ION Setup Device Configuration Guide
Transcript of ION Setup Device Configuration Guide
-
7/24/2019 ION Setup Device Configuration Guide
1/72
70002-0293-00
04/2009
PowerLogicIONSetup 2.2Meter configuration software
Device configuration guide
-
7/24/2019 ION Setup Device Configuration Guide
2/72
-
7/24/2019 ION Setup Device Configuration Guide
3/72
Conventions used in this manualThissectiondescribesthesymbolsandterminologyusedinthismanual.
Symbols
DangerThisalertsyoutothingsthatmaycauseseriousinjurytoaperson.Onlyqualified,properlytrainedpersonnelshouldperformtheseprocedures.
CautionThisalertsyoutothingsthatmaycauselossofdata,damagetoyourcomputeroryourdevices.
NoteAnoteprovidesyouwithadditionalinformationthatyoumightwant
toconsider.
TipThisdrawsyourattentiontoinformationthatwillhelpyouperformataskmorequicklyoreasily.
-
7/24/2019 ION Setup Device Configuration Guide
4/72
Terminology
Clear Place the mouse cursor over the check box option, then click the mouse buttonso that the check mark is removed from the check box.
Click Place the mouse cursor over the specified option or button, then press andrelease the mouse button.
Double-click Place the mouse cursor over the specified option or button, then press andrelease the mouse button twice.
Drag Hold down the mouse button while moving the mouse cursor to the appropriatelocation, then release the button.
Enter Type the information, then press the ENTER or RETURN key.
Point Position the mouse pointer over a submenu or menu command. For example,point to the File menu.
Press Press the specified key or key combination on your keyboard, for example, pressCTRL+ALT+DEL.
Right-clickPlace the mouse cursor over the button or item, then press and release the right
mouse button1.
1. Mouse button means the the primary mouse button (left, by default), while right mouse button
means the secondary mouse button. This configuration can be switched for a left-handed user.
SelectPlace the mouse pointer over the specified option or check box, then click themouse button. A selected check box receives a check mark; a selected radiobutton is marked with a dot.
Type Type the information, but DO NOT press the ENTER or RETURN key.
-
7/24/2019 ION Setup Device Configuration Guide
5/72
Contents
Chapter 1 Introduction .................................................................. 7
Before you begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Overview ............................................................. 8
Quick start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Serial site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Modem site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Ethernet sites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Ethernet gateway sites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 2 E5600 socket-based energy meter ............................... 15
E5600 meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16MetersetupthroughIRopticalport ..................................... 16
MetersetupthroughRS485 ............................................ 18
Firmware upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Meter protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Chapter 3 PM700 series power meter ......................................... 25
PM700 series meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26UsingIONSetup ..................................................... 26
PM700 series setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26BasicSetup .......................................................... 26
Demand ............................................................. 27
FrontPanelDisplay ................................................... 27
I/OSetup ............................................................ 28
OnboardAlarms ..................................................... 28
SerialComms ........................................................ 30
Chapter 4 PM800 series power meter ......................................... 31
PM800 series meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
PM8ECCconsiderations ............................................... 32UsingIONSetup ..................................................... 33
PM800 series setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34AlarmLog ........................................................... 34
BasicSetup .......................................................... 34
BillingLog ........................................................... 35
Clock ............................................................... 36
Comm ECCCard .................................................... 36
Comm OnboardSerial ............................................... 36
DataLog#1,DataLog#2,DataLog#3,DataLog#4 ....................... 37
-
7/24/2019 ION Setup Device Configuration Guide
6/72
-
7/24/2019 ION Setup Device Configuration Guide
7/72
2009 Schneider Electric. All rights reserved. Page 7
1 Introduction
PowerLogicIONSetupsoftwareisameterconfigurationutilityavailablefromtheSchneiderElectricwebsiteatwww.powerlogic.com.
ThisguideassumesyouknowhowtouseIONSetup,andhavereadandunderstoodtheinstallation,basicsetup,andallrelevantproceduresandwarningscontainedintheuserdocumentationforthedeviceyouwanttoconfigurewithIONSetup.
Typically,basicsetupcanbeperformedthroughthemetersfrontpanelorremotedisplay. IONSetupismainlyusedforconfiguringadvancedfeaturesofthemeter,orforsettingupameterthatdoesnothaveafrontpanel/remotedisplay.
DeviceconfigurationinstructionsusingIONSetupsoftwareareprovidedforthefollowing:
PowerLogicE5600powermeter
PowerLogicPM700seriespowermeter
PowerLogicPM800seriespowermeter
PowerLogicBCPM(Branchcircuitpowermeter)
PowerLogicEnerceptmeter
PowerLogicION6200powermeter
FordetailedproceduresonsettingupotherIONdevices(suchasthePowerLogicION8600orPowerLogicION7550 / ION7650meters),refertothedevicespecificinstallationoruserguide.
FordetailedinformationonusingIONSetupsoftware,refertotheonlinehelp.
-
7/24/2019 ION Setup Device Configuration Guide
8/72
Chapter 1 - Introduction PowerLogic ION Setup device configuration guide
Page 8 2009 Schneider Electric. All rights reserved.
Before you beginBeforeusingIONSetup,makesureyouhavecompletedallrequiredinstallation,wiring,andbasicsetupforeachhardwaredevice(meters,communicationsconverters,modems,etc.).
Security considerationsSomedevicesrequireadditionalconfigurationinordertoaccessandmodifycertainsetupparameters. Forexample,arevenueclassorhardwarelockedmetermustbeunlockedbeforeyoucanconfigureit.Refertothedevicesdocumentationforunlockingandbasicsetupprocedures.
OverviewIONSetupsupportsvarioustypesofcommunications. Typically,devicesaregroupedaccordingtoasharedcommunicationslinktype(IONSetupreferstothesecommunicationslinksassites). WhencreatingyourIONSetupnetworkforthefirsttime,youwouldstartbyaddingasitetoyourworkstation,thenadddevicestothesite.
NOTE
Most ION devices use the 8N1 standard (8 data bits, no parity, 1 stop bit) for serial communications. To
prevent communication errors, make sure all the devices on your serial communications loop are set to
8N1 (i.e. make sure the devices serial communications parameter is set to No parity).
Ethernet site
Ethernet devices
Ethernet Gateway
Modem site
RS-485 devices
remote serial device
-
7/24/2019 ION Setup Device Configuration Guide
9/72
PowerLogic ION Setup device configuration guide Chapter 1 - Introduction
2009 Schneider Electric. All rights reserved. Page 9
Quick startThefollowingsummarizesthestepsforaddingsitesanddevicesinIONSetup.
1. Installandwireyourmeters,followingtheinstructionsandwarningsinthemeterspecificdocuments.
2. Followtheinstructionsinthemeterinstallationmanualtoconfigurethebasiccommunicationsparametersforeachmeter(forexample,protocol,baudrate,parityanddeviceaddress/unitID).
NOTE
Make sure all the devices on the same RS-485 loop are set to the same baud rate, and their serial port
parameters are set to 8N1.
3. Ifusingacommunicationsconverterorgateway,configureitscommunicationsparameters,theninstallandwireittothemeter(s).
4. StartION
Setup
and
log
on
using
network
mode
(i.e.,
clear
the
Single ION device configuration modecheckbox). Thedefaultuserissupervisorandpasswordis0(zero).
5. Addandconfigureyoursites. ForEthernetorEthernetGatewaysites,usethefollowingtabletosettheportnumber,asappropriate.
6. AddeachmetertotheappropriatesiteinIONSetup.
IP Port1
1. Some meters support email (SMTP through port 25) and web pages (HTTP through port 80).
Description (communications protocol, connection type)
23 Telnet (used for meter diagnostics)
502 Modbus TCP
7700 ION (direct)
7701 Modbus RTU through an ION meter
7800 EtherGate simultaneously though available COM ports of an ION meter
7801 EtherGate through COM1 of an ION meter
7802 EtherGate through COM2 of an ION meter
7803 EtherGate through COM3 of an ION meter
-
7/24/2019 ION Setup Device Configuration Guide
10/72
Chapter 1 - Introduction PowerLogic ION Setup device configuration guide
Page 10 2009 Schneider Electric. All rights reserved.
Serial siteIfthedeviceisequippedwithanRS232port,youcanuseanRS232cabletodirectlyconnectthedevicetoanavailableserialportonthecomputer.
Toconnecttomorethanoneserialdevice,youcanuseanRS232 to RS485communicationsconverter. TheRS232portontheconverterconnectstothecomputersserialport,andtheRS485portconnectstoupto32RS485devices.
Makesuretheserialcommunications parametersaresetcorrectlyforeachdevice(forexample,protocol,baudrate,parityanduniquedeviceaddress/unitID).
Adding a serial site in ION Setup1. RightclicktheworkstationiconandselectInsertItem.
2. SelectSiteandclickOK.
3. OntheGeneraltab,usetheNameboxtoenteranameidentifyingthisserialsite.
UsetheCommLinkboxtoselectwhichserialportonthecomputeryouareusingtocommunicatewiththemeter(s).
UsetheLinkSpeedboxtosettheserialportsbaudratetothesamevalueastheserialdevice(s).
Fordirectserialcommunicationsthroughtheserialport(orthroughan
RS232 to RS485communicationsconverter),setLinkTypetoRS232/RS
485
Direct.
4. TheTimingsandPollingtabscontainotherserialcommunicationsparameters.Inmostcases,thedefaultsettingsdonotneedtobemodified.
RS-232 to RS-485converter
RS-485 devices(maximum 32)
-
7/24/2019 ION Setup Device Configuration Guide
11/72
PowerLogic ION Setup device configuration guide Chapter 1 - Introduction
2009 Schneider Electric. All rights reserved. Page 11
Modem siteAmodemsiteconsistsofalocalmodemconnectedtothecomputersserialportandaremotemodemconnectedtooneormoreserialdevices.
IONSetupusesthelocalmodemtodialtheremotemodemstelephonenumberandestablishcommunications.
Adding a new serial or modem site in ION Setup
1. RightclicktheworkstationiconandselectInsertItem.
2. SelectSiteandclickOK.
3. OntheGeneraltab,usetheNameboxtoenteranameidentifyingthismodemsite. Enterthephonenumberinthebox. SelectModem,thenusetheModemconfigurationbuttontosetupthecommunicationsport. Followthedirectionsprovided.
4. TheTimingsandPollingtabscontainothercommunicationsparameters;youcanmodify. In mostcases,youdonotneedtochangethedefaultsettings.
ModemGate featureSomeIONmetersareequippedwithaninternalmodemthatyoucansetupasa
communicationsgatewaytoconnecttomultipleRS485devices(e.g.onaremotesite). Formoreinformation,refertothetechnicalnoteTheIONmeterasaModemGate.
localmodem
telephone line
remotemodem
RS-232 to RS-485converter
RS-485devices
-
7/24/2019 ION Setup Device Configuration Guide
12/72
Chapter 1 - Introduction PowerLogic ION Setup device configuration guide
Page 12 2009 Schneider Electric. All rights reserved.
Ethernet sitesIfthedeviceisequippedwithanEthernetcommunicationscard,youcanuseanEthernetcabletoconnectittoyourlocalorwideareanetwork(LAN/WAN).
MakesuretheEthernetcommunicationsparametersaresetcorrectlyforeachdevice(forexample,IP address,subnet mask,default gateway,media type).
Adding a new Ethernet site in ION Setup
1. RightclicktheworkstationiconandselectInsertItem.
2. SelectSiteandclickOK.
3. SelectEthernet,thenclickOK.
4. TheTimingsandPollingtabscontainothercommunicationsparameters;youcanmodify. In mostcases,youdonotneedtochangethedefaultsettings.
LAN / WAN
Ethernetdevices
-
7/24/2019 ION Setup Device Configuration Guide
13/72
PowerLogic ION Setup device configuration guide Chapter 1 - Introduction
2009 Schneider Electric. All rights reserved. Page 13
Ethernet gateway sitesAnEthernetgatewaydevicehasanEthernetporttocommunicatewiththecomputer(throughtheLAN/WAN)andprovidesoneormoreRS485portsforconnectionandcommunicationwithmultipleRS485devices(upto32devicesperloop). TypicalparametersyouconfigureontheEthernetgatewaydeviceinclude:
Ethernetportsettings: IP address,subnetmask,defaultgateway
Serialportsettings: Baudrate,parity,physicalinterface(2wireor4wire)
NOTE
For the Ethernet gateway devices serial port, set the baud rate to the same setting as all the RS-485
devices connected to it. If the serial port parameter setting can be configured, set it to 8N1 (no parity).
AdditionalsettingsmaybeavailablerefertothedocumentationthatcamewithyourEthernetgatewaydevice.
EGX series considerationsThePowerLogicEGXseriesEthernetgatewaycanprovideEthernetaccessto
multipleRS485devicesthatareconnectedtotheEGXsRS485port. AfterwiringtheRS485devicestotheEGX,useawebbrowsertologintotheEGX. BrowsetothedevicelistpageandentereachdevicethatisconnectedtotheEGXsRS485port. Settheappropriatedeviceaddressanddevicetypeforeachdevice. RefertotheEGXSeriesInstallationGuide.
ForinstructionsonaddingametertotheEthernetgatewaysite,refertotheIONSetuponlinehelp.
PM8ECC considerationsSimilartotheEGXseriesgateway,thePM8ECCEthernetcommunicationscard
provides
Ethernet
access
to
multiple
RS
485
devices
that
are
connected
to
the
PM8ECCsRS485port.AfterwiringtheRS485devicestothePM8ECC,useawebbrowsertologintothePM8ECC. BrowsetothedevicelistpageandentereachdevicethatisconnectedtothePM8ECCsRS485port. Settheappropriatedeviceaddressanddevicetypeforeachdevice. RefertothePM8ECCInstallationGuide.
LAN / WAN
RS-485devices
Ethernetgatewaydevice
Ethernet
serial RS-485
-
7/24/2019 ION Setup Device Configuration Guide
14/72
Chapter 1 - Introduction PowerLogic ION Setup device configuration guide
Page 14 2009 Schneider Electric. All rights reserved.
ION7550/ION7650 Modbus gatewayYoucanusetheION7550orION7650meterasanEthernetgatewaytomultipleModbusRTU(serial)devices.RefertotheEtherGatechapter(orsearchthetopicModbusgateway)intheION7550/ION7650UserGuide.
Adding a new Ethernet gateway site in ION Setup
1. RightclicktheworkstationiconandselectInsertItem.
2. SelectSiteandclickOK.
3. SelectEthernet,thenselecttheGatewaybox.
4. IntheGatewayInfoboxes,entertheIPaddress,thentypeorselecttheappropriateportnumber. Forexample,select502forModbusTCPcommunications.
5. TheTimingsandPollingtabscontainothercommunicationsparameters;youcanmodify. In mostcases,youdonotneedtochangethedefaultsettings.
-
7/24/2019 ION Setup Device Configuration Guide
15/72
2009 Schneider Electric. All rights reserved. Page 15
2 E5600 socket-based energy meter
ThePowerLogicE5600isacosteffectiveSbasesocketmeterwithANSI C12.20Class 0.2accuracy.
In This Chapter
E5600 meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16MetersetupthroughIRopticalport ..................................... 16
MetersetupthroughRS485 ............................................ 18
Firmware upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Meter protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
-
7/24/2019 ION Setup Device Configuration Guide
16/72
Chapter 2 - E5600 socket-based energy meter PowerLogic ION Setup device configuration guide
Page 16 2009 Schneider Electric. All rights reserved.
E5600 meter setupTheE5600hastwoconfigurationoptions:viathemetersIRopticalportorthroughtheRS485connection.
IfyouneedtochangeyourmetersdefaultRS485settingsyoumustfirstconnecttoyourmeterthroughtheIRopticalporttoconfigurethemetersRS485communicationssettings.Otherwise,yourmetercanbecompletelyconfiguredthroughtheRS485connection.RefertoDefaultRS485settingsonpage 22.
NOTE
Meter password protection can only be done through the IR optical port.
Tools requiredPleaseensureyouhavethesethingsavailablebeforestartingtosetupyourE5600
meter:
Computer(loadedwithlatestversionofIONSetup)
Optional:ANSIC12.19typeIIopticalprobe(refertotheE5600InstallationandOperation
Guideforthemetersfrontopticalportspecifications)
Optional:Strongmagnet(suchasarareearthorsimilarpermanentmagnet)
NOTE
Optional tools are required to communicate with your meter through the IR optical port.
Meter setup through IR optical portTocommunicatewithyourmeterthroughtheIRopticalport,youmustconfigureyourcomputertousetheopticalprobe.YoucanthenconnecttheprobeandcommunicatetothemeterusingIONSetup.
Computer configurationThisdescribeshowtoconfigurethecomputerscommunicationportforopticalprobecommunication,andhowtoidentifywhichportisbeingusedbytheopticalprobe.
BeforestartingIONSetup,connecttheE5600metertoyourcomputerusinganANSIC12.19typeIIopticalprobe.IftheWindowsdriverfortheUSBopticalprobeisnotinstalled,Windowsdetectstheopticalprobeasnewhardwareandpromptsyoutosearchforacompatibledriver.Usetheinstallationdiscthatcamewiththeopticalprobetoinstallthedriver,ordownloadtheappropriatedriverfromtheopticalprobemanufacturerswebsite.
OpenyourcomputersDeviceManagertoseewhichserialportnumberisassignedtotheopticalprobe:
-
7/24/2019 ION Setup Device Configuration Guide
17/72
PowerLogic ION Setup device configuration guide Chapter 2 - E5600 socket-based energy meter
2009 Schneider Electric. All rights reserved. Page 17
1. RightclickMyComputerandselectManage.
2. ExpandSystemToolsandselectDeviceManager.
3. ExpandPorts.
4. Notetheopticalprobesserialport#.
5. ClosetheComputerManagementscreen.
Meter communicationThisdescribeshowtoputthemeterintodiagnosticmodesothatitcanbeconfiguredthroughtheIRopticalportusingIONSetup.
1. Putthemeterintodiagnosticmode.
Toputthemeterintodiagnosticmode,holdastrongmagnetoverthemeter,approximatelyatthe12oclockposition,toactivatethereedswitch.Whenthereedswitchisactivated,themetersdisplaywillshowallsegments,then
ablank
screen,
and
then
will
start
to
display
the
diagnostic
display
sequence.
DonotremovethemagnetfromthemetersreedswitchwhilecommunicatingthroughthemetersIRport.
NOTE
RS-485 (Modbus) data will not be updated while the meter is communicating via the front optical port.
2. StartandlogontoIONSetupusingsingledeviceconfigurationmode(i.e.,makesuretheSingleIONdeviceconfigurationmodecheckboxisselected).
12 oclock
-
7/24/2019 ION Setup Device Configuration Guide
18/72
Chapter 2 - E5600 socket-based energy meter PowerLogic ION Setup device configuration guide
Page 18 2009 Schneider Electric. All rights reserved.
3. IntheConnectionTypedialog,selecttheopticalprobesserialportnumber.
4. ClickOK.
IONSetupattemptstoestablishaconnection(9600baud,ANSIprotocol)tothe
device.Ifcommunicationattemptsfail,closeIONSetup,checktomakesurethereisgoodphysicalconnectionbetweenthecomputerandthemeterandensurethatthemagnetisactivatingthereedswitch.RestartIONSetupandtryconnectingtothedeviceagain.
5. ConfiguretheE5600meter.Thesetupscreensaredetailedinthesection,MetersetupthroughRS485.
Meter setup through RS-485ToconfigureyourmeterthroughRS485,youmustaddthemeterinIONSetup.Oncethemeterhasbeenadded,youcanconfigureyourmeterusingthesetupscreens.
Adding the E5600 to a site1. IfyourmeterisconnectedthroughtheIRopticalport,exitIONSetupthen
removethemagnetfromthemeter.
2. MakesuretheE5600metersRS485portisconnectedtothecomputer(throughanRS232toRS485converteroranEthernetgatewaydevice).
-
7/24/2019 ION Setup Device Configuration Guide
19/72
PowerLogic ION Setup device configuration guide Chapter 2 - E5600 socket-based energy meter
2009 Schneider Electric. All rights reserved. Page 19
3. StartandlogontoIONSetupusingnetworkmode(makesuretheSingleIONdeviceconfigurationmodecheckboxonthelogonpromptiscleared).
4. CreateandconfigureanewsiteforyourE5600meter,oruseanexistingsiteifappropriate(i.e.,ifanexistingsitealreadyexistsandyouhavewiredtheE5600communicationsporttousethatcommunicationslink).RefertotheIntroductionsectionfordetailsonaddingsitesandmeters.
5. AddtheE5600metertothesite.ForUnitID,entertheModbusaddressyousetforthedevice(refertoRS485Commonpage 22).
6. ConfiguretheE5600meterssetupparameters.
Basic SetupUsethisscreentoconfigurethemetersprimaryandsecondarytransformervalues.
1. SelectthePTMultiplierparameterandclickEdit.
2. ThePT/CTMultiplierSetupscreenappears.EnterthePTMultipliervalueand
clickOK.
ThePTMultiplierisapositiveintegerthatrepresentsthePTprimarytoPTsecondaryratio.Forexample,ifPTprimary=480VandPTsecondary=120V,thenPT Multiplier = 4.
3. RepeatfortheCTMultiplierparameter.
TheCTMultiplierisapositiveintegerthatrepresentstheCTprimarytoCTsecondaryratio.Forexample,ifCTprimary=500AandCTsecondary=5A,thenCTMultiplier=100
ClickSendtosaveyourchangestothemeter.
ClockTo manually set the meters local time
1. SelecttheDate/TimeparameterandclickEdit.
2. UsetheDatedropdownbuttontodisplaythecalendar.Youcanusetheleftorrightscrollbuttontochangethemonth.Clickthecalendardaytosetthemeterdate.
3. Clickthehour,minute,secondorAM/PMsetting,thenusetheup/downscrollbuttons(oruseyourcomputerskeyboard)tochangethevalue.
Thetimeinformationissenttothemeterexactlyasentered.Nocorrections(suchasDaylightSavingsTime)areappliedto,orsupportedbythemeter.
4. ClickOKthenSendtosetthedateandtime.
NOTE
The E5600s front panel display shows hours and minutes in 24 hour clock format.
-
7/24/2019 ION Setup Device Configuration Guide
20/72
Chapter 2 - E5600 socket-based energy meter PowerLogic ION Setup device configuration guide
Page 20 2009 Schneider Electric. All rights reserved.
DemandDemandistheaveragepowerconsumptionoverafixedtimeperiod(demandperiod),typically15 minutes.
1. SelectIntervalLengthparameterandclickEdit.
2. Selecteither
Block
Demand
or
Sliding
Window
Demand.
BlockDemand:SelecttheBlockLengthfromthedropdownlist.
SlidingWindowDemand:SelecttheappropriatePeriod/SubIntervalfromthedropdownlist.Forexample,ifyourequirea30minuteintervalbrokenintotwoperiodsof15minuteseach,select2x15minutes.
3. ClickOKthenSendtosaveyourchangestothemeter.
Device LabelsSelectDeviceIdentificationandclickEdit.TypethedevicelabelfortheE5600meterintheEnterDeviceIdentificationbox.Thedevicelabelcanbe1 18ASCII
characters.
ClickOKthenSendtosaveyourchangestothemeter.
Energy PulsingEnergypulsingtransitionsthedigitaloutputKYrelay(fromlowhigh,orhighlow)eachtimethesourceenergyparameterincreasesbytheKevalue.TherearetwodigitaloutputsontheE5600.
Enable
UsethistoenableordisableenergypulsingforthatKYrelay.
Source
UsethistoselecttheenergymeasurementforKYrelaypulsing.
Ke Value
Usethistosettheamountthatthesourcemustincreasebeforethedigitaloutputtransitions.Youmustsetthistoanumericvaluebetween0.001and16,inordertoenableenergypulsingthroughthedigitaloutput.
NOTE
If Ke is zero (0) the associated KY relay is disabled. You must enter a valid Ke value (between 0.001 and
16) before you can enable the associated KY relay.
1. Selectaparameter(Enable,SourceorKeValue),thenclickEdit.
2. Modifytheparameterbyenteringtherequiredvalueorselectinganoptionfromthedropdownlist.
3. ClickOKthenSendtosaveyourchangestothemeter.
-
7/24/2019 ION Setup Device Configuration Guide
21/72
PowerLogic ION Setup device configuration guide Chapter 2 - E5600 socket-based energy meter
2009 Schneider Electric. All rights reserved. Page 21
Front Panel DisplayConfigurethefollowingtospecifyhowmanydatascreensaredisplayedonthefrontpanel,andthetimedurationforeachdisplayedscreen.
# of Displays
Youcan
configure
amaximum
of
six
(6)
display
screens:
1. Select#ofDisplays,thenclickEdit.
2. UsetheDisplayEditorwindowtoedit,addordeletethedisplayedparameters.
Toeditthedisplayedparameter,selectit,thenclickEdit.IntheDisplayScreenSetupwindow,usetheParameterboxtoselectthequantityyouwanttodisplay.UsetheIndicatorboxtoassignathreecharacterlabelforthedisplayedparameter.
Toaddanewdisplayscreen,clickNew. SettheParameterandIndicatorasdescribedabove.
Todeleteadisplayscreen,selectitthenclickDelete.
3. ClickExittoreturntotheFrontPanelDisplaysetupscreen,thenclickSendtosaveyourchangestothemeter.
Display On Time
Youcanconfigureadurationfrom1secondto15seconds.
1. SelectDisplayOnTime,thenclickEdit.
2. EntertheDisplayOnTimeinthespaceprovidedandclickOK,thenclickSendtosendyourchangestothemeter.
Meter ResetsUsethissetupscreentoenableordisableresetfunctionsforthemeter.
1. SelectaresetparameterthenclickEdit.
PeakDemandReset:clearspeakdemandvalues.
MasterReset:clearsalldemandandenergyvalues,andclearstheloadprofile.
EnergyReset:clearsallenergyaccumulatedvalues(total,delievered,recieved).
2. UsethedropdownboxtoselectResetorNoReset,thenclickOK.
ClickSend
to
save
your
changes
to
the
meter.
-
7/24/2019 ION Setup Device Configuration Guide
22/72
Chapter 2 - E5600 socket-based energy meter PowerLogic ION Setup device configuration guide
Page 22 2009 Schneider Electric. All rights reserved.
RS-485 CommUsethissetupscreentoconfiguretheE5600metersRS485communicationssettings.
Default RS-485 settings
NOTE
Changing RS-485 Comm parameters while communicating through the RS-485 port will cause you to
lose communications with your meter.
Modbus Address
Usethistosetthedeviceaddress(unitID)fortheE5600meter.TheallowableModbusaddressrangeis1to247.MakesuretheModbusaddressisuniquetoeachdeviceonthatRS485loop.
Baud Rate
UsethistosetthebaudrateforRS485communications.MakesurealldevicesconnectedonthesameRS485looparesettothesamebaudrate.
Parity
Makesurethecommunicationslink(site)andalldevicesconnectedtothatsitearesettothesameparitysetting.
NOTE
For serial sites the parity must be set to no parity (Parity = None) for ION Setup to communicate. For
other site types, the meters RS-485 parity must match the site parity.
1. Selectaparameter(ModbusAddress,BaudRateorParity)andclickEdit.
2. Aparametereditingscreenappears.EntertheappropriatevalueintothefieldorusethedropdownlistsandclickOK.
3. ClickSendtosaveyourchangestothemeter.
Parameter Value
Modbus Address Displayed on meter front panel
Baud Rate 9600 bps
Parity No parity or None
-
7/24/2019 ION Setup Device Configuration Guide
23/72
PowerLogic ION Setup device configuration guide Chapter 2 - E5600 socket-based energy meter
2009 Schneider Electric. All rights reserved. Page 23
Firmware upgradeYoucanupgradetheE5600communicationcardsfirmwarethroughtheRS485port.
1. MakesureallnecessaryinformationfromtheE5600meterhasbeenrecorded.
2. SavetheE5600firmwareupgradefiletoyourcomputerdesktoporalocalfolder.
3. RightclicktheE5600metericonandselectProperties.
4. ClicktheToolstab,thenclickFirmwareUpgrade.
5. Apromptdisplays,alertingyouthatallrecordeddataforthedevicewillbereset.ClickOKtoproceed.
NOTE
During firmware upgrade the meters I/O may de-energize or change state.
6. Navigateto
the
location
where
you
saved
the
firmware
upgrade
file,
select
it
thenclickOpen.
7. EntertheIONSetuppasswordtoupgradethefirmware.
NOTE
Do not have any other communications taking place on your RS-485 network while your meter is going
through a firmware upgrade.
Whileyourmeterisundergoingafirmwareupgradeitwillcontinuetomeasureandlogdata,butitwillnotupdaterealtimedisplayedvaluesuntiltheupgradeiscompleted.
-
7/24/2019 ION Setup Device Configuration Guide
24/72
Chapter 2 - E5600 socket-based energy meter PowerLogic ION Setup device configuration guide
Page 24 2009 Schneider Electric. All rights reserved.
Meter protectionMeterprotectioncanbeconfiguredonlythroughthefrontopticalport.SeeMetersetupthroughIRopticalportonpage 16forconnectiondetails.StartIONSetupinsingledevicemode.
Password-protecting the meter1. DoubleclickMeterProtection.
2. SelectProtectionLockoutthenclickEdit.
3. Typeanumericpasswordinthebox,thenclickEnable.Makesureyoudonotloseorforgetthepassword,asthisistheonlywaytodisableprotectionlateron.
4. ClickSendtosavethechangestothemeter.
WithapasswordprotectedE5600meter,youcanstillmakechangestothesesetupscreensthroughtheRS485connection(theseparametersarenotprotectedfrom
modifications):
FrontPanelDisplay
RS485Comm
Disabling password protectionWhentheE5600meterispasswordprotected,youmustenterthecorrectpasswordwhenyouarepromptedthefirsttime.Otherwise,theprotectedparametersaredisplayedasreadonly.
NOTE
Do not lose or forget your password. If you lose your password and need to modify the locked
parameters, a factory reconfiguration is required, which will reset your meter to its factory defaults and
destroy all logged data.
-
7/24/2019 ION Setup Device Configuration Guide
25/72
2009 Schneider Electric. All rights reserved. Page 25
3 PM700 series power meter
ThePM700seriesmeterisacompact,versatileandcosteffectivepowermeter. It issimpletouseandhasabrightLCDdisplayforimprovedvisibilityinpoorlightingconditions. Themetercanbeusedforstandalonemeteringapplications,incustompanels,switchboards,switchgear,gensets,motorcontrolcenters,orUPSsystems.
Someofthefeaturesincludedarepower,demand,energy,powerfactor,andfrequencymeasurements. PM700seriesmetersalsohaveIEC6205321Class 1andIEC6205322Class 0.5S(PM750only)accuracycertificationforbasicsubbillingandcostallocation.
Formoreinformation,refertothemeterdocumentationavailablefromwww.powerlogic.com.
In this chapter
PM700 series meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26UsingIONSetup ..................................................... 26
PM700 series setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26BasicSetup .......................................................... 26
Demand ............................................................. 27
FrontPanelDisplay ................................................... 27I/OSetup ............................................................ 28
OnboardAlarms ..................................................... 28
SerialComms ........................................................ 30
-
7/24/2019 ION Setup Device Configuration Guide
26/72
Chapter 3 - PM700 series power meter PowerLogic ION Setup device configuration guide
Page 26 2009 Schneider Electric. All rights reserved.
PM700 series meter setupBeforeusingIONSetup,makesureallthecommunications settingsforthePM700seriesmeterhasbeenconfigured,asexplainedinthemeterdocumentation.
NOTEThe procedures described here only apply to the meter models that are equipped with communications
(i.e., the PM710 and PM750 meters, but not the PM700 and PM700P).
ThePM700seriesmeterusesModbusRTUprotocoltocommunicatethroughitsRS485serialcommunicationsport.
Devicecommunicationssettings: MakesureallthedevicesonthesameRS485looparesettothesamebaudrateandparity. RecommendedsettingforparityisNone(no parity).
Deviceaddress(unitID)settings: Makesurethedeviceaddress(unitID)isuniqueforeachdeviceinagivenRS485loop(range=1to247forModbus
devices).
Using ION SetupUseNetworkModeinIONSetuptoaddandconfigurethePM700seriesmeter(i.e., cleartheSingleIONdeviceconfigurationmodecheckboxontheLogonscreen).
RefertotheIntroductionsectionforinformationonaddingsitesandmeters.
PM700 series setup screensThefollowingsectionsdescribewhatsetupscreensareavailableonthePM700seriesmeter. Somesetupparametersonlyapplytoparticularmodelsrefertoyourmeterdocumentationfordetailsonsupportedfeatures.
Basic Setup
System Type
Selectthe
option
that
describes
how
your
PM700
series
meter
is
wired
to
the
electricalservice. RefertothePM700seriesmeterinstallationguidefordetailsonthedifferentsystemtypes.
PT Ratio
Selecttheappropriatescalevalue(multiplier)forthePTprimary. Fordirectconnect,selectNo PTs.
-
7/24/2019 ION Setup Device Configuration Guide
27/72
PowerLogic ION Setup device configuration guide Chapter 3 - PM700 series power meter
2009 Schneider Electric. All rights reserved. Page 27
PT Primary
EnterthevalueforthePTprimary,inVolts.
PT Secondary
SelectthevalueforthePTsecondary.
CT PrimaryEnterthevaluefortheCTprimary,inAmps.
CT Secondary
SelectthevaluefortheCTsecondary.
Service Frequency
Selectthesystemfrequencyoftheelectricalservice.
DemandDemandistheaveragepowerconsumptionoverafixedtimeinterval(demandperiod),typically15 minutes.
Demandvaluesarecalculatedforeachsubinterval,thenaveragedoverthenumberofsubintervalsthatmakeupthedemandperiod.
Thermal Dmd Period (mins)
Enterthelengthofthedemandperiod,inminutes.
Block Dmd Period (mins)
Enterthelengthofeachrollingblockperiod(subinterval),inminutes.
Block # of Sub-Intervals
Enterthenumberofsubintervalsusedforcalculatingdemand
NOTE
Refer to the PM700 series documentation for details on how the meter calculates demand.
Front Panel Display
Display ModeSelectIECorIEEEconventionfordisplayingdataonthePM700seriesmetersdisplaypanel.
-
7/24/2019 ION Setup Device Configuration Guide
28/72
Chapter 3 - PM700 series power meter PowerLogic ION Setup device configuration guide
Page 28 2009 Schneider Electric. All rights reserved.
I/O SetupRefertothePM700seriesmeterdocumentationforI/Odescriptionsandconfigurationdetails.
Digital Out KY
Label: ThisfieldidentifiestheKYdigitaloutput.
Mode: SelecttheKYdigitaloutputmodeofoperation.
ExternalControlconfigurestheoutputtobecontrolledbyacommandsentoverthecommunicationslink.
PMAlarmconfigurestheoutputtobecontrolledbythepowermeterinresponsetoasetpointcontrolledalarmcondition.
kWhoutpulsesetsthemetertogenerateafixeddurationpulseoutputthatcanbeassociatedwiththekWhconsumption. UsethePulseWeightregistertoenterhowmanykWhoutoftheloadareassociatedwitheachpulseoftheKYdigitaloutput. ThenusethePulseDurationboxtoselectthepulsewidth(inmilliseconds)foreachkWhpulse.
Digital In S1 and S2 (PM750 only)
Label: Thisfieldidentifiesthedigitalinput.
Mode: SelecttheoperationmodefortheSIdigitalinput:
Forsimpleon/offdigitalinputoperation,selectNormal.
SelectDemandIntervalSyncPulseiftheSIdigitalinputisconfiguredasthedemandsyncinput.
Onboard AlarmsTheOnboardAlarmssetupscreenallowsyoutomakechangesto15preconfiguredalarms(13standardalarmsand2digitalinputalarms). RefertothePM750
Reference
Manualforalistingofthesealarms.
Setting a preconfigured standard alarm1. SelectAllAlarms,thenclickEdit.
-
7/24/2019 ION Setup Device Configuration Guide
29/72
PowerLogic ION Setup device configuration guide Chapter 3 - PM700 series power meter
2009 Schneider Electric. All rights reserved. Page 29
2. IntheAlarmSetupscreen,selectthestandardalarmyouwanttoset.
Enable: Selectthischeckboxtoenablethealarm
Label: Ifrequired,usethisboxtorenametheselectedalarm
SetpointPickup: Enterthemagnitudeabove(forOver)orbelow(forUnder)thatdefinesthealarmONcondition,thenintheDelayboxenterthenumberofsecondsthealarmONconditionneedstobetruebeforethealarmisactivated.
SetpointDropout: Enterthemagnitudebelow(forOver)orabove(forUnder)thatdefinesthealarmOFFcondition,thenintheDelayboxenterthenumberofsecondsthealarmOFFconditionneedstobetruebeforethealarmisdeactivated.
NOTE
Pay special attention to the multipliers for Setpoint Pickup and Setpoint Dropout settings, and adjust thevalues if needed.
AssociateOutput: Selectthischeckboxtoassociatethealarmconditionwithanoutput(e.g.,themetersdigitaloutput).
Redefining a preconfigured alarm
Youcanredefineapreconfiguredalarmbychangingthealarmcondition(OverorUnder)and/orselectingadifferentalarmsourceorinput. MakesureyouupdatetheLabelfieldasappropriate.
Forexample,
Status
Input
On
can
mean
the
alarm
is
activated
when
the
digital
inputisswitchedon,whileStatusInputOffcanmeanthealarmisactivatedwhenthedigitalinputisswitchedoff.
ConditionAlarm sourceor input
Multiplier
-
7/24/2019 ION Setup Device Configuration Guide
30/72
Chapter 3 - PM700 series power meter PowerLogic ION Setup device configuration guide
Page 30 2009 Schneider Electric. All rights reserved.
Setting a preconfigured digital input alarm1. SelectAllAlarms,thenclickEdit.
2. IntheAlarmSetupscreen,selectthedigitalinputyouwanttoconfigureforalarming.
Enable: Selectthischeckboxtoenablethealarm
Label: Ifrequired,usethisboxtorenametheselectedalarm
AssociateOutput: Selectthischeckboxtoassociatethealarmconditionwithanoutput(e.g.,themetersdigitaloutput)
Redefining a preconfigured digital input alarm
Youcanredefineapreconfiguredalarmbychangingthealarmcondition. StatusInputOnmeansthealarmisactivatedwhenthedigitalinputisswitchedon,whileStatusInputOffmeansthealarmisactivatedwhenthedigitalinputisswitchedoff.
Serial Comms
Modbus Address
ThisdisplaystheModbusaddress(unitID)ofthemeter.
Baud Rate
Thisdisplaysthemetersbaudratesetting.
ConditionAlarm source
or input
-
7/24/2019 ION Setup Device Configuration Guide
31/72
-
7/24/2019 ION Setup Device Configuration Guide
32/72
Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide
Page 32 2009 Schneider Electric. All rights reserved.
PM800 series meter setupBeforeusingIONSetup,makesureallthecommunications settingsforthePM800seriesmeterhavebeenconfigured,asexplainedinthemeterdocumentation.
ThePM800seriesmeterusesModbusRTUprotocoltocommunicatethroughitsRS485serialcommunicationsport.
Devicecommunicationssettings: MakesureallthedevicesonthesameRS485looparesettothesamebaudrate. Also,makesureparityissettoNone(no parity)inordertocommunicatewithIONSetup.
Deviceaddress(unitID)settings: Makesurethedeviceaddress(unitID)isuniqueforeachdeviceinagivenRS485loop(range=1to247forModbusdevices).
ThePM800seriesmeterscanalsobeequippedwiththeoptionalEthernetCommunicationsCard,whichprovidesEthernetcommunicationscapabilityandEthernetGatewayfunctionalitytothedevice. ThegatewayusesModbusTCP/IP
protocolto
communicate
on
the
Ethernet
port
and
Modbus
RTU
on
the
serial
port.
PM8ECC considerationsIfyourPM800seriesmeterisequippedwiththePM8ECCEthernetcommunicationcard,youcancommunicatetothemeterdirectlythroughitsEthernetport.
NOTE
Refer to the PM8ECC documentation for instructions on how to set up the device parameters such as
Ethernet & TCP/IP settings.
Adding the PM800 series meter as an Ethernet device1. StartIONSetupinNetworkMode(i.e.cleartheSingleIONdevice
configurationmodecheckboxwhenyoulogon). YoumustaddandconfigureanEthernetsiteiftherearenoEthernetsitesonyourIONSetupnetwork.
2. RightclicktheEthernetsiteiconandselectInsertItem. SelectMeterandclickOK.
-
7/24/2019 ION Setup Device Configuration Guide
33/72
PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter
2009 Schneider Electric. All rights reserved. Page 33
3. TypeadescriptivenameforyourPM800seriesmeter. Selectthetypeofdevice(i.e.,PM800series).TypetheIPaddressofthePM8ECC. IntheIP Portbox,type502. SelectGroup. ClickOK.
Setting up the PM8ECC as an Ethernet gateway
Youcan
set
up
the
PM8ECC
as
an
Ethernet
gateway
this
allows
you
to
communicatewithRS485serialdevicesonthePM8ECCserialport,throughthePM8ECCsEthernetport. MakesurethecommunicationssettingsforalldevicesintheRS485looparesetupproperly(seePM800seriesmetersetuponpage 32).ForRS485wiringinstructions,refertothePM800seriesdocumentation.
EachserialdeviceontheRS485loopmustbeaddedtothePM8ECCsdevicelistbyusingthewebbrowsertoaccessthePM8ECCwebpages. RefertothePM8ECCdocumentationfordetails.
1. StartIONSetupinNetworkMode(i.e.,cleartheSingleIONdeviceconfigurationmodecheckboxwhenyoulogon).
2. Addanew
site.
Select
Ethernet,
then
select
the
Gateway
box.
3. Inthe
Gateway
Info
boxes,
enter
the
IP
address
of
the
PM8ECC.
In
the
IP Port
box,type502. ClickOK.
NOTE
The IP Port must be set to 502 for Modbus TCP communication.
Using ION SetupUseNetworkModeinIONSetuptoaddandconfigurethePM800seriesmeter(i.e., cleartheSingleIONdeviceconfigurationmodecheckboxontheLogonscreen).
RefertotheIntroductionsectionforinformationonaddingsitesandmeters.
-
7/24/2019 ION Setup Device Configuration Guide
34/72
Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide
Page 34 2009 Schneider Electric. All rights reserved.
PM800 series setup screensThefollowingsectionsdescribethePM800seriesmeterssetupscreens.
NOTE
Some setup screens only apply to particular models (e.g., waveform capture for the PM870), while other
screens apply only to installed options (such as the Comm - ECC setup screen for meters equipped with
the optional PM8ECC Ethernet communications card). Refer to your meter documentation for details on
supported features.
Alarm Log
Status
Selecttheappropriateoptiontoenableordisablealarmlogging.
Basic Setup
System Type
SelecttheoptionthatdescribeshowyourPM800seriesmeteriswiredtotheelectricalservice. RefertothePM800seriesmeterdocumentationfordetails.
Primary Scale Factor
Selecttheappropriatescalevalue(multiplier)forthePTprimary. Fordirectconnect,selectNo PTs.
PT PrimaryEnterthevalueforthePTprimary,inVolts.
PT Secondary
SelectthevalueforthePTsecondary.
CT Primary
EnterthevaluefortheCTprimary,inAmps.
CT Secondary
SelectthevaluefortheCTsecondary.
Service FrequencySelectthesystemfrequencyoftheelectricalservice.
Nominal Voltage
Enterthenormalordesignedvoltageleveloftheelectricalservice,inVolts.
Nominal Current
Enterthenormalordesignedcurrentleveloftheelectricalservice,inAmps.
-
7/24/2019 ION Setup Device Configuration Guide
35/72
PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter
2009 Schneider Electric. All rights reserved. Page 35
Billing Log
Status
Selecttheappropriateoptiontoenableordisablethebillinglog.
Interval (mins)Enterhowoften(inminutes)thebillingquantitiesshouldbelogged.
Channels
Thisallowsyoutoselectwhichparameterstoincludeinthebillinglog.
1. SelectChannels,thenclickEdit.
2. Toaddorremoveaparameterfromthebillinglog:
Addingparameters: UnderAvailable,clickthe+signtoexpandanddisplayindividualparameters. Clickaparametertoselectit,thenclickthe
buttontomovetheparametertoSelected.
Removingparameters: UnderSelected,clicktheparameteryouwantto
remove,thenclickthe button.
3. ClickSendtosavethechangestothemeter. Thefollowingpromptappears:
4. NotethatclickingYeswillpowercycle(reset)thedevice. ClickYestoconfirm,orNotocancelandgobacktothepreviousdialog.
-
7/24/2019 ION Setup Device Configuration Guide
36/72
Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide
Page 36 2009 Schneider Electric. All rights reserved.
ClockTheClocksetupscreenallowsyoutosetthedateandtimeonthemeter.ClickEdittochangethedate/timesetting,thenclickSend.
Comm - ECC CardThissectionappliestometersthatareequippedwiththeoptionalPM8ECCEthernetcommunicationscardmodule. Ifinstalled,thePM8ECCsettingscanbeviewedfromthefollowingsetupregisters:
IP Address
ThisdisplaystheIPaddressofthePM8ECC.
Subnet Mask
ThisdisplaystheEthernetsubnetmasksettingforthePM8ECC.
GatewayThisdisplaystheEthernetgatewaysettingforthePM8ECC.
Com3 Protocol
ThisdisplaystheprotocolusedonthePM8ECCsserialport.
Com3 Address
ThisdisplaystheModbusaddressofthePM8ECCsserialport.
Com3 Baud Rate
ThisdisplaysthebaudratesettingofthePM8ECCsserialport.
Com3 Parity
ThisdisplaystheparitysettingofthePM8ECCsserialport.
Comm - Onboard Serial
Com1 Protocol
Thisdisplaysthemetersserialcommunications protocolsetting(e.g.Modbus).
Com1 Address
Thisdisplays
the
Modbus
address
(unit
ID)
of
the
meter.
Com1 Baud Rate
Thisdisplaysthemetersbaudratesetting.
Com1 Parity
Thisdisplaysthemeterscommunicationsportparitysetting. TocommunicatewithIONSetup,thismustbesettoNone.
-
7/24/2019 ION Setup Device Configuration Guide
37/72
PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter
2009 Schneider Electric. All rights reserved. Page 37
NOTE
The remote display adapter (PM8RDA) provides an additional serial communications port (COM2).
However, this COM2 port becomes unavailable if you connect an Ethernet communications card
(PM8ECC) to the meter.
Data Log #1, Data Log #2, Data Log #3, Data Log #4
Status
Selecttheappropriateoptiontoenableordisablethedatalog.
Interval
Thisallowsyoutosettheloggingmodeandintervalforthedatalog.
1. SelectInterval,thenclickEdit.
2. UsetheModeboxtoselectOnlyOnEvent,Continuous,orStart/Stop(refertothemeterdocumentationformoreinformation). Enterhowoften(inminutes)theparametersshouldberecordedinthedatalog.
3. ClickOK.
ChannelsThisallowsyoutoselectwhichparameterstoincludeinthedatalog. ThesetupprocedureissimilartotheonedescribedintheBillingLogsection,underChannelsonpage 35.
Device Labels
Device Label
Youcanusethistextfieldtoassignalabel(e.g.,anabbreviation)foryourmeter.
Device NameplateYoucanusethistextfieldtodescribeyourmeter(e.g.,type,locationorotherdevicedetail).
-
7/24/2019 ION Setup Device Configuration Guide
38/72
Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide
Page 38 2009 Schneider Electric. All rights reserved.
EN50160 Setup
EN50160 Evaluation
SelecttheappropriateoptiontoenableordisabletheEN50160evaluationfeature.
First Day of WeekSelectSundayorMondaytobethefirstdayoftheweek.
Interruption (% Nominal)
Enterthevaluethatdefineswhatconstitutesavoltageinterruption,expressedasapercentageofnominalvoltage.Forexample,ifInterruption(% Nominal)issetto1%,avoltageinterruptionisrecordedifthevoltagedropsbelow99%ofitsnominalvalue.
Max Short Interruption (secs)
Enterthelongesttimeduration,innumberofseconds,thatdefinesashortinterruption. Forexample,ifMaxShortInterruption(secs)issetto270seconds,
avoltage
interruption
lasting
longer
than
that
time
is
considered
along
interruption.
Slow Voltage Variations
Enterthevaluethatdefinestheallowablerangeofslowvoltagevariations,expressedasapercentageofnominalvoltage(typically+/10%ofnominal).
Voltage for 4-Wire Systems
Selectwhetherthevoltagefora4wiresystemisexpressedasLinetoNeutralorLinetoLine.
Frequency Configuration
SelectSynchronousforasystemwithasynchronousconnectiontoaninterconnectedsystem,orUnsynchronousforasystemwithoutasynchronousconnectiontoaninterconnectedsystem.
Formoreinformation,refertothePM800seriesReferenceManual.
Energy & Demand
Accumulated Energy
Selecthowaccumulatedenergyvaluesshouldbestored(absoluteorsigned).
Power Mode
Selectwhichtechniqueisusedtocalculatedemandpower.
Power Interval
Enterthedurationofeachdemandinterval(forcalculatingdemandpower),inminutes.
-
7/24/2019 ION Setup Device Configuration Guide
39/72
PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter
2009 Schneider Electric. All rights reserved. Page 39
Power Sub-Interval
Enterthedurationofeachsubinterval(fordemandpower),inminutes.
Current Mode
Selectwhichtechniqueisusedtocalculatedemandcurrent.
Current IntervalEnterthedurationofeachdemandinterval(forcalculatingdemandcurrent),inminutes.
Current Sub-Interval
Enterthetimeperiodforeachsubinterval(fordemandcurrent),inminutes.
Front Panel Display
Language
SelectwhichlanguageisdisplayedonthePM800seriesmetersLCDpanel.
Date Format
Selectyourdateformat(e.g.yy/mm/dd).
Time Format
Selectyourtimeformat(24houror12hourAM/PM).
Phase Notation
Selectyourlinephaselabelformat(A/B/C/Nor1/2/3/N).
I/O SetupRefertothePM800seriesmeterdocumentationforI/Odescriptionsandconfigurationdetails.
Digital Out KY
Label: TypeanameidentifyingtheKYdigitaloutput.
Mode: SelecttheKYdigitaloutputmodeofoperation:
Normal:UsethismodefornormalON/OFFoperationoftheKYdigitaloutput.
ForTimed
or
End
of
Demand
Intervalmode,
use
the
Hold
Time
register
toenterhowmanysecondstheKYdigitaloutputremainsenergized.
ForAbsolutekWhpulse,AbsolutekVARhpulseorkVAhpulsemode,usethePulseWeightregistertoenterhowmanyabsolutekWh(intoandoutoftheload),absolutekVARh(intoandoutoftheload)orkVAhareassociatedwitheachpulseoftheKYdigitaloutput.
ForkWhinpulseorkVARhinpulsemode,usethePulseWeightregistertoenterhowmanykWhorkVARhintotheloadareassociatedwitheachpulseoftheKYdigitaloutput.
-
7/24/2019 ION Setup Device Configuration Guide
40/72
Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide
Page 40 2009 Schneider Electric. All rights reserved.
ForkWhoutpulseorkVARhoutpulsemode,usethePulseWeightregistertoenterhowmanykWhorkVARhoutoftheloadareassociatedwitheachpulseoftheKYdigitaloutput.
Ifsettoanyoftheabovepulsemodes,theDigitalKYOutputwillpulsebasedonanenergyperpulsevalue. RefertothePM800seriesreferencemanualfordetailsondeterminingthevalueofthePulseWeightsetting.
Control: ForNormal,LatchedorTimedmodeofoperation,selecthowtheKYdigitaloutputiscontrolled,i.e.,eitherExternallyControlledorcontrolledbypowermeteralarm(PMAlarm).
NOTE
For detailed descriptions on the different Mode and Control options, refer to the Relay Output Operating
Modes section in the PM800 series reference manual.
Digital In SI
Label: TypeanameidentifyingtheSIdigitalinput.
Mode: SelecttheoperationmodefortheSIdigitalinput. Fordetaileddescriptionsonthedifferentmodes,refertotheDigitalInputssectioninthePM800seriesreferenceManual.
Normal:UsethismodefornormalON/OFFoperationofthedigitalinput.
DemandIntervalSyncPulse: UsethismodetoconfiguretheSIdigitalinputasthedemandsyncinput(toreceiveademandsyncpulsefromautilitydemandmeter,forexample).
ConditionalEnergyControl: UsethismodetoconfiguretheSIdigitalinputforconditionalenergycontrol.
PulseWeight: ForNormalorInputMeteringmodeofoperation,enterthepulseweightassociatedwiththechangeofstateoftheinput.
Units: ForNormalorInputMeteringmodeofoperation,selecttheunitofmeasurementassociatedwiththeSIdigitalinputpulse(ifapplicable).
Optional I/O modulesThefollowingparametersapplytometersequippedwiththeoptionalI/Omodules. RefertothePM800seriesmeterdocumentationtoseewhichinputsandoutputsareavailableforthetypeofI/Omodule(s)installedonyourmeter.
Relay A-R1, Relay A-R2, Relay B-R1, Relay B-R2
Label: Typeanameidentifyingtherelayoutput.
Mode: Selectwhichmodeofoperationtherelayoutputuses(Normal,Latched,Timed,orEndofDemandInterval).
Control: ForNormal,LatchedorTimedmodeofoperation,selecthowtherelayoutputiscontrolled,i.e.,eitherExternallyControlled(RemotelyControlled)orPMAlarm(PowerMeterControlled).
HoldTime: ForTimedandEndofDemandIntervalmodeofoperation,enterhowmanysecondstherelayremainsenergized.
-
7/24/2019 ION Setup Device Configuration Guide
41/72
PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter
2009 Schneider Electric. All rights reserved. Page 41
NOTE
For detailed descriptions on the different modes of operation, refer to the Relay Output Operating
Modes section in the PM800 series reference manual.
ClickOK. Configuretheotherrelaysasrequired.
Digital In A-S1, Digital In A-S2 Digital In A-S6,Digital In B-S1, Digital In B-S2 Digital In B-S6
Label: Typeanameidentifyingthedigitalinput.
Mode: Selectthedigitalinputmodeofoperation(Normal,DemandIntervalSyncPulse,ConditionalEnergyControl,orInputMetering).
PulseWeight: ForNormalorInputMeteringmode,enterinthePulseWeightboxhowmanyunitsofameasuredorcalculatedquantityisassociatedwitheachpulse.
Units: ForNormalorInputMeteringmode,selecttheunitsusedforthemeasuredorcalculatedquantity(ifapplicable).
NOTE
For detailed descriptions on the different modes of operation, refer to the Digital Inputs section in the
PM800 series reference manual.
Analog I/O
RefertothePM800seriespowermeterinput/outputmoduleinstallationmanualforinstructionsonhowtosetuptheanaloginputs(Analog In AAI1,Analog In AAI2,Analog In BAI1,Analog In BAI2)andanalogoutputs(Analog Out AAO1,Analog Out AAO2,Analog Out BAO1,Analog Out BAO2):
AnalogInputs
Label: Thisnameidentifiesthespecificanaloginput.
Units: Definestheunitsofthemonitoredanalogvalue.
Scalefactor: Defineswhatmultiplierisusedonthemeasuredvalue.
ReportRangeLowerLimit: Thisisthevaluethepowermeterreportswhentheinputreaches(ordropsbelow)thelowestvalidreading.
ReportRangeUpperLimit: Thisisthevaluethepowermeterreportswhentheinputreaches(orexceeds)thehighestvalidreading.
AnalogOutputs
Label: Thisnameidentifiesthespecificanalogoutput. Outputregister: Definesthepowermeterregisterassignedtotheanalog
output.
LowerLimit: Thisistheminimumoutputcurrentthatthepowermetersendstotheanalogoutputwhentheregistervaluereaches(ordropsbelow)thelowerlimit.
-
7/24/2019 ION Setup Device Configuration Guide
42/72
Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide
Page 42 2009 Schneider Electric. All rights reserved.
UpperLimit: Thisisthemaximumoutputcurrentthatthepowermetersendstotheanalogoutputwhentheregistervaluereaches(orexceeds)theupperlimit.
Input MeteringRefertothemeterdocumentationfordetaileddescriptionsonmeteringcapabilitiesandoptions.
Demand Method
Selectwhichmethodisusedforcalculatingdemand.
Demand Interval
Enterthetimeperiodforeachdemandinterval,inminutes.
Demand Sub-Interval
Enterthetimeperiodforeachdemandsubinterval,inminutes.
Channel 1, Channel 2 Channel 5
Beforeyoucanassociateadigitalinputtoachannel,youneedtosetupthedigitalinputforinputmeteringoperation. RefertoI/OSetuponpage 39fordetails.
1. FromtheInputMeteringsetupscreen,selectoneoftheavailablechannels.
2. IntheLabelfield,enteradescriptivenameforthechannel.
3. Selecttheappropriateunitsandrate. Theunitsyouselectmustmatchtheunitsyouselectedforthedigitalinput(whenyouconfigureditforinputmetering).
4. IntheAvailableInputscolumn,selectthedigitalinput,thenclickthebuttontomoveittotheAssignedInputscolumn.
(Tounassigntheinput,selectitfromtheAssignedInputscolumn,thenclickthe button.)
NOTE
Usually, input metering applications also require one input to be set up for Demand Interval Sync Pulse,
to allow customers to synchronize their demand intervals to the utility (typically, the pulse signal is
provided by the utility). To set up an input for demand interval sync pulse, refer to I/O Setup on
page 39.
Meter ResetsToresetthemeter,doubleclickMeterInitthenselectReinitialize. ClickOK.
ClickSendtoinitializethemeter. Attheprompt,clickYestoproceed,orNotoaborttheinitialization.
-
7/24/2019 ION Setup Device Configuration Guide
43/72
PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter
2009 Schneider Electric. All rights reserved. Page 43
NOTE
Initializing a meter will reset or disable certain parameters. Make sure you read the warning prompt
before proceeding.
Metering StandardsHarmonic Distortion
Selecthowtotalharmonicdistortioniscalculated.
PF Sign Convention
SelectwhichstandardsconventiontousefordisplayingPFsign.
Voltage Harmonic Method
Selecthowthemagnitudeofvoltageharmonicisdisplayed.
Current Harmonic MethodSelecthowthemagnitudeofcurrentharmonicisdisplayed.
Onboard Alarms/Events
Standard
Thisallowsyoutoconfigurethestandardalarms. SelectStandardthenclickEdit.
Thenumberedlabels(onthedrawing)aredescribedbelow:
1. Theleftcolumnliststhestandardalarms. Selectaniteminthislisttoeditit.
12
5
3 4
6
9
10
7 8
11
12 13
-
7/24/2019 ION Setup Device Configuration Guide
44/72
Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide
Page 44 2009 Schneider Electric. All rights reserved.
2. Thetwoboxesatthetopliststhestandardalarmconditionandmeasurementthatdefinesthehighlightediteminalarmslist. Youcanusetheseboxestochangetheconditionandmeasurementforthisalarm.
3. SelecttheEnableboxtoenabletheselected(highlighted)alarminthelist,orcleartheboxtodisablethealarm.
4. The
Label
box
identifies
the
name
of
the
standard
alarm.
Use
this
box
to
renamethealarmasnecessary(e.g.,ifyouchangedtheconditionormeasurementforthestandardalarm).
5. Enterthesetpointpickupvalue(absoluteorrelative,seeitem#7below)andthepickupdelay(inseconds).
6. Enterthesetpointdropoutvalue(absoluteorrelative,seeitem#7below)andthedropoutdelay(inseconds).
7. Tospecifyabsolutevaluesforthesetpointpickupanddropoutlimits,clear(uncheck)theRelative(%ofAvg)box. TospecifysetpointpickupanddropoutlimitsasapercentageaboveorbelowtheRMSaveragevalue(Avg),select(check)theRelative(%ofAvg)box.
8. Usethe
Priority
box
to
set
the
alarm
priority.
9. UsetheDataLogscheckboxestoselectwhichonboarddatalog(s)areusedtorecordtheselectedalarm.
10. SelecttheWaveformCaptureboxtotriggerawaveformcaptureonalarm,orcleartheboxtodisablewaveformcaptureonalarm.
11. Ifyouwanttotriggeradigitaloutputorrelayonanalarm,clicktheOutputbutton,selectoneoftheavailableoutputs,thenclickthe buttontomoveittotheSelectedcolumn. ClickOK.
12. Tocreateanewalarm,clickAdd, thenspecifythealarmconditionandmeasurement,asdescribedintheprevioussteps.
NOTEThere is a limit to the number of alarms you can create. The Addbutton is disabled once that limit is
reached. In this case, you must delete an existing alarm before you can create a new one (or you can
select an existing alarm and edit/configure it as necessary).
13. Todeleteanalarm,selectitfromthealarmslist,thenclickDelete.
Tosavethechangestothemeter,clickSend. Dependingonthetypeofchanges,ameterresetmightoccur:
-
7/24/2019 ION Setup Device Configuration Guide
45/72
PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter
2009 Schneider Electric. All rights reserved. Page 45
NotethatclickingYeswillpowercycle(reset)thedevice. ClickYestoconfirmandproceedwithyourchanges,orNotocancelandgobacktothepreviousdialog.
Formoreinformationonconfiguringthealarms,refertothePM800seriesReferenceManual.
Disturbance (PM870 only)Thisallowsyoutoconfigurethedisturbancealarms(i.e.voltagesagsandswells).SelectDisturbancethenclickEdit.
Thenumberedlabels(onthedrawing)aredescribedbelow:
1. Theleftcolumnliststhedisturbancealarms. Selectaniteminthislisttoeditit.
2. Thetwoboxesatthetopliststhedisturbancealarmconditionandmeasurementthatdefinesthehighlightediteminalarmslist. Youcanusetheseboxestochangethecondition(sagorswell)andmeasurement(currentorvoltage)foraselectedalarm.
3. SelecttheEnableboxtoenabletheselected(highlighted)alarminthelist,orcleartheboxtodisablethealarm.
4. TheLabelboxidentifiesthenameofthedisturbancealarm. Usethisboxtorenamethealarmasnecessary(e.g.,ifyouchangedthecondition/measurementforthedisturbancealarm).
5. Enterthesetpointpickupvalue(absoluteorrelative,seeitem#7below)andthe
pickupdelay(innumberof
cycles).
6. Enterthesetpointdropoutvalue(absoluteorrelative,seeitem#7below)andthedropoutdelay(innumberofcycles).
7. Tospecifyabsolutevaluesforthesetpointpickupanddropoutlimits,clear(uncheck)theRelative(%ofAvg)box. TospecifysetpointpickupanddropoutlimitsasapercentageaboveorbelowtheRMSaveragevalue,select(check)theRelative(%ofAvg)box.
1 2
5
3 4
6
9
10
7 8
11
12 13
-
7/24/2019 ION Setup Device Configuration Guide
46/72
Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide
Page 46 2009 Schneider Electric. All rights reserved.
8. UsethePriorityboxtosetthealarmpriority.
9. UsetheDataLogscheckboxestoselectwhichonboarddatalog(s)areusedtorecordtheselectedalarm.
10. SelecttheWaveformCaptureboxtotriggerawaveformcaptureonalarm,orcleartheboxifyoudonotwanttotriggerawaveformcaptureonalarm.
11. Ifyouwanttotriggeradigitaloutputorrelayonanalarm,clicktheOutputbutton,selectoneoftheavailableoutputs,thenclickthe buttontomoveittotheSelectedcolumn. ClickOK.
12. Tocreateanewalarm,clickAdd, thenspecifythealarmconditionandmeasurement,asdescribedintheprevioussteps.
NOTE
There is a limit to the number of alarms you can create. The Addbutton is disabled once that limit is
reached. In this case, you must delete an existing alarm before you can create a new one (or you can
select an existing alarm and configure it as necessary).
13. Todelete
an
alarm,
select
itfrom
the
alarms
list,
then
click
Delete.
Tosavethechangestothemeter,clickSend. Dependingonthetypeofchanges,ameterresetmightoccur:
NotethatclickingYeswillpowercycle(reset)thedevice. ClickYestoconfirmandproceedwithyourchanges,orNotocancelandgobacktothepreviousdialog.
Formoreinformationonconfiguringthealarms,refertothePM800seriesReferenceManual.
Digital
Thisallowsyoutoconfigurethedigitalinputalarms. SelectDigitalthenclickEdit.
-
7/24/2019 ION Setup Device Configuration Guide
47/72
PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter
2009 Schneider Electric. All rights reserved. Page 47
Thenumberedlabels(onthedrawing)aredescribedbelow:
1. Theleftcolumnliststhedigitalinputalarms.Selectaniteminthislisttoeditit.
2. Thisdefinesthealarmcondition.
SelectStatusInputOntosetthealarmwhenthedigitalinputchangesfromofftoon.
SelectStatusInputOfftosetthealarmwhenthedigitalinputchangesfromontooff.
TheEndofincrementalenergyinterval(EndIncEnrInt), Endofdemandinterval(EndDmdInt)andPowerup/reset(PwrUp/Reset)
alarmsare
unary
type
alarms
because
they
use
internal
signals
from
the
powermeter,andcannotbechangedthroughthissetupscreen. Refertothemeterdocumentationformoreinformation.
3. DependingontheI/Omoduleinstalledonyourmeter,thisallowsyoutoselectoneoftheavailabledigitalinputs. Notethatthisisnotconfigurableforunarytypealarmsseeitem#2above.
4. SelecttheEnablecheckboxtoenabletheselected(highlighted)alarminthelist,orcleartheboxtodisablethealarm.
5. TheLabelboxidentifiesthenameofthedigitalalarm. Typeinthisboxtorenamethealarmasnecessary.
6. UsethePriorityboxtosetthepriorityfortheselectedalarm.
7. UsetheDataLogscheckboxestoselectwhichonboarddatalog(s)areusedtorecordtheselectedalarm.
8. SelecttheWaveformCapturecheckboxtotriggerawaveformcaptureonalarm,orcleartheboxto ifyoudonotwanttotriggerawaveformcaptureonalarm.
9. Ifyouwanttotriggeradigitaloutputorrelayonanalarm,clicktheOutputbutton,selectoneoftheavailableoutputs,thenclickthe buttontomoveittotheSelectedcolumn. ClickOK.
1
2
6
4 5
7
8 9
3
10 11
-
7/24/2019 ION Setup Device Configuration Guide
48/72
Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide
Page 48 2009 Schneider Electric. All rights reserved.
10. Tocreateanewalarm,clickAdd, thenspecifythealarmtypeandselectthedigitalinput,asdescribedintheprevioussteps.
11. Todeleteanalarm,selectitfromthealarmslist,thenclickDelete.
Tosavethechangestothemeter,clickSend. Dependingonthetypeofchanges,ameterresetmightoccur:
NotethatclickingYeswillpowercycle(reset)thedevice. ClickYestoconfirmandproceedwithyourchanges,orNotocancelandgobacktothepreviousdialog.
Formoreinformationonconfiguringthealarms,refertothePM800seriesReferenceManual.
Boolean
ThisallowsyoutoconfiguretheBooleanalarms. SelectBooleanthenclickEdit.
NOTE
If you havent set up any Boolean alarms yet, click Addto create a Boolean alarm.
1. SelectaBooleanalarmtoeditit.
2. UsetheLabelboxtorenametheselectedBooleanalarm(e.g.AnyOvercurrent).
3. Selectthetypeoflogicoperation(e.g.,LogicOR)youwanttousetotestforthealarmcondition.
12
4 5
6 7
3
11 12
8
9 10
-
7/24/2019 ION Setup Device Configuration Guide
49/72
PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter
2009 Schneider Electric. All rights reserved. Page 49
4. ThisboxliststhealarmparametersusedfortheBooleanlogictest.
5. ClickEdittoaddorremovealarmparameters.
SelectanalarmparameterunderAvailable,thenclickthe buttontomoveittoSelected. Ifyouwanttoremoveaparameter,selectitunderSelected,thenclickthe button.
6. Selectthe
Enable
check
box
to
enable
the
selected
(highlighted)
alarm
in
the
list,orcleartheboxtodisablethealarm.
7. UsethePriorityboxtosetthepriorityfortheselectedalarm.
8. UsetheDataLogscheckboxestoselectwhichonboarddatalog(s)areusedtorecordtheselectedalarm.
9. SelecttheWaveformCaptureboxtotriggerawaveformcaptureonalarm,orcleartheboxifyoudonotwanttotriggerawaveformcaptureonalarm.
10. Ifyouwanttotriggeradigitaloutputorrelayonanalarm,clicktheOutputbutton,selectoneoftheavailableoutputs,thenclick buttontomoveittoSelected. ClickOK.
11. To
create
a
new
Boolean
alarm,
click
Add,
then
specify
the
alarm
type
and
select
thedigitalinput,asdescribedintheprevioussteps.
12. Todeleteanalarm,selectitfromthealarmslist,thenclickDelete.
Tosavethechangestothemeter,clickSend. Dependingonthetypeofchanges,ameterresetmightoccur:
NotethatclickingYeswillpowercycle(reset)thedevice. ClickYestoconfirmandproceedwithyourchanges,orNotocancelandgobacktothepreviousdialog.
-
7/24/2019 ION Setup Device Configuration Guide
50/72
Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide
Page 50 2009 Schneider Electric. All rights reserved.
Shift EnergyThisallowsyoutogroupenergyusageandcostaccordingtothreedifferenttimeshiftsinsidea24hourperiod(forexample,three8hourshifts).
First Shift Start, Second Shift Start, Third Shift Start
Usethesesettingstoselectwhattimethefirst,secondorthirdshiftstarts.
Cost Scale Factor
Selectthemultiplierusedwhencalculatingenergycost.
First Shift Cost (per kWh), Second Shift Cost (per kWh), Third Shift Cost (per kWh)
UsethesesettingstoenterthecostperkWhforeachshift.
Billing Cycle Setup
SelectthisthenclickEdittosetupthebillingcycle.
UsetheMonthandDayboxestoselectmeterreadingdates. UsetheTimeofDayboxtoselectthehourthemeterreadingisperformed.
Trending & Forecasting
Feature Control
Selecttheappropriateoptiontoenableordisablethisfeature.
Register Trend Item
Selectoneoftheavailablequantitiesyouwouldliketotrend,orselectUserDefined.
User Defined Register
Selectoneoftheavailableitemsfortrending.
User Defined Scaling
Selecttheappropriatemultiplierfortheitemselectedfortrending.
-
7/24/2019 ION Setup Device Configuration Guide
51/72
PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter
2009 Schneider Electric. All rights reserved. Page 51
User Defined Label
Enteradescriptivenameyouwantfortheitemselectedfortrending.
Waveform CaptureWaveformcaptureissupportedonthePM850andPM870.ThePM870allowsyoutoselectandconfigurethewaveformcapture.
Status
Selecttheappropriateoptiontoenableordisablethisfeature.
File Mode
Selectwhichmethodisusedforstoringwaveforms:
FIFO(firstinfirstout)modediscardstheoldestwaveformcapturewhenthewaveformstorageisfull.
Fill
and
Hold
mode
keeps
the
oldest
waveform
capture
and
does
not
record
newoneswhenthewaveformstoragebecomesfull.
Channels (PM870 only)
Thisallowsyoutoselectwhichinputsyouwanttosetupforwaveformcapture.SelectChannelsthenclickEdit.
Dependingonyourwiringconfiguration,certaininputsbecomeN/A(notapplicable). Ifthisisthecase,IONSetupdisplaysthisprompt:
1. Selectthevoltageand/orcurrentinputchannelsyouwanttocapture. ClickNext.
2. Setthecaptureoptions:
Samples/Cycle
Duration(cycles)
PreEventCycles
MaxCaptureindicatesthemaximumnumberofrecordingsforwaveformcapture,andisshownforinformationalpurposeonly.
-
7/24/2019 ION Setup Device Configuration Guide
52/72
Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide
Page 52 2009 Schneider Electric. All rights reserved.
-
7/24/2019 ION Setup Device Configuration Guide
53/72
2009 Schneider Electric. All rights reserved. Page 53
5 BCPM (Branch circuit power meter)
TheBCPM(Branchcircuitpowermeter)providesacosteffectivesolutionforelectricalloadmanagement. TheBCPMisdesignedtomeasurethecurrent,voltage,andenergyconsumptionofeachcircuitinapanelboard,includingthemainbreaker. Bycombiningthefunctionsoftwoboardsintoonedevice,theBCPMscurrentmonitoringcapabilityisincreased,providingsupportforupto92circuits(84 branchcircuits,plus8 auxiliarycircuits)onasingleboard. TheBCPMisavailableina42circuitor84circuitmodel.
Theaccumulatedinformationcanbetransmittedthroughthecommunicationsinterfaceorviewedlocallythroughanoptionallocaldisplay. Dataupdatesoccurapproximatelyeverytwoseconds,providingtimelypreventativemaintenance
information.Asacircuitapproachestheuserconfiguredthresholds,alarmindicatorsaretriggered,preventingcostlydowntimefromoverloadedcircuitsorloadfailures.
Formoreinformation,refertotheBCPMinstallationguide.
In this chapter
BCPM setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54UsingIONSetup ..................................................... 54
BCPM setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55BasicSetup .......................................................... 55
AuxiliaryCTSizes .................................................... 55
BranchCircuitCTSizes................................................ 55
BreakerSizes ......................................................... 55
DemandSetup ....................................................... 56
InstantaneousCurrentAlarms.......................................... 56
LatchingCurrentAlarms .............................................. 57
VoltageAlarms....................................................... 60
-
7/24/2019 ION Setup Device Configuration Guide
54/72
Chapter 5 - BCPM (Branch circuit power meter) PowerLogic ION Setup device configuration guide
Page 54 2009 Schneider Electric. All rights reserved.
BCPM setupBeforeusingIONSetup,makesureallthecommunicationssettingsfortheBCPMhasbeenconfigured,asexplainedintheBCPMinstallationguide.
TheBCPMusesModbusRTUprotocoltocommunicatethroughitsRS485serialcommunicationsport.
Devicecommunicationssettings: MakesureallthedevicesonthesameRS485looparesettothesamebaudrate. MakesureParityswitchissettoOFF(i.e. no parity)foralldevices.
Deviceaddress(unitID)settings: The2stripversionoftheBCPMusesoneModbusaddress,whilethe4stripversionusestwoModbusaddresses. Panel1usesthebaseaddressassetontheCommunicationsAddressDIPswitches.Panel2(forthe4stripversion)isautomaticallyassignedthedeviceaddressequaltoPanel1sbaseaddressplusone. Forexample,ifyousettheunitIDforPanel1to19,theunitIDforPanel2isautomaticallysetto20(i.e.,19+1).RefertotheBCPMinstallationguidefordetailsonusingtheDIPswitchestoset
thedevice
communications
parameters.
NOTE
When setting up the device addresses for multiple BCPMs, make sure each address is unique AND does
not cause address duplication or overlap between the BCPM devices.
Device address considerationsSinceeachBCPMusestwodeviceaddresses,adoptingastandardforassigningBCPMdeviceaddressesishighlyrecommended.Forexample,youcanimplementadeviceaddressassignmentconventionthatspecificallyallowsonlyoddnumberedaddressesforagivenBCPM(i.e.,correspondingtoPanel 1). Usingthisconvention,anevennumbereddeviceaddresswillalwaysbePanel 2ofaparticularBCPM.
BCPM device naming considerationsEachBCPMdeviceisaddedastwometersinIONSetup(i.e.,oneforPanel 1andtheotherforPanel 2). Forthisreason,itisrecommendedthatyouadoptaBCPMdevicenamingconventionsothateachhalfofagivenBCPMdevice(Panel 1,Panel 2)canbeeasilyidentified.
Using ION Setup UseNetworkModeinIONSetuptoaddandconfiguretheBCPM(i.e.cleartheSingleIONdeviceconfigurationmodecheckboxontheLogonscreen).
RefertotheIntroductionsectionforinformationonaddingsitesandmeters.
-
7/24/2019 ION Setup Device Configuration Guide
55/72
PowerLogic ION Setup device configuration guide Chapter 5 - BCPM (Branch circuit power meter)
2009 Schneider Electric. All rights reserved. Page 55
BCPM setup screensThefollowingsectionsdescribewhatsetupscreensareavailableontheBCPM.Somesetupparametersonlyapplytoparticularmodelsrefertoyourmeterdocumentationfordetailsonsupportedfeatures.
Basic Setup
Configuration
Selecttheconfigurationoptionthatmatcheshowthecurrentsensorstripsarearrangedandoriented. RefertotheBCPMinstallationguidefordetails.
NOTE
Make sure Configuration is set to the same value for each half of the BCPM (Panel 1, Panel 2).
Location
Typeanamethatidentifiesthepaneland/ordescribesitsphysicallocation.
Auxiliary CT Sizes
Auxiliary #1 (Amps) to Auxiliary #4 (Amps)
ThesedefinetheAuxiliaryorMainsCTsize(typically200A). TypetheappropriatenumericvalueforeachauxiliaryCTinstalledinthepanel.Dependingonthemodeloptionordered,aBCPMcanhave4,8ornoinputsforauxiliaryCTs.IfanyoftheauxiliaryCTsarenotconnected,settheircorrespondingBreakerSize
valuesto0(zero)inIONSetuptodisablealarmsforthoseunusedchannels.
Branch Circuit CT Sizes
Channel #1 (Amps) to Channel #42 (Amps)
ThesedefinetheChannelorBranchCTsize. Theseregistersarenotconfigurable,butarepresettoafixedvalueof100 A.
Breaker Sizes
Auxiliary #1 (Amps) to Auxiliary #4 (Amps)
ThesedefinetheAuxiliaryorMainsbreakersize(typically225A). Typetheappropriatenumericvalueforeachauxiliarybreakerinthepanel. Forunused
breakers,setthevalueto0(zero)todisablealarmsforthosechannels.
Channel #1 (Amps) to Channel #42 (Amps)
ThesedefinetheChannelorBranchbreakersize(typically20A). Typetheappropriatenumericvalueforeachchannelbreakerinthepanel. Forunused
-
7/24/2019 ION Setup Device Configuration Guide
56/72
Chapter 5 - BCPM (Branch circuit power meter) PowerLogic ION Setup device configuration guide
Page 56 2009 Schneider Electric. All rights reserved.
breakers,settheircorrespondingbreakersizevaluesto0(zero)todisablealarmsforthoseunusedchannels.
Demand Setup
Demandis
the
average
power
consumption
over
afixed
time
interval
(demand
period),typically15 minutes. Demandvaluesarecalculatedforeachsubinterval,thenaveragedoverthenumberofsubintervalsthatmakeupthedemandperiod.
Number of Sub-intervals
Typethenumberofsubintervalsusedforcalculatingdemand(default=1).
Sub-interval Length (secs)
Typethenumberofsecondsforeachsubinterval(default=900seconds).
Instantaneous Current AlarmsTheinstantaneouscurrentalarmsetupparametersdefinethemaximum(highalarm)andminimum(lowalarm)limitsforallbranchandmaincircuitsmonitored
bytheBCPM. InstantaneouscurrentalarmsareONonlyifthealarmconditionsaremet. ThesealarmsareautomaticallyturnedOFForclearedwhencircuitcurrentiswithinthenormalrange.
High Alarm Threshold
Typetheinstantaneouscurrentvalue,expressedasapercentageofthebreakersize(default=60%). Whenthecircuitcurrentexceedsthatvalue,thehighcurrentalarmisactivated.
Example: Ifthethresholdissetto60%,thehighalarmwouldbeactivatedwhen
instantaneouscurrentfora20Abreakerexceeds12A(i.e.,20 A x 0.60).
Low Alarm Threshold
Typetheinstantaneouscurrentvalue,expressedasapercentageofthebreakersize(default=5%). Whenthecircuitcurrentfallsbelowthatvalue,thelowcurrentalarmisactivated.
Example: Ifthethresholdissetto5%,thelowalarmwouldbeactivatedwheninstantaneouscurrentfora20Abreakerdropsbelow1A(i.e.,20 A x 0.05).
Hysteresis
Typethevalue,expressedasapercentageofthealarmthreshold,thatdefineshow
muchthe
circuit
current
must
fall
below
the
High
alarm
threshold
or
rise
above
the
LowalarmthresholdtodeterminethealarmsOFFstate(default=5%). Todisabletheinstantaneouscurrentalarms,setHysteresistozero(0%).
Example: Ifhysteresisissetto5%,theOFFstateforahighalarmthresholdof12 Awouldbeat11.4 Aandbelow(i.e.,12Aminus(12Ax0.05)),whiletheOFFstateforalowalarmthresholdof1 Awouldbeat1.005 Aandabove(i.e.,1Aplus(1 A x 0.05)).
-
7/24/2019 ION Setup Device Configuration Guide
57/72
PowerLogic ION Setup device configuration guide Chapter 5 - BCPM (Branch circuit power meter)
2009 Schneider Electric. All rights reserved. Page 57
Latching Current AlarmsThelatchingcurrentalarmsetupparametersdefinethealarmdelay(timer)andthreshold(limit)forallbranchandmaincircuitsmonitoredbytheBCPM.LatchedalarmsremainONuntiltheuserresetsorclearsthealarms.
Thealarm
delay
setting
defines
how
many
seconds
acircuit
needs
to
be
in
an
alarm
state(i.e.,exceedsthehighorhighhighalarmthreshold,orfallsbelowtheloworlowlowalarmthreshold)beforethealarmisactivated. Areturntonormal(nonalarm)stateisinstantaneous,sothealarmdelaytimerisresetifthecurrentinthecircuitreturnstonormalstatebeforethetimerexpires.
Thealarmthresholdsettingdefinesthelimitforahighcurrentorlowcurrentalarmstate,expressedasapercentageofthebreakersize.
High-High Alarm Delay (s)
TypethenumberofsecondsthecurrentinacircuitneedstobecontinuouslyabovetheHighHighAlarmThresholdbeforetheHighHighalarmisactivated(default = 10 s).
High Alarm Delay (s)
TypethenumberofsecondsthecurrentinacircuitneedstobecontinuouslyabovetheHighAlarmThresholdbeforetheHighalarmisactivated(default =10 s).
Low Alarm Delay (s)
TypethenumberofsecondsthecurrentinacircuitneedstobecontinuouslybelowtheLowAlarmThresholdbeforetheLowalarmisactivated(default = 10 s).
Low-Low Alarm Delay (s)
Typethenumberofsecondsthecurrentinacircuitneedstobecontinuouslybelow
theLow
Low
Alarm
Threshold
before
the
Low
Low
alarm
is
activated
(default = 10 s).
Zero Current Alarm On Time (s)
Typethenumberofsecondsthecurrentinacircuitneedstostayabovethelowlowalarmthresholdlevelbeforethelatchingalarmsarearmed/enabled(default = 10 s).
Zero Current Alarm Delay (s)
TypethenumberofsecondsthecurrentinacircuitneedstobebelowtheLowLowAlarmThresholdlevelbeforetheZerocurrentalarmisactivated(default = 30 s).
High-High Alarm Threshold (%)TypethelimitfortheHighHighcurrentalarmstate,expressedasapercentageofthebreakersize(default = 70%). Forexample,theHighHighalarmthresholdfora20Abreakeris14A(i.e.,20 x 0.70). Todisablethisalarm(forallchannels)setitsthresholdvalueto0%.
High Alarm Threshold (%)
TypethelimitfortheHighcurrentalarmstate,expressedasapercentageofthebreakersize(default = 60%). Forexample,theHighalarmthresholdfora20 A
-
7/24/2019 ION Setup Device Configuration Guide
58/72
Chapter 5 - BCPM (Branch circuit power meter) PowerLogic ION Setup device configuration guide
Page 58 2009 Schneider Electric. All rights reserved.
breakeris12A(i.e.,20 x 0.60). Todisablethisalarm(forallchannels)setitsthresholdvalueto0%.
Low Alarm Threshold (%)
TypethelimitfortheLowcurrentalarmstate,expressedasapercentageofthebreakersize(default = 7.5%). Forexample,theLowalarmthresholdfora20 A
breakeris
1.5 A
(i.e.,
20 x 0.075).
To
disable
this
alarm
(for
all
channels)
set
its
thresholdvalueto0%.
Low-Low Alarm Threshold (%)
TypethelimitfortheLowLowcurrentalarmstate,expressedasapercentageofthebreakersize (default = 2.5%). Forexample,theLowLowalarmthresholdfora20 Abreakeris0.5 A(i.e.,20 x 0.025). Todisablethisalarm(forallchannels)setitsthresholdvalueto0%.
Latching alarm examples
Example 1
1. CurrentrisesaboveLL(lowlowalarmthreshold)thisstartsthezerocurrentalarmONtimer.
2. CurrentdropsbelowLLbeforethezerocurrentalarmONtimeperiodends,soalarmingisnotenabled. ThezerocurrentalarmONtimerisreset.
3. CurrentrisesaboveLL thisstartsthezerocurrentalarmONtimer.
-
7/24/2019 ION Setup Device Configuration Guide
59/72
PowerLogic ION Setup device configuration guide Chapter 5 - BCPM (Branch circuit power meter)
2009 Schneider Electric. All rights reserved. Page 59
4. Currentremainsabovethelowlowalarmthreshold,beyondthetimeperiodspecifiedbythezerocurrentalarmONtimesettingthisenablesthelatchingalarms(alllatchingalarmsarearmed).
5. CurrentrisesaboveH(highalarmthreshold)thisstartsthehighalarmdelaytimer.
6. Current
rises
above
HH
(high
high
alarm
threshold)
this
starts
the
high
high
alarmdelaytimer.
7. CurrentdropsbelowHHbeforethehighhighalarmdelayperiodends,sothehighhighalarmdelaytimerisreset.
8. Highalarmislatchedattheendofthehighalarmdelaytimeperiod.
Example 2
1. CurrentrisesaboveLL(lowlowalarmthreshold)thisstartsthezerocurrentalarmONtimer.
2. Currentremainsabovethelowlowalarmthreshold,beyondthetimeperiodspecifiedbythezerocurrentalarmONtimesettingthisenablesthelatching
alarms(alllatchingalarmsarearmed).
3. CurrentdropsbelowL(lowalarmthreshold)thisstartsthelowalarmdelaytimer.
4. CurrentdropsbelowLL(lowlowalarmthreshold)thisstartsthelowlowalarmdelaytimerandthezerocurrentalarmdelaytimer.
5. LowalarmislatchedattheendoftheLdelay(lowalarmdelay)timeperiod.
-
7/24/2019 ION Setup Device Configuration Guide
60/72
Chapter 5 - BCPM (Branch circuit power meter) PowerLogic ION Setup device configuration guide
Page 60 2009 Schneider Electric. All rights reserved.
6. LowlowalarmislatchedattheendoftheLLdelay(lowlowalarmdelay)timeperiod.
7. Currentremainsbelowthelowlowalarmthreshold,beyondthetimeperiodspecifiedinthezerocurrentalarmdelaytimesetting,thuslatchingthezerocurrentalarm.
Voltage AlarmsThevoltagealarmsetupparametersdefinethealarmdelay(timer)andthreshold(limit)forvoltageinputsmonitoredbytheBCPM(ifyourBCPMmodeloptionsupportsit).
Thealarmdelaysettingdefineshowmanysecondsavoltageinputneedstobeinanalarmstate(i.e.exceedstheovervoltagealarmthreshold,orfallsbelowtheundervoltagealarmthreshold)beforethealarmisactivated. Areturntonormal(nonalarm)stateisinstantaneous,sothealarmdelaytimerisresetifthevoltagereturnstonormalstatebeforethetimerexpires.
Thealarmthresholdsettingdefinesthelimitforahighvoltageorlowvoltagealarmstate,expressedasapercentageofthebreakersize. Todisableanalarm,setitsthresholdvalueto0 (zero) Volts.
Over Voltage Delay (s)
TypethenumberofsecondsthevoltageneedstobecontinuouslyabovetheOverVoltageThresholdlevelbeforetheOverVoltagealarmisactivated.
Under Voltage Delay (s)
TypethenumberofsecondsthevoltageneedstobecontinuouslybelowtheUnderVoltageThresholdlevelbef