I NVERTERS FOR PHOTOVOLTAIC PLANTS SOLARGATE5000 An Ansaldo Sistemi Industriali S.p.A. Company

Transcript of INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The...

Page 1: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

INVERTERS FORPHOTOVOLTAIC

PLANTS

SOLARGATE5000

An Ansaldo Sistemi Industriali S.p.A.Company

Page 2: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

>> TABLE OF CONTENTS <<

> Reliable and Efficient page 03

> Solargate 5000 page 06

> Solargate 5000 Multipower Inverter page 14

> The Solargate 5000 Station page 18

> The “MIRO” Function page 24

> ARTICS Smart Energy page 28

> Control and Monitoring page 32

> Technical Specifications page 38

> The Energy Meter page 54

> The Weather Station page 56

> The Web Portal page 58

> Our services page 62

Page 3: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

2

THE ANSWERIN RENEWABLE ENERGY

>> ANSWER DRIVES <<

Page 4: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

3

>> RELIABLE AND EFFICIENT <<

The right solution for your needs

Answer Drives offers a complete range of solutions for high powergrid-connected PV plants.

Our Solargate 5000 inverter had different configurationsincluding: centralized and multipower versions

and turnkey stations.

We also provide all of the support technology including: > String boxes and subfield cabinets > Transformers > Substations with medium voltage cells > Monitoring System >Weather stations

Our solutions have been designed to obtain thegreatest quantity of power from your PV plant

enabling fast return on investments andensuring extended MTBF periods for long

lasting operation over the years.

>> Cutting Edge solutions......protecting the environment <<

Page 5: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

4

>> ANSWER DRIVES <<

Page 6: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

5

Page 7: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

6

Solargate 5000

>> SOLARGATE 5000 <<

Page 8: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

7

>> Standardization and longevity: the roots of flexibility <<

The Solargate 5000 derives from our experience in inverter manufacture for heavy industry.

The Solargate 5000 base module is, actually, our GT3000 inverter, which has been used in numerousinstallations all over the world owing to its reliability and efficiency.

Our experience in applications requiring AFE (Active Front End) solutions has enabled us to develop aproduct particularly suited for the power production industry that works with on-site distribution ofelectricity into the grid and commercial PV systems.

We believe that only the best can be expected from an industry leader: our best is supplying a solutionthat guarantees the highest level of flexibility in response to the specific demands of your system whilstensuring the longevity of our inverters.

This is achieved using a high level of standardization: Answer Drives offers its customers 2 versions ofinverters (depending on point of delivery), each available in 4 classes depending on the voltage range ofthe PV system.

In addition, our inverters have been designed with a careful choice of components to ensure the highestlevels of performance during the life cycle of your system.

Class

PV5

PV7

PV8

PV8 (option)

PV9

MPPT

200 - 400Vdc

320 - 630Vdc

430 - 760Vdc

528 - 800Vdc

540 - 950Vdc

CC (UDC max)

800V

800V

880V

1000V

1100V

AC (Uac) Three-phase

125V

202V

270V

330V

337V

Voltage range Maximum voltage Output voltage

Page 9: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

8

>> SOLARGATE 5000 <<

Page 10: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

9

Page 11: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

10

>> SOLARGATE 5000 <<

Page 12: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

11

VersionsEach class of Solargate 5000 inverters is available in two versions depending on the application and thevoltage of the grid to be supplied with power from the inverter.

Net metering Low voltage 400VL Version

Utilities Medium voltage 15/20KVM Version

Control

INVERTERClean PowerFilter

400V 50Hz

TRS

FIilter EMC

GRID

Modbus

Low voltage PVxL Version

The transformer is mounted inside of the panel only for the lowest power outputs.

*

Filter EMC

* Insulation control

DK

15/20KV 50Hz

TRS

FIilter EMC

CEI-016

GRID

Modbus

Medium voltage PVxM Version

Clean Power Filter

Control

INVERTER

*

Filter EMC

* Insulation control

Page 13: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

12

>> SOLARGATE 5000 <<

Page 14: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

13

Page 15: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

14

>> MULT I POWER <<

Solargate 5000Multipower Inverter

Page 16: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

15

>> Maximum performance......for a greater energy production <<

The Multipower version, particularly suited for roof mounted PV arrays, has been configured withindependent conversion units to allow customizations of the PV system in order to optimize theperformance during irregular insolation of the panels.

> Keeping loss of power in a faulty module to a minimum

> Greater production in case of partial shading of the PV array

> Reduction in maintenance costs owing to a unique spares kit for the installed converters

> Each module is equipped with its own MPPT to maximize the power produced

> Configuration of modules based on the system size and the number of panels used

> Module synchronization to reduce electromagnetic emissions

> DC end load circuit breaker and AC end breaker switch for each inverter module for the purpose of

enabling localized intervention whilst keeping the rest of the system in operation

840

630

420

210

101 202 303 404

Current [A]

Rated power [kW]

Page 17: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

16

>> MULT I POWER <<

Page 18: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

17

Page 19: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

18

The Solargate 5000Station

> > S T A T I O N < <

Page 20: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

19

>> The Plug&Play solution <<

The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply of mediumvoltage power to the distribution grid produced by large PV systems or solar parks.

This is an economic turnkey solution, including wired equipment and cooling system (available in twoversions: either air or water-cooled).

The station is factory tested before delivery and is ready to hook up on site to the PV system and then tothe distribution grid.

> Easy to install

> Does not require any additional structures

> Requires just the connection of the PV System and the MV distribution grid

The flexibility of the Solargate 5000 station enables the best configuration for every type of system.

Availability: single station, multiple stations with star configuration and multiple stations with ringconfiguration.

Page 21: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

20

> > S T A T I O N < <

Safety doors: each enclosure is equipped with doors with locks, for the safekeeping of the various components. The doors have tamper-proof hinges, that open outwards and anti-panic handles.

3

The enclosure with a painted and insulated carbon steel structure and raised false flooring ensures long-lasting durability(over 25 years).1

The insulation of the walls and the roof provides high thermal insulation fromthe environment.2

3

1

2

Page 22: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

21

>> Container Solargate 5000 <<

The input line room contains the MV input line panel, equippedwith an automatic general DC switch, protection relay andrelative auxiliaries, the transformer for auxiliary power supply,the UPS and an optional night time power factor correctionbank.

4

The MV/LV transformer room contains an MV/LV transformer withone or two secondaries and induced-draft cooling towers. Thetransformer room a safety lock included.

5

The LV equipment room includes the Solargate 5000 converter system with “MIRO” function for conversionsystem optimization even with low insolation levels. There are also service cabinets, air conditioners, the UTF[fiscal counter] meters that measure the electricity produced and the supervision system that monitors all systemdata from a remote location.

6

The IP54 rating guarantees the installation in any environmental conditions.

5

6

4

Page 23: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

22

> > S T A T I O N < <

Page 24: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

23

Proper operational temperature increases the service life of components (IGBTs, capacitors, boards, etc.)and therefore the reliability of the system and the efficiency of the inverters during the hottest periods,maintaining the power components (IGBTs) at a constant temperature.

Air-cooling uses industrial air conditioners with a “Free Cooling” function.

> Pure Free Cooling: with low external air temperature the conditioner acts like a normal ventilation systemwith external air exchange. The compressor is turned off.

> Assisted Free Cooling: with relatively low external air temperature the free cooling operates yet if it is notlow enough to keep the internal temperature at the required value, the compressor comes on as requiredby the temperature.

> Cooling: the compressor is running. The system acts like a regular air conditioner.

The “Free Cooling”, function, by modulating the use of the compressor, ensures reduced power consumptionfor enclosure cooling. Full power application occurs only when outside temperatures are very high.

To ensure the continuos operation, the overall cooling power for the enclosure is oversized: the systemoperates even if one of the air conditioners is out of service.

The free coolers, compared to regular ventilator fans, eliminate dust and reduce the level of humidity in theair, being potential causes of electronic equipment malfunction.

AnswerDrives has also certified the Solargate 5000 for use with water-cooling.

This cooling method improves dissipation.

The water-cooled enclosure, compared to the air-cooled version, is smaller and easier to maintain (thereare no filters to change and no liquids to top up).

An integrated water/water cooling control unit is available upon request for combined heat and powersystems.

>> Cooling System: efficiency optimisation <<

Page 25: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

24

>> “MIRO” FUNCTION <<

The “MIRO” Function

Page 26: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

The “MIRO” function significantly increases the efficiency of the system, in particular under conditions ofpartial insolation of the array and/or under poor weather conditions.

In fact, the “MIRO” enables the conversion units to be activated/deactivated according to the power to besupplied with the objective of maintaining active only the units necessary for conversion of the electricitycoming from the PV array.

Thanks to the modularity of our approach, the conversion efficiency may be optimized by activating just theminimum number of units required for the supply of the power coming from the PV strings in large systems.

In this manner, the active conversion units will work within their most efficient operational range.

The graph illustrates the increased efficiency obtainable with the “MIRO” function.

The “MIRO” function with a Master-Slave rotation system balances the operation time of all units over thelong term, reducing wear and downtimes and prolonging the inverter's life cycle.

25

>> Aim for efficiency <<

100

99

98

97

96

95

94

93

92

91

905 10 20 30 40 50 60 70 80 90 100

� � � � � � � � ��

��

Eta

Load

Mirox1Mirox2

Mirox3Mirox4

�“MIRO” Function

Page 27: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

26

>> “MIRO” FUNCTION <<

Page 28: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

27

>> Performance Optimization: the objective of the "MIRO" function <<

Page 29: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

28

ARTICS Smart Energy

> > A R T I C S < <

Page 30: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

29

>> Control at your fingertips <<

ARTICS Smart Energy is the control platform by Ansaldo Sistemi Industriali for the intelligent managementof low/medium voltage micro-networks capable of integrating traditional residential and industrial loadswith the production of renewable energy managing variability without compromising the quality of service.

The mode of operation known as “grid-connected” (the micro-network is connected to the distribution gridat a single connection point) and “island” (the micro-network is disconnected from the main grid) not onlyrequire their own independent monitoring and control system, but also a power supply system created withsmart devices, above all the inverters that input the power to the grid.

To be used within a micro-network, the inverters shall satisfy the following prerequisites, they must:> not produce EM interference that interfere with the network, especially when there are many inverters

connected> contribute to the frequency and voltage stability of the network, managing the active and reactive power

produced depending on the load requirements> maintain service even in the presence of strong network disturbances> be equipped with a communications system suitable both for the transfer of the data required for

network control to a higher-level control system in order to receive the proper commands

Page 31: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

30

> > A R T I C S < <

Making use of the experience of the parent company, Ansaldo Sistemi Industriali, Answer Drives has madeits inverters smart by including advanced functions necessary for their application within the ARTICS SmartEnergy active energy management platform.

The system includes the following features:

Power limitation in conformity with the law EEG §6 on renewableenergy and grid safety managementTo avoid short term overloads on the grid it is possible to establish themaximum amount of power the inverter will input into the grid by settinga parameter. The maximum amount, variable from 0 to 100%, isdefined by the utility provider and is transmitted to the inverter by wayof serial port.

Active power regulation according to the frequencyThe inverter automatically reduces the active power input in the event ofan increase in frequency over the established value by a parameter witha ΔP% / Hz gradient of the power available. The active power may beincreased again only if the frequency value returns below theparameter. The power gradient is set with a parameter. This functioncontributes to the stabilization of the grid frequency.

Grid support by way of reactive powerTo keep the mains voltage constant, inverters provide inductive or capacitive reactive power to the grid.Three variations may occur:

a) Fixed value for reactive power*.The utility provider defines the fixed value, set by way of a parameter, for reactive power. If the reactivepower is positive then it is of the inductive type, and when vice versa it is capacitive. Some utility providersrequire the reference value to be set at tanΦ. The tanΦ, value set by way of serial, is defined with aparameter in the -0.484 to +0.484 range corresponding to cosΦ = -0.9 to +0.9.b) Setpoint variable of reactive power according to the grid voltage VgridThe input of reactive power according to the network voltage is used to compensate the slow voltagevariations at the point of connection of the power plant to the grid.

* The reactive power value required must be taken into consideration when sizing the inverters.

P

Pn

0

Pnom Fgrid [Hz]

∆P%

Page 32: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

31

Reactive power is managed according to three parameters:

> The parameter that defines the minimum voltage variation required,causing a reactive power variation.> The parameter that establishes the reactive power variation caused by

a grid voltage variation during operation with active power at anominal level; the reactive power variation is implemented after atime that may be set.> The parameter that sets the minimum time that the voltage variation

must last to require that the correspondent reactive power variation beactivated.

Dynamic voltage control (FRT)The dynamic network support, is the control set out to ensure gridstability in case of sudden drops in voltage. This type of control is oftenindicated as Fault Ride Through.

Power plants that sustain the grid must, in case of a voltage drop, avoidunintentional disconnection so as not to cause a collapse of the grid.Reactive power input into the grid must also contribute to its support.After recovery from a malfunction, reactive power input must not begreater than the input before the fault.

ARTICS Smart Energy responds to the requisites set by MV directives and by the BDEW directive.

Q [%]

+0,31

-0,31

0 Vgrid

0

Q [%]

Vgrid

Page 33: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

32

Control and Monitoring

> > C O N T R O L < <

Page 34: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

33

Control of your PV plant is essential to ensure the maintenance of the highest possible level of powerproduction efficiency over the years, maximizing return on investment. Answer Drives provides two levels of control depending on the size and complexity of the system.

ADLog remote controlADLog is an operator terminal with data logging functions enabling the acquisition of data, results analysisand diagnostics of connected devices.ADLog has been designed to control medium and large sized PV power plants.

Features> Acquisition of data using analogue sensors> Connection of the PV system inverters and of the string boxes to the grid> Digital/analogue output control for alarm signals or external device management> The number of inputs/outputs and communications ports satisfies the requirements of the systems > Multidrop (RS485) control with data gathering on the production status of each inverter> Multidrop (RS485) local string connection boxes control, with acquisition of the process variables (voltage

and current) and operational status> Display of system information with a large LCD graphic display> Navigation and accessibility to data with a 12-button keyboard, plus 4 programmable function keys> System monitoring with alarm conditions from inverters or string control boards> Control of external devices and analogue/digital sensors> Local connection to the system network by way of Ethernet 10/1 000 Mbps port> Remote connection via GSM/GPRS for plant data transmission to the remote control system> E-mail and SMS message transmission> Internal Web Server, HTML pages navigable from a PC with an Internet browser for plant operational

data and on the status of the inverters

>> ADLog remote control <<

Page 35: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

34

> > C O N T R O L < <

Page 36: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

35

The Smart Control is based on a PLC system with a PC

The PLCs are capable of acquiring and checking all available information from the field whilst the PCensures all of the data management and processing functions including reporting.

The system is equipped with two supervision servers.

The string boxes, connected by way of Modbus RTU to the PLCs, read the current of each string.

A network analyser also assesses the AC output integrity for each individual inverter.

The GSE meters for each inverter (for point of delivery) and for auxiliaries bypass point enabling an exactand detailed calculation of production.

The weather station, equipped with “secondary standard" insolation sensors enable calculation ofperformance indexes with the highest possible precision.

>> Smart Control for large systems <<

Page 37: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

36

Smart Control performs the following functions:

PLC> System automation management (alarms, commands, etc.)> Acquisition of string box data> Acquisition of inverter data> Acquisition of the data from the different system safety features> Acquisition of MV areas data> System auxiliary management> Performance of media and integration operations for production of log data to be archived

PC> Continuity of logging owing to the hot redundancy between 2 machines> Logging calculated on a 15-minute frequency base, with daily, monthly and yearly aggregation> Logging of significant field signals every 15 minutes> Field signals reporting at any time interval> Export of log data into Excel format spread sheets> Display of the line status at all levels> Calculation of the performance indexes pursuant to the IEC 61724 standard

12000

10000

8000

6000

4000

2000

0

-20000 0,2 0,4 0,6 0,8 1,0 1,2

> > C O N T R O L < <

Page 38: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

37

> Calculation of the real time PR (Performance Ratio) and at time intervals> Calculation of the annual PR> Internal use of the PVSYST software models for the formation of the PR;> Supervisor management and configuration of all of the system's string boxes> Extended alarm management> Network diagnostics> Possible weather station readings> E-mail transmission of alarms

Other Functions> Synchronization of all devices using the NTP server> External weather station data acquisition> Remote access using dedicated software> Remote automation system maintenance (PC and PLC) with possibility of software updating

ET,LOSS

Recalculation

EG,LOSS

ES,LOSS

EW,LOSS

EM,LOSS

ESail,LOSS

ESTAND

EDC

EAC

90

81

72

63

54

45

36

27

18

9

[o]

05:00:00 08:45:45 12:31:31 16:17:16 20:03:0219:02:2011 19:02:2011 19:02:2011 19:02:2011 19:02:2011

Page 39: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

38

>> SPECIFICATIONS <<

Technical Specifications

Page 40: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

39

>> General Technical Specifications <<

Series 7 8 9

PV voltage range* UDC 320 - 630Vdc 430 - 760Vdc 540 - 950Vdc(520 - 800Vdc option)

Maximum DC voltage UDC, max 810Vdc 880Vdc 1100Vdc(1000Vdc option)

Maximum operational DC voltage UDC, max 740Vdc 820Vdc 1050Vdc

Nominal AC output voltage UAC 202Vac 270Vac 330Vac

DC voltage ripple UPP < 3%

Overvoltage protection PV end integrated, optional on grid end

Output voltage UDC 270Vca/15-20kVca (330Vca/15-20kVca option)

Type of Utility IT Grid

Grid frequency Hz 50/60

AC current distortion THDIca < 3%

Power factor cosφ > 0,99 @Pac

Auxiliary power supply 3 x 400Vac +N, 230V 1f from UPS

Protection degree EN 60529 IP54

Dimensions H = 2,9m, L = 2,4m, P = 6 - 9,1m depending on power

Operating temperature -10 ~+40 °C (> 40 °C reduced by 1% per °C max 50 °C)

Altitude Up to 1000 m a.s.l. (> 1000 m reduced by 1% for each 100 m,max 3000 m)

Relative humidity < 95% (non condensing)

Earthing kit Optional (on negative or positive pole)

User interface Back lit graphic display, 3 led, 20 keys

Low voltage EU Directive EMC 2006/95/EC

EMC Harmonized technical standard: CENELEC EN 60439-1

Harmonized technical standard: CENELEC EN 50178

Conformity EU Directive EMC 2004/1 08/EC

Legislative Decree no. 194/07

Connection to CEI 016

the grid REAL DECRETO RD 1663/2000 (Spain)

* Note: If the minimum PV voltage is greater, the AC ouput voltage can be increased in the ratio. The output power will be increased by the same ratio.

Page 41: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

40

>> SPECIFICATIONS <<

Dati di uscita

Rated Rated Maximumcurrent power power

Iac Pac PMac

A KW KW

210 73 81240 84 92302 106 116361 126 139420 147 162510 178 196610 213 235680 238 262800 280 308840 294 323

1020 357 3931220 427 4701360 476 5231530 535 589800 280 30833 22 2439 26 2948 33 3663 42 4779 53 5991 61 68

106 72 79121 82 90153 103 113

1182 123 135212 143 158

Rated Rated current power Idc Pdc PPV

A KW KW

221 75 89 252 86 101 317 108 127 379 130 152 441 151 177 536 183 215 641 219 258 714 244 287 840 287 338 882 301 355

1071 366 431 1281 438 515 1428 488 574 1607 549 646 840 287 338

68 23 27 81 28 33 101 34 41 130 44 52 164 56 66 189 65 76 221 75 89 252 86 101 317 108 127 379 130 152 441 151 177

L H P

mm mm mm

1400 2260 8001400 2260 8001800 2170 8001800 2170 8001800 2170 8001800 2170 8002000 2170 8002000 2170 8003200 2170 6003200 2170 6003200 2170 6003200 2170 6003200 2170 6004000 2170 6003200 2050 6001200 2260 6001200 2260 6001200 2170 8001200 2170 8001400 2170 8001400 2170 8001400 2170 8001400 2170 8002000 2170 8002000 2170 8002000 2170 800

OUTPUT DATA INPUT DATA DIMENSIONSMax.

recom.PV power

INVERTER

SVGT150FEPSVGT166FEPSVGT200FEPSVGT250FEPSVGT292FEPSVGT340FEPSVGT420FEPSVGT470FEPSVGT520FEPSVGT580FEPSVGT670FEPSVGT780FEPSVGT940FEPSVGT1K0FEP

SVGT045FEPSVGT053FEPSVGT066FEPSVGT086FEPSVGT108FEPSVGT125FEPSVGT150FEPSVGT166FEPSVGT200FEPSVGT250FEPSVGT292FEP

CABINET

PV7MPV7M090NPPV7M100NPPV7M130NPPV7M150NPPV7M180NPPV7M220NPPV7M260NPPV7M290NPPV7M340NPPV7M360NPPV7M430NPPV7M520NPPV7M580NPPV7M650NP

PV7LPV7L027NPPV7L033NPPV7L041NPPV7L052NPPV7L066NPPV7L076NPPV7L090NPPV7L100NPPV7L130NPPV7L150NPPV7L180NP

CABINETPV7L027NPPV7L033NPPV7L041NPPV7L052NPPV7L066NPPV7L076NPPV7L/M090NPPV7L/M100NPPV7L/M130NPPV7L/M150NPPV7L/M180NP/ PV7M360NPPV7M220NP/ PV7M430NPPV7M260NP/ PV7M520NP

INVERTERSVGT045FEPSVGT053FEPSVGT066FEPSVGT086FEPSVGT108FEPSVGT125FEPSVGT150FEPSVGT166FEPSVGT200FEPSVGT250FEPSVGT292FEP/ SVGT580FEPSVGT340FEP/ SVGT670FEPSVGT420FEP/ SVGT780FEP

Eta max Euro eta97,83% 97,18%97,79% 97,20%97,8% 97,17%97,77% 97,18%97,8% 97,23%97,85% 97,21%97,83% 97,22%97,8% 97,24%97,07% 97,62%97,02% 97,58%97,04% 97,61%97,70% 97,21%97,66% 97,22%

LOW VOLTAGE VERSION

MEDIUM VOLTAGE VERSION

Efficiency of the inverter and Clean Power filter measured without control losses. Other powers upon request.

Rated output current for low voltage version @ 400 V.

SOLARGATE 5000 PV7M Efficiency @ 650V DC

Solargate 5000 PV7M and PV7L Inverters

Page 42: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

41

Dati di uscita

Rated Rated Maximumcurrent power power

Iac Pac* PMac*

A KW KW

210 98 108240 112 123302 141 155361 169 186420 196 216510 239 262610 285 314680 318 350800 374 412840 393 4321020 477 5251220 571 6281360 636 7001530 716 787800 280 30844 30 3352 35 3965 44 4884 57 62

105 71 78122 82 90142 96 105162 109 120204 138 151244 165 181284 192 211

Rated Rated current power

Idc Pdc PPV

A KW KW

221 101 119 252 115 135 317 145 170 379 173 204 441 201 237 536 245 288 641 293 344 714 326 384 840 384 451 882 403 474 1071 489 576 1281 585 688 1428 652 767 1607 734 863 840 287 338 68 31 37 81 37 43 101 46 54 130 59 70 164 75 88 189 86 102 221 101 119 252 115 135 317 145 170 379 173 204 441 201 237

L H P

mm mm mm

1400 2260 8001400 2260 8001800 2170 8001800 2170 8001800 2170 8001800 2170 8002000 2170 8002000 2170 8003200 2170 6003200 2170 6003200 2170 6003200 2170 6003200 2170 6004000 2170 6003200 2050 6001200 2260 6001200 2260 6001200 2170 8001200 2170 8001400 2170 8001400 2170 8001400 2170 8001400 2170 8002000 2170 8002000 2170 8002000 2170 800

OUTPUT DATA INPUT DATA DIMENSIONSMax.

recom.PV power

INVERTER

SVGT150GEPSVGT166GEPSVGT200GEPSVGT250GEPSVGT292GEPSVGT340GEPSVGT420GEPSVGT470GEPSVGT520GEPSVGT580GEPSVGT670GEPSVGT780GEPSVGT940GEPSVGT1K0GEP

SVGT045GEPSVGT053GEPSVGT066GEPSVGT086GEPSVGT108GEPSVGT125GEPSVGT150GEPSVGT166GEPSVGT200GEPSVGT250GEPSVGT292GEP

CABINET

PV8MPV8M120NPPV8M140NPPV8M170NPPV8M205NPPV8M240NPPV8M290NPPV8M350NPPV8M390NPPV8M460NPPV8M480NPPV8M580NPPV8M700NPPV8M770NPPV8M860NP

PV8LPV8L037NPPV8L043NPPV8L054NPPV8L070NPPV8L090NPPV8L100NPPV8L120NPPV8L140NPPV8L170NPPV8L205NPPV8L240NP

CABINETPV8L037NPPV8L043NPPV8L054NPPV8L070NPPV8L090NPPV8L100NPPV8L/M120NPPV8L/M140NPPV8L/M170NPPV8L/M205NPPV8L/M240NP/ PV8M480NPPV8M290NP/ PV8M580NPPV8M350NP/ PV8M700NPPV8M390NP/ PV8M770NP

INVERTERSVGT045GEPSVGT053GEPSVGT066GEPSVGT086GEPSVGT108GEPSVGT125GEPSVGT150GEPSVGT166GEPSVGT200GEPSVGT250GEPSVGT292GEP/ SVGT580GEPSVGT340GEP/ SVGT670GEPSVGT420GEP/ SVGT780GEPSVGT470GEP/ SVGT940GEP

Eta max Euro eta98,08% 97,39%98,06% 97,43%98,04% 97,37%98,02% 97,42%98,05% 97,45%98,09% 97,41%98,07% 97,44%98,05% 97,44%97,46% 97,83%97,41% 97,96%97,43% 97,97%98,00% 97,45%97,93% 97,40%98,08% 97,62

LOW VOLTAGE VERSION

MEDIUM VOLTAGE VERSION

Efficiency of the inverter and Clean Power filter measured without control losses. Other powers upon request.

* See note at page 39 Rated output current for low voltage version @ 400 V.

SOLARGATE 5000 PV8M Efficiency @ Vdc 650V

Solargate 5000 PV8M and PV8L Inverters

Page 43: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

42

>> SPECIFICATIONS <<

Page 44: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

43

Dati di uscita

Rated Rated Maximumcurrent power power

Iac Pac PMac

A KW KW

170 99 109220 128 141270 158 173330 193 212400 233 257440 257 283540 315 347660 385 424800 467 514880 514 5651020 357 39374 50 5588 60 66

120 81 90143 97 106185 125 138227 154 169278 188 207337 228 250371 250 275

Rated Rated current power

Idc Pdc PPV

A KW KW

178 102 120 231 132 155 283 162 190 346 198 232 420 239 282 462 263 310 567 323 380 693 395 465 840 479 563 924 527 620 1071 366 431 92 53 62 110 63 74 150 86 101 179 102 120 231 132 155 284 162 190 347 198 232 420 239 282 462 263 310

L H P

mm mm mm

2000 2170 8002000 2170 8002000 2170 8002000 2170 8002000 2170 8002000 2170 8002000 2170 6002000 2170 6002000 2170 6002000 2170 6003200 2170 6001400 2260 8001400 2260 8001400 2260 8002000 2170 8002000 2170 8002000 2170 8002000 2170 8002000 2170 8002000 2170 800

OUTPUT DATA INPUT DATA DIMENSIONSMax.

recom.PV power

INVERTER

SVGT200KEPSVGT260KEPSVGT320KEPSVGT390KEPSVGT480KEPSVGT521KEPSVGT640KEPSVGT780KEPSVGT960KEPSVGT1K0KEP

SVGT105KEPSVGT130KEPSVGT170KEPSVGT200KEPSVGT260KEPSVGT320KEPSVGT390KEPSVGT480KEPSVGT521KEP

CABINET

PV9MPV9M120NPPV9M160NPPV9M190NPPV9M230NPPV9M280NPPV9M310NPPV9M380NPPV9M470NPPV9M560NPPV9M620NP

PV9LPV9L060NPPV9L075NPPV9L100NPPV9L120NPPV9L160NPPV9L190NPPV9L230NPPV9L280NPPV9L310NP

CABINETPV9L060NPPV9L075NPPV9L100NPPV9L/M120NPPV9L/M160NPPV9L/M190NP/ PV9M380NPPV9L/M230NP/ PV9M470NPPV9L/M280NP/ PV9M560NPPV9L/M310NP/ PV9M620NP

INVERTERSVGT105KEPSVGT130KEPSVGT170KEPSVGT200KEPSVGT260KEPSVGT320KEP/ SVGT640KEPSVGT390KEP/ SVGT780KEPSVGT480KEP/ SVGT960KEPSVGT521KEP/ SVGT1K0KEP

Eta max Euro eta97,14% 97,31%97,13% 97,39%97,09% 97,46%97,00% 97,48%97,00% 97,48%97,13% 97,63%97,10% 97,33%97,07% 97,39%97,63% 97,65%

LOW VOLTAGE VERSION

MEDIUM VOLTAGE VERSION

Efficiency of the inverter and Clean Power filter measured without control losses. Other powers upon request.

Rated output current for low voltage version @ 400 V.

SOLARGATE 5000 PV9M Efficiency @ 812 V DC

Solargate 5000 PV9M and PV9L Inverters

Page 45: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

44

>> SPECIFICATIONS <<

Solargate 5000 Station with air cooling

PV Voltage range UDC 430 - 760Vdc (528-800Vdc option)Maximum DC voltage UDC, max 880V (1000Vdc option)Maximum operational DC voltage UDC, max 820VDC voltage ripple UPP < 3%Overvoltage protection PV end integrated, optional on grid endOutput voltage UAC 270Vca/15-20kVca (330Vca/15-20kVca option)Type of Utility IT GridGrid frequency Hz 50/60AC current distortion THDIca < 3%Power factor cosφ > 0,99 @PacAuxiliary power supply 3 x 400Vac +N, 230V 1f from UPSProtection degree EN 60529 IP54Dimensions H = 2,9m, L = 2,4m, P = 7,6 - 10,7m depending on powerOperating temperature -10 ~+40°C (> 40°C reduced by 1 % per °C max 50°C)Altitude Up to 1000 m a.s.l. (> 1000 m reduced by 1% for each 100 m,

max 3000 m)Relative humidity < 95% (non condensing)User interface Back lit graphic display, 3 led, 20 keys

Low voltage EU Directive EMC 2006/95/ECEMC Harmonized technical standard: CENELEC EN 60439-1

Harmonized technical standard: CENELEC EN 50178Conformity EU Directive EMC 2004/1 08/EC

Legislative Decree no. 194/07Connection to CEI 016the grid REAL DECRETO RD 1663/2000 (Spain)

Dati di uscita

Rated Rated Maximumcurrent power power

Iac Pac PMac

A KW KW

1020 477 5251220 571 6281530 716 7872040 954 10502440 1142 12563060 1432 1574

Rated Rated current power

Idc Pdc PPV

A KW KW

1071 489 576 1281 585 688 1606 734 863 2142 978 1152 2562 1170 1376 3212 1468 1726

OUTPUT DATA INPUT DATAMax.

recom.PV power

CODECN8M580N25FCN8M700N25FCN8M860N25FCN8M1K1N30FCN8M1K4N30FCN8M1K7N30F

ENCLOSURE25 feet25 feet35 feet35 feet35 feet35 feet

SIZE500kW600kW800kW

1000kW1300kW1700kW

5% 10% 20% 30% 50% 80% 100% eta[%]CN8M580-1K1 92,62 95,55 97,05 97,53 97,87 98,00 97,96 97,45CN8M700-1K4 92,71 95,00 97,06 97,54 97,85 97,93 97,91 97,40CN8M860-1K7 92,62 95,55 97,05 97,53 97,87 98,00 97,96 97,45

Efficiency of the inverter and Clean Power filter measured without control losses.Euro-eta: 0.03x [5%]+ 0.06x• [10%] + 0.13x• [20%] + 0.10x• [30%]+ 0.48x• [50%]+ 0.20x• [100%].

Note: Efficiency of the supplied Answer Drives transformer at rated power ≥ 99%.Efficiency is indicated without the MIRO function.

Efficiency [%], Pdc/ Pdc_nom @ Vdc (650V) Euro THE SOLARGATE 5000 STATION

SOLARGATE 5000

Page 46: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

45

Solargate 5000 Station with water-cooling

PV voltage range UDC 430 - 760Vdc (528-800Vdc option)Maximum DC voltage UDC, max 880V (1000Vdc option)Maximum operational DC voltage UDC, max 820VDC voltage ripple UPP < 3%Overvoltage protection PV end integrated, optional on grid endOutput voltage UAC 270Vca/15-20kVca (330Vca/15-20kVca option)Type of Utility IT GridGrid frequency Hz 50/60AC current distortion THDIca < 3%Power factor cosφ > 0,99 @PacAuxiliary power supply 3 x 400Vac +N, 230V 1f from UPSProtection degree EN 60529 IP54Dimensions H = 2,9m, L = 2,4m, P = 6 - 9,1m depending on powerOperating temperature -10 ~+40 °C (> 40 °C reduced by 1% per °C max 50 °C)Cooling method Standard version Water/Air

Cogeneration Water/WaterRelative humidity < 95% (non condensing)User interface Back lit graphic display, 3 led, 20 keys

Low voltage EU Directive EMC 2006/95/ECEMC Harmonized technical standard: CENELEC EN 60439-1

Harmonized technical standard: CENELEC EN 50178Conformity EU Directive EMC 2004/1 08/EC

Legislative Decree no. 194/07Connection to CEI 016the grid REAL DECRETO RD 1663/2000 (Spain)

Dati di uscita

Rated Rated Maximumcurrent power power

Iac Pac PMac

A KW KW

1020 477 5251530 716 7871830 856 9413060 1431 1575

Rated Rated current power

Idc Pdc PPV

A KW KW

1071 489 576 1606 734 8631921,5 878 1033 3213 1467 1728

OUTPUT DATA INPUT DATAMax.

recom.PV power

CODECN8M580N20WCN8M860N25WCN8M1K0N25WCN8M1K7N30W

ENCLOSURE20 feet25 feet25 feet30 feet

SIZE500kW800kW

1000kW1500kW

5% 10% 20% 30% 50% 80% 100% eta[%]CN8M580N20W 92,6 95,6 97,1 97,5 97,9 98,0 98,0 97,5CN8M860N25W 92,6 95,6 97,1 97,5 97,9 98,0 98,0 97,5CN8M1K0N25W 92,7 95 97,1 97,5 97,9 97,9 97,9 97,4CN8M1K7N30W 92,6 95,6 97,1 97,5 97,9 98,0 98,0 97,5

Efficiency of the inverter and Clean Power filter measured without control losses.Euro-eta: 0.03x [5%]+ 0.06x• [10%] + 0.13x• [20%] + 0.10x• [30%]+ 0.48x• [50%]+ 0.20x• [100%].

Note: Efficiency of the supplied Answer Drives transformer at rated power ≥ 99%.Efficiency indicated without the MIRO function.

Efficiency [%], Pdc/ Pdc_nom @ Vdc (650V) Euro STATIONSOLARGATE 5000

SOLARGATE 5000

Page 47: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

46

The string box enables the connection of several strings in parallel.

The current from each string is measured by way of a transducer and any faults are immediately detectedby the monitoring system with fast identification of any problem in the panels.

Each box has overvoltage protection installed to protect the inverter from overvoltage peaks.

The output DC switch facilitates maintenance operations on the section with the system still running inperfect safety.

Thanks to the double insulation and the IP65 protection rating, the box ensures the highest level ofprotection both for the operator and for the internal equipment.

For rooftop installation, generally the authorities require that the string box be equipped with an output DCswitch with a remote trip so as to respond to heightened safety requirements.

This string box may be supplied with a DC switch equipped with a minimum voltage coil to separate thePV generator from the inverter (Options are to be requested during the order).

> System for monitoring andidentifying any faults in the strings.

> Input peak overvoltage inverterprotection.

> Fuses on the positive and negativepoles.

> Simplified maintenance with theoutput DC switch with opening under load.

>> String boxes <<

>> SPECIFICATIONS <<

Page 48: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

47

Case material UV ray resistant polycarbonate

Assembly Wall mount

String fuses 10A (900/1000Vdc)

Max. input current (IPV, max) 8A (>8A upon request)

String cable cross section 1,5 - 6 mm2

Maximum output cable cross section Up to 2x35 -120 mm2

Earth wire cross section 25 - 35 mm2

Anti-inversion diodes yes

Power supply 55VDC (-15%, +30%) 200mA (standard)

Output contact surge arrester intervention NC [1,5 mm2]

Output contact switch status NC [1,5 mm2]

Multi-contact MC4 connectors Standard (double - optional)

DC overvoltage protection (dischargers) yes

Protection rating IP 65

Operating temperature – 25°C +50°C

Relative humidity From 0 to 95%

Altitude 1000 m s.l.m.

Anti theft Optional

Data communications Modbus RTU

Analogue and digital inputs 0÷1 0V/4-20mA/PT1 00/programmable

SizePVS 8S 08NNPVS 8S 16NNPVS 9S 08NNPVS 9S 16NN

Number of strings (parallel)

8168

16

PV Voltage range

0 - 760 V0 - 760 V0 - 950 V0 - 950 V

Max voltage (Ucc, max)

880 V880 V1000 V1000 V

Max output current (OPV, max)

64 A128 A64 A

128 A

L A P920 388 2021523 388 202920 388 2021523 388 202

Dimensions (mm)

Page 49: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

48

>> SPECIFICATIONS <<

Page 50: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

49

Page 51: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

50

>> SPECIFICATIONS <<

Page 52: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

51

The QPSC parallel cabinet sub-field unites the DC output lines for 4-5 PV plant string boxes enabling connectionto the Solargate 5000 cabinet with a large cross-section cable in order to ensure a reduced losses.

Two versions are available:

IP55 suitable for outdoor installation in protected areas (e.g., under a shed roof). Dimensions: 800 × 1200 × 400 mm. (l × h × d).

>> The QPSC sub-field parallel cabinet <<

Fuses (1 pair) for each input

Sorge voltage arrester

Output DC Switch with opening under load

50 Vdc-9 A power supply for the string boxes

1 microswitch for each input fuse

A current transducer and a GPVCA* control board

A power supply for field sensors (optional)

Basic Advanced

*The board collects data from the QPSC and makes them available to the RS485 serial with Modbus RTU protocol

Page 53: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

52

>> SPECIFICATIONS <<

*Other voltage values are supplied by request.

Page 54: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

AnswerDrives supplies high efficiency medium voltage-cast resin transformers with power ratings up to 2MVA. The transformers are available with one, two or three secondaries. The secondary voltages mirrorthe function of the inverter output voltage: 125 V, 202 V, 270 V and 337 V *.

> Optional electronic control unit and temperature, alarm set configuration and trip display> Contact in output for fault sensor fault signalling and configurable contact for cooling fan control

53

>> Medium voltage transformers <<

Primary voltage 15-20KV

Frequency 50Hz/60Hz

Vector Group Dyn1 1

Primary insulation class 24/50/95KV

Secondary insulation class 1,1/3 KV

D.C. voltage at 75 °C (AN) 6,0%

MV output 3 M12 brass shanks

LV output with plate

Winding temperature sensor 3 PT100

MV output side insulators Yes

Primary regulation field +/-2x2,5%

Insulation material class F/F

Environmental class (EN 60076) E2

Climate class (EN 60076) C2

Partial discharge level < 1 0pC

Earthing plates 2

Fire resistance (EN 60076) F1

K ANSI/IEEE 57.110 Factor 1

Ambient temperature -25 ÷ +40 °C

Humidity 80%

Installation ≤1000 m s.l.m.

Protection rating IP00 (indoor installation)

Trucks 2

Wheels movable obliquely 4

Hoisting eyebolts 4

Page 55: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

54

> > M E T E R < <

Energy Meter

Page 56: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

55

A static meter with LV connection is foreseen for measurement of subsidized electricity.

The meter may be mounted onto the Solargate 5000 cabinet or in a separate box.

The meter is to be checked and certified with a cumulative certification +CT and VT including tax duty.

Supplied standard are: UTF, CT e VT proof terminal block for BT Cl 0.5 (with UTF certificate), GSMMODEM power supply, stylus antenna, terminal board and wiring for connection to meter.

The meter, besides in situ reading, can acquire the impulses from one or more meters.

In systems with LV/MV transformers with two secondaries, two meters are required, one of which will bethe master acquiring the reading of the second so as to provide a single electricity reading.

> ENEL Approved> Activite energy accuracy in compliance with EN50470-3:

class C> Conformity to Legislative Decree no. 22 dated

02/02/2007 (Implementation of the MID Directive)> Indirect insertion (by way of CT and VT)> Rated Frequency 50/60 Hz> Auxiliary power supply (48 - 240 V DC or 57 - 415 V AC

auto-ranging)> Auxiliary and impulse inputs and outputs in complete con-

figuration> Communication ports 1 RS232 + 1 RS485> CE Marking

>> For subsidized energy metering <<

Page 57: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

56

> > W E A T H E R < <

The Weather Station

Page 58: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

57

The weather station is ideal for users who give great importance to the total analysis of performance evenon the PV power generation side.

Weather conditions influence PV electricity production to a great degree, yet this does not mean thatefficiency cannot be optimized.

The Answer Drives weather station uses a multi-function sensor, which, besides module insolation andtemperature data, also manages an ambient temperature sensor and an anemometer for the purpose ofmaking even more precise calculations on the operation of the PV system.

The data gathered by the station enable the calculation of the nominal power provided by the currentinsolation and by the module temperatures and the comparison of this with the actual power measured bythe inverters. Significant downward shifts signal faulty system operation.

In this manner shaded areas, dirty panels and hard to find power reductions — due, for example, to thedegradation of one of the panels — can be identified.

The sensor output is in RS485 with the Modbusprotocol, particularly indicated in applicationswhere the sensors are far from the data logger.Just make the simple connection of the station,by way of the Data Logger serial port, whichwill then transmit the data received to a PC orto an Internet site for further processing.

For users with less weighty needs, the stationmay be provided in a basic version that willmeasure the insolation, ambient temperatureand module temperatures.

>> Don't let the weather put you off <<

Page 59: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

58

>> WEB PORTAL <<

The Web Portal

Page 60: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

59

Answer Drives’ web portal service is available to customers. This service enables a remote check on PVsystems via the Web with acquisition of data relative to the plant.

The user accesses the site using a personal password ensuring a high level of confidentiality and securityfor the data.

The user will be capable of checking on the efficiency of the system in terms of electricity production and interms of economic earnings whilst diagnostics on the entire plant may be run at any moment duringoperation.

Management service of any alarms warns staff in regard to the possibility of a malfunction either by theweb or SMS enabling a timely intervention on the plant.

The service interface is intuitive and makes data recovery easy.

>> Data anywhere <<

TOTAL PRODUCTION (from the meter, if present)

Total electricity production [kWh]: 691.070,6

Total C02 savings [Kg]: 380.088,8

Daily electricity production [kWh]: 6.481,1

CURRENT SYSTEM DATA (last update Section 1 15:00)

Power input to the grid [kW]: 662,16

Maximum Power input to the grid [kW] (at 13:15): 799,42

Electricity produced [kWh]: 6.481,10

CO2 saved [Kg]: 3.564,61

Page 61: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

60

>> WEB PORTAL <<

0

2.000

1.000

3.000

4.000

5.000

6.000

7.000

8.000

9.000

06 07 08 09 10 11 12 13 14 15 16 17 1918

INV 1 INV 2 TOTAL SYSTEM

G

[kW

h/h]

Daily and Hourly Production Graph

> Name: San Vito> City: San Vito dei Normanni> Latitude [°]: 40.658> Longitude [°]: 17.708> Number of sections (= datalogger) system: 1> Total inverters installed: 2> Rated power installed [kWp]: 1000> Service start date: 28/07/2010

>> Actual Case: operational statistics <<

Page 62: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

61

0

1.000

2.000

3.000

4.000

5.000

6.000

7.000

8.000

9.000

10.000

1 2 3 4 5 6 7 8 9 10111213141516171819202122232425262728293031

Complete Electricity Production System

Weekly Electricity Production Graph (system)

Monthly Electricity Production Graph (system)

0

1.000

2.000

3.000

4.000

5.000

6.000

7.000

06/03/2011 08/03/2011 10/03/2011DAY

12/03/2011 14/03/2011

ELEC

TRIC

ITY

[kW

h]

Complete Electricity Production System

Page 63: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

62

> > S E R V I C E S < <

Our services

Page 64: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

63

Pre-Sales SupportAnswer Drives can provide technical consultancy and commercial estimates.

Installation and Start UpOur team of specialist technicians at Answer Drives is operative at an international level to assist youduring installation and commissioning.

After Sales SupportThrough our web portal our technicians have access to information relative to your system and are able totake your place in its management and control.

Maintenance ContractsAnswer Drives offers a complete range of customised service contracts with varying durations makingavailable the experience and professionalism of our highly qualified technical personnel. Our service guarantees continuing efficiency of your system.

Warranty ExtensionIt is possible to continue to make use of the warranty privileges by activating the extension of the warrantyperiod.

>> Reliability even in the management of your plant <<

Page 65: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

CORPORATEAnswer Drives S.r.l. Viale Sarca 336 I - 20126 MilanoPhone +39 02 6445 1Fax +39 02 6445 4401

MANUFACTURING FACILITYS.S. 11 - Via Cà Sordis, 4I-36054 Montebello Vicentino (VI)Phone +39 0444 449 268Fax +39 0444 449 276www.answerdrives.com

CUSTOMER SERVICE AND SUPPORTS.S. 11 - Via Cà Sordis, 4I-36054 Montebello Vicentino (VI)Phone +39 0444 449 226Fax +39 0444 449 276www.answerdrives.com

REPRESENTATIVE OFFICE CHINASilver Tower Rm. 3208 No. 2Dongsanhuan Beilu Chao Yang DistrictBeijing 100027Phone +86 10 6410 6601

+86 10 6410 6602Fax +86 10 6554 4493

ANSALDO SISTEMI INDUSTRIALI INTERNATIONAL NETWORK SUPPORTING ANSWER DRIVES

CHINAASI Industrial Systems Beijing Co. Ltd. (subsidiary of Ansaldo Sistemi Industriali S.p.A.)Room 3206 – 3208 / Beijing Silver TowerNo. 2 Dong San Huan Bei Road-Chaoyang DistrictBeijing People’s Republic of ChinaPhone +86 10 6554 4490/91/92 Fax +86 10 6554 4493

FRANCEAnsaldo Sistemi Industriali SAZ.I. du Buisson, Rue de la PoudrièreF-42230 Roche-La-MolièrePhone +33 4 77907600Fax +33 4 77907629

GERMANYAnsaldo Sistemi Industriali GmbHIm Teelbruch 104D-45219 Essen - KettwigPhone +49 (0) 2054 104980 Fax +49 (0) 2054 1049811

ROMANIAAnsaldo Sistemi Industriali RO235b Darzei II St. - Crevedia, Jud. Dambovita137180 RomaniaPhone +40 374 00 33 54Fax +40 757 71 02 04

RUSSIAAO Ansaldo - VEIKrasnokazarmennaya Ul 12111250 Moscow, RussiaPhone +7 495 3619163Fax +7 495 2734391

Ansaldo Sistemi Industriali – Moscow OfficeProezd zavodaSerp i Molot 6/1111250 Moscow – RussiaPhone +7 495 6623752Fax +7 495 6623750

THAILANDAnsaldo Sistemi Industriali SpA Thailand BranchMuang Thai-Phatra Office Tower II 24th Fl252/119 Rachadaphisek Rd, HuaywangBangkok 10310 ThailandPhone +66 2 6932930Fax +66 2 6932934

USAAnselectric LLCan Ansaldo Sistemi Industriali SpA Company4900 Woodway Dr., Suite 970Houston, Texas 77056 USAPhone +1 832 214 4185Fax +1 713 583 7775

VIETNAMASI Industrial Systems - Representative Office of AnsaldoSistemi Industriali S.p.A.Room 702 – Floor 7th No. 3 Mai Hac De street, Hai Ba Trung district - HanoiPhone +84 4 394 47415Fax +84 4 394 47415

For information on the sales office or sales representative nearest you contact us at: [email protected]

Page 66: INVERTERS FOR PHOTOVOLTAIC PLANTS An Ansaldo Sistemi Industriali S.p.A… · 2012-09-21 · The Solargate 5000 station by Answer Drives is an integrated PV power plant for the supply

8000

0089

31

www.answerdrives.com