -36º at 10 kHz; -72º at 20 kHz; -180º at 50 kHz;
Distribution voltage:
When open circuit voltage is -24V and distribution voltage is -19.5V, the full load current is greater than or equal to
15mA.
Safety parameter certified by China National Quality Supervision and Test Centre for Explosion Protected Electrical
Products (CQST): Um=250 VAC/DC
Between terminal 1 & 2: Uo=1.2 V, Io=0.12 mA, Po=0.036 mW
IIC: Co=70 μF, Lo=1000 mH; IIB: Co=700 μF, Lo=1000mH; IIA: Co=700 μF, Lo=1000 mH
Between terminal 1 & 3: Uo=26 V, Io=87.6 mA, Po=570 mW
IIC: Co=0.069 μF, Lo=3.2 mH; IIB: Co=0.53 μF, Lo=9.6 mH; IIA: Co=1.82 μF, Lo=25.6 mH
Dielectric strength: ≥2500 V AC (Input /Output /Power supply, 1 mA leakage current, 1 minute test time)
Insulation coordination: ≥100 MΩ (Input /Output /Power supply)
Electromagnetic compatibility: IEC 61000-4
Power supply: 18~32 V DC (Recommended voltage:24V DC)
Power consumption: ≤1.2 W
NPEXA-C87
Referenced Model
This isolated safety barrier can detect and transmit the output
signal of eddy-current transducer from hazardous area to safe
area by repeating the input signal. Meanwhile, it provides isolated
power to field apparatus in hazardous area. The input, output,
and power supply are galvanically isolated from each other.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Eddy Current Signal Input / Output Type
Wiring Diagram
Dimension W×H×D (12.8mm×100mm×115mm)
Installation Method Standard 35mm DIN rail installation, attention that position shall be stable and firm.
In order to facilitate the heat of the instrument, Please mounted it vertically if possible.
3
1
(0V)
2
9
10
5
6Common
Signal
-VT Power
+
-
+
-
Eddy current
sensor input
-20~-0.5V DC
output
Power supply
Safe areaHazardous area115mm
100mm12.8mm17.8mm
PWR
1 2
3 4
109
7 8
5 6
PWR
1 2
3 4
109
7 8
5 665
87
9 10
43
21
PWR PWR
1 2
3 4
109
7 8
5 665
87
9 10
43
21
PWRPWR
1 2
3 4
109
7 8
5 6
Operation Conditions Installation position shall not be affected by strong
mechanical vibration, impact and electromagnetic
induction from signal terminal and power supply,
should conformity with the requirements on
electromagnetic interference resistance of products in
Class 3 industrial field atmosphere stipulated in IEC
61000-4, and the atmosphere shall be free from gases
that are corrosive to metal and plastic components.
Supplementary Information If there is any content difference between the
specification and the website or samples, this
specification shall prevail. We reserve the rights to
change or update the product information without
prior noticing the users.
Panel light Indication Light indicating: PWR (green) remains glitters during
normal operation.
Ambient Conditions Operating temperature range: −20 oC~+60 oC
Relative humidity: 10%RH~90%RH (40 oC)
Operating atmospheric pressure: 80kPa~106kPa
Storage and delivery temperature: −40 oC~+80 oC
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Magnetic Resistance Signal Input / Output Type
Main Technical Parameters
Explosive-proof grade: [Ex ia] II C
Direct current transmitting accuracy: ±0.5%F•S (25 oC±2 oC)
Direct current transmitting accuracy: ±0.2%F•S (25 oC±2 oC)
Permissible input signal from hazardous area:
0~10V AC (magneto-resistive transducer output signal)
Input impedance:
≥10kΩ
Output signal to safe area:
0~10V AC (1:1 repeating signal)
Output resistance:
<10Ω
Voltage stability bandwidth:
-0.1dB (at 5 kHz)
-3 dB (at 25 kHz)
Safety parameter certified by China National Quality Supervision and Test Centre for Explosion Protected Electrical
Products (CQST):
Um=250VAC/DC
Between terminal 1 & 2:
Uo=18.3V, Io=4mA, Po=18.3mW
IIC: Co=0.20μF, Lo=1000mH
IIB: Co=1.19μF, Lo=1000mH
IIA: Co=5μF, Lo=1000mH
Dielectric strength:
≥2500V AC (Input/Output/Power supply, 1 mA leakage current, 1 minute test time)
Insulation coordination:
≥100MΩ (Input/Output/Power supply)
Electromagnetic compatibility:
IEC 61000-4
Power supply:
18~32V DC (Recommended voltage: 24V DC)
Power consumption:
≤ 0.6 W
NPEXA-C89
Referenced Model
This isolated safety barrier can detect and transmit the output
voltage signal of magneto-resistive transducer from hazardous
area to safe area by repeating the input signal. The input,
output, and power supply are galvanically isolated from each
other.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Magnetic Resistance Signal Input / Output Type
Wiring Diagram
Dimension W×H×D (12.8mm×100mm×115mm)
Panel light Indication Light indicating: PWR (green) remains illuminated during normal operation.
Ambient Conditions Operating temperature range: −20 oC~+60 oC
Relative humidity: 10%RH~90%RH (40 oC)
Operating atmospheric pressure: 80kPa~106kPa
Storage and delivery temperature: −40 oC~+80 oC
Supplementary Information If there is any content difference between the specification and the website or samples, this specification shall prevail. We
reserve the rights to change or update the product information without prior noticing the users.
6
5
10
9
1
Magneto-resistive
Transducer Input
2
0~10V AC
output
Power supply
-
+
Hazardous area Safe area
Warning: because of high output resistance requirement,
short circuit of output ports is prohibited.
115mm
100mm12.8mm17.8mm
Installation Method Standard 35mm DIN rail installation, attention that position
shall be stable and firm.
In order to facilitate the heat of the instrument, Please
mounted it vertically if possible.
PWR
1 2
3 4
109
7 8
5 6
PWR
1 2
3 4
109
7 8
5 665
87
9 10
43
21
PWR PWR
1 2
3 4
109
7 8
5 665
87
9 10
43
21
PWRPWR
1 2
3 4
109
7 8
5 6
Operation Conditions Installation position shall not be affected by strong mechanical
vibration, impact and electromagnetic induction from signal
terminal and power supply, should conformity with the
requirements on electromagnetic interference resistance of
products in Class 3 industrial field atmosphere stipulated in
IEC 61000-4, and the atmosphere shall be free from gases that
are corrosive to metal and plastic components.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Magneto-electronic Signal Input / Output Type
Main Technical Parameters
Explosive-proof grade:
[Exia] IIC
Transmitting accuracy:
±0.2%F•S (25 oC±2 oC)
Permissible input signal from hazardous area:
0~10V AC
Input impedance:
≥10kΩ
Output signal to safe area:
0~10V AC
Output resistance:
<10Ω
Voltage stability bandwidth:
-0.1dB (at 1 kHz)
Vibration frequency range:
5Hz~500Hz
Safety parameter certified by China National Quality Supervision and Test Centre for Explosion Protected Electrical
Products (CQST):
Um=250VAC/DC
Between terminal 1 & 2:
Uo=18.3V, Io=4mA, Po=18.3mW
IIC: Co=0.20μF, Lo=1000mH
IIB: Co=1.19μF, Lo=1000mH
IIA: Co=5μF, Lo=1000mH
Dielectric strength:
≥2500V AC (Input/Output/Power supply, 1 mA leakage current, 1 minute test time)
Insulation coordination:
≥100MΩ (Input/Output/Power supply)
Electromagnetic compatibility:
IEC 61000-4
Power supply:
18~32V DC (Recommended voltage: 24V DC)
Power consumption:
≤ 0.6 W
NPEXA-C88
NPEXA-C8871
Referenced Model
This isolated safety barrier can detect and transmit the output
signal of magneto-electric transducer from hazardous area to safe
area by repeating the input signal. The input, output, and power
supply are galvanically isolated from each other.
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com
Products Overview - Magneto-electronic Signal Input / Output Type
Wiring Diagram
Dimension W×H×D (12.8mm×100mm×115mm)
Installation Method Standard 35mm DIN rail installation, attention that position shall be stable and firm.
In order to facilitate the heat of the instrument, Please mounted it vertically if possible.
6
5
10
9
1
Magneto-electric
sensor Input
2
0~10V AC
output
-
+
Hazardous area Safe area
Power supply
115mm
100mm12.8mm17.8mm
PWR
1 2
3 4
109
7 8
5 6
PWR
1 2
3 4
109
7 8
5 665
87
9 10
43
21
PWR PWR
1 2
3 4
109
7 8
5 665
87
9 10
43
21
PWRPWR
1 2
3 4
109
7 8
5 6
Operation Conditions Installation position shall not be affected by strong
mechanical vibration, impact and electromagnetic induction
from signal terminal and power supply, should conformity with
the requirements on electromagnetic interference resistance of
products in Class 3 industrial field atmosphere stipulated in IEC
61000-4, and the atmosphere shall be free from gases that are
corrosive to metal and plastic components.
Supplementary Information If there is any content difference between the specification and
the website or samples, this specification shall prevail. We
reserve the rights to change or update the product information
without prior noticing the users.
Panel light Indication Light indicating: PWR (green) remains glitters during normal
operation.
Ambient Conditions Operating temperature range: −20 oC~+60 oC
Relative humidity: 10%RH~90%RH (40 oC)
Operating atmospheric pressure: 80kPa~106kPa
Storage and delivery temperature: −40 oC~+80 oC
Tosilon Automation Co.,Ltd Add: No. 229, Daqing Rd, Lianhu District, Xi’an Shaanxi, China TEL: 0086-029-8823 8550 Email: [email protected] Website: www.tosilon.com