Interfacing Fire Alarm , Sprinkler and Elevator System
-
Upload
kanate-sangmanee -
Category
Documents
-
view
239 -
download
0
Transcript of Interfacing Fire Alarm , Sprinkler and Elevator System
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
1/113
Interfacing Fire Alarm,
Sprinkler and Elevator Systems
Bruce FraserFraser Fire Protection [email protected]
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
2/113
Agenda:
Elevator Recall and Power Shut-down
Historical Perspective
Where we are today, code-wise
Look at specific code sections
Discuss some of the issues
Where we appear to be headed
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
3/113
ASME A17.1
P hase I - Em ergency Reca l l Ope ra t ion
The operation of an elevator wherein it is automatically
or manually recalled to a specific landing and removed
from normal service because of activation of firefighters
service
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
4/113
ASME A17.1
Pow e r Shu t dow n ( shun t tr ip )
Mainline elevator power is disconnected from the elevator
to eliminate potential problems as a result of sprinkler
actuation in the hoistway or elevator machine room
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
5/113
Elevator Recall: Historical Perspective
1973 ASME A17.1b(supplement to the 1971 Code)
Purpose:
Prevent people from using elevators
Allow firefighters to account for elevators
Stage equipment (hose lines, air tanks, etc.)
Evacuate occupants with mobility restrictions
Prevent cars from being called to the fire floor
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
6/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
7/113
Identified a Recall Level
Both Manual and Automatic Recall
Key Switch (only by firefighters)Smoke Detectors in Lobbies
Travel of 25 above or below designated level
1981 introduced the Alternate Level
Elevator Recall: Historical Perspective
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
8/113
1984 introduced only lobby and machine room
detectors were to initiate recall
A17.1 referred users to NFPA 72E, Automatic Fire
Detectors
NFPA first mentions A17.1 requirements in 1987 edition of
NFPA 72A, under Elevator Recall for Firefighters Service
Elevator Recall: Historical Perspective
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
9/113
Two elevator zone circuits now required to be
terminated at the associated elevator controller
In 1989, A17.1 required smoke detectors in hoistways
only when hoistways had sprinklers
A17.1b, 1992 Supplement drops the 25 ft. criterion
now applies to a l l automatic elevators regardless of
travel distance
Elevator Recall: Historical Perspective
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
10/113
A third control circuit was added to provide a warning
of fire in the hoistway or elevator machine room
The 2000 A17.1 was harmonized with the CanadianB44 Elevator Safety Standard
NFPA 72 [2002] and A17.1 [2004] now both address
new technology elevators machine room-less
elevators
Elevator Recall: Historical Perspective
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
11/113
Elevator Shunt Trip: Historical Perspective
First introduced in ASME A17.1 - 1984
Purpose:
Remove main-line power prior to sprinkler activation
Prevent elevators from moving/operating dangerously
No t e :
the requirement
does not include circuits for ventilation,
in-car lights and communication, pit receptacles and lights, etc.
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
12/113
A17.1 applies to all new elevator installations
A17.3 (where adopted) applies to existing elevators
A17.3 re: Firefighters Service
3.11 .3 F i re f igh te rs Se rv i ce
Elevators shall conform to the requirements of
ASME/ANSI A17.11987 Rules 211.3 through 211.8
(see Appendix C) unless at the time of installation or
alteration it was required to comply with a later edition of
A17.1.
Recall & Shunt Trip: Historical Perspective
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
13/113
Applicable Codes
Elevator
& Escalator
Safety Code
ASME/ANSI
A17.1/B44
Building
Codes and
NFPA 101
NFPA 13
NFPA 70
NFPA 72
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
14/113
ASM E A17 .1
3 4 Y ea r Cy cl e w i th Y ea r ly Addenda
A17 .1 - 20 04
A17 .1a - 200 5A17 .1S - 200 5
A17 .1 - 20 07
A17 .1a - 200 8
A17 .1b - 200 9
A17 .1 20 10
Jus t in t roduced 3 -yea r cyc le
N F PA 72 an d N F PA 13
3 Y ea r Cyc le
20 07 , 20 10 , 201 3 e t c .
Out of Sync Codes
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
15/113
Cant find all the information in one place!
Confusion?
M us t u se A1 7 .1 , N FPA 72 an d N FPA 1 3
t oge th e r
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
16/113
Heres where to find them!
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
17/113
Sec t i on 2 .27
Em ergency Opera t i on and S igna l i ng Dev i ces
2.27.3.2 Phase I Emergency Recall Operation
by Fire Alarm Initiating Devices
ASME A17.1 - 2010
Note : Section2 .27 applies to Electric Elevators and section 3.27
applies to Hydraulic Elevators section 3.27 says refer to 2.27.
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
18/113
Sec t ion 2 .8
Equ ipm ent in Ho i s tw ays , M ach ine ry Spaces ,
M ach ine R oom s , Con t ro l Spaces and Con t ro l Room s
2.8.3.3.2
(Shunt Trip / Power Disconnect requirement)
ASME A17.1 - 2010
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
19/113
NFPA 72 - 2010
23.17.1 Emergency Elevator Operations Emergency
elevator operations shall meet the requirements of Sections
21.3, 21.4, 21.5, and 21.6.
23 .17 P ro tec ted P rem ises F i re Sa fe ty Func t i ons
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
20/113
Chap te r 21 Em ergency Con t ro l Func ti on s and
In te r faces
21 .3* E leva to r R eca l l f o r F ire f igh te r s Serv i ce
21 .4 E leva to r Shu tdow n
21 .5 F i rs t R espond ers Use E leva to r s
21 .6 E leva to r s fo r Occup ant -Con t ro l led Evacua t ion
NFPA 72 - 2010
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
21/113
Chap te r 8 I n s ta l la t ion R equ i rem en t s
8 .15 Spec ia l S i tua t ions .
8 .15.5 Elevator Hoistways and Machine Rooms.
NFPA 13 - 2010
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
22/113
DesignatedLevel
AlternateLevel
Elevator
MachineRoom
SimplifiedTractionElevator
System
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
23/113
Heat Detector
Smoke Detector
Sprinkler
Detector Operation
Recall to Alternate Level
Recall to Designated LevelFlash FF Helmet in Car (warning)
Power Disconnect (shunt trip)
23
4
1
DesignatedLevel
AlternateLevel
ElevatorMachine
Room
1
2
34
2
2
1
SimplifiedHydraulicElevator
System
43
1
23
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
24/113
DesignatedLevel
AlternateLevel
Machine room-lessElevators
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
25/113
Machine room-lessElevators
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
26/113
2.27.3.2.1In jurisdictions not enforcing the NBCC, fire alarm
initiating devices used to initiate Phase I Emergency Recall
Operation shall be installed in conformance with the requirements
of NFPA 72, and shall be located
(a) at each floor served by the elevator
(b) in the associated elevator machine room, machinery space
containing a motor controller or electric driving machine, control space,or control room
(c) in the elevator hoistway, when sprinklers are located in thosehoistways.
ASME A17.1 - 2010
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
27/113
NFPA 72 - 2010
21 .3 E levato r R eca l l fo r F i re figh ters Serv i ce
21.3.1All initiating devices used to initiate firefighters
service recall, shall be connected to the building fire alarm
system.
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
28/113
NFPA 72 - 2010
21.3.2* In facilities without a building fire alarm system,
initiating devices used to initiate firefighters service recall
shall be connected to a dedicated function fire alarm system
control unit that shall be designated aselevator recall control
and supervisory control unit,permanently identified on the
dedicated function fire alarm control unit and on the record
drawings.
21 .3 E levato r R eca l l fo r F i re figh ters Serv i ce
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
29/113
NFPA 72 - 2010
21.3.3 Unless otherwise required by the authority having
jurisdiction, onlythe elevator lobby, elevator hoistway, and
the elevator machine room smoke detectors shall be
used to recall elevators for firefighters service.
21 .3 E levato r R eca l l fo r F i re figh ters Serv i ce
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
30/113
NFPA 72 - 2010
21.3.6 Smoke detectors shall not be installedin
unsprinkleredelevator hoistways unlessthey are
installed to activate the elevator hoistway smoke
relief equipment.
21 .3 E levato r R eca l l fo r F i re figh ters Serv i ce
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
31/113
NFPA 72 - 2010
21.3.7 If ambient conditionsprohibit installation of
automatic smoke detection, other automatic fire detection
shall be permitted.
21 .3* E levato r R eca l l fo r F i re figh ter s Serv i ce
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
32/113
NFPA 72 - 2010
17 .7 Sm ok e-Sens ing F ir e De tec to r s
17.7.1.8* Unless specifically designed and listed for the
expected conditions, smoke detectors shall not be installed ifany of the following ambient conditions exist:
(1) Temperature below 32F
(2) Temperature above 100F
(3) Relative humidity above 93 percent
(4) Air velocity greater than 300 ft/min
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
33/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
34/113
21.3.5*A lobby smoke detector shall be located on the
ceiling within 21 ft. of the centerline of each elevator
door within the elevator bank under control of the
detector.
NFPA 72 - 2010
21 .3 E levato r R eca l l fo r F i re figh ters Serv i ce
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
35/113
Sm ok e De tec t o r Loca t ion
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
36/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
37/113
21.3.5* A lobby smoke detector shall be located on the
ceiling within 21 ft. of the centerline of each elevator
door within the elevator bank under control of the
detector.
NFPA 72 - 2010
21 .3 E levato r R eca l l fo r F i re figh ters Serv i ce
Excep t i on :
For lobby ceiling configurations exceeding 15 ft in
height or that are other than flat and smooth, detector
locations shall be determined in accordance with Chapter 17.
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
38/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
39/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
40/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
41/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
42/113
17.7.3.1.4* If the intent is to initiate action when smoke/fire
threatens a specific object or space, the detector shall be
permitted to be installed in close proximity to that object or
space.
17 .7 .3 Loca t i on and Spac ing
NFPA 72 - 2010
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
43/113
A.17.7.3.1.4 There are some applications that do not require
full area protection, but do require detection to initiate action
when specific objects or spaces are threatened by smoke or fire
such as at elevator landings that have ceilings in excess of 15 ft.
and for protection of fire alarm control units. In high ceiling
areas, to achieve the desired initiation such as for elevator recall
and protection of FACUs, detection should be placed on the wallabove and within 60 in. from the top of the elevator door(s) or
FACU.
NFPA 72 - 2010
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
44/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
45/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
46/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
47/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
48/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
49/113
NFPA 72 - 2010
21.3.9Actuation from the elevator hoistway, elevator machine
room, elevator machinery space, elevator control space, or
elevator control room smoke detectors shall cause
separate and distinct visible annunciationat the building fire
alarm control unit and at required annunciators to alertfire fighters and other emergency personnelthat the elevators
are no longer safe to use.
21 .3 E levato r R eca l l fo r F i re figh ters Serv i ce
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
50/113
2 .27 .3 .2 Phase I Emergency Reca l l Opera t i on by
F ir e A l a rm In i t ia t i ng D ev i ces
2.27.3.2.6 When a fire alarm initiating device in the machine
room, control space, control room or hoistway initiates Phase 1
Emergency Recall Operation, the visual signal shall
illuminate intermittently onlyin a car(s) with equipment in that
machine room, control space, control room or hoistway .
ASME A17.1 - 2010
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
51/113
FIG . 2 .27 .3 .1 .6(h)
V i sua l S igna l
W hen f l a sh ing , ex i t e leva to r
or
ASME A17.1 - 2010
2 .27 .3 F i re f igh te r s Em ergency Opera t i on -
Au tom at i c E l eva to r s
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
52/113
21.3.12.1 Designated Level Recall. For each elevator
or group of elevators, an output shall be provided to
signal elevator recall to the designated level in response
to the following:
NFPA 72 - 2010
(1)Activation of smoke detectors located at any elevator
lobby served by the elevator(s) other than the lobby at the
designated level.
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
53/113
21.3.12.1 Designated Level Recall. Contd.
NFPA 72 - 2010
(2)Activation of smoke detectors located at any elevator
machine room, elevator machinery space, elevator control
space, or elevator control room serving the elevator(s) except
where such room or spaces are located at the designated level.
(3)Activation of smoke detectors located in the elevator
hoistway serving the elevator when sprinklers are located in
the elevator hoistway unless otherwise specified in
21.3.12.2(3).
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
54/113
21.3.12.2 Alternate Level Recall. For each elevator or
group of elevators, an output shall be provided to signal
elevator recall to the alternate level in response to the
following:
NFPA 72 - 2010
(1)Activation of smoke detectors located at the
designated lobby served by the elevator(s).
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
55/113
21.3.12.2 Alternate Level Recall. Contd.
NFPA 72 - 2010
(2)Activation of smoke detectors located in the elevator
machine room, elevator machinery space, elevator control
space, or elevator control room serving the elevator(s) if such
rooms or spaces are located at the designated level.
(3)*Activation of initiating devices identified in 21.3.12.1(3) if
they are installed at or below the lowest level of recall in the
elevator hoistway and the alternate level is located above the
designated level.
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
56/113
Designated and Alternate Recall Level
(1) All elevator lobby smoke detectors except those on the designatedlevel return cars to the designated level.
(2) The elevator lobby smoke detector(s) on the designated level willcause cars to return to the alternate level.
(3) Elevator machine room smoke detectors return cars to thedesignated level unless
The machine room is on the designated level, in which case, thecars will be returned to the alternate level
(4) Smoke detectors at the top of the hoistway return cars to thedesignated level
(5) Smoke detectors in the pit return cars to the uppermost recallfloor
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
57/113
NFPA 72 - 2010
For each elevator or group of elevators, an output(s) shall be
provided for the elevator visual warning signal in response to
the following:
(1) Activation of the elevator machine room, elevator machinery
space, elevator control space, or elevator control room
initiating devices identified in
(2) Activation of the elevator hoistwayinitiating devices
identified in
21.3.12.3* Visual Warning.
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
58/113
3 Signals from the Fire Alarm Systemto the Elevator System
Recall to
Alternate Level1
Recall to
Designated Level2
Warning toElevator Car
3
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
59/113
Recall to
Designated Level
Recall to
Alternate Level
Warning to
Elevator Car
Elevator ControllerFire Alarm System
Pictorial Representation of Signals fromFire Alarm System to Elevator Controller
Ac t i va t i on o f sm oke de tec to r (s ) causes s i gna l ( s ) to e l eva to r cont ro l l e r
1
2
Elevator L obby
Detector at
Designated Level
Elevator Lobb y
Detectors
Elevator Machine Room
Detector(s)
3
Elevator Hoistway
Detector(s)
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
60/113
Elevator Lobby
Smoke Detector
Ground Floor
(Designated Level)
Elevator Lobby
Smoke Detector
3rd Floor
Elevator Lobby
Smoke Detector
Basement
Elevator Lobby
Smoke Detector
2nd Floor
(Alternate Level)
Elevator Lobby
Smoke Detector
4th Floor
Elevator Lobby
Smoke Detector
5th Floor
Elevator
Machine Room
Smoke Detector(s)
Elevator
Hoistway
Heat Detector(s)
Elevator
Hoistway
Smoke Detector(s)
Elevator Controller
Fire Alarm Control Unit
SCC 1
actuation
causes
recall to
alternate
level
SCC 2
actuation
causes
recall to
designated
level
SCC 3
R 1
EOL
R 2
EOL
R 3
EOL
actuation
causes
flashing of
warning
signalConventional or
Addr essab le
Zone / Circuit
Module
Elevator
Machine Room
Heat Detector(s)
Fire Alarm System / Elevator Control ler Relationship
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
61/113
NFPA 72 - 2010
21.2.4*A listed relay or other listed appliance connected to
the fire alarm system used to initiate control of protectedpremises emergency control functions shall be located within
3 ftof the controlled circuitor appliance.
21.2.5 The relay or other appliance shall function within the
voltage and current limitations of the fire alarm control unit.
Chap te r 21 - Em ergency Con t ro l Func ti on s and
In te r faces
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
62/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
63/113
Addressable Control Relays
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
64/113
NFPA 13 - 2010
8 .15 .5 E l eva to r Ho is tw ays and M ach ine R oom s .
8.15.5.4* Upright, pendent, or sidewall spray sprinklers shall
be installed at the top of elevator hoistways.
8.15.5.5 The sprinkler required at the top of the elevator
hoistway by 8.15.5.4 shall not be required where the hoistway
for passengerelevators is noncombustible or limited
combustible and the car enclosure materials meet the
requirements of ASME A17.1
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
65/113
Massachusetts Approach
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
66/113
On May 14, 2002, the Massachusetts State Building Code was
amended to:
Delete the requirement for sprinklers in all elevator machine
rooms, hoistways, and pits.
Massachusetts Building Regulations
Boa rd o f Bu i ld ing R egu la t ion s CM R 780
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
67/113
On March 14, 2003, changes were filed to:
Require removal of sprinklers and their piping from locations where
they were installed before or during the code action.
Require the removal or deactivation of the shunt trip circuit breakers
in the elevator machine rooms
Regulations to become effective January 1, 2004
Massachusetts Elevator Regulations
Boa rd o f E le va to r Regu l a t ion s CM R 524
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
68/113
Imp lementa t i on :
After 1-1-2004, and during regular annual inspection of elevators by
the Department of Public Safety, owners will be cited and advised that
the existence of sprinklers and the shunt trip circuit breakers are not
in compliance with regulations and must be removed within 180 days.
Massachusetts Building Regulations
Boa rd o f Bu i ld ing R egu la t ion s CM R 780
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
69/113
Im p l em en t a t i on con t d :
Notice must be given to and a permit received from the FireDepartment prior to the removal of sprinklers as required by MGL
148 Sec. 27A.
The Department of Public Safety will also require a permit for the
removal of the shunt trip circuit breaker to ensure it has been
deactivated.
Massachusetts Building Regulations
Boa rd o f Bu i ld ing R egu la t ion s CM R 780
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
70/113
Im p l em en t a t i on con t d :
During annual inspection, the department will verify theexistence of:
Fire stopping that seals all holes caused by the removal of
sprinkler pipes
Housekeeping measures to remove all combustibles from the
Elevator Machine Room
Required signage on the EMR door
Massachusetts Building Regulations
Boa rd o f Bu i ld ing R egu la t ion s CM R 780
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
71/113
NFPA 13 - 2010
8 .15 .5 E l eva to r Ho is tw ays and M ach ine R oom s .
8.15.5.6
Sprinklers shall be installed at the top and bottom of elevators
that utilize polyurethane-coated steel belts or other similar
combustible belt material.
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
72/113
8.15.5.1* Sidewall spray sprinklers shall be installed at the
bottom of each elevator hoistway not more than 2 ft above
the floor of the pit.
8.15.5.2 The sprinkler required at the bottom of the elevator
hoistway by 8.15.5.1 shall not be required for enclosed,
noncombustible elevator shafts that do not contain
combustible hydraulic fluids.
NFPA 13 - 2010
8 .15 .5 E l eva to r Ho is tw ays and M ach ine R oom s .
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
73/113
2 .8 Equ i pm en t in H o is tw ay and M ach in e R oom s
2.8.2.3.2 means shall be provided to automatically
disconnect the main line powersupply to the affected
elevator upon or prior tothe application of water from the
sprinklers located in the machine room or in the hoistway
more than 24 in. above the pit floor.
ASME A17.1 - 2004
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
74/113
2 .8 Equ i pm en t i n H o is tw ays and M ach ine r y Spaces ,
M ach ine R oom s , Con t ro l Spaces , and Con t ro l Room s
2.8.3.3.2 In jurisdictions not enforcing the NBCC, where
elevator equipment is located or its enclosure is configured
such that application of water from sprinklers could cause
unsafe elevator operation, means shall be provided to
automatically disconnect the main line power supply to theaffected elevator and any other power supplies used to move
the elevator upon or prior to the application of water.
ASME A17.1 - 2010
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
75/113
NFPA 72 - 2010
21 .4 E leva to r Shu tdow n
21.4.2* If heat detectors are used to shut down elevator
power prior to sprinkler operation, they shall be placed within24 in. of each sprinkler headand be installed in accordance
with the requirements of Chapter 17.
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
76/113
NFPA 72 - 2010
21 .4 E leva to r Shu tdow n
21.4.2* If heat detectors are used to shut down elevator
power prior to sprinkler operation, they shall be placed within
24 in. of each sprinkler head and be installed in accordance
with the requirements of Chapter 17.
Alternatively, engineering methods, such as specified in Annex
B, shall be permitted to be used to select and place heat
detectors to ensure response prior to any sprinkler head
operation under a variety of fire growth rate scenarios.
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
77/113
NFPA 72 - 2010
21 .4 E leva to r Shu tdow n
21.4.3* If pressure or waterflow switches are used to shut
down elevator power immediately upon or prior to the
discharge of water from sprinklers, the use of devices with
time-delay switches or time-delay capability shall not be
permitted.
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
78/113
Backg round :
W ate r fr om sp r in k l er s in t he ho i stw ay and
e leva to r m ach ine r oom p resen t s a haza rd t o s a fe
e levato r opera t ion :
Shorts on circuit conductors
-Uncontrolled and dangerous elevator operation
Wet brakes (traction elevators)
-Uncontrolled stopping
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
79/113
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
80/113
Shu nt Tr ip Ope ra t ion
( theore t i ca l )
Smoke detector actuates, initiating elevator recall
Elevators arrive at the recall floor and open doors
Heat buildup causes heat detector to actuate
Shunt trip operates, removing power from the elevator
Sprinkler operates
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
81/113
Potential of passengers becoming entrapped in the
elevator if a heat detector or waterflow switch actuates
(to cause shunt trip) prior to the completion of the
recall function!
Concern:
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
82/113
A17.1 Task Group addressed Shunt Trip and Sprinklers
Hazard Analysis was performed
Concern of over-temperature of elevator controller
Equipment stops
Equipment runs erratically / uncontrollably
Concern water from sprinklers may cause:
Braking Failure Shorting out of an electrical safety or control circuit
Equipment runs erratically / uncontrollably
Sp r in k l e r/ Pow e r Shu t dow n Conce rn s :
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
83/113
A1 7 .1 Task G roup R ecom m enda t i on s:
Exempt sprinklers from being installed in elevator
machine rooms and the top of the hoistway
If sprinklers are installed in elevator machine rooms
and/or the top of the hoistway, then the delay of the
release of water from sprinklers will be required so
recall can be completed first.
thedelay strategy
Sp r in k l e r/ Pow e r Shu t dow n Conce rn s :
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
84/113
A.21.4.2Upon activation of the heat detector used for elevator
power shut down,there should be a delay in the activation ofthe power shunt trip.This delay should be the time that it takes
the elevator cab to travel from the top of the hoistway to the
lowest recall level.
NFPA 72 - 2010
21 .4 E leva to r Shu tdow n
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
85/113
Pre-action orOther Listed Valve Sprinkler(s)
Release Water
Open Valve(Pre-action or Other)
Shu n t T ri p Ope ra t i on - De lay S t ra tegy
Elevator Arrival
Heat Detector
X Time Delay
Smoke Detector
Recall
Shunt Trip
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
86/113
Shu n t T ri p Ope ra t i on - De lay S t ra tegy
Pre-Action Sprinkler System
Fail-Safe Sprinkler Valve
Ei ther :
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
87/113
Fire Alarm System / Elevator Control ler Relationship
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
88/113
Elevator Lobby
Smoke Detector
Ground Floor
(Designated Level)
Elevator Lobby
Smoke Detector
3rd Floor
Elevator Lobby
Smoke Detector
Basement
Elevator Lobby
Smoke Detector
2nd Floor
(Alternate Level)
Elevator Lobby
Smoke Detector
4th Floor
Elevator Lobby
Smoke Detector
5th Floor
Elevator
Machine Room
Smoke Detector(s)
Elevator
Hoistway
Heat Detector(s)
Elevator
Hoistway
Smoke Detector(s)
Elevator Controller
Fire Alarm Control Unit
SCC 1
actuation
causes
recall to
alternate
level
SCC 2
actuation
causes
recall to
designated
level
SCC 3
R 1
EOL
R 2
EOL
R 3
EOL
actuation
causes
flashing of
warning
signalConventional or
Addr essab le
Zone / Circuit
Module
R 4
SCC 4
Shunt Trip Breaker
EOL
Hot Neut
120 VAC
Circuit
(Power to Operate
Shunt Trip Breaker)
From Emergency
Power Source
actuation
causes
disconnect
of main line
elevator
power
Elevator
Machine Room
Heat Detector(s)
y p
actuation
causes
sprinkler valve
to open
SCC 5
ConditionsSprinklerRelease
Simultaneously
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
89/113
21.4.4*Control circuits to shut down elevator power shall be
monitored for presence of operating voltage. Loss of voltage tothe control circuit for the disconnecting means shall cause a
supervisory signalto be indicated at the control unit and
required remote annunciators.
NFPA 72 - 2010
21 .4 E leva to r Shu tdow n
Fire Alarm System / Elevator Control ler Relationship
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
90/113
Elevator Lobby
Smoke Detector
Ground Floor
(Designated Level)
Elevator Lobby
Smoke Detector
3rd Floor
Elevator Lobby
Smoke Detector
Basement
Elevator Lobby
Smoke Detector
2nd Floor
(Alternate Level)
Elevator Lobby
Smoke Detector
4th Floor
Elevator Lobby
Smoke Detector
5th Floor
Elevator
Machine Room
Smoke Detector(s)
Elevator
Hoistway
Heat Detector(s)
Elevator
Hoistway
Smoke Detector(s)
Elevator Controller
Fire Alarm Control Panel
SCC 1
actuation
causes
recall to
alternate
level
SCC 2
actuation
causes
recall to
designated
level
SCC 3
R 1
EOL
R 2
EOL
R 3
EOL
actuation
causes
flashing of
warning
signal
Conventional or
Addr essab le
Zone / Circuit
Module
R 4
SCC 4
Shunt Trip Breaker
EOL
R 5
*
Hot Neut
120 VAC
Circuit
(Power to Operate
Shunt Trip Breaker)
From Emergency
Power Source
actuation
causes
disconnect
of main line
elevator
power
IDC 1
(Supervisory)
*relay R5 contacts shownin deenergized position
actuation
causes
supervisory
signal
EOL
Elevator
Machine Room
Heat Detector(s)
Fire Alarm System / Elevator Control ler Relationship
actuation
causes
sprinkler valve
to open
SCC 5
ConditionsSprinklerRelease
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
91/113
Ongoing Industry Effort
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
92/113
Backg round :
Em ergency eg ress and eva cua t i on s t ra teg ies
fo r h igh - r ise s t ruc tu res re -exam ined fo r ta l l
bu i l d ings as a resu l t o f Sep tem ber 11 , 20 01
a t t a ck on the W TC
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
93/113
W orkshop on the Use o f El eva to r s i n F ir es and
o the r Em ergenc ie s (Atlanta March 2-4, 2004)
Backg round :
Co-sponso red b y A SM E, N IST , ICC , N FPA , IA FF ,
and the U S Ac ces s Boa rd
20 F ir e se rv ice rep resen ta t ives funded by N IST
and FEM A
R epresen ta t i on f rom a c ross sec t ion o f i ndus t r y
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
94/113
W ork shop P r ogr am :
Focu s:
Use of Elevators by Firefighters
Use of Elevators by Occupants During Emergencies
Goa l : to develop proposals that can be submitted to
various code writing organizations
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
95/113
Process :
ASM E took l ead on the haza rd ana l y si s
2 Task g roups
Occupan t Use - to evaluate the use of elevators for
egress in emergencies what can be done to decreaseegress time
F i re figh te r U se to evaluate use of elevators by
firefighters during fire operations what can be done
to mitigate existing hazards
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
96/113
Work shop
:
Cons i s ten t Them es - Concerns :
Culture change since 9-11 total evacuation
Elevators are not a substitute for stairs
Evacuation of mobility impaired people
Lack of firefighter confidence in using elevators
Elevator reliability issues
Water entering hoistways
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
97/113
Work shop
:
Cons i s ten t Them es - Concerns :
Rescue of passengers
Shunt trip entrapment
Loss of elevator power from elsewhere in the building
Retraining occupants to use elevators (in some buildings)
Cost concerns
Not enough information for occupants to make an informed
decision
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
98/113
Work shop
:
Cons is t en t Them es - R ecom m enda t i on s:
Mandatory adoption of ASME A17.3 everywhere
Ensure reliability of Phase I, Phase II operation
Better training on elevator operation for firefighters
Regular testing by qualified (certified?) personnel
Building Emergency Action Plan enforcement
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
99/113
Work shop
:
Cons is t en t Them es - R ecom m enda t i on s:
Sprinkler all buildings
Compartmented/pressurized lobbies/vestibules
Area of Refuge / Rescue Assistance
Better real time communications to occupants
Better real time communications to firefighters
Elevator technician respond to building emergencies
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
100/113
Work shop
:
Cons i s ten t Them es - P rocess:
Utilize Hazard Analysis
Involve firefighters in decisions
Involve appropriate committees and organizations
(ASME-A17-B44, IBC, NFPA, Access Board, etc.)
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
101/113
Process :
Haza rd Ana l y s i s (not a risk analysis)
Develop scenarios
Identify hazards
Mitigate the hazard Identify residual hazards
Mitigate the residual hazards
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
102/113
R es idua l haza rd
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
103/113
Recommenda t i on s :
R obus t F i r e Se rv i ce E leva to r s
Provides greater protection allowing the elevator to continue
to operate for the firefighters during their operations.
Protection from water
Protection from smoke and heat
Direct access to protected lobby and stairwell containing
standpipe
Protection of primary and backup power supplies
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
104/113
Recommenda t i on s :
Occupan t Evacua t i on Op era t i on [OEO]
A l l ow s e l eva to r s to be used fo r evacua t i on un t i l t hey a re
reca l led .
Routing of elevators
Cancel all pre-existing calls
Respond only to hall calls at affected floors
As the fire grows to include more floors, the zone of affected
floors would also increase
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
105/113
Recommenda t i on s :
Provide protected elevator lobbies
Dynamic signage at elevator lobbies
Early warning detection
2-hour fire rating for elevator power feeders
Remote control operation of elevators for firefighter use
(shuttle equipment, etc.)
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
106/113
A1 7 .1 - 20 10 Ed i t ion (has been released)
N FPA 72 - 2010 Ed it io n (has been released)
E leva to r Use i n F i r es and O ther Em ergenc ies
For Occupants
For Firefighters
Hazard Analysis almost finished
NFPA and ICC jum p ing t h e gun
NFPA 101 and IBC
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
107/113
Cu r ren t S ta tu s :
P roceed ing a t GLAC I AL SP EED
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
108/113
21.5.1The conditions monitored and displayed shall include,
but are not limited to the following: (various temperatures,availability of emergency power, elevator location and status, etc.)
21.5.2 The conditions shall be displayed on a standard
emergency services interface complying with Section 18.11
NFPA 72 - 2010
21 .5 F ir s t R esponders Use E l eva to r s
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
109/113
21.6 talks about required status indicators (red and green) and
signage for the use of these elevators, however this is reallypre-mature
For instance, the current thinking of the task group is that these
status indicators and signage will be provided by the elevator provider.
NFPA 72 - 2010
21 .6 E leva to r s fo r Occupan t -Con t ro l l ed Evacua t i on
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
110/113
R esponse to cu r ren t cons t ru c t ion d em and
D i f fe ren t te rm s used
occupant-controlled evacuation
elevator evacuation operation
occupant evacuation elevators
N F PA 101 An n ex B in mandatory language
so can be adopted as needed
Con fe rence he l d in O r l ando , F L - 12 / 201 0
Provided status report to industry
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
111/113
M any changes com ing in t he new code ed it ion s
Dozens of p roposa ls f or IB C and NFPA
S u ch a s
NFPA 13 conditionally eliminates requirement for sprinklers
in hoistways and machine rooms of traction elevators
S ta y tu n ed
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
112/113
Sign of the times
-
7/27/2019 Interfacing Fire Alarm , Sprinkler and Elevator System
113/113
Interfacing Fire Alarm,
Sprinkler and Elevator Systems
Bruce FraserFraser Fire Protection Services