INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN BUILDINGS William P. Bahnfleth, Ph.D., P.E., FASHRAE, FASME Indoor Environment Center, The Pennsylvania State University

Transcript of INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of...

Page 1: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN BUILDINGSWilliam P. Bahnfleth, Ph.D., P.E., FASHRAE, FASME

Indoor Environment Center, The Pennsylvania State University

Page 2: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Outline

� Connection between indoor air quality and energy use

� Importance of indoor air quality (IAQ)

� Current status of IAQ control� Current status of IAQ control

� Efficient IAQ technologies

� Integrating IAQ and energy efficiency

February 20, 2014Lisbon, Portugal

Page 3: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Energy conservation and ambient environment are high priorities…

� Component efficiency

� Reduced system energy use intensity

� Stratospheric ozone depletion

� Global climate change� Global climate change

� Use of alternative fuels

� Protection of water supplies

February 20, 2014Lisbon, Portugal

Page 4: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Buildings are the largest energy end-use sector

� ~ 40% of US primary energy use

� 22% residential /18% commercial

Source: US Energy Information Administration (2010)

February 20, 2014Lisbon, Portugal

Page 5: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Priority of energy, ambient environment apparent in law, policy, programs…

� US Energy Laws� National Energy Conservation Policy Act (1978, amended)

� Energy Policy Act of 1992

� Energy Policy Act of 2005

� Energy Independence and Security Act of 2007

� Other Public and Private Initiatives� Montreal Protocol (1987, amended

� Kyoto Protocol (1997, amended)

� Directive on Electricity Security Act of 2007

� Emergency Economic Stabilization Act of 2008

� American Recovery and Reinvestment Act of 2009

� Directive on Electricity Production from Renewable Energy Sources (EU, 2001)

� Directive on the energy performance of buildings (EU, 2002)

� ASHRAE Vision 2020

� many others…

February 20, 2014Lisbon, Portugal

Page 6: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

More than half of building energy use is for environmental control

� US buildings, all types

� Space heating 37%

� Lighting 10%

� Space cooling 9%� Space cooling 9%

� Ventilation 3%

� TOTAL 59%

� HVAC 46%

Source: US DOE Buildings Energy Data Book (2010)

February 20, 2014Lisbon, Portugal

Page 7: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

“That all people should have free access to air

and water of acceptable quality is a fundamental

human right.”

~World Health Organization, Air Quality Guidelines for Europe, 2nd ed.

“An energy declaration without a declaration “An energy declaration without a declaration

related to the indoor environment makes no

sense.”

~Bjarne Olesen, Olli Seppänen, Atze Boerstra. Criteria for the Indoor Environment for Energy Performance Of Buildings – A New European Standard.

February 20, 2014Lisbon, Portugal

Page 8: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Importance of IEQ - asthma

� According to US CDC based on data collected in 2007, 2008, 2009� 8.2 % of population/26 million people affected

� 10.5 million missed

� Asthma triggers (CDC)� ETS� Dust mites� Outdoor air pollution� Cockroach allergens

� 10.5 million missed school days

� 14.2 million missed work days

� 475,000 hospital stays� 3,447 deaths

Cockroach allergens� Pets� Mold� Wood smoke� Respiratory infections

February 20, 2014Lisbon, Portugal

Page 9: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Poor IAQ/IEQ is costly – national scale(Fisk, W. How IEQ Affects Health, Productivity. ASHRAE J., May 2000)

� Potential health and productivity saving from feasible IAQ and IEQ improvements

Source of Gain Potential Annual Benefits

Lower

$ (€) Billion

(2012)

Higher

$ (€) Billion

(2012)

Reduced Respiratory Illness

16 - 37 Million Avoided Cases of Common Cold or Influenza

9 (6.8) 21 (15.8)

Reduced Allergies and Asthma

8% - 25% Decrease in Symptoms - 53 Million Allergy Sufferers, 16 Million Asthmatics

1 (0.8) 6 (4.5)

Reduced Sick Building Syndrome Symptoms

20% - 50% Less SBS Symptoms at Work for ~15 Million Workers

15 (11.3) 44 (33.1)

Lighting/ Thermal Gain 30 (22.6) 237 (178.2)

TOTAL 55 (41.4) 308 (231.6)

February 20, 2014Lisbon, Portugal

Page 10: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

IAQ benefits are worth more than energy savings

� Value of the health and productivity of building occupants can be more than an order of magnitude greater than the cost of the energy it consumes

� Annual energy cost: $1 - $3/ft2 (~€9 – €25/m2)� Annual energy cost: $1 - $3/ft (~€9 – €25/m )

� Annual functional costs: $80 - $600/ft2

(~€680 – €5100/m2)

February 20, 2014Lisbon, Portugal

Page 11: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Poor IAQ is not a problem of wealthy countries alone

� Unvented indoor biomass cooking remains common in developing nations

� ~2,000,000 deaths per year due to chronic exposure

� Mostly women and children

(Smith, K. R. 2003. The global burden of disease from unhealthy buildings: preliminary results from comparative risk assessment. Proc. Healthy Buildings 2003)

…plus concern about the role of indoor exposure in real or feared epidemics – SARS, tuberculosis, influenza

February 20, 2014Lisbon, Portugal

Page 12: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Practical knowledge of IAQ is limited

� Factors correlated with perceived air quality and air quality problems

� Dampness

� Ventilation rate� Ventilation rate

� Building materials and other sources

� Indoor air chemistry

� Not enough known to prescribe specific control levels for most contaminants and for mixtures of many interacting contaminants

February 20, 2014Lisbon, Portugal

Page 13: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Methods are few and simple -

� Source control

� Task ventilation and general ventilation – dilute

� Non-specific particulate filtration – inorganic, viable and non-viable organicand non-viable organic

� Moisture control – prevent mold growth

…and the basis for ventilation rates is fundamentally subjective impression of people

February 20, 2014Lisbon, Portugal

Page 14: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

ASHRAE Standard 62.1

Acceptable Indoor Air Quality: air in which there are no known contaminants at harmful concentrations as determined by cognizant authorities and with as determined by cognizant authorities and with which a substantial majority (80% or more) of the people exposed do not express dissatisfaction.

February 20, 2014Lisbon, Portugal

Page 15: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Comfort vs. Sensory Load &Ventilation

1 olf sensory load(1 sedentary adult)

Fanger, P. O. (2008) “Perceived Air Quality and Ventilation Requirements” in Indoor Air Quality Handbook, J. Spengler, J. McCarthy and J. Samet eds.

Note definition of class A ventilation – 10 L/s-olf

February 20, 2014Lisbon, Portugal

Page 16: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

ASHRAE Standard 62.1- Air Quality

February 20, 2014Lisbon, Portugal

Page 17: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Ventilation rates too low? SBS Symptoms

Source: W. Fisk, A Mirer, M. Mendell. 2009. Quantitative relationship of sick building syndrome symptoms with ventilation rates. Indoor Air

February 20, 2014Lisbon, Portugal

Page 18: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Ventilation rates too low? Productivity

Source: Seppänen, O. and W. Fisk. 2006. Some Quantitative Relations between Indoor Environmental Quality and Work Performance or Health. HVAC&R Research.

February 20, 2014Lisbon, Portugal

Page 19: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Ventilation rates too low?Decision Making Ability

February 20, 2014Lisbon, Portugal

Source: Satish, U., M. Mendell, K. Shekhar, T. Hotchi, D. Sullivan, S. Streufert, and W. Fisk. 2013. Is CO2 an Indoor Pollutant? Direct Effects of Low-to-Moderate CO2 Concentrations on Human Decision-Making Performance. Env. Health Perspectives 20(12):1671-1677.

Page 20: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Ventilation rates too low? Infection

� Wells-Riley model

1 expv f d

ipqt

VP

η η η

− = −+ +

� Air change rate (η) affect probability of airborne infection (P)

February 20, 2014Lisbon, Portugal

v f dη η η+ +

Source: Sun, Y., Z. Wang, Y. Zhang, J. Sundell. 2011, In China, Students in Crowded Dormitories with a Low Ventilation Rate Have More Common Colds: Evidence for Airborne Transmission. PLoS ONE 6(11) e27140.

Page 21: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Are we doing enough to support indoor air quality? Probably not

� Typical HVAC designer

� Assumes code/standard compliance provides good IAQ

� Focuses on minimizing energy use/cost, carbon emissions

� Has limited awareness of costs of bad IAQ and has � Has limited awareness of costs of bad IAQ and has difficulty applying published research to practice

February 20, 2014Lisbon, Portugal

Page 22: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

IAQ is a part of larger problem of IEQ

…and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC

February 20, 2014Lisbon, Portugal

Source: Seppänen, O. and W. Fisk. 2006. Some Quantitative Relations between Indoor Environmental Quality and Work Performance or Health. HVAC&R Research.

Page 23: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Achieving High IAQ Efficiently

� Energy recovery from ventilation air

� Allowance for intermittent occupancy

� Dynamic ventilation control

� DOAS� DOAS

� Air treatment as a substitute/supplement for ventilation

…all permitted by ASHRAE Standard 62.1, encouraged by 90.1

February 20, 2014Lisbon, Portugal

Page 24: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Achieving High IAQ Efficiently

� US Green Building Council (USGBC) “Leadership in Energy Efficient Design (LEED) Rating System

� Increased ventilation (ASHRAE 62.1 or CEN Standard EN 15251: 2007+30%)

� Dynamic ventilation

� Natural ventilation

� Low emission materials

February 20, 2014Lisbon, Portugal

Page 25: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Integrating IAQ and Energy Efficiency

� Design emphasis is imbalanced� IAQ is reduced to code ventilation rate

� Real effort goes into energy efficiency – evaluation and optimization of system alternatives using modeling

Few simulation tools have integrate coupled � Few simulation tools have integrate coupled simulation of energy and IAQ

� In the research arena, IAQ and energy are mainly the domains of different communities that work independently

February 20, 2014Lisbon, Portugal

Page 26: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Elements of an integrated analysis

� Energy simulation� Thermal� Equipment performance

� Air (and contaminant) flow modelingflow modeling� Multizone (e.g. CONTAM)� CFD

� IAQ performance modeling

� Economic analysis

February 20, 2014Lisbon, Portugal

Page 27: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Studies directed at integrated design:Fisk, et al., effect of economizer

� Fisk, W., D. Faulkner, O. Seppänen, J. Huang. 2005. Economic Benefits of an Economizer System: Energy Savings and Reduced Sick Leave. ASHRAE Transactions 111(2).

Would not classify as a “low energy IAQ � Would not classify as a “low energy IAQ technology” because IAQ benefit, if realized, is accidental

� Combines energy modeling with Wells-Riley based sick leave analysis for two-story office in Washington DC.

February 20, 2014Lisbon, Portugal

Page 28: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Fisk, et al. results

Health benefit is 3 – 8 times greater than energy savings

February 20, 2014Lisbon, Portugal

Page 29: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Studies directed at integrated design:Lee, et al., In-duct UVGI vs. filters

� Lee, B., W. Bahnfleth, and K. Auer. 2009. Life-cycle cost simulation of in-duct ultraviolet germicidal irradiation systems. Proc. Building Simulation 2009, Glasgow, Scotland.

� Energy analysis, Wells-Riley based sick-leave analysis, life-cycle cost analysis of UVGI air disinfection compared with equivalent (MERV 12) filter

� Office building in New York City

February 20, 2014Lisbon, Portugal

Page 30: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Lee, et al. scenarios

� New York City office building

� Base HVAC system (minimum OA, MERV 6) + UVGI downstream of cooling coil

� Base HVAC system + UVGI upstream of cooling coil

� Base HVAC system + filtration equivalent to UVGI (MERV 12)

February 20, 2014Lisbon, Portugal

Page 31: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Lee, et al. results overview

Annual Energy Use Best UVGI MERV 12 Filter

kWh/ft2 0.1 1

kWh/m2 1 11

Annual Energy Cost Best UVGI MERV 12 Filter

$/ft2 0.01 0.104

February 20, 2014Lisbon, Portugal

$/ft 0.01 0.104

€/m20.08 0.84

Annualized Life Cycle Cost Best UVGI MERV 12 Filter

$/ft2 0.01 0.104

€/m20.08 0.84

Health and productivity benefit: 3.5 $/ft2, 28.3 €/ m2

Page 32: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Studies directed at integrated design:Johansson – Life cycle optimization

� Johansson, D. 2009. The life cycle costs of indoor climate systems in dwellings and offices taking into account system choice, airflow rate, health and productivity. Building and Environment (44):368-376.376.

� PhD dissertation – cost-optimal system and ventilation rate selection based on equipment, energy, health/productivity cost

February 20, 2014Lisbon, Portugal

Page 33: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Johansson – representative result: optimal ventilation vs. salary in an office

-Cost to occupants has a significant effect on desirable ventilation rate-Lower energy HVAC makes higher ventilation rate cost effective

February 20, 2014Lisbon, Portugal

Page 34: INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY …€¦ · IAQ is a part of larger problem of IEQ …and observe ~12% increase in SBS symptoms per 1ºC above 22.5ºC Lisbon,

Summary

� Maintaining even mediocre IAQ uses lots of energy –and costs society a lot in quality of life and productivity

� We can do better with basic IEQ measures like ventilation, but that knowledge has not penetrated far into practiceinto practice

� The energy and IAQ worlds do not overlap a lot – not enough yet – integration is interdisciplinary

� Process and tools are needed for design, and lots more research into parameters of IAQ and interactions of IEQ parameters

February 20, 2014Lisbon, Portugal