INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

55
INSULATION INSULATION COORDINATION COORDINATION AC HIGH VOLTAGE AC HIGH VOLTAGE CIRCUIT BREAKERS CIRCUIT BREAKERS STEPHEN R. LAMBERT STEPHEN R. LAMBERT SHAWNEE POWER CONSULTING, LLC SHAWNEE POWER CONSULTING, LLC

Transcript of INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

Page 1: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

INSULATIONINSULATIONCOORDINATIONCOORDINATION

AC HIGH VOLTAGEAC HIGH VOLTAGECIRCUIT BREAKERSCIRCUIT BREAKERS

STEPHEN R. LAMBERTSTEPHEN R. LAMBERTSHAWNEE POWER CONSULTING, LLCSHAWNEE POWER CONSULTING, LLC

Page 2: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

1. Preinsertion Resistor

2. Grading Capacitor

3. Interrupter

4. Support Column

Page 3: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

INSULATION PATHSINSULATION PATHS

PHASE TO GROUND

ACROSS THE OPEN BREAKER

PHASE TO PHASE

Page 4: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

1. Preinsertion Resistor

2. Grading Capacitor

3. Interrupter

4. Support Column

Page 5: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

VOLTAGE STRESSESVOLTAGE STRESSES

60 Hz

SWITCHING SURGES

LIGHTNING SURGES

Page 6: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

60 Hz Overvoltages60 Hz Overvoltages

UNGROUNDED SYSTEMS – 1.73 PUWITH FAULTS

ACROSS OPEN BREAKER – 2.2 PU

Page 7: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

SWITCHING SURGE SWITCHING SURGE OVERVOLTAGESOVERVOLTAGES

NO SURGE CONTROLENERGIZING – 3.0 PURECLOSING (trapped charge) – 4.0 PU

WITH PREINSERTION RESISTORS – 2.2 PU

SURGE ARRESTERS LIMITING – 1.9 PU

Page 8: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

2.90 PU Phase to Ground Switching Surge345 kV System

-1000

-800

-600

-400

-200

0

200

400

600

800

20 30 40 50 60 70 80 90 100 110 120

Time (ms)

kV

Page 9: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

Application of 276 kV Surge Arrester1.83 PU

-600

-400

-200

0

200

400

600

20 30 40 50 60 70 80 90 100 110 120

Time (ms)

kV

Page 10: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

-1000

-800

-600

-400

-200

0

200

400

600

800

20 30 40 50 60 70 80 90 100 110 120

Time (ms)

kV

Application of 276 kV Surge Arrester1.83 PU

Page 11: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGHTNINGLIGHTNINGFLASHFLASH

CHARACTERISTICSCHARACTERISTICS

Page 12: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

+++++++++ ++++++++++++++++ +++++++

++---------------------- -------------------- ++

-- ++-- ++

Neg Flash Pos Flash

Page 13: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

FLASH STATISTICSFLASH STATISTICS55% OF FLASHES HAVE MORE THAN ONE STROKE

90% OF FLASHES HAVE LESS THAN NINE STROKES

MEAN NUMBER OF STROKES/FLASH -THREE

80-90% OF STROKES ARE NEGATIVE

Page 14: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGHTNINGLIGHTNING

CHARACTERIZED BY

CURRENT MAGNITUDE

STROKE RISE TIME

KERAUNIC LEVEL OR FLASHES/km2

Page 15: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

STROKE MAGNITUDESSTROKE MAGNITUDES

0.01

0.1

1

10

100

0 50 100 150 200 250

Stroke Current kA

Prob

. of E

xcee

ding

Abs

ciss

a First Stroke

Page 16: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

STROKE MAGNITUDESSTROKE MAGNITUDES

0.01

0.1

1

10

100

0 50 100 150 200 250

Stroke Current kA

Prob

. of E

xcee

ding

Abs

ciss

a

First StrokeSubsequent Strokes

Page 17: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

TYPICAL FIRST STROKETYPICAL FIRST STROKE

-1

-0.9

-0.8

-0.7

-0.6

-0.5

-0.4

-0.3

-0.2

-0.1

0

0 5 10 15 20 25 30 35 40

μs

pu c

urre

nt

First Stroke

Page 18: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

SUBSEQUENT STROKESSUBSEQUENT STROKES

-1

-0.9

-0.8

-0.7

-0.6

-0.5

-0.4

-0.3

-0.2

-0.1

0

0 5 10 15 20 25 30 35 40

μs

pu c

urre

nt

First Stroke

Subsequent Strokes

Page 19: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

1.2 x 50 IMPULSE SHAPE1.2 x 50 IMPULSE SHAPE

-1

-0.9

-0.8

-0.7

-0.6

-0.5

-0.4

-0.3

-0.2

-0.1

0

0 5 10 15 20 25 30 35 40

μs

pu c

urre

nt

First Stroke

Subsequent Strokes

1.2 x 50 wave

Page 20: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

GROUND FLASH DENSITYGROUND FLASH DENSITY

Page 21: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

GROUND FLASH DENSITYGROUND FLASH DENSITY

Page 22: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

HOW DOES LIGHTNING GET HOW DOES LIGHTNING GET INTO THE SYSTEM?INTO THE SYSTEM?

SHIELDING FAILURES

BACKFLASHOVERS

INDUCED

Page 23: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

BACK FLASHOVERBACK FLASHOVER

`

Zsw

Zsw

Is

Ztwr

Ztfr

Vph

Vtwr

Page 24: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

SHIELDING FAILURESHIELDING FAILUREZph 400 Ω

Is = 10 kA

Vph = ? `

Zsw

Zsw

Is

Ztwr

Vph

Vtwr

`

Zph

`

Zph

Page 25: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

SHIELDING FAILURESHIELDING FAILUREZph 400 Ω

Is = 10 kA

Vph = 2 MV`

Zsw

Zsw

Is

Ztwr

Vph

Vtwr

`

Zph

`

Zph

Page 26: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

EXAMPLEEXAMPLE

TLine TLine

Page 27: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

SHIELDING FAILURESHIELDING FAILUREPHASE TO GROUND SURGEPHASE TO GROUND SURGE

@ OPEN BREAKER@ OPEN BREAKER

-1000

-500

0

500

1000

1500

2000

2500

3000

3500

5 7 9 11 13 15 17 19

Time (μs)

kV

Page 28: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

INSULATION CAPABILITYINSULATION CAPABILITY& TESTING& TESTING

EARLY 1900’s

60 Hz TESTING ONLY

TEST LEVEL:2.25 x RATED VOLTAGE + 2000 V

1 MINUTE DRY – 10 SECONDS WET

Page 29: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

POWER FREQUENCY TEST POWER FREQUENCY TEST LEVELSLEVELS

-960800

-860550

-555362

350425245

315365170

275310145

230260123

14016072.5

758038

506025.8

455015.5

10 Second Wet(kV, rms)

1 Minute Dry(kV, rms)

Rated MaximumVoltage (kV, rms)

Power Frequency Test

Page 30: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

CONTACTS OPENCONTACTS OPEN

Page 31: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

CONTACTS CLOSEDCONTACTS CLOSED

Page 32: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

RATIO TEST VOLTGE TO RATEDRATIO TEST VOLTGE TO RATEDMAXIMUM VOLTAGEMAXIMUM VOLTAGE

2.08960800

2.71860550

2.66555362

3.00425245

3.72365170

3.70310145

3.66260123

3.8216072.5

3.658038

4.036025.8

5.595015.5

In pu of Rated L-G Voltage

1 Minute Dry

(kV, rms)

Rated Maximum

Voltage (kV, rms)

Power Frequency Test

Page 33: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

MINIMUM CREEPAGE DIST.MINIMUM CREEPAGE DIST.CONTAMINATION ISSUES

LIGHT CONTAMINATION

MINIMUM CREEP AT 27.7 mm/kVrms, p-g

SALT FOG, INDUSTRIAL CONTAMINATION MAY NEED MORE CREEP

Page 34: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

CREEPAGE REQUIREMENTSCREEPAGE REQUIREMENTS

12900800

8890550

5850362

3960245

2750170

2340145

1990123

117072.5

61038

42025.8

25015.5

Minimum Creepage to Ground,(mm)

Rated Maximum Voltage (kV, rms)

Page 35: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGHTNING IMPULSE TESTLIGHTNING IMPULSE TESTINTRODUCED IN 1930’s

TEST LEVEL – 2 x LF TEST + 40 kV

1.5 x 40 μs WAVE SHAPE

NOW – 1.2 x 50 μs

FULL WAVE & 2 μs CHOPPED WAVE

10 % PROB. OF FLASHOVER OR LESS

Page 36: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGHTNING IMPUSE LIGHTNING IMPUSE WAVESHAPEWAVESHAPE

0

0.2

0.4

0.6

0.8

1

1.2

0 10 20 30 40 50 60

Time μs

V

Page 37: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGHTNING IMPUSE TEST LEVELSLIGHTNING IMPUSE TEST LEVELS

26402050800

23201800550

16801300362

1160900245

968750170

838650145

710550123

45235072.5

25820038

19415025.8

14211015.5

Chopped Wave (2μs)Full WaveRated MaximumVoltage (kV, rms)

Lightning Impulse

Page 38: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

TEST PROCEEDURETEST PROCEEDURECONTACTS OPEN – ALL OTHER TERMINALS GROUNDED

CONTACTS CLOSED – ALL OTHER PHASES GROUNDED

APPLY THREE IMPULSES (NEG AND POS)

IF ZERO FLASHOVERS – PASS

IF ONE FLASHOVER IN FIRST THREE, THEN 9 MORE TESTS WITH NO FLASHOVERS

Page 39: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

RATIO OF FULL WAVE IMPULSE RATIO OF FULL WAVE IMPULSE TO RATED MAXIMUM VOLTAGETO RATED MAXIMUM VOLTAGE

3.1420508004.0118005504.4013003624.509002455.407501705.496501455.485501235.9135072.56.45200387.1215025.88.6911015.5

In pu of Rated L-G Crest Voltage

Full WaveRated MaximumVoltage (kV, rms)

Lightning Impulse

Page 40: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

SWITCHING IMPULSE TESTINGSWITCHING IMPULSE TESTING

INCREASE IN SYSTEM VOLTAGE TO EHV LEVELS - 345 AND 500 kV

BEGUN IN EARLY 1960’S

TEST WAVESHAPE - 250 x 2500 μs

Page 41: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

TEST PROCEDURETEST PROCEDUREPOSITIVE AND NEGATIVE POLARITIES

SAME 3 – 9 TEST SERIES

WET AND DRY TESTS REQUIRED

OPEN AND CLOSED TEST VALUES DIFFERENT

10 % PFO OR LESS

Page 42: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

TEST LEVELSTEST LEVELS

15001425800

13001175550

900825362--245--170--145--123--72.5--38--25.8--15.5

Breaker Open(kV, cr)

Breaker Closed(kV, cr)

Rated MaximumVoltage (kV, rms)

Switching Impulse Terminal toTerminal

Page 43: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

RATIO OF TEST LEVELS TO RATIO OF TEST LEVELS TO RATED MAXIMUM VOLTAGERATED MAXIMUM VOLTAGE

2.181425800

2.621175550

2.79825362

In pu of Rated L-G Crest Voltage

Breaker Closed(kV, cr)

Rated MaximumVoltage (kV, rms)

Switching Impulse Terminal toTerminal

Page 44: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

2.90 PU Phase to Ground Switching Surge345 kV System

-1000

-800

-600

-400

-200

0

200

400

600

800

20 30 40 50 60 70 80 90 100 110 120

Time (ms)

kV

Page 45: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

Application of 276 kV Surge Arrester1.83 PU

-600

-400

-200

0

200

400

600

20 30 40 50 60 70 80 90 100 110 120

Time (ms)

kV

Page 46: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGHTNING SURGE PROTECTIONLIGHTNING SURGE PROTECTIONUSE OF GAPUSE OF GAP

TLine TLine

Page 47: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

LIGNTINING SURGE LIGNTINING SURGE PROTECTION PROTECTION -- GAPSGAPS

-4000

-3000

-2000

-1000

0

1000

2000

5 7 9 11 13 15 17 19

Time (μs)

kV

2 m Rod Gap

No Protection

Page 48: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

APPLICATION OF ARRESTERAPPLICATION OF ARRESTERSEPARATION DISTANCESEPARATION DISTANCE

TLine TLine

Page 49: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

APPLICATION OF ARRESTERAPPLICATION OF ARRESTERPHASE TO GROUND AT OPEN BREAKERPHASE TO GROUND AT OPEN BREAKER

-500

0

500

1000

1500

2000

5 7 9 11 13 15 17 19

Time μs

kV

80 m separation40 m0 m

Page 50: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

APPLICATION OF ARRESTERAPPLICATION OF ARRESTERACROSS OPEN BREAKERACROSS OPEN BREAKER

0

500

1000

1500

2000

2500

5 7 9 11 13 15 17 19

Time μs

kV

80 m separation40 m0 m

Page 51: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

EFFECT OF ALTITUDEEFFECT OF ALTITUDE

TESTED AT NTP (normal temperature and pressure)

REDUCTION IN EXTERNAL INSULATION WITH INCREASING ALTITUDE

Page 52: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

ALTITUDE CORRECTION ALTITUDE CORRECTION FACTORFACTOR

H – ALTITUDE IN METERS

m – GAP FACTOR1 FOR POWER FREQUENCY, LIGHTNING AND PHASE TO PHASE SWITCHING SURGES0.9 FOR INSULATION ACROSS OPEN GAP0.75 FOR PHASE TO GROUND SWITCHING SURGES

)8150

( Hm

d ek−

=

Page 53: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

ALTITUDE CORRECTIONALTITUDE CORRECTION

0.6

0.65

0.7

0.75

0.8

0.85

0.9

0.95

1

1.05

0 500 1000 1500 2000 2500 3000 3500 4000

Alltitude Above Sea Level, m

Alti

tude

Den

sity

Cor

rect

ion

Fact

or

Switching Surge to GroundLightning

Page 54: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …
Page 55: INSULATION COORDINATION AC HIGH VOLTAGE CIRCUIT …

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

-3 -2.5 -2 -1.5 -1 -0.5 0 0.5 1

Deviation in Strength in Number of Sigmas

Prob

abili

ty o

f Pas

sing

Tes

t

3+33+915x2