Integration of Offshore Wind Farms using HVDC Technologies: Results from … · 2018. 5. 31. · 1...

65
1 Dr. Carlos E. UGALDE-LOO Cardiff University, Wales, UK Integration of Offshore Wind Farms using HVDC Technologies: Results from the BEST PATHS Project EES-UETP HVDC and HVDC Grids for Future Transmission May 28 June 1, 2018 Leuven, Belgium Additional credit to: Daniel ADEUYI, Sheng WANG, (Cardiff University); Salvador CEBALLOS, (Tecnalia, Spain); Salvatore D’ARCO and Gilbert BERGNA (SINTEF, Norway); Mireia BARENYS (GAMESA, Spain); Max PARKER and Stephen FINNEY (University of Strathclyde, Scotland); Andrea PITTO and Diego CIRIO (RSE SpA, Italy); Jakob GLASDAM (Energinet, Denmark); and Íñigo AZPIRI (Iberdrola, Spain).

Transcript of Integration of Offshore Wind Farms using HVDC Technologies: Results from … · 2018. 5. 31. · 1...

  • 1

    Dr. Carlos E. UGALDE-LOOCardiff University, Wales, UK

    Integration of Offshore Wind Farms using HVDC

    Technologies: Results from the BEST PATHS Project

    EES-UETP

    HVDC and HVDC Grids for Future Transmission

    May 28 – June 1, 2018

    Leuven, Belgium

    Additional credit to:

    Daniel ADEUYI, Sheng WANG, (Cardiff University); Salvador CEBALLOS, (Tecnalia, Spain);

    Salvatore D’ARCO and Gilbert BERGNA (SINTEF, Norway); Mireia BARENYS (GAMESA, Spain);

    Max PARKER and Stephen FINNEY (University of Strathclyde, Scotland);

    Andrea PITTO and Diego CIRIO (RSE SpA, Italy);

    Jakob GLASDAM (Energinet, Denmark); and Íñigo AZPIRI (Iberdrola, Spain).

  • 2

    Outline of the Presentation

    1. Introduction

    2. The BEST PATHS Project

    3. BEST PATHS Demo 1:

    a) Network Topologies

    b) Key Performance Indicators

    c) The ‘Open Access’ Toolbox

    4. Simulation Results

    5. Real-Time Demonstrator

    6. Experimental Results

    7. On-Going (Simulation and Experimental) Work

    8. Conclusions and Next Steps

  • 3

    Introduction

    • Wind energy will be the most widely adopted renewable energy source (RES) by 2050 to contribute towards the abatement of green house gas emissions.

    • Europe’s installed wind capacity is 168.7 GW* (18% of EU’s total installed power generation capacity). In the UK:

    • Operational in 2018:

    o Onshore: 12.1 GW (1523 projects, 7057 turbines);

    o Offshore: 7.11 GW (33 projects, 1832 turbines).

    o Total: 19.214 GW**

    * https://windeurope.org/wp-content/uploads/files/about-wind/statistics/WindEurope-Annual-Statistics-2017.pdf** https://www.renewableuk.com/page/UKWEDhome

  • 4

    Introduction (2)

    • HVAC technology is mature and suitable for subsea transmission at typical voltages up to 150 kV and distances up to 100 km.

    • HVDC has better control capabilities, lower power losses and occupies less space compared with HVAC.

    • A ‘Business as Usual’ approach to improve infrastructure will not be sufficient to meet policy objectives at reasonable cost.

    • Operators and manufacturers are now considering HVDC solutions over HVAC for offshore power transmission systems:

    o A higher quality and more reliable wind resource with higher average wind speeds is farther away from shore, and thus,

    o Long distances to shore.

    o Above 150 kV and beyond 100 km HVAC is not practical due to capacitance and hence charging current of submarine cable.

  • 5

    Introduction (3)

    • Voltage source converter (VSC) based schemes are becoming the preferred option over line commutated converter (LCC) alternatives due to their decoupled power flow control, black-start capability and control flexibility.

    • MTDC grids will facilitate a cross-border energy exchange between different countries and will enable reliable power transfer from offshore wind farms (OWFs).

    • The interactions between wind turbine (WT) converters and different VSC types in a meshed topology need further investigation.

  • 6

    Introduction (4)

    SubstationWind farm

    > 100 km

  • 7

    Introduction (5)

    SubstationWind farm

  • 8

    Introduction (6)

    SubstationWind farm

    HVDC

    HVAC

  • 9

    The BEST PATHS Project

    Key Figures

    • Budget of €62.8M, 56% co-funded by the European Commission under the 7th Framework Programme for Research, Technological Development and Demonstration (EU FP7 Energy).

    • Duration: 01/10/2014 – 30/09/2018 (4 years).

    • Composition: 5 large-scale demonstrations, 2 replication projects, 1 dissemination project.

    Key Aims

    • Through the contribution of 40 leading research institutions, industry, utilities, and transmission systems operators (8), the project aims to develop novel network technologies to increase the pan-European transmission network capacity and electricity system flexibility.

    BEyond State-of-the-art Technologies for re-Powering Ac corridors & multi-Terminal Hvdc Systems

  • 10

    The BEST PATHS Project (2)

    BEyond State-of-the-art Technologies for re-Powering Ac corridors & multi-Terminal Hvdc Systems

  • 11

    BEST PATHS Demo #1

    • Objectives:

    1. To investigate the electrical interactions between the HVDC link converters and the wind turbine (WT) converters in OWFs.

    2. To de-risk multivendor and multi-terminal HVDC (MTDC) schemes.

    3. To demonstrate the results in a laboratory environment usingscaled models.

    4. To use the validated models to simulate a real grid with OWFs connected in HVDC.

  • 12

    BEST PATHS Demo #1 (2)

    HVDC equipment manufacturers provide ‘black boxes’

    We intend to use ‘open models’R&D Centres

    TSOs

    Utilities & RES developers

    Independent Manufacturers

    ?

    Detailed models

    Simulation & Validation

  • 13

    Network Topologies

    ➢System configurations have been implemented in Simulink

    • A number of topologies has been modelled, simulated and analysed.

    • The topologies considered constitute likely scenarios to be adopted for the transmission of offshore wind energy in future years.

    • Full details available in Deliverable D3.1 of the BEST PATHS project.

    GSC

    Pw1

    Pg1,Qg1Onshore

    AC Grid #1

    DC CABLE

    Vdc and Q

    Controller

    AC Voltage

    Control

    Vdc_g1

    Vdc_g1*fw1*|Vac_w1*|

    Vac_w1

    Offshore

    Grid #1WFC Offshore Onshore

    Qg1*

    θw1*

    ➢Point-to-Point HVDC Link (Topology A)

  • 14

    Network Topologies (2)

    ➢Three-Terminal HVDC System

    Pw1

    DC

    NETWORK

    AC Voltage

    Control

    fw1*Vac_w1*

    Vac_w1

    Offshore

    Grid #1

    WFC #1

    Offshore Onshore

    θw1*

    GSC #1Pg1,Qg1

    Onshore

    AC Grid #1

    (Vdc vs. P) and Q

    Controller

    Vdc_g1* Qg1*

    Vdc_g1

    AC Voltage

    Control

    fw12*Vac_w2*

    Vac_w2

    WFC #2

    θw2*

    Pw2

    Offshore

    Grid #1

  • 15

    Network Topologies (3)

    GSC #1

    Pw1

    Pg1,Qg1Onshore

    AC Grid #1

    (Vdc vs. P) and Q

    Controller

    AC Voltage

    Control

    Vdc_g1

    Vdc_g1*fw1*Vac_w1*

    Vac_w1

    Offshore

    Grid #1

    WFC #1

    Qg1*θw1*

    GSC #2

    Pw2

    Pg2,Qg2Onshore

    AC Grid #2

    (Vdc vs. P) and Q

    Controller

    AC Voltage

    Control

    Vdc_g2

    Vdc_g2*fw2*Vac_w2*

    Vac_w2Offshore

    Grid #2WFC #2

    Qg2*θw2*

    GSC #3

    Pw3

    Pg3,Qg3Onshore

    AC Grid #3

    (Vdc vs. P) and Q

    Controller

    AC Voltage

    Control

    Vdc_g3

    Vdc_g3*fw3*Vac_w3*

    Vac_w3

    Offshore

    Grid #3WFC #3

    Qg3*θw3*

    DC

    NETWORK

    Offshore Onshore

    AC interlink

    ➢Six-Terminal HVDC System with Offshore AC Links (Topology B)

  • 16

    Network Topologies (4)

    GSC #1

    Pw1

    Pg1,Qg1Onshore

    AC Grid #1

    (Vdc vs. P) and Q

    Controller

    AC Voltage

    Control

    Vdc_g1

    Vdc_g1*fw1*Vac_w1*

    Vac_w1

    Offshore

    Grid #1

    WFC #1

    Qg1*θw1*

    GSC #2

    Pw2

    Pg2,Qg2Onshore

    AC Grid #2

    (Vdc vs. P) and Q

    Controller

    AC Voltage

    Control

    Vdc_g2

    Vdc_g2*fw2*Vac_w2*

    Vac_w2

    Offshore

    Grid #2WFC #2

    Qg2*θw2*

    GSC #3

    Pw3

    Pg3,Qg3Onshore

    AC Grid #3

    (Vdc vs. P) and Q

    Controller

    AC Voltage

    Control

    Vdc_g3

    Vdc_g3*fw3*Vac_w3*

    Vac_w3

    Offshore

    Grid #3WFC #3

    Qg3*θw3*

    DC

    NETWORK

    Offshore Onshore

    DC interlink

    ➢Six-Terminal HVDC System with Offshore DC Links (Topology C)

  • 17

    Network Topologies (5)

    ➢Twelve-Terminal HVDC System with

    Offshore DC Links (Topology D)

    GSC #4

    Pg3,Qg3

    (Vdc vs. P) and Q

    Controller

    Vdc_g4

    Vdc_g4* Qg4*

    GSC #5

    Pg2,Qg2

    (Vdc vs. P) and Q

    Controller

    Vdc_g2

    Vdc_g2* Qg2*

    GSC #6

    Pg1,Qg1

    Onshore

    AC Grid #B

    (Vdc vs. P) and Q

    Controller

    Vdc_g6

    Vdc_g6* Qg6*

    DC

    NETWORK

    Offshore Onshore

    Pw1

    AC Voltage

    Control

    fw1*Vac_w1*

    Vac_w1

    Offshore

    Grid #1

    WFC #1

    θw1*

    Pw2

    AC Voltage

    Control

    fw2*Vac_w2*

    Vac_w2

    Offshore

    Grid #2WFC #2

    θw2*

    Pw3

    AC Voltage

    Control

    fw3*Vac_w3*

    Vac_w3

    Offshore

    Grid #3WFC #3

    θw3*

    Pw4

    AC Voltage

    Control

    fw4* Vac_w4*

    Vac_w4

    Offshore

    Grid #4

    θw4*

    Pw5

    AC Voltage

    Control

    fw5* Vac_w5*

    Vac_w5

    Offshore

    Grid #5WFC #5

    θw5*

    Pw6

    AC Voltage

    Control

    fw6* Vac_w6*

    Vac_w6

    Offshore

    Grid #6WFC #6

    θw6*

    GSC #1

    Pg6,Qg6

    (Vdc vs. P) and Q

    Controller

    Vdc_g1

    Vdc_g1* Qg1*

    GSC #2

    Pg5,Qg5

    (Vdc vs. P) and Q

    Controller

    Vdc_g5

    Vdc_g5* Qg5*

    GSC #3

    Pg4,Qg4

    Onshore

    AC Grid #A

    (Vdc vs. P) and Q

    Controller

    Vdc_g3

    Vdc_g3* Qg3*

    DC

    NETWORK

    Offshore Onshore

    WFC #4

    (100 km)

    (5 k

    m)

    (10 km)

    (10 km)

    (10

    km)

    (10

    km)

    (100 km)

  • 18

    Key Performance Indicators

    KPI.D1.1 – AC/DC interactions: power and harmonics

    Steady state Power quality WT ramp rates

    • To assess the suitability of the models and proposed HVDC network topologies, converter configurations and control algorithms, a set of KPIshave been defined.

    • Full details available in Deliverable D2.1 of the BEST PATHS project.

    KPI.D1.2 – AC/DC Interactions –Transients & Voltage Margins

    Normal operation Extreme operation

    KPI.D1.3 – DC Protection Performance / Protection & Faults

    Protection selectivity Peak current and clearance time

    KPI.D1.4 – DC Inter-array Design

    Inter-array topology

    Power unbalance

    Fault tolerance

    Motorising capability

    KPI.D1.5 – Resonances

    AC systems oscillation Internal DC resonance

    KPI.D1.6 – Grid Code Compliance

    Active and reactive power

    Fault ride-through

  • 19

    The ‘Open Access’ Toolbox

    • A set of models and control algorithms has been developed, simulated and assessed.

    • Their portability as basic building blocks will enable researchers and designers to study and simulate any system configuration of choice.

  • 20

    The ‘Open Access’ Toolbox (2)

    • The models and control algorithms have been published in the BEST PATHS website as a MATLAB ‘Open Access’ Toolbox: http://www.bestpaths-project.eu/.

    • The toolbox was originally presented last year in the 13th IET Conference on AC and DC Power Transmission (ACDC2017):

    o CE Ugalde-Loo, et al., “Open Access Simulation Toolbox for the Grid Connection of Offshore Wind Farms using Multi-Terminal HVDC Networks”, 13th IET ACDC17, Manchester, UK, 2017.

    http://www.bestpaths-project.eu/

  • 21

    The ‘Open Access’ Toolbox (3)

    • A user manual is also provided, together with the published models and accompanying examples.

    • Full details of the models available in Deliverable D3.1 of the BEST PATHS project.

  • 22

    The ‘Open Access’ Toolbox (4)

    ➢ Converter Stations

    ➢ AC Grid

    • Averaged and switched models for an MMC.

    • The combined averaged-switched model consists of two blocks:

    o Power electronics block,

    o Low level controller block: circulating current reference generation, circulating current controller, nearest level control modulation strategy & sub-module voltage regulator.

    • AC network adapted from the classical nine-bus power system.

    ➢ DC Cable

    • The DC cable section has been modelled as a one-phase, frequency-dependent, travelling wave model.

    • It is based on the universal line model (ULM), which takes into account the frequency dependence of parameters.

  • 23

    The ‘Open Access’ Toolbox (5)

    ➢ Wind Farm

    • It accurately represents the behaviour of an aggregated OWF.

    • To avoid large simulation times and undesirable computer burden, simplifications have been carried out in the electrical system:

    o The converter of the a wind turbine generator (WTG) is modelled with averaged-model based voltage sources.

    o A current source represents the remaining WTGs of the OWF. The current injection of the first WTG is properly scaled to complete the rated power of the whole OWF.

    • The detailed WTG contains

    o a permanent magnet synchronous generator model;

    o Averaged models: machine- and grid-side converters, including filters and DC link;

    o An LV/MV transformer and internal control algorithms.

  • 24

    The ‘Open Access’ Toolbox (6)

    ➢ High Level Controller

    • It considers converter operation in three control modes.

    • The aim is to cover the main control needs for different system configurations.

    id1*, iq1*

    High Level Controller

    Vdc – Q

    Mode

    Selector

    P – Q AC Island

    Mode 1 Mode 2 Mode 0

    id2*, iq2*

    Outer

    Loop

    Inner Current

    Loopabc-dq

    Vdq

    idq

    Vdq*

    dq-abc

    Vabc

    iabc

    PLL θ

    vabc*vabc*

    θ

    Half-Bridge

    MMC

    L

    ± VDC

    Vabciabc

    AC Voltage

    Control

    fwf*

    |Vwf*|

    θwf*

    Low Level Controller

    Current Limiter

    DC

    Grid

    AC

    System

    idq*

    P – Vdc

    Droop

    Select

    Vdc – P

    Droop

    Select

    Imax

    dq-φ θ

    θ*

    θwf*

  • 25

    The ‘Open Access’ Toolbox (7)

    ➢ High Level Controller

    o Mode 0: Vac voltage control: The converter sets the voltage and frequency.

    Offshore

    AC Grid

    Vdc

    ω = 2πf

    Vwf,a =Msin(ωt +θ)

    Vwf,b = Msin(ωt+θ+2π/3)

    Vwf,c=Msin(ωt+θ-2π/3)

    fwf* = const

    θwf* = const

    f

    θ

    WFC

    M

    vabc

    Vabcma

    Pwf

    ski3kp3+

    |Vwf*|

    +-

    Switching

    Control

    vabc*

    |Vwf|

  • 26

    The ‘Open Access’ Toolbox (8)

    ➢ High Level Controller

    Mode 1: Vdc – Q control scheme with a P – Vdc droop

    id*Vdc

    Vdc,0*s

    ki,V+kp,V

    P*kpv

    +-

    P

    id1*Vdc*

    Outer Loop

    Outer

    LoopInner Current

    Loop

    Switching

    Control

    Vabc

    Liabc

    vabc*

    abc-dq

    vdq

    P, Qabc-dq

    idq

    dq-abc

    vdq*

    Vdc MTDC system

    PLL

    θ

    θ

    Vdc

    idq*

    vabc

    Main AC

    Grid

    ΔVdc,0

    iq*

    -1

    vd

    ++ +

    -id

    vd*kp +

    iq

    vdInner Current Loop

    ωL

    vq*

    +-

    ++

    +

    ωL

    kp ++-

    ++

    IQ*

    q-axis

    Limited iq*

    Limited id*

    iq* before limiting

    id* before limiting

    d-axis

    ski

    ski

    Radius

    Imax

    Imax

    Q*

    Current

    Limiter

    Current

    Limiter

    idq1*

  • 27

    The ‘Open Access’ Toolbox (9)

    ➢ High Level Controller

    Mode 2: P – Q control scheme with a Vdc – P droop

    id*

    Vdc

    Vdc*

    P0*

    kvp

    +-

    POuter Loop

    Outer

    LoopInner Current

    Loop

    Switching

    Control

    vabc

    Liabc

    vabc*

    abc-dq

    vdq

    P, Qabc-dq

    idq

    dq-abc

    vdq*

    Vdc MTDC system

    PLL

    θ

    θ

    Vdc

    idq*

    vabc

    Main AC

    Grid

    ΔP*

    iq*

    -1

    vd

    ++

    +-

    id

    vd*kp +

    iq

    vdInner Current Loop

    ωL

    vq*

    +-

    ++

    +

    ωL

    kp ++-

    ++

    q-axis

    Limited iq*

    Limited id*

    iq* before limiting

    id* before limiting

    d-axis

    ski

    ski

    Radius

    Imax

    Imax

    Q*

    Current

    Limiter

    P*1

    vd

    Current

    Limiteridq2*

    id2*

    id2*

  • 28

    The ‘Open Access’ Toolbox (10)

    o Universities include Aalborg University, KU Leuven, Fukui University of Technology, Imperial College London, Technical University of Denmark, University College of Dublin, Ensam, Technical University of Darmstadt, Technical University of Eindhoven, University College London, Pontifical Comillas University, King Fahd University of Petroleum and Minerals, Shanghai Jiao Tong University, Huazhong university, Florida State University, and Technical University Kaiserslautern.

    o Research centres include KTH Royal Institute of Technology, the SuperGrid Institute, GridLab, IREC (Institut de Recerca en Energia de Catalunya) and L2EP (Laboratoire d’Electrotechnique et Electronique de Puissance, Lille).

    o Companies include Siemens, Tractebel, Sarawak Energy, DNV GL, IBM Research, SP Energy Networks, TenneT Offshore, Nissin, Enstore, SCiBreak, and General Electric.

    • Toolbox and user manual uploaded on BEST PATHS website on 14th February 2017.

    • Presentation at 13th IET ACDC2017; advertisement via social media and on project website.

    • 5,076 new users have been recorded on the website since the toolbox was uploaded.

    • The toolbox has been downloaded by 119 different users (until 23rd

    May 2018).

    Purposes of use

    Testing

    Information

    Research

    Evaluation

    Training

    Type of organisation

    University

    Research centre

    Company

    http://bestpaths-project.eu/en/publications

  • 29

    Simulation Results

    Example: KPI Assessment

    • Simulation results for three topologies are presented.

    • A subset of the KPIs is shown.

    GSC

    Pw1

    Pg1,Qg1Onshore

    AC Grid #1

    DC CABLE

    Vdc and Q

    Controller

    AC Voltage

    Control

    Vdc_g1

    Vdc_g1*fw1*|Vac_w1*|

    Vac_w1

    Offshore

    Grid #1WFC Offshore Onshore

    Qg1*

    θw1*

    Pw1

    DC

    NETWORK

    AC Voltage

    Control

    fw1*Vac_w1*

    Vac_w1

    Offshore

    Grid #1

    WFC #1

    Offshore Onshore

    θw1*

    GSC #1Pg1,Qg1

    Onshore

    AC Grid #1

    (Vdc vs. P) and Q

    Controller

    Vdc_g1* Qg1*

    Vdc_g1

    AC Voltage

    Control

    fw12*Vac_w2*

    Vac_w2

    WFC #2

    θw2*

    Pw2

    Offshore

    Grid #1

    GSC #1

    Pw1

    Pg1,Qg1Onshore

    AC Grid #1

    (Vdc vs. P) and Q

    Controller

    AC Voltage

    Control

    Vdc_g1

    Vdc_g1*fw1*Vac_w1*

    Vac_w1

    Offshore

    Grid #1

    WFC #1

    Qg1*θw1*

    GSC #2

    Pw2

    Pg2,Qg2Onshore

    AC Grid #2

    (Vdc vs. P) and Q

    Controller

    AC Voltage

    Control

    Vdc_g2

    Vdc_g2*fw2*Vac_w2*

    Vac_w2

    Offshore

    Grid #2WFC #2

    Qg2*θw2*

    GSC #3

    Pw3

    Pg3,Qg3Onshore

    AC Grid #3

    (Vdc vs. P) and Q

    Controller

    AC Voltage

    Control

    Vdc_g3

    Vdc_g3*fw3*Vac_w3*

    Vac_w3

    Offshore

    Grid #3WFC #3

    Qg3*θw3*

    DC

    NETWORK

    Offshore Onshore

    Topology 1

    Topology 2

    Topology 3

    • Full details of KPI assessment for all defined topologies available in Deliverable D3.2 of the BEST PATHS project.

  • 30

    Simulation Results (2)

    Example: KPI Assessment (continued…)

    • The converter control performance is assessed when references for DC voltage and reactive power are changed to onshore converter GSC in Topologies 1 and 2 and GSC2 in topology 3.

    o Reactive power changed from 330 MVAr to 165 MVAr at 1.5 s;

    o DC voltage changed from 640 kV to 576 kV at 1.8 s.

    Topology 1 Topology 2 Topology 3

    ➢ Assessment of KPI.D1.1 – Steady state error (SSE)

  • 31

    Simulation Results (3)

    Example: KPI Assessment (continued…)➢ Assessment of KPI.D1.6 – Grid Code Compliance

    • The AC fault ride-through capability of the systems is evaluated.

    o A voltage dip at an onshore grid converter is applied at 1.5 s during 300 ms, reducing the AC voltage from 1 p.u. to 0.15 p.u.

    Topology 1 Topology 2 Topology 3

  • 32

    Simulation Results (4)

    Example: KPI Assessment (continued…)

    ➢ Assessment of KPI.D1.1 – Harmonics and SSE

    • The THD of the AC voltage and the converter performance are evaluated during AC voltage regulation (offshore converter).

    o The offshore AC voltage (rms) is changed from 1 p.u. (380 kV) to 0.9 p.u. (342 kV) at 1.5 s.

    Topology 1 Topology 2 Topology 3

  • 33

    Simulation Results (5)

    KPI Assessment Summary

    • Full details of the models available in Deliverable D3.2 of the BEST PATHS project.

    Steady State AC/DC Interactions

    Transient AC/DC Interactions

    Protection Performance

    DC Inter-array Design

    Resonances

    Grid Code Compliance

    1.1

    1.2

    1.3

    1.4

    1.5

    1.6

    KPI Description Status

    Due to converter overloading and DC overvoltage during extreme conditions (e.g. AC faults). Overloading sustained for a very short time

  • 34

    Real-Time Demonstrator

    ➢ Built in the premises of SINTEF (Trondheim, Norway), it aims to:

    • Provide experimental validation to the results obtained from simulations:

    o Establish a correspondence between simulation and experimental setup on single components and at system level;

    o Identify relevant scenarios to test in the laboratory;

    o Perform experiments.

    • Reduce risks of HVDC link connecting OWFs.

    • Validate meshed HVDC grids with different VSC technologies.

    • Foster new suppliers and sub-suppliers of HVDC technology.

    ➢ Facilities include:

    • a four-terminal 50 kW HVDC grid with 3 VSC-based MMCs and 1 two-level VSC;

    • a 20 kW synchronous generator;

    • DC circuit breakers;

    • a wind emulator;

    • a real-time simulator system and control unit (OPAL-RT).

  • 35

    Real-Time Demonstrator (2)

    • Further detail on the demonstrator available in Deliverable D8.1 of the BEST PATHS project.

  • 36

    Real-Time Demonstrator (3)

    ➢ National SmartGrid Laboratory (SINTEF)

  • 37

    Real-Time Demonstrator (4)

    ➢ MMC Power Cells Boards

  • 38

    Real-Time Demonstrator (5)

    ➢ MMC Assembling Stages

  • 39

    Real-Time Demonstrator (6)

    ➢ MMC Assembling Stages (2)

  • 40

    Experimental Results

    ➢ Matching converter parameters of demonstrator with those of

    simulation models

    • The matching process was based on experimental results from the demonstrator running in open loop connected to a resistive load.

    • This way, the MMC arm current and submodule voltages would depend only on converter parameters and not on the control action.

    • MMC parameters were iteratively matched, including arm inductance, arm resistance, and submodule capacitance.

    • With component parameters matched, the delay between measurements of arm current and submodule voltage could be determined from experimental results.

    • The main aim of this iterative exercise was to:

    o Increase the accuracy of the simulation models.

    o Obtain a highly reliable representation to perform offline tests.

    o Help ensure adequate performance of test configurations.

    o Identify adverse operating conditions via software.

  • 41

    Experimental Results (2)

    ➢ Matching converter parameters of demonstrator with those of

    simulation models (continued…)

    MMC12

    60 kVA

    690V DC

    Source

    Inner Current

    Loop

    Power Amplifier 200 kVA

    Real Time

    Simulator

    Iabc

    id*

    VabcVdc*

    300V AC

    Source

    Vabc1* Vabc*

    MMC12

    60 kVA

    690V DC

    Source

    AC Voltage

    Control

    Power Amplifier

    200 kVA

    Real Time

    Simulator

    Iabc

    f*

    V*θ*

    11 Ω

    Load

    VabcVdc* Vabc*

    • MMC with AC voltage control connected to a load resistance.

    o The control schemes creates an AC voltage with a reference amplitude of 330 V and 50 Hz.

    • MMC with inner current control connected to an islanded AC grid.

  • 42

    Experimental Results (3)

    ➢ Matching converter parameters of demonstrator with those of

    simulation models (continued…)

    18-level 12-level 6-level

    AC

    Vo

    ltag

    e [V

    ]

    AC

    Cu

    rren

    t [A

    ]

    Arm

    Cu

    rren

    t [A

    ]

    MMC with AC voltage control connected to load resistance

  • 43

    Experimental Results (4)

    ➢ Matching converter parameters of demonstrator with those of

    simulation models (continued…)

    MMC with inner current control connected to islanded AC grid

    18-level 12-level 6-level

    RM

    S A

    C C

    urr

    ent

    [A]

    • Reference of d-axis current increased from 20 to 30 A at t = 2.5 s.

    18-level 12-level 6-level

    RM

    S A

    C C

    urr

    ent

    [A]

  • 44

    Experimental Results (5)

    ➢ Experimental Validation for Topology A

    • Sending converter (18-level half-bridge) uses a nearest level modulation (NLM) and operates in a P/Q mode.

    • Receiving converter (6-level half-bridge) uses a phase disposition PWM (PD-PWM) and operates in a Vdc/Q mode.

    • Both converters make use of a circulating current regulator and voltage balancing algorithms.

  • 45

    Experimental Results (6)

    ➢ Experimental Validation for Topology A (continued…)

    • Reference currents at the sending end:

  • 46

    Experimental Results (7)

    ➢ Experimental Validation for Topology A (continued…)

    • DC voltage. Performance upon changes in current reference id and changes in the DC voltage reference:

  • 47

    Experimental Results (8)

    ➢ Experimental Validation for Topology A (continued…)

    • Upper and lower arm currents and voltages at the receiving end converter in steady-state.

  • 48

    On-Going Work

    Point-to-Point System

    Objective:

    Evaluate the operation of the point-to-point link when the WF powervaries.

    Procedure:

    Change active power of the WF from 0 to 1 p.u. with ramp rate

    limitation of 10 p.u./s.

  • 49

    On-Going Work (2)

    Point-to-Point System (continued…)

    0.9 1 1.1 1.2 1.3 1.4 1.5-50

    0

    50

    Curr

    ent

    (A)

    time(s)

    19-Level AC current

    Demonstrator

    Simulation

    0.9 1 1.1 1.2 1.3 1.4 1.5-50

    0

    50

    Curr

    ent

    (A)

    time(s)

    7-Level AC current

    0.5 1 1.5 2660

    670

    680

    690

    700

    710

    720

    Voltage (

    V)

    time (s)

    DC-bus Voltage Vdc

    Demonstrator

    Simulation

    0.5 1 1.5 2-40

    -30

    -20

    -10

    0

    Curr

    ent

    (A)

    time (s)

    DC-bus Current Idc

  • 50

    On-Going Work (3)

    Point-to-Point System (continued…)

    0.9 1 1.1 1.2 1.3 1.4 1.5-40

    -30

    -20

    -10

    0

    10

    20

    Curr

    ent

    (A)

    time (s)

    19-Level Arm current

    Demonstrator

    Simulation

    0.9 1 1.1 1.2 1.3 1.4 1.5-20

    -10

    0

    10

    20

    30

    40

    Curr

    ent

    (A)

    time (s)

    7-Level Arm current

    0.9 1 1.1 1.2 1.3 1.4 1.5660

    680

    700

    720

    740

    Voltage (

    V)

    time (s)

    19-Level Arm voltage

    Demonstrator

    Simulation

    0.9 1 1.1 1.2 1.3 1.4 1.5660

    680

    700

    720

    740

    Voltage (

    V)

    time (s)

    7-Level Arm voltage

  • 51

    On-Going Work (4)

    Three-Terminal System

    Objective:

    Evaluate the operation of a three-terminal system when the WF power varies.

    Procedure:

    - Set the power of the PQ node to -0.5 p.u (injecting power into the

    grid).

    - Change active power of the WF from 0 to 1 p.u. with ramp rate

    limitation 10 p.u./s

  • 52

    On-Going Work (5)

    Three-Terminal System (continued…)

    1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 20

    50

    100

    7-Level Id

    time(s)

    Curr

    ent

    (A)

    Demonstrator

    Simulation

    1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2

    -60

    -40

    -20

    0

    19-Level Id

    time(s)

    Curr

    ent

    (A)

    1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2

    -60

    -40

    -20

    0

    13-Level Id

    time(s)

    Curr

    ent

    (A)

    1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2

    680

    700

    720DC-bus voltage Vdc

    time(s)

    Voltage (

    V)

    Demonstrator

    Simulation

    1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 20

    50

    7-Level DC current

    time(s)

    Curr

    ent

    (A)

    1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2-80-60-40-20

    0

    19-Level DC current

    time(s)

    Curr

    ent

    (A)

    1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2-80-60-40-20

    0

    13-Level DC current

    time(s)

    Curr

    ent

    (A)

  • 53

    On-Going Work (6)

    Three-Terminal System (continued…)

    1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2

    -50

    0

    50

    7-Level Arm current

    time(s)

    Curr

    ent

    (A)

    Demonstrator

    Simulation

    1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2

    -50

    0

    50

    19-Level Arm current

    time(s)

    Curr

    ent

    (A)

    1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2

    -50

    0

    50

    13-Level Arm current

    time(s)

    Curr

    ent

    (A)

    1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2

    650

    700

    750

    7-Level Arm voltage

    time(s)

    Voltage (

    V)

    Demonstrator

    Simulation

    1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2

    650

    700

    750

    19-Level Arm voltage

    time(s)V

    oltage (

    V)

    1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2

    650

    700

    750

    13-Level Arm voltage

    time(s)

    Voltage (

    V)

  • 54

    On-Going Work (7)

    Three-Terminal System – TEST TWO

    Objective:

    Evaluate the operation of a three-terminal system when the power flow of the PQ node is reversed.

    Procedure:

    - Set the power of the WF to 0.5 p.u.

    - Change the active power of the PQ node from -0.5 p.u to 0.5 p.u.

    with ramp rate limitation 10 p.u./s.

  • 55

    On-Going Work (8)

    Three-Terminal System – TEST TWO (continued…)

    1.5 1.6 1.7 1.8 1.9 2 2.1 2.2-100

    0

    1007-Level Id

    time(s)

    Curr

    ent

    (A)

    Demonstrator

    Simulation

    1.5 1.6 1.7 1.8 1.9 2 2.1 2.2-100

    0

    10019-Level Id

    time(s)

    Curr

    ent

    (A)

    1.5 1.6 1.7 1.8 1.9 2 2.1 2.2-100

    0

    10013-Level Id

    time(s)

    Curr

    ent

    (A)

    1.5 1.6 1.7 1.8 1.9 2 2.1 2.2600

    650

    700

    DC-bus voltage Vdc

    time(s)

    Voltage (

    V)

    Demonstrator

    Simulation

    1.5 1.6 1.7 1.8 1.9 2 2.1 2.2-50

    0

    50

    7-Level DC current

    time(s)

    Curr

    ent

    (A)

    1.5 1.6 1.7 1.8 1.9 2 2.1 2.2-50

    0

    50

    19-Level DC current

    time(s)

    Curr

    ent

    (A)

    1.5 1.6 1.7 1.8 1.9 2 2.1 2.2-50

    0

    50

    13-Level DC current

    time(s)

    Curr

    ent

    (A)

  • 56

    On-Going Work (9)

    Three-Terminal System – TEST TWO (continued…)

    1.5 1.6 1.7 1.8 1.9 2 2.1 2.2

    -50

    0

    50

    7-Level Arm current

    time(s)

    Curr

    ent

    (A)

    Demonstrator

    Simulation

    1.5 1.6 1.7 1.8 1.9 2 2.1 2.2

    -50

    0

    50

    19-Level Arm current

    time(s)

    Curr

    ent

    (A)

    1.5 1.6 1.7 1.8 1.9 2 2.1 2.2

    -50

    0

    50

    13-Level Arm current

    time(s)

    Curr

    ent

    (A)

    1.5 1.6 1.7 1.8 1.9 2 2.1 2.2600

    650

    700

    7-Level Arm voltage

    time(s)

    Voltage (

    V)

    Demonstrator

    Simulation

    1.5 1.6 1.7 1.8 1.9 2 2.1 2.2600

    650

    700

    19-Level Arm voltage

    time(s)V

    oltage (

    V)

    1.5 1.6 1.7 1.8 1.9 2 2.1 2.2600

    650

    700

    13-Level Arm voltage

    time(s)

    Voltage (

    V)

  • 57

    On-Going Work (10)

    Interactions of droop and power control characteristics

    Conv2Pg2,Qg2 AC Grid

    #2

    (Vdc vs. P) and Q

    Controller

    Vdc_g2

    Qg2*

    DC

    NETWORK

    Conv3Pg3,Qg3AC Grid

    #3

    P and Q

    Controller

    Pg3*Qg3*

    Vdc_g3

    Conv1Pg1,Qg1

    AC Grid

    #1

    P and Q

    Controller

    Qg1*

    Vdc_g1

    Vdc_g1* Vdc_g2*

    • Different droop and power control strategies could have adverse interactions from multiple crossings of the control characteristics.

    • Conv1 (in black): an exporting converter (inverter).

    • Conv2 (in blue): an importing converter (rectifier), voltage

    reference is given as 1 p.u. and the droop gain is 1.25 p.u.

    • Conv3 (in red): an exporting converter (inverter).

    • Bases are 650 V, 32500 W and 50 A.

  • 58

    On-Going Work (11)

    Interactions of droop and power control characteristics

    • The green power curve is an equivalent curve of adding those of Conv1 (black line) and Conv3 (red line).

    • The droop curve is intersected by the power curve. This results in three different operation points.

    Vdc

    1 p.u. Idc

    Vopt

    Vopt1

    Vopt2 Conv2

    1 p.u.

    Conv2

    Power change

    from 0 to

    |32500| W

    Conv3 +Conv1 Conv3 +Conv1

    0 p.u.

    Vdc

    Conv3 Conv1

    0.31 p.u. 0.69 p.u. Idc

    Vdc

    Conv3 +Conv1

    1 p.u.

    1 p.u.

    Idc

  • 59

    On-Going Work (12)

    Interactions of droop and power control characteristics

    Power/current

    reference (p.u.)

    1.5 s Time (s)1.7 s

    (1 p.u.)

    (-0.31 p.u.)

    (-0.69 p.u.)

    Conv3

    Conv1

    Conv2

    • Initial power referencesfor all converters are 0 p.u.

    • From 1.5 to 1.7 s, ramp changes are applied to the power references. The power reference of Conv1is changed to -1 p.u. and the power references of Conv2 and Conv3 are changed to 0.69 p.u. and 0.31 p.u., respectively.

    • DC voltage in steady-state shifted.

    • The current cannot be regulated effectively.

  • 60

    On-Going Work (13)

    Interactions of droop and power control characteristics

    • An additional test is performed, where the sign of all power references in the previous test is reversed.

    • The multiple-crossing problem is avoided.

    Vdc

    1 p.u. Idc

    Vopt

    Conv1

    1 p.u.

    Conv1

    Power change

    from 0 to

    |32500| W

    Conv3 +Conv1 Conv3 +Conv1

  • 61

    On-Going Work (14)

    Interactions of droop and power control characteristics

    • I-V trajectory for Conv 2’s voltage and current.

    • The voltage for the characteristic without multiple crossings (green curve)

    stays around 650 V (from Vopt to Vopt_new). Following the transient regime, the

    current stays at 50 A (1 p.u.) at one end and hence it is well regulated.

    • The voltage for the characteristic with multiple crossings (yellow curve)

    shifts from 650 to 610 V (Vopt2) in steady-state and also there are significant

    oscillations. The current settles at −54.2 A (−1.084 p.u.) and hence not

    accurately regulated at −50 A.

    𝑉𝑜𝑝𝑡

    𝑉𝑜𝑝𝑡 _𝑛𝑒𝑤

    𝑉𝑜𝑝𝑡 2

  • 62

    Conclusions and Next Steps

    • A set of models and control algorithms has been developed, simulated and assessed. These have been published as an ‘Open Access’ Toolbox.

    • Network topologies constituting likely scenarios for the transmission of offshore wind energy have been proposed.

    • To assess the suitability of the models, topologies and control algorithms, a set of KPIs have been defined.

    • An experimental demonstrator for the integration of grid-connected OWFs using HVDC grids has been presented.

    • Results demonstrating the capabilities of the demonstrator have been compared against simulation results. These show good agreement.

    ➢ Main Contributions of this Work

  • 63

    Conclusions and Next Steps (2)

    ➢ Main Contributions of this Work (continued)

    • The main contribution of this work is the provision to TSOs, utilities, manufacturers and academic institutions with simulation and experimental tools to generate the necessary knowledge for the development, construction and connection of MTDC systems –aiming to help de-risking the use of MTDC grids for the connection of OWFs.

    • Using the real-time experimental demonstrator, conduct tests for different system topologies representing future scenarios to validatesimulation results obtained using computational tools.

    • Make the demonstrator available to interested parties for R&D activities.

    ➢ On-Going and Future Work

  • 64

    Conclusions and Next Steps (3)

    ➢ Some papers linked to this presentation

    • Ugalde-Loo CE, et al., “Lessons Learnt from the BEST PATHS Project for the Integration of Offshore Wind Farms using Multi-Terminal HVDC Grids,” 47th CIGRE Session 2018, Paris, France, 26-31 August 2018, pp. 1-10.

    • Parker M, Finney S, Holliday D, “DC protection of a multi-terminal HVDC network featuring offshore wind farms,” Energy Procedia, vol. 142, Dec. 2017, pp. 2195-2201.

    • Azpiri I, Ciapessoni E, Cirio D, Glasdam J, Lund P, Pitto P, “Grid code compliant controllers for multi-terminal HVDC grids aimed to integrate wind power: assessing their impact on the operational security of a real-world system,” Energy Procedia, vol. 142, Dec. 2017, pp. 2165-2170.

    • Ciapessoni, et al., “Assessing the impact of multi-terminal HVDC grids for wind integration on future scenarios of a real-world AC power system using grid code compliant open models,” 2017 IEEE Power Tech, Manchester, UK, 18-22 June 2017, pp. 1-6

    • Ugalde-Loo CE, et al., “BEST PATHS Project: Real-Time Demonstrator for the Integration of Offshore Wind Farms using Multi-Terminal HVDC Grids,” Offshore Wind Energy (OWE 2017), London, UK, 6-8 June 2017, pp. 1-11.

    • Ugalde-Loo CE, et al., “Open access simulation toolbox for the grid connection of offshore wind farms using multi-terminal HVDC networks,” 13th IET International Conference on AC and DC Power Transmission (ACDC 2017), Manchester, UK, 14-16 February 2017, pp. 1-6.

  • 65

    Questions?

    The authors gratefully acknowledge the financial support provided by the EU FP7 Programme through the project “BEyond State of the art Technologies for re-Powering AC corridors & multi-Terminal HVDC Systems” (BEST PATHS), grant agreement number 612748.

    Dr Carlos UGALDE

    [email protected]

    Cardiff University, Wales, UK